Selection and ordering data for system components (switch disconnectors, fuse switch disconnectors, cable-protection and semiconductor-protection fuses, fuse bases, circuit-breakers, contactors, radio-interference suppression filters, commutating reactors) matched to Siemens SIMOVERT MASTERDRIVES Vector Control Compact PLUS, Compact and chassis rectifier units. Each row pairs a drive power rating with the corresponding component order numbers.
Ключові дані
| Supply voltages | 3-ph. 380 V to 480 V AC / 500 V to 600 V AC / 660 V to 690 V AC |
|---|---|
| Power ratings covered | 15 kW to 1500 kW |
| Radio-interference suppression filter Pv range | 57 W to 840 W |
| Commutating reactor vD = 2 % | rated current 35.5 A to 1600 A |
| Commutating reactor vD = 4 % | rated current 35.5 A to 1600 A |
Застосування
- Rectifier units for Compact PLUS units (supply voltage 3-ph. 380 V to 480 V AC), 15/50/100 kW
- Rectifier units for Compact and chassis units: supply voltage 3-ph. 380 V to 480 V AC (15 to 800 kW), 500 V to 600 V AC (22 to 1100 kW), 660 V to 690 V AC (160 to 1500 kW)
- Rectifier unit for parallel connection
Особливості
- Semiconductor-protection fuses aR (without cable protection) already integrated in the standard unit from size 1000 A upwards
- Radio-interference suppression filters for 500 V and 690 V TT/TN systems with suffix codes R21/R22/S@@ depending on earthed or insulated IT systems
- Cable-protection fuses duty class gL; semiconductor-protection fuses duty class gR to IEC/DIN5)
Технічні дані
| Parameter | Value |
|---|---|
| Supply voltage ranges | 3-ph. 380 V to 480 V AC; 3-ph. 500 V to 600 V AC; 3-ph. 660 V to 690 V AC |
| Nominal power ratings covered | 15 kW … 1500 kW |
| Switch disconnector series | 3KA50…3KA58, 3KE45 |
| Fuse switch disconnector series | 3NP40, 3NP42, 3NP53, 3NP54 |
| Fuse sizes used in tables | 000, 00, 0, 1, 2, 3, 4, 4a |
| Cable-protection fuses | 3NA3 series, duty class gL, rated currents 40 A … 1250 A (up to 1000 A as single unit) |
| Semiconductor-protection fuses | 3NE1 series, duty class gR, rated currents 40 A … 630 A; aR fuses integrated in standard unit ≥ 1000 A |
| Fuse bases | 3NH3 530 (1000/4), 3NH7 520 (1250/4a) |
| Circuit-breakers | 3WN61 (800 A), 3WN62 (1000 A), 3WN63 (1250 A), 3WN64 (1600 A), 3WN65 (2000 A) |
| Main contactor/AC contactor | 3RT10 34 (45 A) … 3 x 3TK15 (1950 A); AC-1 rated currents up to 2000 A |
| Radio-interference suppression filter Pv | 57 W … 840 W |
| Commutating reactor vD = 2 % | 4EP37/4EP39/4EP40/4EU24…4EU43 series, Pv 57/60 W … 750 W, rated current 35.5 A … 1600 A |
| Commutating reactor vD = 4 % | 4EP39/4EP40/4EU24…4EU52 series, Pv 82/87 W … 1350 W, rated current 35.5 A … 1600 A |
Варіанти замовлення
- Filter suffix code selection (B84143–B xxx–S@@): for 500 V TT and TN systems (earthed system) → 20; for 690 V TT and TN systems (earthed system) → 21; for 380 V to 690 V IT systems (non-earthed and insulated system) → 24
- Example order codes for filters: B84143–A50–R21, B84143–A80–R21, B84143–A120–R21, B84143–B1000–S@@, B84143–B1600–S@@
Допуски та стандарти
- DIN5 (fuse standard reference per document footnote)
- IEC/DIN5 (semiconductor-protection fuses)
- DIN VDE 0100, VDE 0298 Part 4 (cable cross-section dimensioning)
Текст документа
SIMOVERT MASTERDRIVES Vector Control
Compact PLUS, Compact and Chassis Units
Recommended system components Compact PLUS units
for rectifier units Compact and chassis units
Selection and ordering data
Nominal Rectifier unit Switch disconnector2) Switch disconnector Fuse switch disconnectors1)2)
power with fuse holders1)2)
rating
Rated Rated Max. Rated Max.
