YLAA0041 - YLAA0230 Air-Cooled Scroll Chillers with Brazed Plate Heat Exchanger, Style B (60 Hz), 4 to 12 Fan, 40 ton to 230 ton, 140kW to 800 kW, Installation, Operation, Maintenance

Document typeInstallation Operation and Maintenance Guide
Document number150.72-ICOM6
EquipmentYLAA Scroll Chiller
BrandYORK
Revised2026-02-24
File size17.9 MB

Fault codes in this document

Unit Safeties

Code / displayMeaningCauseActionPage
UNIT FAULT:
LOW AMBIENT TEMP
Unit Fault Code 2 – Low Ambient Temperature CutoutOutdoor ambient temperature falls below the programmable Low Ambient Temp Cutout setpoint.Chiller shuts down. Auto reset: restart can occur when the temperature rises 2°F above the cutoff.144
UNIT FAULT:
LOW LIQUID TEMP
Unit Fault Code 4 – Low Leaving Chilled Liquid Temperature Cutout (evaporator freeze-up protection)Leaving chilled liquid temperature (water or glycol) drops below the cutout point; can occur under low flow conditions or if the micro panel setpoint values are improperly programmed.Chiller shuts down. Auto reset: restart can occur when chilled liquid temperature rises 2°F above the cutout.144
UNIT FAULT:
CHECK LIQ TEMP SENS
Check Liquid Temperature Sensor fault (unit fault)While the unit is running and the control panel is programmed for leaving chilled liquid temperature control, the leaving chilled liquid temperature rises over 2.0°F above the entering chilled liquid temperature for 60 continuous seconds. Disabled if the Entering Chilled Liquid Temperature Sensor is disabled under Unit Setup.Chiller shuts down; requires a manual reset to restart the unit.141
UNIT FAULT:
PUMP TRIP
Unit Fault Code 27 – Pump Trip (Hydro Pumps 1 or Hydro Pumps 2)Single pump: the manual motor starter protecting the pump from short circuit or overload conditions has tripped or been set to OFF. Two pumps (duty and standby): both manual motor starters protecting the pumps have tripped or both have been set to OFF.Setting the device to ON (at least one of the devices on dual-pump units) resets the trip. Auto per Table 15.144
UNIT FAULT:
PUMP FAIL MAKE FLOW
Unit Fault Code 28 – Pump Flow Failure (Hydro Pumps 1 or Hydro Pumps 2)After the 30-second stop-to-start timer the pump is started (Leaving Liquid Temperature Cutout active, any compressor running, or daily schedule not calling for shutdown with unit switch ON and remote stop/start input closed) but the flow switch does not close within 10 seconds. On dual-pump units the running pump is stopped and the standby pump started; if the flow switch still does not close within a further 10 seconds the unit locks out.Unit locks out and the running pump is stopped. Reset by setting the unit switch to OFF then back to ON. Locks out on the first fault (1x). When attempting to clear this fault, check that one of the manual motor starters protecting the pumps has not tripped.141
UNIT FAULT:
115 VAC UNDER VOLTAGE
Under Voltage Safety (unit fault)The 115 VAC to the micro panel drops below a certain level, where malfunction of the microprocessor could result in system damage.A unit fault is initiated to safely shut down the unit. Restart is allowed after the unit is fully powered again and the anti-recycle timers have finished counting down.141
UNIT FAULT:
HIGH MTR CURR
Unit Fault Code 22 – Unit High Motor Current (Current Feedback One Per Unit option)With the CURRENT FEEDBACK ONE PER UNIT option selected, the voltage exceeds the programmed trip voltage for 5 seconds. The trip voltage is programmed at the factory according to compressor or unit RLA.Unit shuts down; restart occurs after the anti-recycle timer times out. Auto per Table 15.144
FLOW SWITCH OPENUnit Fault Code 31 – Flow Switch OpenThe flow switch contacts connected to Terminals 13 and 14 of XTBC1 are open. A 3-second delay is built into software to prevent nuisance shutdowns due to erroneous signals from the flow switch.Auto per Table 15: allows restart once meeting the required conditions.137
HIGH AMBIENT TEMPERATUREUnit Fault Code 29 – High Ambient TemperatureAuto per Table 15/Table 16: allows restart once meeting the required conditions.144

Unit Warnings

Code / displayMeaningCauseActionPage
!! LOW BATTERY !!
CHECK PROG/SETP/OPTN
Low Battery Warning (unit warning; not a unit safety, not logged to the history buffer)On micro panel power-up the RTC battery is checked and a low battery is found; all programmed setpoints, program values, options, time, schedule, and history buffers are lost and reset to their default values, which may not be the required operating values.Unit is prevented from running until the PROGRAM key is pressed; pressing PROGRAM sets the anti-recycle timers to the programmed anti-recycle time to allow checking/reprogramming of values and options. Replace the RTC/battery (031-02565-000, located at U5 on the microboard) as soon as possible. Will not auto-restart; operator intervention required.145
INCORRECT
UNIT TYPE
Incorrect Unit Type warningThe condensing unit jumper is installed between J11-12 and J11-7.This jumper must be removed to operate the chiller. Will not auto-restart; operator intervention required.145

