| Вид документа | Каталожна сторінка |
|---|---|
| Виробник | SIEMENS |
| Моделі | 6SE7011-5EP60, 6SE7013-0EP60, 6SE7015-0EP60, 6SE7018-0EP60, 6SE7021-0EP60, 6SE7021-4EP60, 6SE7022-1EP60, 6SE7022-7EP60 |
| Група обладнання | electrical |
| Мова документа | англійська |
| Розмір файлу | 0.1 МБ |
Про документ
Air-cooled vector-control AC converters (with integrated braking chopper) and DC-fed inverters from the SIMOVERT MASTERDRIVES family. The catalogue lists selection and ordering data across three frame families: Compact PLUS units (small frame sizes with integrated braking chopper), and larger Compact and Chassis units in converter/inverter pairs.
Ключові дані
| Supply voltage (converters) | 3-ph. 380 V to 480 V AC |
|---|---|
| DC link voltage | 510 V to 650 V DC |
| Power range Compact PLUS converters | 0.55 … 15 kW |
| Power range Compact PLUS inverters | 0.75 … 18.5 kW |
| Power range Compact/Chassis units | 2.2 … 710 kW |
| Short-time current | 1.6 x IN for 30 s or 1.36 x IN for 60 s (Compact PLUS) |
Застосування
- Multi-motor drive configurations (converter feeds additional inverters)
- Single- and multi-motor drives with external braking resistor
Особливості
- Integrated braking chopper on Compact PLUS converters (braking power with Rmin up to P20/P3 ratings)
- Short-time current capability: 1.6 x IN for 30 s or 1.36 x IN for 60 s (Compact PLUS); short-time current = 1.6 x IUN possible for 30 s up to 200 kW (Compact/Chassis)
- Air-cooled design; sound pressure levels LpA from 18 dB (Compact PLUS) up to 89 dB (largest chassis sizes)
Технічні дані
| Parameter | Value |
|---|---|
| Supply voltage, Compact PLUS converters | 3-ph. 380 V to 480 V AC |
| DC link voltage, Compact PLUS inverters | 510 V to 650 V DC |
| Supply voltage / DC voltage, Compact & Chassis | 3-ph. 380 V to 480 V AC and DC voltage 510 V to 650 V DC (400 V table) |
| Nominal power rating, Compact PLUS converters | 0.55 / 1.1 / 1.5 / 3 / 4 / 5.5 / 7.5 / 11 / 15 kW |
| Nominal power rating, Compact PLUS inverters | 0.75 / 1.5 / 2.2 / 4 / 5.5 / 7.5 / 11 / 15 / 18.5 kW |
| Rated output current IN, Compact PLUS converters | 1.5 / 3.0 / 5.0 / 8.0 / 10.0 / 14.0 / 20.5 / 27.0 / 34.0 A |
| Rated output current IN, Compact PLUS inverters | 2.0 / 4.0 / 6.1 / 10.2 / 13.2 / 17.5 / 25.5 / 34.0 / 37.5 A |
| Base load current IG | e.g. 1.4 A (1.5 kW) up to 30.9 A (15 kW), converter; 1.8 A (0.75 kW) up to 34.1 A (18.5 kW), inverter |
| Short-time current | 1.6 x IN for 30 s or 1.36 x IN for 60 s |
| Rated supply current, converter without additional inverter | per column 2) of table; if converter feeds additional inverters: 1.76 x IN |
| Supply current, converter feeding inverter | 1.76 x IN (footnote 3) |
| Braking power with Rmin, Compact PLUS converters | P20 = 80 / 80 / 80 / 40 / 40 / 20 / 20 / 11 / 11 kW; P3 = 7.5 / 7.5 / 7.5 / 15 / 15 / 30 / 30 / 54 / 54 kW |
| Smallest permissible single-motor rating with external resistor | 0.05 … 0.39 kW (values per order No.) |
| Nominal power rating, Compact/Chassis units | 2.2 / 3 / 4 / 5.5 / 7.5 / 11 / 15 / 18.5 / 22 / 30 / 37 / 45 / 55 / 75 / 90 / 110 / 132 / 160 / 200 / 250 / 315 / 400 / 500 / 630 / 710 kW |
| Rated supply current IUN, largest chassis unit | 1300 A (710 kW) |
