64- 378- 14, Rev. D

                                                                                 Technical Bulletin A-4400
                                                                                       Issue Date 0316

                            A-4400 Series Refrigerated Air Dryers
                                Installation and Maintenance

                                INTRODUCTION                                                             3

                                 Product Overview                                                        3

                                INSTALLATION PROCEDURES                                                  4

                                 Location                                                                4

                                 Unpacking the Unit                                                      4

                                 Conventional Wall Mounting Arrangement                                  4

                                 Air Connections                                                         5

                                 Base Mounting Arrangement                                               6

                                 Activated Carbon Filter Installation                                    6

                                 Drain Connections                                                       7

                                 Permanent Wiring Using Conduit                                          8

                                 Wiring to Air Compressor                                                9

                                COMMISSIONING                                                          10

                                 Gauge Correction                                                       10

                                 Evaporator Pressure Adjustment                                         10

                                 Altitude Compensation                                                  10

                                 Low Ambient Temperature Compensation                                   11

                                SERVICING PROCEDURES                                                   12

                                 Particle Filter                                                        12

                                 Coalescing Oil Removal Filter                                          13

© 2016 Johnson Controls, Inc.                                                                            1
  Part No. 64-378-14, Rev. D
  Code No. LIT-718050T
                          Replacement Coalescing Oil Removal Filter Element Kit   14

                          Activated Carbon Oil Vapor Removal Filter               15

                          Pressure Reducing Valve                                 15

                          Power On/Fail Lamp                                      15

                          Refrigeration Service                                   16

                          Condenser Fan Motor Replacement                         21

                          Condenser                                               23

                          Air Dryer Compressor Motor Wiring Circuit               23

                          Excessive Vibration                                     24

                       SPECIFICATIONS                                             25

                       REPAIR INFORMATION                                         26

2 Air Dryers—A-4400 Series Technical Bulletin
           Introduction

Product    The A-4400 Series Refrigerated Air Dryers are designed for continuous
Overview   operation to supply dry air to pneumatic control systems. All components
           are selected and assembled to provide dependable service over a long
           period of time with a minimum amount of maintenance.
           Note: For units without a factory mounted Air Purification System
                 (consisting of a coalescing oil removal filter with integral
                 pressure drop indicator, packed column type activated carbon oil
                 vapor removal filter, service bypass valve, pressure reducing
                 valve, safety relief valve, and power on/fail lamp), a properly
                 configured system must include a coalescing oil removal filter as
                 well as an activated carbon oil vapor removal filter as outlined in
                 Product Data A-4000 and the Installation and Service Manual for
                 PureFlow™ Air Compressors (Publication No. 2629).

               Table 1: Ordering Data
                                      Flow Capacity at               Air            Shipping
                  Code                Rated Condition*           Purification        Weight
                 Number                    scfm                   System              lb**
                                            (L/s)
                  A-4412-1                   12
                                                                      Yes               72
                                            (5.7)
                  A-4412-2                   12
                                                                       No               67
                                            (5.7)
                  A-4417-1                   17
                                                                      Yes               78
                                            (8.0)
                  A-4417-2                   17
                                                                       No               73
                                            (8.0)
                  A-4423-1                   23
                                                                      Yes               78
                                           (10.9)
                  A-4423-2                   23
                                                                       No               72
                                           (10.9)
                 * The rated condition is 20 psig (140 kPa) supply pressure, 100 °F (38°C)
                   saturated inlet air temperature, 100°F ambient temperature, and 80 psig
                   (560 kPa) inlet pressure.
                ** lb x 0.454 = kg.

                                                Air Dryers—A-4400 Series Technical Bulletin    3
                        Installation Procedures

Location               The A-4400 Series Refrigerated Air Dryer must be located in an open area
                       that will permit free circulation of air through the ends of the unit. The
                       A-4400 requires 12 in. (305 mm) top clearance (as measured from the top
                       of the cabinet) and 12 in. clearance at either end. When the unit is wall
                       mounted, it is recommended that there also be 10 in. (254 mm) bottom
                       clearance.

Unpacking the          Hand protection is required when removing the A-4400 from its shipping
Unit                   carton. Proceed as follows:
                       1.   Cut the two adjacent corners of the front carton panel from top to
                            bottom, then fold the panel down. Remove the air dryer from its
                            shipping carton through the exposed side.
                       2.   Wearing proper eye protection and using a pair of wire cutters, reach
                            into the air connection side of the air dryer and cut the steel packing
                            band securing the compressor to the shipping chipboard.
                       3.   Tip the air dryer slightly on its edge and carefully remove the steel
                            packing band and discard. Also slide the shipping chipboard out and
                            discard.
                       4.   Remove and discard the packaging cardboard from behind the
                            coalescing filter, if applicable (Models A-4412-1, A-4417-1, and
                            A-4423-1).