current current fuse current fuse
size size
kW Order No. Order No. A Order No. A Order No. A
Compact PLUS units
Supply voltage 3-ph. 380 V to 480 V AC
15 6SE7024–1EP85–0AA0 3KA50 30–1EE01 63 3KL50 30–1EB01 63 00; 000 3NP40 10–0CH01 100 000
50 6SE7031–2EP85–0AA0 3KA53 30–1EE01 160 3KL53 30–1EB01 160 00; 000 3NP42 70–0CA01 250 0; 1
100 6SE7032–3EP85–0AA0 3KA55 30–1EE01 250 3KL55 30–1EB01 250 1; 2 3NP42 70–0CA01 250 0; 1
Compact and chassis units
Supply voltage 3-ph. 380 V to 480 V AC
15 6SE7024–1EB85–0AA0 3KA50 30–1EE01 63 3KL50 30–1EB01 63 00 3NP40 10–0CH01 100 000
37 6SE7028–6EC85–0AA0 3KA51 30–1EE01 80 3KL52 30–1EB01 125 00 3NP40 10–0CH01 100 000
75 6SE7031–7EE85–0AA0 3KA53 30–1EE01 160 3KL55 30–1EB01 250 0; 1; 2 3NP42 70–0CA01 250 0; 1
110 6SE7032–7EE85–0AA0 3KA55 30–1EE01 250 3KL55 30–1EB01 250 0; 1; 2 3NP42 70–0CA01 250 0; 1
160 6SE7033–8EE85–0AA0 3KA57 30–1EE01 400 3KL57 30–1EB01 400 1; 2 3NP53 60–0CA00 400 1; 2
200 6SE7034–6EE85–0AA0 3KA57 30–1EE01 400 3KL57 30–1EB01 400 1; 2 3NP53 60–0CA00 400 1; 2
250 6SE7036–1EE85–0AA0 3KA58 30–1EE01 630 3KL61 30–1AB0 630 3 3NP54 60–0CA00 630 2; 3
400 6SE7038–2EH85–0AA0 3KE45 30–0AA 1000 – – – – – –
500 6SE7041–0EH85–0AA0 3KE45 30–0AA 1000 – – – – – –
630 6SE7041–3EK85–0A@0 % 1250 – – – – – –
800 6SE7041–8EK85–0A@0 % 1600 – – – – – –
Supply voltage 3-ph. 500 V to 600 V AC
22 6SE7024–1FB85–0AA0 3KA50 30–1EE01 63 3KL50 30–1EB01 63 00 3NP40 10–0CH01 100 000
37 6SE7027–2FC85–0AA0 3KA50 30–1EE01 63 3KL50 30–1EB01 63 00 3NP40 10–0CH01 100 000
55 6SE7028–8FC85–0AA0 3KA51 30–1EE01 80 3KL52 30–1EB01 125 00 3NP40 70–0CA01 160 00
75 6SE7031–4FE85–0AA0 3KA53 30–1EE01 160 3KL52 30–1EB01 125 00 3NP40 70–0CA01 160 00
132 6SE7032–4FE85–0AA0 3KA55 30–1EE01 250 3KL55 30–1EB01 250 0; 1; 2 3NP42 70–0CA01 250 0; 1
200 6SE7033–5FE85–0AA0 3KA57 30–1EE01 400 3KL57 30–1EB01 400 1; 2 3NP53 60–0CA00 400 1; 2
250 6SE7034–2FE85–0AA0 3KA57 30–1EE01 400 3KL57 30–1EB01 400 1; 2 3NP53 60–0CA00 400 1; 2
315 6SE7035–4FE85–0AA0 3KA58 30–1EE01 630 3KL61 30–1AB0 630 3 3NP54 60–0CA00 630 2; 3
450 6SE7037–7FH85–0AA0 3KE45 30–0AA 1000 – – – – – –
630 6SE7041–0FH85–0AA0 3KE45 30–0AA 1000 – – – – – –
800 6SE7041–3FK85–0A@0 % 1250 – – – – – –
900 6SE7041–5FK85–0A@0 % 1600 – – – – – –
1100 6SE7041–8FK85–0A@0 % 2000 – – – – – –
Supply voltage 3-ph. 660 V to 690 V AC
