SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Alarm · SINAMICS G120XA

A52963Mpc PID deviation exceeded

What it means

The alarm reports that, in the multi-pump control, the technology controller system deviation r2273 has exceeded the threshold p29546 at a moment when all motors of the system are running — the only motors not running are those that are under service or locked.

Why it appears

  • The technology controller system deviation r2273 has risen above the threshold set in p29546.
  • At the same time, all motors are running; the only exceptions are motors that are under service or locked.

What to check

  1. Determine whether any motors in the system are under service or locked, and repair or unlock them.
  2. Check the number of motors in the system; if it is less than four, add more motors to the system.

Parameters the manual names

  • r2273 (CO: technology controller system deviation) — the value this alarm monitors against the p29546 threshold.
  • p29546 (multi-pump control deviation threshold) — the limit that r2273 must stay below; the alarm is signalled once r2273 exceeds it.

The same on every family

Every manual that describes A52963 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
G120XANONENONESINAMICS G120XA PN converter · p. 1169

Questions technicians ask

What does alarm A52963 mean in the SINAMICS G120XA?

It signals that the technology controller system deviation r2273 has exceeded the threshold p29546 while all motors are running, apart from motors that are under service or locked.

How is A52963 remedied?

Repair or unlock any motors that are under service or locked. If the system contains fewer than four motors, add more motors to the system.

Which parameters belong to A52963?

r2273 holds the technology controller system deviation and p29546 sets the multi-pump control deviation threshold; the alarm appears when r2273 exceeds the p29546 value.

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A52xxx group · SINAMICS manuals · Siemens manuals