YVAA, YVFA, YVAM, YLAA EBMPapst Variable Speed Fan Troubleshooting Guide

Document typeService Information Letter
Document numberSI0487
EquipmentYLAA Scroll Chiller
BrandYORK
File size1.6 MB

Fault codes in this document

Fault Code (Red LED color)

Code / displayMeaningCauseActionPage
Phase failure
(Red LED, 1 pulse)
Automatic restart once phase failure is corrected4
Power module overheated
(Red LED, 3 pulses)
Power cycle required4
Internal communications error between primary/secondary controller
(Red LED, 4 pulses)
Primary = electronics, Secondary = motorPower cycle required4
Motor overheated
(Red LED, 6 pulses)
Power cycle required4
Hall sensor error
(Red LED, 7 pulses)
Power cycle required4
Motor blocked
(Red LED, 8 pulses)
Automatic restart after blockage is cleared4
Speed limit exceeded
(Red LED, 9 pulses)
Automatic restart4
Rotor position sensor calibration error
(Red LED, 11 pulses)
Power cycle required4
DC-link undervoltage
(Red LED, 13 pulses)
Automatic restart after undervoltage is cleared4

Fault Code (Yellow LED color)

Code / displayMeaningCauseActionPage
Current limitation in action
(Yellow LED, 1 pulse)
Current limited to prevent damage of the electronics4
Line impedance too high
(Yellow LED, 2 pulses)
DC link voltage is instable4
Power limiter in action
(Yellow LED, 3 pulses)
Derating is active4
Output stage temperature high
(Yellow LED, 4 pulses)
Temperature > 105°C4
Motor temperature high
(Yellow LED, 5 pulses)
Temperature > 130°C4
Temperature inside electronics high
(Yellow LED, 6 pulses)
Temperature > 105°C4
DC-link voltage low
(Yellow LED, 7 pulses)
DC-link < 460 V4
Calibration of rotor position
(Yellow LED, 9 pulses)
Calibration of rotor position sensor in progress4
Cable break at analog or PWM input for analog set value
(Yellow LED, 11 pulses)
Check wiring. NOTE: This fault code may be present if the command signal to the motor is 0%. Increase command signal to check if wiring issue.4
DC-link voltage high
(Yellow LED, 13 pulses)
DC-link > 850 V4
Line-voltage high
(Yellow LED, 15 pulses)
U1_peak > 850 VDC4
Shedding function active
(Yellow LED, 16 pulses)
Shedding function is active and fan is blocked4