Conventional           Two key slots are provided at the rear of the A-4400 for wall mounting the
Wall Mounting          unit (refer to Figure 1). Install the bolts and appropriate anchors
Arrangement            (field furnished) in the wall at 16 in. (406 mm) center-to-center spacing, in
                       a level arrangement. Hang the A-4400 on the bolts and tighten as
                       required.
                       Note: The key slots (center to center spacing) can be hand adjusted
                             approximately 1/2 in. (13 mm) if needed when hanging the unit on
                             the mounting bolts.
                       This wall mounting arrangement provides proper air circulation, allows
                       easy access to the interior of the unit, and makes it convenient to remove
                       the particle filter and automatic condensate drain trap assembly through
                       the bottom of the unit for any necessary cleaning or replacement.

4 Air Dryers—A-4400 Series Technical Bulletin
                                                                                                                                 12-15/16
        Note: The A-4400 requires 12 in. (305 mm)                                                                                   329
              top clearance and 12 in. clearance
              on either end. When wall mounting
              the A-4400, 10 in. (254 mm) bottom
              clearance is recommended.

                Also, attach the 3/8 in. discharge main
                air line to the PRV before mounting.                                           17-1/2
                                                                                   A-4412-1:    445     A-4417-1 and A-4423-1:
                                                                                   21-3/4                   22-1/16
                                                                                    552                       560

                                                     A-4412-1:                                                                            Key Slots
                                                    18-1/16                                        16                                 (Two Locations)
          In                                          459                                         406                                  for 1/4 in. Bolts
                                                                               +                                           +
                                                                                                                                     (Field Furnished)

                                               12-5/8
                                                321
                                                                                                                                   14-1/4
                                                                                                                                    362

                                                   A-4417-1 and
                                                    A-4423-1:
                                                    23-3/16
                                                      589

               Out
                               Capped High Pressure Connection
                                     for High Pressure Riser
                     (Models with a Factory Mounted Air Purification System)

               Figure 1: A-4400 Series Refrigerated Air Dryer Shown with
                       Optional Factory Mounted Air Purification System
                                                    in.
                                      Dimensions
                                                    mm

Air                         The high pressure side of the compressed air line, after the compressor
Connections                 tank, must be connected to the 3/8 in. compression inlet air connection.
                            On models with an optional factory mounted Air Purification System, this
                            inlet air connection is located on the service bypass valve. These models
                            also include a capped high pressure outlet connection (refer to Figure 1)
                            directly ahead of the PRV. To use this connection, remove the cap and
                            connect the high pressure outlet line to the 3/8 in. compression connection
                            provided. Check all air line connections for leakage.

                                                                                      Air Dryers—A-4400 Series Technical Bulletin                          5
       Base Mounting          Several mounting hole patterns are provided in the base of the A-
       Arrangement            4400 (refer to Figure 2) for securing the unit to a platform. These
                              mounting holes are sized for 1/4-20 self-tapping screws or a No.
                       12 nut and bolt combination (all field furnished).

                                                                                                 11/16
                                                                                                  17

                                       Mounting Holes
                                       (Eight Locations)
                                       for 1/4-20                                             10-7/8
                                       Self-tapping Screws                                     276
                                       or a No. 12 Nut and
                                       Bolt Combination
                                       (All Field Furnished)

                                         5-1/2
                                         140         7-1/2
                                                     191       9-11/32
                                                                 237     13-11/16
                                                                           348

                              Figure 2: DryFlow A-4400 Series Refrigerated Air Dryer
                                     Base Mounting Hole Patterns (Plan View)
                                                             in.
                                                Dimensions
                                                             mm

 Activated             On models with an optional factory mounted Air Purification System, the
Carbon Filter          activated carbon oil vapor removal filter is packaged separately within the
Installation           dryer shipping carton and must be installed on the unit in the field as
                       follows:
                       1.   Referring to Table 2, note the life of the activated carbon oil vapor
                            removal filter element being installed.
                       2.   Divide the element life noted in Step 1 by the average system scfm or
                            L/s to obtain the expected life in days.

6 Air Dryers—A-4400 Series Technical Bulletin
              3.   Use the expected life calculated in Step 2 to determine the
                   replacement date, and record this date on the servicing label on the
                   carbon filter element.
              4.   Remove the red plastic dust cap from the carbon filter pipe
                   connection.
              5.   With the black sealing washer in position on the base of the carbon
                   filter element, screw the element onto the male pipe thread and hand
                   tighten to complete the installation.