| Dimensions WxHxD, Compact PLUS | 45 x 360 x 260 mm to 180 x 360 x 260 mm |
| Dimensions WxHxD, Compact/Chassis | 90 x 425 x 350 mm to 1100 x 1750 x 565 mm |
| Weight, approx. | 3.0 kg (smallest Compact PLUS) to 625 kg (largest chassis) |
| Cooling air requirement | 0.002 m³/s to 0.92 m³/s |
| Sound pressure level LpA (1 m) | 18 dB to 89 dB depending on size |
| Power connections, supply line | finely stranded/multi-stranded, 2.5 mm² up to max. 4 x 300 mm² depending on size |
| Power connections, motor | finely stranded/multi-stranded, 2.5 mm² up to M 12/M 16 lug retaining bolts depending on size |
| DC bus connection (inverters) | DIN 46 433 E-Cu, 3 x 10 mm² |
| Auxiliary current requirement 24 V DC, standard/max. version | 1.3 / 1.3 A up to 3.0 / 4.2 A (sizes A–D); 24 V DC and 230 V 50/60 Hz fan variants on larger sizes |
| Fan current (inverters, 1-ph./2-ph. 230 V) | 0.35 A at 50 Hz / 0.44 A at 60 Hz up to 12.8 A / 22.0 A |
Варіанти замовлення
Order numbers are listed per power rating in the tables above:
- Compact PLUS converters (integrated braking chopper):
6SE7011-5EP60(0.55 kW),6SE7013-0EP60(1.1 kW),6SE7015-0EP60(1.5 kW),6SE7018-0EP60(3 kW),6SE7021-0EP60(4 kW),6SE7021-4EP60(5.5 kW),6SE7022-1EP60(7.5 kW),6SE7022-7EP60(11 kW),6SE7023-4EP60(15 kW) - Compact PLUS inverters:
6SE7012-0TP60(0.75 kW),6SE7014-0TP60(1.5 kW),6SE7016-0TP60(2.2 kW),6SE7021-0TP60(4 kW),6SE7021-3TP60(5.5 kW),6SE7021-8TP60(7.5 kW),6SE7022-6TP60(11 kW),6SE7023-4TP60(15 kW),6SE7023-8TP60(18.5 kW) - Compact/Chassis converters:
6SE7016-1EA61,6SE7018-0EA61,6SE7021-0EA61,6SE7021-3EB61,6SE7021-8EB61,6SE7022-6EC61,6SE7023-4EC61,6SE7023-8ED61,6SE7024-7ED61,6SE7026-0ED61,6SE7027-2ED61,6SE7031-0EE60,6SE7031-2EF60,6SE7031-5EF60,6SE7031-8EF60,6SE7032-1EG60,6SE7032-6EG60,6SE7033-2EG60,6SE7033-7EG60 - Compact/Chassis inverters:
6SE7016-1TA61,6SE7018-0TA61,6SE7021-0TA61,6SE7021-3TB61,6SE7021-8TB61,6SE7022-6TC61,6SE7023-4TC61,6SE7023-8TD61,6SE7024-7TD61,6SE7026-0TD61,6SE7027-2TD61,6SE7031-0TE60,6SE7031-2TF60,6SE7031-5TF60,6SE7031-8TF60,6SE7032-1TG60,6SE7032-6TG60,6SE7033-2TG60,6SE7033-7TG60, plus large-frame chassis inverters6SE7035-1TJ60,6SE7036-0TJ60,6SE7037-0TJ60,6SE7038-6TK60,6SE7041-1TK60,6SE7041-3TL60, and large-frame chassis converters6SE7035-1EK60,6SE7036-0EK60,6SE7037-0EK60
Допуски та стандарти
- DIN 46 433 (DC bus bar cross-section specification)
Текст документа
SIMOVERT MASTERDRIVES Vector Control
Compact PLUS Units
Air-cooled converters and inverters Compact PLUS units
Selection and ordering data
Compact PLUS converters
Nominal Rated Base Short- Supply Line Power loss at Braking power with integrated braking chopper
power output load time current2) current3) 2.5 kHz single- Smallest Rated braking Short-time
rating current current current1) Single- Multi- motor drive permissible power P20 braking
motor motor (multi-motor value of external with Rmin power P3
drive drive drive) braking resistor with Rmin
IN IG Rmin
kW A A A A A Order No. kW W kW kW
Supply voltage 3-ph. 380 V to 480 V AC
0.55 1.5 1.4 2.4 1.7 2.6 6SE7011–5EP60 0.05 (0.05) 80 5 7.5
1.1 3.0 2.7 4.8 3.3 5.3 6SE7013–0EP60 0.07 (0.08) 80 5 7.5
1.5 5.0 4.6 8.0 5.5 8.8 6SE7015–0EP60 0.10 (0.11) 80 5 7.5
