SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Fault · YORK YK · Water-cooled centrifugal chiller

YORK YKHIGH OIL TEMP

On the display

The panel reads MON XX:XX AM - HIGH OIL TEMP; MON XX:XX AM is the date and time the shutdown was recorded, not part of the message text. In the chiller's history log the same event is printed as HIGH OIL TEMPERATURE (the sample log shows, for instance, DAY 10:30 AM - HIGH OIL TEMPERATURE). The manual lists it among the system shutdown messages.

What it means

HIGH OIL TEMP is a safety shutdown: the chiller is shut down because the oil temperature has increased to 180°F (82.2°C). The temperature is sensed by thermistor RT3. The system will be allowed to restart when the temperature decreases to 179°F (81.6°C), so the chiller remains shut down until the oil has cooled to that point.

Why it appears

  • Oil temperature rose to the 180°F (82.2°C) trip point, sensed by thermistor RT3.
  • Improper lubrication brought about by restricted oil lines or oil passages, or by dirty oil filters — the manual names these in connection with a unit shutting down on high oil temperature (HOT).

What to check

  1. Confirm from the display or the history that HIGH OIL TEMP is the shutdown message, and note the time it occurred.
  2. Allow the oil temperature to decrease; the system permits no restart until it has fallen to 179°F (81.6°C).
  3. Check the oil lines and oil passages for restriction and the oil filters for dirt, since the manual ties HOT shutdowns to improper lubrication from these restrictions.
  4. Once the oil temperature is at or below the restart point, take the restart action described below.

Setpoints and thresholds

  • Safety shutdown trip point: 180°F (82.2°C) oil temperature.
  • Restart allowed when the oil temperature decreases to 179°F (81.6°C).
  • Sensing device: thermistor RT3.

Reset and restart

Restart is a manual step at the panel and is permitted only after the oil temperature has decreased to 179°F (81.6°C). The manual's instruction: To restart the chiller, press COMPRESSOR switch to STOP/RESET position and then to the START position.

Questions engineers ask

What oil temperature trips a YORK YK on HIGH OIL TEMP?

The safety shutdown occurs when the oil temperature increases to 180°F (82.2°C); the temperature is sensed by thermistor RT3.

How do I reset a YORK YK after a HIGH OIL TEMP shutdown?

Wait until the oil temperature decreases to 179°F (81.6°C), then press the COMPRESSOR switch to the STOP/RESET position and then to the START position.

Why does my YORK YK keep shutting down on high oil temperature?

The manual connects HOT shutdowns with improper lubrication brought about by restricted oil lines, passages, or dirty oil filters.

Messages next to this one

The same message on other models

Source

Written from the manufacturer's manuals for the YORK YK; every number and designation on this page is checked against them before publication. The row of the manual this message comes from:

All YORK YK messages: fault codes · YORK YK documentation · YORK manuals