              Table 2: Carbon Filter Element Life
               Carbon Filter Element        Flow
                                                                     Element Life
                  Code Number              Capacity
                      A-4000-147        10 scfm (4.7 L/s)   4,000 scfm-Days (1,888 L/s-Days)
                      A-4000-146        20 scfm (9.4 L/s)   13,000 scfm-Days (6,136 L/s-Days)

Drain         The automatic condensate drain trap assembly has a 1/8 in. internal NPT
Connections   drain connection and the coalescing oil removal filter assembly
              (on air dryers with an optional factory mounted Air Purification System)
              has a 1/8 in. external NPT drain connection. Two styles of couplers are
              available for connecting the drain line to the coalescing oil removal filter
              assembly if needed: the F-400-20 kit is a 1/8 in. external NPT x 1/8 in.
              internal NPT coupler, and the F-400-10 kit is a 1/8 in. internal
              NPT x 1/4 in. O.D. compression coupler. Both coupler kits must be
              ordered separately.
              Attach tubing to the connections on the automatic condensate drain trap
              assembly and the coalescing oil removal filter assembly (if present),
              keeping the runs as short as practical in order to reduce back pressure on
              the automatic drains. Use separate drain lines for the automatic
              condensate drain and the coalescing oil removal filter drain; never connect
              the lines together.
              Note: An override feature is incorporated in the coalescing oil removal
                    filter and automatic condensate drain trap, which allows manual
                    draining of the bowl. To activate the override, it will be necessary
                    to remove the tubing and connections from the 1/8 in. NPT drain
                    connection at the bottom of the bowl. Then, using a 1/8 in.
                    diameter or smaller rod, insert it up into the drain connection until
                    it contacts the override needle. This will cause the bowl to drain.
                    When the bowl has been drained, replace the connections and
                    tubing.

                                               Air Dryers—A-4400 Series Technical Bulletin      7
       Permanent               All A-4400 Series Refrigerated Air Dryers are furnished with a
       Wiring Using            cord and plug to fit a standard 115 volt receptacle. If permanent
       Conduit                 wiring is required using conduit, proceed as follows:
                               1. Cut the line cord to a sufficient length so that it will reach
                            from the compressor terminal box through Hole 1 as illustrated in
                            Figure 3; 12 in. (305 mm) should be long enough.
                       2.   Strip the wires back approximately 1 in. (25 mm).
                       3.   Attach the strain relief bushing (provided with each unit) to the line
                            cord approximately 3 in. (76 mm) from the cut end and insert it into
                            Hole 1.
                       4.   Connect the conduit to Hole 2 as illustrated in Figure 3, and join the
                            leads together using the appropriate wire nuts (field furnished).

                                     Figure 3: Permanent Wiring Using Conduit

8 Air Dryers—A-4400 Series Technical Bulletin
Wiring to Air        Wiring may be run through the load side of the air compressor disconnect
Compressor           switch ahead of the Pressure Electric (PE) switch, as illustrated in
                     Figure 4. Doing so will allow continuous A-4400 operation whenever the
                     disconnect switch is closed, while control over the air compressor is
                     retained by the PE switch.
                     Note: The air dryer motor voltage must match the air compressor motor
                           voltage in order to wire the unit as illustrated in Figure 4.

                                                 Air
                                                 Dryer

                115 VAC
                60 Hz

                                                                  Pressure           Air Compressor
                                Air Compressor
                                                                  Switch
                                Disconnect

                               Figure 4: Single-Phase Air Compressor Motor

                                                    Air Dryers—A-4400 Series Technical Bulletin       9
                       Commissioning

Gauge                  The evaporator pressure gauge is calibrated to a test gauge at the factory.
Correction             Readings are recorded on a label inside the dryer cabinet base. Apply this
                       correction to the evaporator gauge to obtain a precise reading.

Evaporator             The A-4400 Series Refrigerated Air Dryers are factory set to protect
Pressure               against air side freeze-up down to ambient temperatures of 40°F (4°C) and
Adjustment             altitudes up to 1500 ft.
                       Using the corrected no load evaporator pressure gauge reading and current
                       ambient temperature, refer to the graph in Figure 5 to determine if the
                       evaporator pressure is at the proper setting. If the value is within the
                       acceptable operating zone as shown on the graph, then no further
                       adjustments are necessary. If the value is not within the acceptable
                       operating zone, then it will be necessary to adjust the expansion valve.
                       Refer to the Refrigeration Service section and follow Steps 1 through 5
                       (readjusting the expansion valve setting) to properly adjust the expansion
                       valve until the evaporator pressure gauge is at the adjusted pressure.
                       Note: All of the expansion valve settings are based on no load
                             conditions, position the service bypass valve into the bypass mode.
                             Allow the unit to run unloaded a minimum of 10 minutes prior to
                             checking evaporator pressure or adjusting the expansion valve.

