SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

YK Style F MaxE with OptiView Control Center for Electro-Mechanical Starter, Solid State Starter and Variable Speed Drive, Control Panel

Document typeOperation Guide
Document number160.73-O2
EquipmentYK Centrifugal Chiller
BrandYORK
Revised2024-04-25
File size1.5 MB

Fault codes in this document

Table 2: Operational analysis chart

Code / displayMeaningCauseActionPage
1. SYMPTOM: ABNORMALLY HIGH DISCHARGE PRESSURETemperature difference between condensing temperature and water off condenser higher than normal. High discharge pressure.Air in condenser.25
1. SYMPTOM: ABNORMALLY HIGH DISCHARGE PRESSURETemperature difference between condensing temperature and water off condenser higher than normal. High discharge pressure.Condenser tubes dirty or scaled.Clean condenser tubes. Check water conditioning.25
1. SYMPTOM: ABNORMALLY HIGH DISCHARGE PRESSURETemperature difference between condensing temperature and water off condenser higher than normal. High discharge pressure.High condenser water temperature.Reduce condenser water inlet temperature. (Check cooling tower and water circulation.)25
1. SYMPTOM: ABNORMALLY HIGH DISCHARGE PRESSURETemperature difference between condenser water on and water off higher than normal, with normal evaporator pressure.Insufficient condensing water flow.Increase the quantity of water through the condenser to proper value.25
2. SYMPTOM: ABNORMALLY LOW SUCTION PRESSURETemperature difference between leaving chilled water and refrigerant in evaporator greater than normal with high discharge temperature.Insufficient charge of refrigerant.Check for leaks and charge refrigerant into system.25
2. SYMPTOM: ABNORMALLY LOW SUCTION PRESSURETemperature difference between leaving chilled water and refrigerant in evaporator greater than normal with high discharge temperature.Variable orifice problem.Remove obstruction.25
2. SYMPTOM: ABNORMALLY LOW SUCTION PRESSURETemperature difference between leaving chilled water and refrigerant in the evaporator greater than normal with normal discharge temperature.Evaporator tubes dirty or restricted.Clean evaporator tubes.25
2. SYMPTOM: ABNORMALLY LOW SUCTION PRESSURETemperature of chilled water too low with low motor amperes.Insufficient load for system capacity.Check prerotation vane motor operation and setting of low water temperature cutout.25
3. SYMPTOM: HIGH EVAPORATOR PRESSUREHigh chilled water temperature.Prerotation vanes fail to open.Check the prerotation vane motor positioning circuit.25
3. SYMPTOM: HIGH EVAPORATOR PRESSUREHigh chilled water temperature.System overload.Be sure the vanes are wide open (without overloading the motor) until the load decreases.25
4. SYMPTOM: NO OIL PRESSURE WHEN SYSTEM START BUTTON PUSHEDLow oil pressure displayed on control center; compressor will not start.Oil pump running in wrong direction.Check rotation of oil pump (Electrical Connections).25
4. SYMPTOM: NO OIL PRESSURE WHEN SYSTEM START BUTTON PUSHEDLow oil pressure displayed on control center; compressor will not start.Oil pump not running.Troubleshoot electrical problem with oil pump VSD.25
5. SYMPTOM: UNUSUALLY HIGH OIL PRESSURE DEVELOPS WHEN OIL PUMP RUNSUnusually high oil pressure is displayed when the oil pressure display key is pressed when the oil pump is running.High oil pressure transducer defective.Replace low or high oil pressure transducer.26
6. SYMPTOM: OIL PUMP VIBRATES OR IS NOISYOil pump vibrates or is extremely noisy with some oil pressure when pressing OIL PRESSURE display key.Oil not reaching pump suction inlet in sufficient quantity.Check oil level.26
6. SYMPTOM: OIL PUMP VIBRATES OR IS NOISYWhen oil pump is run without an oil supply it will vibrate and become extremely noisy.Worn or failed oil pump.Repair/Replace oil pump.26
7. SYMPTOM: REDUCED OIL PUMP CAPACITYOil pump pumping capacity.Excessive end clearance pump.Inspect and replace worn parts.26
7. SYMPTOM: REDUCED OIL PUMP CAPACITYOil pump pumping capacity.Other worn pump parts.Inspect and replace worn parts.26
7. SYMPTOM: REDUCED OIL PUMP CAPACITYOil pump pumping capacity.Partially blocked oil supply inlet.Check oil inlet for blockage.26
8. SYMPTOM: OIL PRESSURE GRADUALLY DECREASES (Noted by Observation of Daily Log Sheets)When oil pump VSD frequency increases to 55 + hz to maintain target oil pressure.Oil filter is dirty.Change oil filter.26
9. SYMPTOM: OIL PRESSURE SYSTEM CEASES TO RETURN AN OIL/REFRIGERANT SAMPLEOil refrigerant return not functioning.Filter-drier in oil return system dirty.Replace old filter-drier with new.26
9. SYMPTOM: OIL PRESSURE SYSTEM CEASES TO RETURN AN OIL/REFRIGERANT SAMPLEOil refrigerant return not functioning.Jet or orifice of oil return jet clogged.Remove jet, inspect for dirt. Remove dirt using solvent and replace.26
10. SYMPTOM: OIL PUMP FAILS TO DELIVER OIL PRESSURENo oil pressure registers when pressing OIL PRESSURE display key when oil pump runs.Faulty oil pressure transducer.Replace oil pressure transducer.26
10. SYMPTOM: OIL PUMP FAILS TO DELIVER OIL PRESSURENo oil pressure registers when pressing OIL PRESSURE display key when oil pump runs.Faulty wiring/connectors.26

Every row above cites the page of this document it came from, and each one is re-read against that page by an automatic check before publication.

Manufacturer document, published here as reference material for equipment we supply. The original lives at docs.johnsoncontrols.com. The rights holder may ask us to take it down — we will.