YCAV, YCIV IPU2 Software Version V15 – Low Temp Brine Control

Document typeService Information Letter
Document numberSI0617
EquipmentYCAV Variable Speed Drive Screw Chiller
BrandYORK
File size0.2 MB

Fault codes in this document

Faults

Code / displayMeaningCauseActionPage
Low Differential Oil Pressure CutoutSafety cutout.Differential pressure falls below the cutout.Software V15 adjustment to safety protocols during soft shutdown: for part numbers 031-03476-202, -210, -225, and AGR, if the VSD frequency is less than 25 Hz and soft shutdown is in progress, the safety is ignored and the VSD continues ramping the frequency at the soft shutdown rate. 30 seconds bypass time is added at the end of Soft Shutdown for this safety.2