Altitude               If the air dryer is installed in high altitudes, the expansion valve will
Compensation           have to be adjusted to compensate for the new ambient pressure.
                       For altitudes from 1500 to 5000 ft, increase the expansion valve setting by
                       2.5 psig (17.5 kPa), and for altitudes over 5000 ft, increase the expansion
                       valve setting by 4.0 psig (28 kPa). This increase in evaporator pressure
                       must be added to the value determined by the graph in Figure 5 to account
                       for altitude effects. Refer to the Refrigeration Service section and follow
                       Steps 1 through 5 (readjusting the expansion valve setting) to properly
                       adjust the expansion valve until the evaporator pressure gauge is at the
                       adjusted pressure.
                       Example:

                       If:    Altitude = 4000 ft above sea level
                              Ambient temperature = 80°F
                              Evaporator pressure gauge reading at no load condition = 34.8 psig

                       Then: Corrected evaporator pressure = 34.8 psig + 2.5 psig = 37.3 psig

10 Air Dryers—A-4400 Series Technical Bulletin
                                             43

                                             42

                                             41

                                             40

                                             39

                                             38

                                             37

                Evaporator Pressure (psig)
                                             36

                                             35

                                             34

                                             33

                                             32

                                             31

                                             30

                                             29

                                             28

                                             27

                                             26

                                              40    50          60          70          80         90       100   110   120     130
                                                                                 Ambient Temperature (°F)

                                                     Acceptable Operating Zone
                                                     Nominal Setting

                                              Figure 5: Evaporator Pressure vs. Ambient Temperature
                                                          (Sea Level--No Load Condition)

Low Ambient    If the air dryer is used in ambient conditions between 35 and 40°F
Temperature    (2 and 4°C) the expansion valve must be adjusted to increase the expansion
Compensation   valve gauge pressure by 3 psig (21 kPa) to offset a possible freeze-up
               condition. This increase in evaporator pressure must be added to the value
               determined by the graph in Figure 5 to account for low ambient temperature
               effects. At high altitudes and low ambient temperatures, it will be necessary
               to add both pressure corrections and readjust the expansion valve. Refer to the
               Refrigeration Service section and follow Steps 1 through 5 (readjusting the
               expansion valve setting) to properly adjust the expansion valve until the
               evaporator pressure is at the adjusted pressure. Operation of the A-4400 in
               ambient temperatures below 35°F (2°C) is not recommended.
               Note: If it was necessary to adjust the expansion valve settings and position
                     the service bypass valve to bypass the air dryer, then return the service
                     bypass valve to normal mode in order to resume operation. Also, if
                     the pressures were changed from the normal settings, indicate the
                     changes on the air dryer to facilitate future service.

                                                                                  Air Dryers—A-4400 Series Technical Bulletin         11
                       Servicing Procedures

Particle Filter        The A-4400 Series Refrigerated Air Dryer is equipped with an automatic
                       condensate drain trap assembly with a particle filter. The particle filter
                       should be replaced annually or whenever the filter element appears dirty.
                       To replace the particle filter element and/or automatic drain valve, refer to
                       Figure 6 and proceed as follows:
                       1.   Remove the service bypass valve locking pin and push the plunger to
                            the right into the bypass position. Doing so will unload the pressure
                            in the drain bowl.
                       2.   Turn the filter bowl  counterclockwise and remove. Also remove
                            the O-ring .
                       3.   Visually inspect the filter bowl  for signs of cracking. If the bowl is
                            cracked, it is necessary to replace the complete assembly
                            (See Table 3, Item E ordered separately). If the bowl is not cracked,
                            clean it using a liquid household detergent.
                       4.   Turn the baffle  counterclockwise and remove.
                       5.   Remove the old particle filter element  and discard.
                       6.   Install the new particle filter element (See Table 3, Item E ordered
                            separately). Screw the baffle  into the filter body  until contact is
                            made with the filter element , then tighten an additional 1/4 turn.
                       7.   To replace the auto drain (See Table 3, Item E ordered separately),
                            remove the drain retaining nut , invert the bowl, and remove and
                            discard the float  and seal .
                       8.   Install the new seal  and float  and tighten the drain retaining
                            nut  to approximately 25 in.lb of torque.
                       9.   Reinstall the filter bowl  and O-ring . Return the service bypass
                            valve to normal operation by pushing the plunger left to its original
                            position. Reinstall the locking pin to ensure that the plunger remains
                            positioned for normal operation.

12 Air Dryers—A-4400 Series Technical Bulletin
                                          4

                                                                    7

                                          3
                                                                    6

                                          2

                                          8

                                          1

                                                                     5

                           Figure 6: Particle Filter/Auto Drain Replacement

Coalescing Oil   The coalescing oil removal filter is equipped with an automatic drain for
Removal Filter   discharging accumulations of entrapped liquids. This filter also features a
                 pressure drop indicator integral to the top of the unit (refer to Figure 7).
                 On a new filter, this indicator is green in color. As the pressure drop
                 across the filter increases, a slide within the indicator moves, bringing
                 some red color into view. When the pressure drop reaches 7.5 psig
                 (52.5 kPa), the indicator becomes entirely red, indicating that the filter
                 element needs to be replaced. Even if the indicator is not entirely red, it is
                 recommended that the filter element be replaced annually.

                                                 Air Dryers—A-4400 Series Technical Bulletin   13
                                                                  Pressure Drop
                                                                  Indicator

                                                                        Note: Even if the indicator
                                                                              is not entirely red,
                                                                              it is recommended
                                                                              that the filter element
                                                                              be replaced annually.

