V24 YK OptiView Chiller Control Panel

Document typeService Information Letter
Document numberSI0265
EquipmentYK Centrifugal Chiller
BrandYORK
File size0.2 MB

Fault codes in this document

2 of these messages are explained on a page of their own — cause, what to check, reset — written from this manual:

Subcooler Tube Freeze Prevention Logic

Code / displayMeaningCauseActionPage
Warning – Condenser – Freeze Threat From Low Pressure Panel warning of a potential condenser/subcooler tube freeze threat while the chiller is stopped. The chiller is Stopped and the Saturated Condenser Temperature falls below 35.0 °F. This warning will automatically reset whenever the chiller is running or the Saturated Condenser Temperature is > 40.0 °F. 2
Condenser – Freeze Threat – Flow Switch Open Panel warning of a potential condenser/subcooler tube freeze threat with the condenser flow switch open while the chiller is stopped. The Chiller is Stopped, the Saturated Condenser Temperature < 35.0 °F and the Condenser Flow Switch has been open for > 60 seconds or longer. This warning will automatically reset whenever the chiller is running or the Saturated Condenser Temperature is > 40.0 °F or the Condenser Flow Switch closes. 2