Fault · YORK YK · Water-cooled centrifugal chiller

YORK YKProgram Initiated Reset

On the display

The display shows PROGRAM INITIATED RESET. In the manual's printed example the message carries a time stamp in front of it: MON XX:XX AM - PROGRAM INITIATED RESET. The shutdown table lists the same message as Program Initiated Reset; these are the only spellings used for this message in the manuals.

What it means

This is a cycling shutdown: the watchdog timer circuit has reset the software program, and the chiller shuts down as a result. The manual explains the mechanism this way — the Micro Board did not receive a hardware-generated interrupt on schedule, the typical case being an Analog/Digital Converter interrupt. When the time needed to step through the program is longer than allowable, the watchdog timer circuit resets the microprocessor and the software program is initialized at its beginning. Because it is a cycling shutdown rather than a lockout, the unit comes back by itself, as described under Reset below.

Why it appears

  • The watchdog timer circuit has reset the software program — the shutdown cause listed in the manual's Table 1.
  • The Micro Board did not receive a hardware-generated interrupt on schedule; the typical interrupt is an Analog/Digital Converter interrupt.
  • A Micro Board hardware failure — the manual says the message is indicative of this.
  • Electrical noise on the Micro Board.

Reset and restart

No reset action is required. The manual's action for this message is simply: The chiller will automatically restart. No key-press reset procedure is described for this message; the unit returns to operation on its own after the cycling shutdown.

Questions engineers ask

What does Program Initiated Reset mean on a YORK YK?

It is a cycling shutdown: the watchdog timer circuit has reset the software program, so the program is initialized at its beginning and the chiller shuts down.

Why does the YORK YK show Program Initiated Reset?

The Micro Board did not receive a hardware-generated interrupt on schedule, typically an Analog/Digital Converter interrupt. The manual says the message is indicative of a Micro Board hardware failure or electrical noise on the Micro Board.

How do I clear Program Initiated Reset on a YORK YK?

You do not reset it by hand. The manual states that the chiller will automatically restart after this cycling shutdown.

Source

Written from the manufacturer's manuals for the YORK YK; every number and designation on this page is checked against them before publication. The row of the manual this message comes from:

All YORK YK messages: fault codes · YORK YK documentation · YORK manuals