                                          Coalescing
                                          Filter Element,
                                          and O-rings                             Replacement
                                                                                  Drain Valve
                       Complete
                       Assembly

                                          Universal
                                          O-ring Kit

                                       Figure 7: Coalescing Oil Removal Filter

Replacement            Each kit includes one replacement filter element, one filter element
Coalescing Oil         O-ring, and one filter bowl O-ring (refer to Figure 7). To replace the filter
Removal Filter         element, proceed as follows:
Element Kit            1.   Remove the service bypass valve locking pin, and push the plunger to
                            the right into the bypass position. Doing so will unload the pressure
                            in the filter bowl.
                       2.   Disconnect the drain tubing.
                       3.   Depress the lever on the filter bowl clamp, and turn it 1/8 revolution
                            in either direction. Drop the metal bowl guard and bowl to expose the
                            filter element.

14 Air Dryers—A-4400 Series Technical Bulletin
                 4.   Viewing the old filter from the bottom, turn the element
                      counterclockwise to remove it.
                 5.   Clean the small screen around the drain seat of the automatic drain
                      valve by turning the filter bowl upside down and tapping it lightly.
                 6.   Visually inspect the bowl for signs of cracking. If the bowl is
                      cracked, it will be necessary to replace the complete assembly
                      (A-4000-1048 or A-4000-1049 ordered separately). If the bowl is not
                      cracked, clean it and the drain valve assembly using a liquid
                      household detergent.
                 7.   Install the new filter element and connect the drain. For optimal
                      filtering performance, it is recommended that the filter element be
                      presoaked with clean oil.
                 8.   Return the service bypass valve to normal operation by pushing the
                      plunger left to its original position. Reinstall the locking pin to ensure
                      that the plunger remains positioned for normal operation.

Activated        Refer to the white service label on the activated carbon filter element
Carbon Oil       being replaced for the proper replacement procedure.
Vapor Removal    After the activated carbon filter element has been replaced, apply the
Filter           white service label included with the new element, and record the next
                 replacement date (month and year). Determine this date following the
                 procedure outlined earlier in the Activated Carbon Filter Installation
                 section.

Pressure         Upon system startup, the output of the pressure reducing valve would be
Reducing Valve   approximately 15 to 20 psig (105 to 140 kPa).
                 Note:    For optimal performance, it is suggested that the pressure
                          reducing valve be readjusted at the normal system flow rate.
                 To adjust this pressure, pull up on the black knob and turn until the
                 desired pressure is read on the low pressure gauge. Push down on the
                 knob to lock the desired pressure setting. The safety relief valve is factory
                 set at approximately 33 psig (231 kPa).

Power On/Fail    The power on/fail lamp is located below the coalescing oil removal filter.
Lamp             The lamp is ON (illuminated) when there is power to the A-4400 and the
                 compressor overload relay is closed (no overload condition exists). If the
                 air dryer is running and the power on/fail lamp is OFF, the lamp will need
                 to be replaced as follows:
                 1.   Disconnect the power supply to the air dryer.
                 2.   Cut the two leads leaving behind a convenient length of wire for use
                      with the replacement bulb.

                                                 Air Dryers—A-4400 Series Technical Bulletin   15
                       3.   Slide the old lamp forward out of its cutout and discard; a pliers may
                            be required.
                       4.   Splice the replacement bulb to the existing leads using wire nuts (field
                            furnished).
                       5.   Slide the replacement lamp (A-4300-602 ordered separately) into the
                            cutout and push in until it reaches the chrome stop.
                       6.   Reconnect the power supply to the air dryer.
                       7.   Check that the lamp is illuminated when the compressor is running.

Refrigeration          Note: Due to the extremely small refrigerant charge in these units
Service                      (as noted on the unit nameplate), the service valve should only be
                             used when evacuating and recharging the unit. When removing
                             charging equipment from the service valve, care must be taken to
                             avoid releasing any amount of refrigerant. The integral evaporator
                             pressure gauge (with its gauge correction) on each unit should be
                             used for all service procedures.
                       The A-4400 is factory set to follow the Evaporator Pressure vs. Ambient
                       Temperature curve illustrated in Figure 5. If at no load, the evaporator
                       pressure rises above the acceptable operating zone, one or more of the
                       following conditions may exist.
                       •    The ambient temperature or the air flow may be above the specified
                            limits.
                       •    The expansion valve may be out of adjustment or stuck in the open
                            position.
                       •    The condenser may be dirty.
                       •    The condenser fan motor may be inoperative.
                       •    The compressor may be inoperative.
                       If the evaporator pressure is below the acceptable operating zone
                       (refer to Figure 5) then either the expansion valve is out of adjustment
                       or the refrigerant charge is low.
                       If it is necessary to readjust the expansion valve, proceed as follows:
                       1.   Switch the service bypass valve in order to bypass the dryer. Allow
                            the unit to run unloaded a minimum of 10 minutes prior to adjusting
                            the expansion valve.
                       2.   Remove the cover from the dryer.