System Safeties

Code / displayMeaningCauseActionPage
SYS 1 HIGH DSCH PRES
SYS 2 HIGH DSCH PRES
System Fault Code 5 – High Discharge Pressure (software cutout, backed up by the mechanical high pressure cutout switch in the refrigerant circuit)The programmable discharge pressure cutout is exceeded; discharge transducers must be installed for this function. When an operating envelope is enabled, the effective cutout is set to 10 psig above the discharge pressure unload limit if suction pressure is less than 94.0 psig (standard envelope) or less than 42.0 psig (extended envelope).System shuts down; restart allowed when the discharge pressure falls 40 psig below the cutout. 3x: automatic restart on the first and second fault with a lockout on the third fault within 90 minutes; clear the lockout by turning the system switch (under OPTIONS key) OFF and then back ON.150
SYS 1 LOW SUCT PRESS
SYS 2 LOW SUCT PRESS
System Fault Code 7 – Low Suction Pressure cutout (protects the chiller from evaporator freeze-up)Suction pressure falls below the ramped cutout point: at system start the cutout is set to 10% of the programmed value and ramped up to the programmed point over 3 minutes (completely ignored for the first 30 seconds of run time); after the first 3 minutes, if suction pressure falls below the programmed cutout, a transient protection routine sets the cutout at 10% of the programmed value and ramps it up over the next 30 seconds. Can occur with a low refrigerant charge or a restriction in the refrigerant circuit.System stops. 3x: automatic restart on the first and second fault with a lockout on the third fault in 90 minutes; clear the lockout via the system switch (under OPTIONS key) OFF then back ON. Repeated starts after resetting a low suction pressure fault will cause evaporator freeze-up – immediate steps should be taken to identify the cause.145
SYS 1 SP/ FREEZE WARN
SYS 2 SP/ FREEZE WARN
Suction pressure / freeze warning – transient protection routine activeAfter the first 3 minutes, the suction pressure falls below the programmed cutout setting; the cutout is set at 10% of the programmed value and ramped up over the next 30 seconds. Suction pressure transducers must be enabled for this function to work.The system will stop if at any time during this 30 seconds the suction pressure falls below the ramped cutout.145
SYS 1 MP/HPCO FAULT
SYS 2 MP/HPCO FAULT
System Fault Code 18 – Motor Protector / Mechanical High Pressure Cutout faultCR1 (SYS 1) or CR2 (SYS 2) relays de-energize due to the HP switch or motor protector opening, causing 0 VDC to be read on the microboard input. The internal motor protector opens at 185°F to 248°F (85°C to 120°C); the mechanical HP switch opens at 585 psig plus or minus 10 psig and closes at 330 psig plus or minus 25 psig. The compressor discharge temperature sensor also opens the motor protector circuit when it senses high internal scroll temperature (e.g., low refrigerant charge or superheat too high). Message displayed only after the third fault in 90 minutes.System is locked out and will not restart; the fault condition is cleared when a 30 VDC signal is restored to the input. During the first two faults the MP/HP INHIBIT message is displayed and the system is not locked out. Whenever the motor protector or discharge sensor shuts down a compressor, the internal compressor contacts open for 30 minutes so motor/scroll temperatures can dissipate before the system is permitted to restart.188
SYS 1 HIGH MTR CURR
SYS 2 HIGH MTR CURR
System Fault Code 17 – System High Motor Current (System Current Feedback option)Condition present when CR1 (SYS 1) or CR2 (SYS 2) opens, causing 0 V to be read on the input (motor protector faulted or mechanical high pressure cutout open); only occurs when a system is not running.Condition cleared and the system allowed to start when a 30 V signal is restored to the input by CR1 or CR2 closing. 3x per Table 15.150
SYS 1 LOW SUPERHEAT
SYS 2 LOW SUPERHEAT
System Fault Code 23 – Low Suction Superheat cutout (EEV mode only); also displayed as “SYS x LOW SUCT SHE AT”Protects the compressors from liquid flowing back due to low suction superheat. Triggered when the suction superheat is lower than 2.0°F for 3 seconds, or when the LLSV is closed 10 times in 2 minutes due to low superheat. Ignored for the first 15 seconds of system run time; trips after the programmed trip time has passed.Fault resets if the superheat rises above 2°F; lockout after three shutdowns in 90 minutes. 3x per Table 15.145
SYS 1 SENSOR FAILURE
SYS 2 SENSOR FAILURE
System Fault Code 24 – Sensor Failure cutout (EEV mode only)Prevents the EEV from running when the sensors measuring superheat are not functioning properly; shuts the system down if either the suction temperature or suction pressure sensors read out of range high or low for 3 seconds. Ignored for the first 15 seconds of system run time.Locks out on the first fault; will not automatically restart. 1x per Table 15.145
LOW EVAPORATOR TEMPERATURE (R407c ONLY – N/A HP HEATING MODE)System Fault Code 19 – Low Evaporator Temperature (R407c only; not applicable in heat pump heating mode)3x: automatically restarts on the first and second fault with a lockout on the third fault in 90 minutes.144
DISCHARGE INHIBIT (HEAT PUMP HEATING MODE ONLY)System Fault Code 25 – Discharge Inhibit (heat pump heating mode only)3x: automatically restarts on the first and second fault with a lockout on the third fault in 90 minutes.144