160 6SE7032–2HE85–0AA0 3KA57 30–1EE01 400 3KL55 30–1EB01 250 0; 1; 2 3NP42 70–0CA01 250 0; 1
250 6SE7033–5HE85–0AA0 3KA57 30–1EE01 400 3KL57 30–1EB01 400 1; 2 3NP53 60–0CA00 400 1; 2
315 6SE7034–2HE85–0AA0 3KA57 30–1EE01 400 3KL57 30–1EB01 400 1; 2 3NP53 60–0CA00 400 1; 2
400 6SE7035–4HE85–0AA0 3KA58 30–1EE01 630 3KL61 30–1AB0 630 3 3NP54 60–0CA00 630 2; 3
630 6SE7037–7HH85–0AA0 3KE45 30–0AA 1000 – – – – – –
800 6SE7041–0HH85–0AA0 3KE45 30–0AA 1000 – – – – – –
1000 6SE7041–3HK85–0A@0 % 1250 – – – – – –
1100 6SE7041–5HK85–0A@0 % 1600 – – – – – –
% 2000 – – – – – –
s
1500 6SE7041–8HK85–0A@0
Rectifier unit A
Rectifier unit with power section3) D
1) Switch disconnectors: 2) Can be optionally used depending on require- 3) For parallel connection.
Note size of cable-protection and semicon- ments. For further information see catalog
% Not available from Siemens.
ductor-protection fuses! “Low-voltage switchgear”.
SIMOVERT MASTERDRIVES Vector Control
Compact PLUS, Compact and Chassis Units
Compact PLUS units Recommended system components
Compact and chassis units for rectifier units
Cable-protection fuses Duty class gL1)2) Semiconductor-protection Fuse bases Circuit-breaker4) Main contactor/
fuses to IEC/DIN5) AC contactor4)
Duty class gR2)
(incl. cable protection)
Rated Size Rated Size Rated Rated AC 1 Rated
current current current/ current duty current
size 55 °C
Order No. A Order No. A Order No. A Order No. A Order No. A
3NA3 817 40 000 3NE1 802–0 40 000 – – – – 3RT10 34 50
3NA3 032 125 0 3NE1 022–0 125 00 – – – – 3RT10 54 160
3NA3 142 224 1 3NE1 227–0 250 1 – – – – 3RT10 64 275
3NA3 820 50 00 3NE1 802–0 40 000 – – – – 3RT10 34 45
3NA3 830 100 00 3NE1 820–0 80 000 – – – – 3RT10 44 90
3NA3 140 200 1 3NE1 224–0 160 1 – – – – 3TK50 190
3NA3 252 315 2 3NE1 227–0 250 1 – – – – 3TK52 315
3NA3 260 400 2 3NE1 331–0 350 2 – – – – 3TK54 380
3NA3 365 500 3 3NE1 332–0 400 2 – – – – 3TK56 500
3NA3 372 630 3 3NE1 435–0 560 3 – – – – 2 x 3TK52 567
3NA3 4803)6) 1000 4 Semiconductor protection 3NH3 530 1000/4 3WN61 800 3 x 3TK52 788
3NA3 6823)6) 1250 4a fuses aR (without cable 3NH7 520 1250/4a 3WN62 1000 3 x 3TK54 950
protection) already integrated
2 x 3NA3 4753)6) 800 4 in the standard unit 3NH3 530 1000/4 3WN63 1250 3 x 3TK56 1250
2 x 3NA3 4803)6) 1000 4 3NH3 530 1000/4 3WN65 2000 3 x 3TK15 1950