16 Air Dryers—A-4400 Series Technical Bulletin
3.   Turn the expansion valve adjusting screw to provide an evaporator
     pressure that corresponds to the ambient temperature determined in
     Figure 5. Turning the screw clockwise increases the pressure;
     counterclockwise decreases the pressure. One complete revolution
     (360 degrees) equals a pressure change of approximately 10.5 psi
     (73.5 kPa).
     Note: If when adjusting the screw clockwise and counterclockwise,
           the expansion valve does not respond and the evaporator
           pressure remains high, a foreign object may be lodged in the
           expansion valve orifice. To clear the orifice, turn the
           expansion valve adjusting screw clockwise as far as possible,
           taking note of the number of revolutions made. Then return
           the screw counterclockwise to its original position and check
           the evaporator pressure.
4.   Allow 20 minutes running time to stabilize the system, then reset the
     refrigerant pressure if required.

If after adjusting the expansion valve setting, the evaporator pressure is
still too low, the refrigerant charge is probably low. To recharge the
system, proceed as follows:
1.   Disconnect the power supply to the air dryer.
2.   Remove the filter bowl and test for possible internal refrigerant leaks
     by allowing a small amount of supply air to pass through the unit.
     Check for traces of gaseous refrigerant in the escaping air using a
     HFC-134a detector at the condensate drain trap (refer to Figures 10
     and 11). If an internal leak is discovered, unit replacement is
     required. Reinstall the filter bowl when testing has been completed.
3.   Using a HFC-134a detector, test for possible external refrigerant
     leaks, paying particular attention to all solder joints. If an external
     leak is discovered, proceed as follows:
     Note: The service valve (as illustrated in Figures 8 and 9) provides
           access to the evaporator for checking or servicing. The
           service valve is a Schrader type valve with a sealing cap.
           To use the valve, unscrew the cap to expose the Schrader
           valve pin.
     a.   Use a vacuum pump to evacuate the unit of all refrigerant into an
          approved refrigerant receptacle before repairing leaks.
     b.   Repair any external leaks found using hard solder and flux.

                                Air Dryers—A-4400 Series Technical Bulletin    17
                       4.   Using a vacuum pump, evacuate any remaining air and moisture.
                       5.   Charge the unit with R-134a refrigerant to within 1/4 ounce of the
                            amount specified on the air dryer nameplate.
                       6.   Remove the charging manifold and replace the cap securely on the
                            service valve.
                       7.   Reinstall the A-4400 cover and reconnect the power supply to the air
                            dryer.
                       8.   If the evaporator pressure (gauge reading plus correction) does not
                            return to normal as illustrated in Figure 5, adjust the expansion valve
                            as described in the Refrigeration Service section.

                                         Cap

                             Figure 8: Service Valve Detail for Access to Evaporator

18 Air Dryers—A-4400 Series Technical Bulletin
Figure 9: A-4400 Series Refrigerated Air Dryer with Cover Removed

                            Air Dryers—A-4400 Series Technical Bulletin   19
                                                                                       Service Bypass
                                                                                            Valve
                                                                          Inlet From                                        Safety Relief
                                                                      Air Compressor                                           Valve
          Evaporator
                                                                                                                                  Regulated
           Pressure
                                                                                                                                   Output
            Gauge                                                                                                  PRV
                          Suction Line
                                                                                                                 With Low
               Discharge Line                          Tube-In-Tube
                                         Heat                                                                    Pressure
                                                        Counterflow
             Service                     Exchanger                                                                Gauge
                                                        Evaporator
              Valve                                                                                     High Pressure
                                  Condenser                                                                Output
                                Line      Auto Exp.                                  Activated
                                Voltage     Valve      Automatic        Coalescing    Carbon
                                                      Condensate        Oil Removal Oil Vapor
                                                      Drain Trap         Filter With Removal
                                                                         Automatic     Filter
                                                                            Drain

        Figure 10: Schematic of A-4400 Series Refrigerated Air Dryer with Service Bypass
                            Valve Positioned for Normal Operation
                 (Shown with Optional Factory Mounted Air Purification System)

                                                                         Inlet From                                         Safety Relief
                                                                      Air Compressor                                           Valve
          Evaporator
           Pressure                                                                              Exhaust                         Regulated
            Gauge                                                                                                                 Output
                                                                                  Service                         PRV
                        Suction Line
                                                                                  Bypass                        With Low
              Discharge Line                           Tube-In-Tube                Valve
                                         Heat                                                                   Pressure
                                                        Counterflow
            Service                      Exchanger                                                               Gauge
                                                        Evaporator
             Valve                                                                                      High Pressure
                                 Condenser                                                                 Output
                                Line     Auto Exp.                                  Activated
                                Voltage    Valve Automatic             Coalescing Carbon
                                                      Condensate       Oil Removal Oil Vapor
                                                      Drain Trap        Filter With Removal
                                                                        Automatic    Filter
                                                                           Drain