3 8.0 7.3 12.8 8.8 14 6SE7018–0EP60 0.14 (0.16) 40 10 15
4 10.0 9.1 16.0 11.0 18 6SE7021–0EP60 0.15 (0.17) 40 10 15
5.5 14.0 12.7 22.4 15.4 25 6SE7021–4EP60 0.17 (0.20) 20 20 30
7.5 20.5 18.7 32.8 22.6 36 6SE7022–1EP60 0.22 (0.26) 20 20 30
11 27.0 24.6 43.2 29.7 48 6SE7022–7EP60 0.29 (0.34) 11 36 54
15 34.0 30.9 54.4 37.4 60 6SE7023–4EP60 0.39 (0.46) 11 36 54
Compact PLUS inverters
Nominal Rated Base Short- Rated Power loss at
power output load time DC link 2.5 kHz
rating current current current1) current
IN IG
kW A A A A Order No. kW
DC voltage 510 V to 650 V DC
0.75 2.0 1.8 3.2 2.4 6SE7012–0TP60 0.05
1.5 4.0 3.6 6.4 4.8 6SE7014–0TP60 0.06
2.2 6.1 5.6 9.8 7.3 6SE7016–0TP60 0.07
4 10.2 9.3 16.3 12.1 6SE7021–0TP60 0.09
5.5 13.2 12.0 21.1 15.7 6SE7021–3TP60 0.14
7.5 17.5 15.9 28.0 20.8 6SE7021–8TP60 0.17
11 25.5 23.2 40.8 30.3 6SE7022–6TP60 0.22
15 34.0 30.9 54.4 40.5 6SE7023–4TP60 0.30
18.5 37.5 34.1 60.0 44.6 6SE7023–8TP60 0.35
1) Short-time current = 1.6 x IN for 30 s or 2) Rated supply current for converter without addi- 3) Converter feeds additional inverter;
1.36 x IN for 60 s. tional inverter. If the converter feeds additional Supply current = 1.76 x IN.
inverters, the rated supply current is 1.76 x IN.
SIMOVERT MASTERDRIVES Vector Control
Compact PLUS Units
Compact PLUS units Air-cooled converters and inverters
Dimensions For Weight, Cooling air Sound Power connections Auxiliary current
WxHxD dimension approx. require- pressure –Terminals for requirement 24 V DC
drawing, ment level supply line Motor Max. version
see LpA finely stranded/ finely stranded/ (max. at 20 V)
Section 7 (1 m) multi-stranded multi-stranded
mm No. kg m3/s dB mm2 mm2 A
45 x 360 x 260 1 3.4 0.002 18 4/ 4 4/ 4 1.3
67.5 x 360 x 260 1 3.9 0.009 40 4/ 4 4/ 4 1.3
67.5 x 360 x 260 1 4.1 0.009 40 4/ 4 4/ 4 1.3
90 x 360 x 260 1 4.5 0.018 37 4/ 4 4/ 4 1.3
90 x 360 x 260 1 4.5 0.018 37 4/ 4 4/ 4 1.3
135 x 360 x 260 2 10.8 0.041 48 10 / 16 10 / 16 1.5
135 x 360 x 260 2 10.9 0.041 48 10 / 16 10 / 16 1.5
180 x 360 x 260 2 14.7 0.061 59 25 / 35 16 / 25 1.9
180 x 360 x 260 2 14.9 0.061 59 25 / 35 16 / 25 1.9
Dimensions For Weight, Cooling air Sound Power connections Auxiliary current
WxHxD dimension approx. require- pressure DC bus –Terminals for motor requirement 24 V DC
drawing, ment level finely stranded/ Max. version
see LpA multi-stranded (max. at 20 V)
Section 7 (1 m)
mm No. kg m3/s dB DIN 46 433 mm2 A
45 x 360 x 260 3 3.0 0.002 18 E-Cu 3 x 10 4/ 4 1.3
67.5 x 360 x 260 3 3.4 0.009 40 E-Cu 3 x 10 4/ 4 1.3
67.5 x 360 x 260 3 3.4 0.009 40 E-Cu 3 x 10 4/ 4 1.3
90 x 360 x 260 3 3.8 0.018 37 E-Cu 3 x 10 4/ 4 1.3
135 x 360 x 260 4 8.8 0.041 48 E-Cu 3 x 10 10 / 16 1.5
135 x 360 x 260 4 8.9 0.041 48 E-Cu 3 x 10 10 / 16 1.5
135 x 360 x 260 4 9.0 0.041 48 E-Cu 3 x 10 10 / 16 1.5
180 x 360 x 260 4 12.7 0.061 59 E-Cu 3 x 10 16 / 25 1.7
180 x 360 x 260 4 12.9 0.061 59 E-Cu 3 x 10 16 / 25 1.7
SIMOVERT MASTERDRIVES Vector Control
Compact and Chassis Units
Air-cooled converters and inverters Compact and chassis units
Selection and ordering data
Nominal Rated Base Short- Rated Supply Converter Inverter Power loss Dimensions For Weight
power output load time DC link current at 2.5 kHz WxHxD dimen- approx.
