YK Centrifugal Chiller Software Enhancements Effective February 2003, Control Panel

Document typeService Information Letter
Document numberSI0058
EquipmentYK Centrifugal Chiller
BrandYORK
File size0.2 MB

Fault codes in this document

Oil Pressure Threshold

Code / displayMeaningCauseActionPage
Oil – High Differential PressureSafety shutdown; with this Flash Memory Card version the trip threshold for this safety shutdown is changed from 90 PSID to 120 PSID1

VSD Cycling Shutdown Messages

Code / displayMeaningCauseActionPage
VSD – Low Phase A Inverter Baseplate TemperatureCycling shutdown message applicable to this VSD (p/n 371-03789-xxx)The chiller has shutdown because the Baseplate temperature has decreased to <37 ºF.2
VSD – Low Phase B Inverter Baseplate TemperatureCycling shutdown message applicable to this VSD (p/n 371-03789-xxx)Same as Phase A: the chiller has shutdown because the Baseplate temperature has decreased to <37 ºF.2
VSD – Low Phase C Inverter Baseplate TemperatureCycling shutdown message applicable to this VSD (p/n 371-03789-xxx)Same as Phase A: the chiller has shutdown because the Baseplate temperature has decreased to <37 ºF.2

VSD Safety Shutdown Messages

Code / displayMeaningCauseActionPage
VSD – High Phase A Inverter Baseplate TemperatureSafety shutdown message applicable to this VSD (p/n 371-03789-xxx)The chiller has shutdown because the Baseplate temperature has increased to >158 ºF.2
VSD – High Phase B Inverter Baseplate TemperatureSafety shutdown message applicable to this VSD (p/n 371-03789-xxx)Same as Phase A: the chiller has shutdown because the Baseplate temperature has increased to >158 ºF.2
VSD – High Phase C Inverter Baseplate TemperatureSafety shutdown message applicable to this VSD (p/n 371-03789-xxx)Same as Phase A: the chiller has shutdown because the Baseplate temperature has increased to >158 ºF.2
Harmonic Filter – High Baseplate TemperatureSafety shutdown message applicable to this VSD (p/n 371-03789-xxx)The chiller has shutdown because the Baseplate temperature has increased to >194 ºF.2

Every row above cites the page of this document it came from, and each one is re-read against that page by an automatic check before publication.

Manufacturer document, published here as reference material for equipment we supply. The original lives at docs.johnsoncontrols.com. The rights holder may ask us to take it down — we will.