        Figure 11: Schematic of A-4400 Series Refrigerated Air Dryer with Service Bypass
                                   Valve in Bypass Position
                 (Shown with Optional Factory Mounted Air Purification System)

20 Air Dryers—A-4400 Series Technical Bulletin
Condenser     To replace the condenser fan motor, refer to Figure 12 and proceed as follows:
Fan Motor     1.    Disconnect the power supply to the air dryer.
Replacement
              2.    Remove the cover mounting screws and take the cover off the unit.
                    Retain screws for reassembly.
              3.    Remove the cable tie securing the cord to the protecting screen.
              4.    Working from underneath the cabinet and using a 3/8 in. wrench, remove
                    the two mounting screws that secure the fan assembly to the cabinet base.
                    Retain screws for reassembly.
              5.    Slide the fan motor assembly out of the cabinet.
              6.    Noting the orientation of the fan blade, use a pliers to loosen and remove
                    the fan blade retaining nut and the fan blade. Retain parts for reassembly.
              7.    Using a wire cutter, cut the two leads in a convenient location.
              8.    Using a 1/4 in. wrench, loosen and remove the two motor mounting
                    screws and the fan motor support “L” bracket. Retain the screws and
                    bracket for reassembly.
              9.    Noting the orientation of the motor and its leads, peel the old fan motor
                    off of the protecting screen, leaving as much of the black vibration
                    dampening tape behind as possible.
              10.   Install the replacement fan motor (A-4300-601 ordered separately) in the
                    same orientation noted in Step 9.
              11.   Secure the motor and the fan motor support “L” bracket to the mounting
                    bracket using the screws retained in Step 8.
              12.   Using a cable tie (field furnished), secure the motor leads to the
                    protecting screen to keep the motor leads away from the fan blades
                    during operation.
              13.   Reassemble the fan blade to the motor in the same orientation noted in
                    Step 6, and secure it in place using the fan blade retaining nut.
              14.   Slide the fan motor assembly into the cabinet, over its base mounting
                    location.
              15.   Secure the fan motor assembly to the cabinet base using a 3/8 in. wrench
                    and the mounting screws retained in Step 4.

                                                  Air Dryers—A-4400 Series Technical Bulletin   21
                       16.   Splice the two leads of the replacement fan motor to the existing leads
                             using wire nuts (field furnished).
                       17.   Reconnect the power supply to the air dryer.
                       18.   Check for excessive vibration. If the unit is vibrating excessively, it is
                             likely that one or more of the fan blades is misaligned. To align the
                             blades, refer to the Excessive Vibration section in this bulletin.
                       19.   Reinstall the cabinet cover, and using a 1/4 in. hex-head wrench blade
                             screwdriver, secure it in place using the cover mounting screws retained
                             in Step 2.

                                       Figure 12: Condenser Fan Motor Assembly

22 Air Dryers—A-4400 Series Technical Bulletin
Condenser           Check the condenser periodically for dust/particle buildup between the fins;
                    this buildup could eventually lead to a reduction in heat transfer. If there is a
                    buildup, remove it using a vacuum cleaner and a soft brush.

     Air Dryer      If there is power to the air dryer and the compressor is not operating, using an
     Compressor     ohmmeter and referring to Figure 13, check the electrical service as follows:
     Motor Wiring   1.   Disconnect the power supply to the air dryer.
     Circuit
                    2.   Remove the screw terminal from the overload at 3 and check for
                         continuity between 3 and C1 on the overload. If there is no continuity,
                         the overload may be tripped. Allow 10 minutes to pass, then check again.
                         If there is still no continuity, the overload relay (Tecumseh 830-10041)
                         must be replaced.
                    3.   Pull the relay off the compressor terminals (keeping the relay upright) and
                         check for continuity between 1 and S1. If there is continuity, the relay
                         contacts are closed when they should be open and the relay (Tecumseh
                         820-10052) must be replaced.
                    4.   Check for continuity between 1 and M1. If there is no continuity, the
                         relay (Tecumseh 820-10052) must be replaced.
                    5.   Check for continuity between compressor terminals C and M. At an
                         ambient temperature of 77°F (25°C), the run winding resistance across
                         terminals C and M should be approximately 3.1 ohms. If the run winding
                         resistance is drastically different from the above, either replace the
                         compressor or the entire air dryer.
                    6.   Check for continuity between compressor terminals C and S. At an
                         ambient temperature of 77°F (25°C), the start winding resistance across
                         terminals C and S should be approximately 5.6 ohms. If the start winding
                         resistance is drastically different from the above, replace either the
                         compressor or the entire air dryer.
                    7.   Check for continuity between compressor terminal C and the shell of the
                         compressor. If there is continuity, either replace the compressor or the
                         entire air dryer.

