24- 3596- 4, Rev. C
Product Bulletin C-9506
Issue Date March 2016
C-9506
Air Switching Cumulator
The C-9506 Air Switching Calibration
Cumulator is an auxiliary device
designed to switch its output Note: The calibration
pressure from zero to full supply procedure below should only
pressure when the pilot pressure be followed when the C-9506
reaches the switch point. It is is used as an air switching
ideally suited for exhaust cumulator. To calibrate the C-
damper applications requiring a 9506 when it is used as a
high output volume for quick positioner, refer to Product
operation. The switch point is Data D-9502 and/or V-9502 for
factory set at approximately the proper procedure.
9 PSIG (63 kPa) and is
adjustable from 2 to 12 PSIG To adjust the switch point of the
(14 to 84 kPa). C-9506 air Switching Cumulator,
refer to Fig. 2 and proceed as Fig. 1: C-9506 Air Switching
The C-9506 also doubles as the follows: Cumulator
unit replacement for all models
of D-9502 and V-9502 1. Furnish 20 PSIG (140 kPa)
Positioners. to the supply “S” port. Note: The output pressure
2. Apply the desired switch reading can be taken either
Operation point pressure to the pilot using a pressure gage in
“P” port. the output line or at the
The C-9506 is a two-position hypodermic needle test
device with a 1 PSI (7 kPa) 3. Remove the cover and turn
point on the cumulator
differential. When the pilot the adjusting screw
body.
pressure is below the switch counterclockwise to
point, the output will be zero. As increase or clockwise to 4. Increase and decrease the
the pilot pressure rises above decrease the switch point pilot pressure to check the
the switch point, the output will until the output pressure switch point differential of
switch to full supply pressure. switches to 20 PSIG. the C-9506.
When the pilot pressure drops to
1 PSI below the switch point, the
output pressure will drop back to
zero.
Note: The C-9506 should not
Specifications
be activated by a transmitter
or low-sensitivity controller. A
low volume input change
could cause the instrument to
cycle.
Mounting
The C-9506 is designed for
mounting in any position using
the two mounting holes in the
base of the instrument. Allow
enough clearance for cover
removal and switch point
adjustment. Air connections are
made to barbed fittings for 5/32
or 1/4 in. O.D. polytubing.
© 2016 Johnson Controls, Inc. 1
Part No. 24-3596-4, Rev. C
Code No. LIT-7171455
Application and Drawing
Identification
2 C-9506 Product Bulletin
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS
WESTENDHOF 3 507 E MICHIGAN ST C/O CONTROLS PRODUCT MANAGEMENT
45143 ESSEN MILWAUKEE WI 53202 NO. 22 BLOCK D NEW DISTRICT
GERMANY USA WUXI JIANGSU PROVINCE 214142
CHINA
Controls Group
507 E. Michigan Street
P.O. Box 423 Printed in U.S.A.
Milwaukee, WI 53202
SQ-6100 Product Bulletin 3Позиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.