to 500 V to 600 V
3NA3 820 3NA3 820–6 50 00 3NE1 802–0 40 000 – – – – 3RT10 34 45
3NA3 824 3NA3 824–6 80 00 3NE1 818–0 63 000 – – – – 3RT10 44 90
3NA3 830 3NA3 830–6 100 00 3NE1 021–0 100 00 – – – – 3RT10 44 90
3NA3 136 3NA3 136–6 160 1 3NE1 022–0 125 00 – – – – 3RT14 46 135
3NA3 144 3NA3 144–6 250 2 3NE1 227–0 250 1 – – – – 3TK52 315
3NA3 260 3NA3 260–6 400 2 3NE1 231–0 350 2 – – – – 3TK52 315
3NA3 365 3NA3 365–6 500 3 3NE1 332–0 400 2 – – – – 3TK54 380
3NA3 372 630 3 3NE1 334–0 500 2 – – – – 3TK56 500
3NA3 4803)6) 1000 4 Semiconductor protection 3NH3 530 1000/4 3WN61 800 2 x 3TK54 788
3NA3 6823)6) 1250 4a fuses aR (without cable 3NH7 520 1250/4a 3WN62 1000 3 x 3TK54 950
protection) already integrated
2 x 3NA3 4753)6) 800 4 in the standard unit 3NH3 530 1000/4 3WN63 1250 3 x 3TK56 1250
2 x 3NA3 4753)6) 800 4 3NH3 530 1000/4 3WN64 1600 3 x 3TK14 1410
2 x 3NA3 4803)6) 1000 4 3NH3 530 1000/4 3WN65 2000 3 x 3TK15 1950
3NA3 144–6 250 2 3NE1 225–0 200 1 – – – – 3TK50 190
3NA3 260–6 400 2 3NE1 230–0 315 1 – – – – 3TK52 315
3NA3 365–6 500 3 3NE1 225–0 400 2 – – – – 3TK54 380
3NE1 436–0 630 3 3NE1 334–0 500 3 – – – – 3TK56 500
Semiconductor protection – – 3WN61 800 2 x 3TK54 788
fuses aR (without cable – – 3WN62 1000 3 x 3TK54 950
protection) already integrated
in the standard unit – – 3WN63 1250 3 x 3TK56 1250
– – 3WN64 1600 3 x 3TK14 1410
– – 3WN65 2000 3 x 3TK15 1950
1) Does not provide 100 % protection for the input 3) See catalog “Low-voltage switchgear”. 4) See catalog “Low-voltage switchgear”.
rectifier of the unit. Used for drive converters with a line supply
5) Size and quantity dependent on the fuses used.
inductance of ³ 3 % referred to the drive
2) The cable cross-sections must be dimensioned For further information see catalog “Low-vol-
converter impedance, i.e. so that the ratio of the
according to DIN VDE 0100, VDE 0298 Part 4 tage switchgear”.
system fault level to the converter output is
as a function of the rated fuse currents.
33 : 1 or 100 : 1 if an additional 2 % line reactor is 6) Cables can also be protected with circuit-
used. breakers with appropriate cable protection.
See catalog “Low-voltage switchgear”.
Impedance of unit:
V Caution:
Z = Short-circuit capacity and loadability at ambient
3 ⋅ IUN temperature must be taken into account.