rating current current current current (only for sion
1) conver- draw-
ters) ing,
IUN IG Imax. Con- In- see
verter verter Section 7
kW A A A A A Order No. Order No. kW kW mm No. kg
Supply voltage 3-ph. 380 V to 480 V AC and DC voltage 510 V to 650 V DC
400 V
2.2 6.1 5.6 8.3 7.3 6.7 6SE7016–1EA61 6SE7016–1TA61 0.11 0.09 90 x 425 x 350 6 8.5
3 8 7.3 10.9 9.5 8.8 6SE7018–0EA61 6SE7018–0TA61 0.12 0.10 90 x 425 x 350 6 8.5
4 10.2 9.3 13.9 12.1 11.2 6SE7021–0EA61 6SE7021–0TA61 0.16 0.12 90 x 425 x 350 6 8.5
5.5 13.2 12 18.0 15.7 14.5 6SE7021–3EB61 6SE7021–3TB61 0.16 0.13 135 x 425 x 350 6 12.5
7.5 17.5 15.9 23.9 20.8 19.3 6SE7021–8EB61 6SE7021–8TB61 0.21 0.16 135 x 425 x 350 6 12.5
11 25.5 23.2 34.8 30.4 28.1 6SE7022–6EC61 6SE7022–6TC61 0.34 0.27 180 x 600 x 350 6 21
15 34 30.9 46.4 40.5 37.4 6SE7023–4EC61 6SE7023–4TC61 0.47 0.37 180 x 600 x 350 6 21
18.5 37.5 34.1 51.2 44.6 41.3 6SE7023–8ED61 6SE7023–8TD61 0.60 0.50 270 x 600 x 350 6 32
22 47 42.8 64.2 55.9 51.7 6SE7024–7ED61 6SE7024–7TD61 0.71 0.58 270 x 600 x 350 6 32
30 59 53.7 80.5 70.2 64.9 6SE7026–0ED61 6SE7026–0TD61 0.85 0.69 270 x 600 x 350 6 32
37 72 65.5 98.3 85.7 79.2 6SE7027–2ED61 6SE7027–2TD61 1.06 0.85 270 x 600 x 350 6 32
45 92 84 126 110 101 6SE7031–0EE60 6SE7031–0TE60 1.18 1.05 270 x 1050 x 365 8 65
55 124 113 169 148 136 6SE7031–2EF60 6SE7031–2TF60 1.67 1.35 360 x 1050 x 365 8 75
75 146 133 199 174 160 6SE7031–5EF60 6SE7031–5TF60 1.95 1.56 360 x 1050 x 365 8 75
90 186 169 254 221 205 6SE7031–8EF60 6SE7031–8TF60 2.17 1.70 360 x 1050 x 365 8 75
110 210 191 287 250 231 6SE7032–1EG60 6SE7032–1TG60 2.68 2.18 508 x 1450 x 465 8 160
132 260 237 355 309 286 6SE7032–6EG60 6SE7032–6TG60 3.40 2.75 508 x 1450 x 465 8 160
160 315 287 430 375 346 6SE7033–2EG60 6SE7033–2TG60 4.30 3.47 508 x 1450 x 465 8 180
200 370 337 503 440 407 6SE7033–7EG60 6SE7033–7TG60 5.05 4.05 508 x 1450 x 465 8 180
250 510 464 694 607 – – 6SE7035–1TJ60 – 5.8 800 x 1400 x 565 10 350
250 510 464 694 607 561 6SE7035–1EK60 – 7.1 – 800 x 1750 x 565 12 400
315 590 537 802 702 – – 6SE7036–0TJ60 – 6.6 800 x 1400 x 565 10 350
315 590 537 802 702 649 6SE7036–0EK60 – 8.2 – 800 x 1750 x 565 12 400
400 690 628 938 821 – – 6SE7037–0TJ60 – 8.8 800 x 1400 x 565 10 350
400 690 628 938 821 759 6SE7037–0EK60 – 10.2 – 800 x 1750 x 565 12 400
500 860 782 1170 1023 – – 6SE7038–6TK60 – 11.9 800 x 1750 x 565 10 520
630 1100 1000 1496 1310 – – 6SE7041–1TK60 – 13.4 800 x 1750 x 565 10 520
710 1300 1183 1768 1547 – – 6SE7041–3TL60 – 14.5 1100 x 1750 x 565 11 625
1) Short-time current = 1.6 x IUN, possible for 30 s
to 200 kW.