                    If all of the above tests prove satisfactory and the unit still fails to operate
                    properly, replace the relay (Tecumseh 820-10052). Doing so eliminates any
                    faulty electrical characteristics (such as improper pickup or dropout), which
                    cannot be determined by any of the above tests. If the new relay fails to
                    correct the problem, either replace the compressor or the entire air dryer.

                                                         Air Dryers—A-4400 Series Technical Bulletin    23
                                Figure 13: Air Dryer Compressor Motor Wiring Diagram

Excessive              If the A-4400 appears to be vibrating excessively, it is likely that one or more
Vibration              of the condenser fan blades is misaligned. To align all five fan blades, proceed
                       as follows:
                       1.   Disconnect the power supply to the air dryer.
                       2.   Place a reference (such as a piece of cardboard) against the trailing edge of
                            one of the fan blades.
                       3.   Manually rotate the fan and observe the relative alignment of all five
                            blades with respect to the reference in Step 2.
                       4.   If a blade appears to be out of alignment as compared to the other blades,
                            bend the blade back into line by hand. Continue until the trailing edges of
                            all five blades are aligned horizontally within 1/4 in. (6 mm).
                       5.   Reconnect the power supply to the air dryer and check that the excessive
                            vibration has been eliminated. Repeat the above procedure as necessary.

24 Air Dryers—A-4400 Series Technical Bulletin
                Specifications
                    Product       A-4400 Series Refrigerated Air Dryers
            Electrical Rating     115 Volt 60 Hz, Single-phase Electrical Service
               Current Draw       5.75 Amperes
                 Refrigerant      R-134a (HFC)
                Compressor        Hermetically Sealed
            Agency Listings       UL Listed, cUL Listed, Category Code SROT, File SA8490
         Ambient Operating        40 to 115°F (4 to 46°C) with maximum dew point of 86°F (30°C), non-condensing
         Temperature Limits
           Ambient Storage
         Temperature Limits       -40 to 140°F (-40 to 60°C)
         Pressure Drop with       A-4412-1: 10 psig (70 kPa);         A-4412-2: 4 psig (28 kPa)
80 psig (560 kPa) Supply and      A-4417-1: 17 psig (119 kPa); A-4417-2: 8 psig (56 kPa)
                 Rated Flow       A-4423-1: 33 psig (231 kPa); A-4423-2: 15 psig (105 kPa)
    Maximum Input Pressure        125 psig (875 kPa)
               Connections        3/8 in. Compression Fittings for Polytubing or Copper Tubing
                       Finish     Gray Enamel
Accessory (Order Separately)      A-4000-154 Manual Override for Coalescing Oil Filters
               The performance specifications are nominal and conform to acceptable industry standards. For application at
               conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not
               be liable for damages resulting from misapplication or misuse of its products.

                                                                   Air Dryers—A-4400 Series Technical Bulletin                   25
                       Repair Information

                                           Figure 14: Repair Parts (See Table 3)

                                           Figure 15: Repair Parts (See Table 3)

26 Air Dryers—A-4400 Series Technical Bulletin
Table 3: Repair Parts
                                            Shipping                           CodeNumber
                   Description               Weight          Date Codes          Date Codes            Date Codes
 Item                                          lb*          through RY1         after RY1 9923          after RY1
                                                                9923                                       1351
   A      System Pressure Gauge                 0.1                                G-2010-5
   B      Evaporator Pressure Gauge             0.2                              A-4300-603
   C      Pressure Reducing Valve               1.7                                R-130-14
   D      Service Bypass Valve                  0.4                              A-4300-600
          Condensate Filter:
               Complete Assembly                1.1          A-4000-158**                     A-4000-156
   E           Bowl O-Ring                     0.02           A-4110-610                      A-4400-610
               Replacement Drain Valve          0.1           A-4110-607                      A-4400-607
               Particle Filter Element         0.05           A-4110-608                      A-4400-608
          Coalescing Filter:
               Complete Assembly for
               Air Dryer Model
               A-4412                           2.0                              A-4000-1048
               A-4417 and A-4423                2.5                              A-4000-1049
          Filter Element with O-Rings:
               Air Dryer Model
   F
               A-4412                           0.1                              A-4110-604
               A-4417 and A-4423                0.1                              A-4000-604
          Universal O-Ring Kit for Filter
                                               0.03                              A-4000-620
          Element Bowl
          Replacement Drain Valve***            0.2                            A-4000-6010****
          Manual Override for Drain             .25                            A-4000-1054****
          Valve
          Carbon Filter Element Only:
               Air Dryer Model
   G
               A-4412                           1.7                              A-4000-632
               A-4417 and A-4423                3.8                              A-4000-633
   H      Safety Relief Valve                   0.1                              A-4000-144
   J      Condenser Fan Motor                   2.2                              A-4300-601
   K      Power On/Fail Lamp                   0.05                              A-4300-602
          Insulating Tape (Not Shown)
   L
          (Order in multiples of 30 ft)         1.2                              A-4210-603