SIMOVERT MASTERDRIVES Vector Control
Compact PLUS, Compact and Chassis Units
Recommended system components Compact PLUS units
for rectifier units Compact and chassis units
Selection and ordering data
Nominal Rectifier unit Radio-interference Commutating reactor1)
power suppression filter vD = 2 %
rating
Pv Rated
50/60 Hz current
kW Order No. Order No. Order No. W A
Compact PLUS units
Supply voltage 3-ph. 380 V to 480 V AC
400/480 V, 50/60 Hz
15 6SE7024–1EP85–0AA0 6SE7023–4ES87–0FB12) 4EP37 00–2US00 57/ 60 35.5
50 6SE7031–2EP85–0AA0 6SE7031–8ES87–0FA12) 4EU24 52–2UA00–0AA0 154/163 160
100 6SE7032–3EP85–0AA0 6SE7033–2ES87–0FA12) 4EU25 52–5UA00–0AA0 187/201 250
Compact and chassis units
Supply voltage 3-ph. 380 V to 480 V AC
400/480 V, 50/60 Hz
15 6SE7024–1EB85–0AA0 6SE7023–4ES87–0FB12) 4EP37 00–2US00 57/ 60 35.5
37 6SE7028–6EC85–0AA0 6SE7027–2ES87–0FB12) 4EP39 00–2US00 82/ 87 80
75 6SE7031–7EE85–0AA0 6SE7031–8ES87–0FA12) 4EU24 52–2UA00–0AA0 154/163 160
110 6SE7032–7EE85–0AA0 6SE7033–2ES87–0FA12) 4EU25 52–5UA00–0AA0 187/201 250
160 6SE7033–8EE85–0AA0 6SE7033–2ES87–0FA12) 4EU27 52–7UA00–0AA0 253/275 315
200 6SE7034–6EE85–0AA0 6SE7036–0ES87–0FA12) 4EU27 52–8UA00–0AA0 253/275 400
250 6SE7036–1EE85–0AA0 6SE7036–0ES87–0FA12) 4EU30 52–5UA00–0AA0 334/367 560
400 6SE7038–2EH85–0AA0 6SE7041–0ES87–0FA12) 4EU36 52–8UA00–1BA0 450/495 720
500 6SE7041–0EH85–0AA0 6SE7041–0ES87–0FA12) 4EU36 52–0UB00–1BA0 450/495 910
630 6SE7041–3EK85–0A@0 6SE7041–6ES87–0FA12) 4EU36 52–7UC00–1BA0 450/495 1120
800 6SE7041–8EK85–0A@0 6SE7041–6ES87–0FA12) 4EU39 51–0UC00–0A 570/627 1600
Supply voltage 3-ph. 500 V to 600 V AC
500 V, 50 Hz
22 6SE7024–1FB85–0AA0 B84143–A50–R212)3) 4EP37 00–1US00 57 35.5
37 6SE7027–2FC85–0AA0 B84143–A80–R212)3) 4EP39 00–1US00 82 63
55 6SE7028–8FC85–0AA0 B84143–A80–R212)3) 4EP40 00–1US00 96 80
75 6SE7031–4FE85–0AA0 B84143–A120–R212)3) 4EU24 52–1UA00–0AA0 154 140
132 6SE7032–4FE85–0AA0 B84143–B 250–S@@3) 4EU25 52–6UA00–0AA0 187 200
200 6SE7033–5FE85–0AA0 B84143–B 320–S@@3) 4EU27 52–3UA00–0AA0 253 315
250 6SE7034–2FE85–0AA0 B84143–B 600–S@@3) 4EU27 52–4UA00–0AA0 253 400
315 6SE7035–4FE85–0AA0 B84143–B 600–S@@3) 4EU30 52–2UA00–0AA0 334 450
450 6SE7037–7FH85–0AA0 B84143–B1000–S@@3) 4EU36 52–3UA00–0AA0 450 710
630 6SE7041–0FH85–0AA0 B84143–B1000–S@@3) 4EU36 52–4UA00–1BA0 450 910
800 6SE7041–3FK85–0A@0 B84143–B1600–S@@3) 4EU39 51–5UB00–0A 570 1120
900 6SE7041–5FK85–0A@0 B84143–B1600–S@@3) 4EU39 51–7UB00–0A 570 1250
1100 6SE7041–8FK85–0A@0 B84143–B1600–S@@3) 4EU43 51–2UB00–0A 750 1600
Supply voltage 3-ph. 660 V to 690 V AC
690 V, 50 Hz
