SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

V24 YK OptiView Chiller Control Panel

Document typeService Information Letter
Document numberSI0265
EquipmentYK Centrifugal Chiller
BrandYORK
File size0.2 MB

Fault codes in this document

Subcooler Tube Freeze Prevention Logic

Code / displayMeaningCauseActionPage
Warning – Condenser – Freeze Threat From Low Pressure Panel warning of a potential condenser/subcooler tube freeze threat while the chiller is stopped. The chiller is Stopped and the Saturated Condenser Temperature falls below 35.0 °F. This warning will automatically reset whenever the chiller is running or the Saturated Condenser Temperature is > 40.0 °F. 2
Condenser – Freeze Threat – Flow Switch Open Panel warning of a potential condenser/subcooler tube freeze threat with the condenser flow switch open while the chiller is stopped. The Chiller is Stopped, the Saturated Condenser Temperature < 35.0 °F and the Condenser Flow Switch has been open for > 60 seconds or longer. This warning will automatically reset whenever the chiller is running or the Saturated Condenser Temperature is > 40.0 °F or the Condenser Flow Switch closes. 2

Every row above cites the page of this document it came from, and each one is re-read against that page by an automatic check before publication.

Manufacturer document, published here as reference material for equipment we supply. The original lives at docs.johnsoncontrols.com. The rights holder may ask us to take it down — we will.