Fault codes in this document
Detection and Removal of Non-Condensible Gases
| Code / display | Meaning | Cause | Action | Page |
|---|---|---|---|---|
| Pressure in the storage vessel exceeds the saturation pressure of the refrigerant at the ambient temperature | Presence of non-condensible gases – if the pressure exceeds the saturation pressure by the amount shown in Table 8, there is a need to vent the non-condensible gases | Vent the non-condensible gases from the Schraeder type valve located on the top of the storage vessel for a period of fifteen seconds; repeat until the saturation pressure in the storage vessel is within the pressure range shown in Table 8; allow the storage vessel and contained refrigerant to equalize to ambient temperature between ventings | 17 |
Checking Compressor for Performance
| Code / display | Meaning | Cause | Action | Page |
|---|---|---|---|---|
| Discharge pressure drops more than 5 Ibs. (34.5 kPa) in one minute | Indicates the discharge valves of the valve assembly are leaking | Leaking discharge valves of the valve assembly | Discharge valves should be replaced; if in doubt as to whether the discharge valves leak, turn the compressor over by hand – if pressure rises and falls with each revolution, this will confirm the discharge valve leak | 31 |
| Failure of a compressor to reach 25” (85 kPa) vacuum | Indicates leaky suction valves; all compressors should pump a 25” (85 kPa) vacuum against normal head pressures | Leaky suction valves | 31 |
Gurgling Noise – Vacuum Pump Model CRR-1
| Code / display | Meaning | Cause | Action | Page |
|---|---|---|---|---|
| Gurgling noise | The vacuum pump will gurgle when the oil level in the pump is low | Oil level in the pump is low | 43 | |
| Gurgling noise | The vacuum pump will gurgle when a large leak is present in the system being evacuated | Large leak present in the system being evacuated | 43 |
Suction and Discharge Pressure Problems – Vacuum Pump Model CRR-1
| Code / display | Meaning | Cause | Action | Page |
|---|---|---|---|---|
| Insufficient suction pressure | Insufficient suction or discharge pressure | Leakage; oil contamination; V-belt slippage; low oil level – four major causes of insufficient suction or discharge pressure | Determine the pump’s ultimate pressure capability: if the suction obtainable is very poor, the pump may be badly contaminated, low on oil or malfunctioning; if the pressure is only slightly higher than the guaranteed ultimate pressure of the pump, an oil change may be all that is required | 43 |
| Insufficient discharge pressure | Discharge pressure insufficient although the recovery and/or recycle system is free from leaks and sufficient suction exists | Insufficient flow of refrigerant vapor into the vacuum pump; low oil level; V-belt slippage; leak in the oil case of the vacuum pump | Check to see that the tubing connecting the suction port to the chiller is not obstructed; if none of these explanations fit the observations, the pump may be malfunctioning and should be sent back to a repair facility | 43 |