System Inhibits

Code / displayMeaningCauseActionPage
SYS 1 MP/HPCO INHIB
SYS 2 MP/HPCO INHIB
System Inhibit Code 26 – Motor Protector / High Pressure Cutout InhibitPrevents the system from trying to start when a motor protector is faulted or the mechanical high pressure cutout is open; condition present when CR1 (SYS 1) or CR2 (SYS 2) opens, causing 0 VDC to be read on the input. Only occurs when a system is not running; also displayed during the 30-minute timeout after a motor protector/discharge-sensor shutdown while the internal compressor contacts are open or the HPCO is open.Compressors will not be permitted to start while displayed; condition cleared and restart allowed when a 30 VDC signal is restored to the input by CR1 or CR2 closing (contacts close after the 30-minute timeout). Auto per Table 15.188
SYS 1 ATV SUCT PRESS
SYS 2 ATV SUCT PRESS
System Inhibit Code 30 – Anti-Vacuum Low Pressure CutoutIf the system is running, it shuts down when the suction pressure falls below the anti-vacuum low pressure cutout for longer than the programmed Anti-Vacuum Delay Time; if the system is not running, it is inhibited from starting while the suction pressure is below the anti-vacuum low pressure cutout.Standard system fault: lockout after 3 occurrences in 90 minutes; the fault cannot be reset until the fault condition is resolved. 3x per Table 15.143
LEAVING CHILLED LIQUID TEMPERATURE SENSOR FAULTSystem Inhibit Code 32 – Leaving Chilled Liquid Temperature Sensor Fault3x: automatically restarts on the first and second fault with a lockout on the third fault in 90 minutes.144
SYS 1 LOW DS CH SHE AT
SYS 2 LOW DS CH SHE AT
System Inhibit Code 33 – Low Discharge SuperheatSystem Discharge Superheat drops below 18°F; trips after 5 minutes have passed. Only active when Discharge Temperature Sensors are enabled.Fault resets if the superheat rises above 18°F; will lockout after three shutdowns in 90 minutes. Listed as Auto in Table 15 (allows restart once meeting the required conditions).145

Real Time Error Numbers

Code / displayMeaningCauseActionPage
0All okNo error present.175
1Datum type ok test failedReset via the REAL TIME ERROR screen (set RESET = 1/YES); reboot required (cycle power) after settings are changed.175
2English text too longReset via the REAL TIME ERROR screen (set RESET = 1/YES); reboot required (cycle power) after settings are changed.175
3Floating point exceptionReset via the REAL TIME ERROR screen (set RESET = 1/YES); reboot required (cycle power) after settings are changed.175
4Get packet failedReset via the REAL TIME ERROR screen (set RESET = 1/YES); reboot required (cycle power) after settings are changed.175
5Get type failedReset via the REAL TIME ERROR screen (set RESET = 1/YES); reboot required (cycle power) after settings are changed.175
6Invalid unit conversionReset via the REAL TIME ERROR screen (set RESET = 1/YES); reboot required (cycle power) after settings are changed.175
7Invalid hardware selectionReset via the REAL TIME ERROR screen (set RESET = 1/YES); reboot required (cycle power) after settings are changed.175
8Real time faultReset via the REAL TIME ERROR screen (set RESET = 1/YES); reboot required (cycle power) after settings are changed.175
9Spanish text too longReset via the REAL TIME ERROR screen (set RESET = 1/YES); reboot required (cycle power) after settings are changed.175
10Thread exitedReset via the REAL TIME ERROR screen (set RESET = 1/YES); reboot required (cycle power) after settings are changed.175
11Thread failedReset via the REAL TIME ERROR screen (set RESET = 1/YES); reboot required (cycle power) after settings are changed.175
12Thread stalledReset via the REAL TIME ERROR screen (set RESET = 1/YES); reboot required (cycle power) after settings are changed.175
13IO board resetReset via the REAL TIME ERROR screen (set RESET = 1/YES); reboot required (cycle power) after settings are changed.175
14BRAM invalidReset via the REAL TIME ERROR screen (set RESET = 1/YES); reboot required (cycle power) after settings are changed.175
15BACnet setup failedReset via the REAL TIME ERROR screen (set RESET = 1/YES); reboot required (cycle power) after settings are changed.175

Flash Card Update

Code / displayMeaningCauseActionPage
FLASH CARD UPDATE
ERROR XXXXX
Flash card operating-software update error (error code shown as XXXXX)An error occurred during the flash card update: the incorrect Flash Card was used, incorrect chiller software was used, the Flash Card is defective, or the IPU and I/O combo board is bad.The original program will still be active and no reboot will occur; ensure the correct Flash Card was used.168