SIMOVERT MASTERDRIVES Vector Control
Compact and Chassis Units
Compact and chassis units Air-cooled converters and inverters
Cooling air Sound Power connections Auxiliary current requirement
requirement pressure – Terminals for sizes A to D
level – Lugs for sizes E to Q
LpA – Location: at top for AC/DC, at bottom for motor
(1 m)
Finely Single- and Retaining bolt 24 V DC 24 V DC 1-ph. or 2-ph. 230 V
stranded multi-stranded Standard version Max. version fan for inverters
max. at 20 V max. at 20 V
50 Hz 50 Hz 60 Hz
m3/s dB mm2 mm2 A A A A
0.009 60 2.5 to 10 2.5 to 16 1.5 2.5 none none
0.009 60 2.5 to 10 2.5 to 16 1.5 2.5 none none
0.009 60 2.5 to 10 2.5 to 16 1.5 2.5 none none
0.022 60 2.5 to 10 2.5 to 16 1.5 2.5 none none
0.022 60 2.5 to 10 2.5 to 16 1.5 2.5 none none
0.028 60 2.5 to 16 10 to 25 1.5 2.5 none none
0.028 60 2.5 to 16 10 to 25 1.5 2.5 none none
0.054 65 2.5 to 35 10 to 50 1.5 2.5 0.35 0.44
0.054 65 2.5 to 35 10 to 50 1.5 2.5 0.35 0.44
0.054 65 2.5 to 35 10 to 50 1.5 2.5 0.35 0.44
0.054 65 2.5 to 35 10 to 50 1.5 2.5 0.35 0.44
0.10 69 max. 2 x 70 M 10 1.7 2.7 0.35 0.44
0.14 69 max. 2 x 70 M 10 2.1 3.2 0.43 0.60
0.14 69 max. 2 x 70 M 10 2.1 3.2 0.43 0.60
0.14 69 max. 2 x 70 M 10 2.1 3.2 0.43 0.60
0.31 80 max. 2 x 150 M 12 2.3 3.5 0.76 1.1
0.31 80 max. 2 x 150 M 12 2.3 3.5 0.76 1.1
0.41 82 max. 2 x 150 M 12 2.3 3.5 0.95 1.4
0.41 82 max. 2 x 150 M 12 2.3 3.5 0.95 1.4
0.46 77 max. 2 x 300 M 12/M 16 3.0 4.2 2.2 3.4
0.46 77 max. 2 x 300 M 12/M 16 3.1 4.3 – –
0.46 77 max. 2 x 300 M 12/M 16 3.0 4.2 2.2 3.4
0.46 77 max. 2 x 300 M 12/M 16 3.1 4.3 – –
0.60 80 max. 4 x 300 M 12/M 16 3.0 4.2 4.5 6.9
0.60 80 max. 4 x 300 M 12/M 16 3.1 4.3 – –
0.60 80 max. 4 x 300 M 12/M 16 3.0 4.2 4.5 6.9
0.88 82 max. 4 x 300 M 12/M 16 3.0 4.2 12.8 22.0
0.92 89 max. 6 x 300 M 12/M 16 3.0 4.2 12.8 22.0
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.