160 6SE7032–2HE85–0AA0 B84143–B 250–S@@3) 4EU27 52–6UA00–0AA0 253 224
250 6SE7033–5HE85–0AA0 B84143–B 320–S@@3) 4EU30 52–3UA00–0AA0 334 315
315 6SE7034–2HE85–0AA0 B84143–B 600–S@@3) 4EU30 52–4UA00–0AA0 334 400
400 6SE7035–4HE85–0AA0 B84143–B 600–S@@3) 4EU36 52–5UA00–0AA0 450 500
630 6SE7037–7HH85–0AA0 B84143–B1000–S@@3) 4EU36 52–7UA00–1BA0 450 710
800 6SE7041–0HH85–0AA0 B84143–B1000–S@@3) 4EU39 51–0UA00–0A 570 910
1000 6SE7041–3HK85–0A@0 B84143–B1600–S@@3) 4EU39 51–6UB00–0A 570 1120
1100 6SE7041–5HK85–0A@0 B84143–B1600–S@@3) 4EU43 51–0UB00–0A 750 1250
B84143–B1600–S@@3) 4EU45 51–4UA00 840 1600
s ss
1500 6SE7041–8HK85–0A@0
Rectifier unit A
Rectifier unit for parallel connection D
1) For commutating reactors for converters and
for 500 V TT and TN systems (earthed system) 2 0 rectifier units, see catalog PD 30.
for 690 V TT and TN systems (earthed system) 2 1
2) Can only be used with TT and TN systems
for 380 V to 690 V IT systems (non-earthed and insulated system) 2 4 (earthed system).
3) Further information on the filters can be
obtained from EPCOS (www.epcos.com) at
www4.ad.siemens.de. Please enter the follo-
wing number under “Entry ID”: 65 67 129.
SIMOVERT MASTERDRIVES Vector Control
Compact PLUS, Compact and Chassis Units
Compact PLUS units Recommended system components
Compact and chassis units for rectifier units
Commutating reactor1)
vD = 4 %
Pv Rated
50/60 Hz current
Order No. W A
400/480 V, 50/60 Hz
4EP39 00–5US00 82/ 87 35.5
4EU27 52–1UB00–0AA0 253/275 160
4EU30 52–7UA00–0AA0 334/367 280
400/480 V, 50/60 Hz
4EP39 00–5US00 82/ 87 35.5
4EU24 52–4UA00–0AA0 154/163 80
4EU27 52–1UB00–0AA0 253/275 160
4EU30 52–7UA00–0AA0 334/367 280
4EU30 52–8UA00–0AA0 334/367 355
4EU36 52–3UB00–0AA0 450/495 400
4EU36 52–4UB00–0AA0 450/495 560
4EU39 51–6UA00–0A 570/627 710
4EU39 51–1UB00–0A 570/627 910
4EU43 51–3UB00–0A 750/830 1120
4EU43 51–5UB00–0A 750/830 1600
500 V, 50 Hz
4EP40 01–0US00 96 35.5
4EU24 52–5UA00–0AA0 154 63
4EU25 52–1UB00–0AA0 187 80
4EU27 52–3UB00–0AA0 253 140
4EU30 52–0UB00–0AA0 334 200
4EU36 52–5UB00–0AA0 450 315
4EU36 52–6UB00–0AA0 450 400
4EU36 52–7UB00–1BA0 450 500
4EU39 51–7UA00–0A 570 710
4EU43 51–5UA00–0A 570 910
4EU45 51–5UA00–0A 840 1120
4EU45 51–6UA00–0A 840 1250
4EU47 51–3UA00–0A 965 1600
690 V, 50 Hz
4EU36 52–8UB00–0AA0 450 224
4EU36 52–0UC00–0AA0 450 315
4EU39 51–8UA00–0A 570 400
4EU39 51–0UB00–0A 570 500
4EU43 51–6UA00–0A 750 710
4EU45 51–3UA00 840 910
4EU47 51–2UA00 965 1120
4EU50 51–1UA00 1180 1250
4EU52 51–1UA00 1350 1600
1) Commutating reactors for converters and
rectifier units, see catalog PD 30.