SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

SIMOVERT MASTERDRIVES Motion Control – recommended line-side power options for rectifier/regenerative units

Вид документаКаталожна сторінка
ВиробникSIEMENS
Група обладнанняelectrical
Мова документаанглійська
Розмір файлу0.1 МБ

Про документ

Selection and ordering data for recommended line-side power components (switch disconnectors, fuse switch-disconnectors, cable-protection and semiconductor-protection fuses, contactors, commutating reactors, radio-interference suppression filters, regenerative autotransformers, free-wheeling diodes and clamping caps) matched to SIMOVERT MASTERDRIVES Motion Control rectifier/regenerative units in Compact and Compact PLUS chassis versions. The units are rated 7.5 to 250 kW with a supply voltage of 3-ph. 380 V to 480 V AC and 25 % power-on duration in generating mode.

Ключові дані

Supply voltage3-ph. 380 V to 480 V AC
Power ratings covered7.5 … 250 kW
Rectifier/regenerative unit duty25 % power-on duration in generating mode
Commutating reactor optionsVD = 2 % and VD = 4 %, 400/480 V 50/60 Hz
Radio-interference suppression filter classesB1, A1
Radio-interference standardEN 61 800-3

Застосування

  • Line-side power configuration for rectifier/regenerative units (Compact and Compact PLUS chassis units)
  • Cable protection and semiconductor protection of the input rectifier
  • Regenerative operation: 25 % power-on duration in generating mode

Особливості

  • Switch disconnectors and fuse switch-disconnectors optionally selectable depending on requirements (refer to Catalog NS K)
  • Semiconductor fuses do not ensure total protection for the input rectifier of the unit
  • Radio-interference suppression filters only for TT and TN systems (earthed systems); compliance with EN 61 800-3 only ensured with a line commutating reactor of VD = 2 %
  • Regenerative autotransformer: cycle duration 22 min (max. 5.5 min regenerating, 16.5 min rectifying at 25 % power-on duration)
  • Free-wheeling diodes from SEMIKRON GmbH u. Co. KG; clamping-cap disc diodes from EUPEC GmbH u. Co. KG

Технічні дані

Parameter Value
Supply voltage 3-ph. 380 V to 480 V AC
Nominal power rating range 7.5 / 15 / 37 / 75 / 90 / 132 / 160 / 200 / 250 kW
Rectifier/regenerative unit order numbers 6SE7022–1EC85–1AA0, 6SE7024–1EC85–1AA0, 6SE7028–6EC85–1AA0, 6SE7031–7EE85–1AA0, 6SE7032–2EE85–1AA0, 6SE7033–1EE85–1AA0, 6SE7033–8EE85–1AA0, 6SE7034–6EE85–1AA0, 6SE7036–1EE85–1AA0
Switch disconnector with fuse holders 3KA50 30–1EE01 (63 A) up to 3KA58 30–1EE01 (630 A)
Fuse switch-disconnectors 3NP42 70–0CA01 (250 A), 3NP53 60–0CA00 (400 A), 3NP54 60–0CA00 (630 A)
Cable-protection fuses (Duty class gL) 3NA3 810 (25 A) up to 3NA3 372 (630 A)
Semiconductor-protection fuses (Duty class aR) 3NE4 101 (32 A) up to 3NE3 338–8 (800 A)
Main contactor / AC contactor (AC1 duty, 55 °C) 3RT10 25 (35 A) up to 2 x 3TK52 (567 A)
Commutating reactor VD = 2 %, 400/480 V 50/60 Hz 4EP36 00–4US00 (52/57 W, 18 A) up to 4EU30 52–5UA00–0AA0 (334/367 W, 560 A)
Commutating reactor VD = 4 %, 400/480 V 50/60 Hz 4EP37 00–7US00 (57/60 W, 18 A) up to 4EU36 52–4UB00–0AA0 (450/495 W, 560 A)
Radio-interference suppression filters 6SE7023–4ES87–0FB1 (Class B1) up to 6SE7036–0ES87–0FA1 (Class A1)
Regenerative autotransformer, 380–415 V 50/60 Hz 4AP25 95–0UA11–8AN2 (0.35 kW Pv) up to 4BU51 95–0UA31–8A (6.00 kW Pv)
Regenerative autotransformer, 440–480 V 50/60 Hz 4AP25 95–0UA21–8AN2 (0.35 kW Pv) up to 4BU51 95–0UA41–8A (6.00 kW Pv)
Free-wheeling diode on DC bus SKR 3 F 20/12, SKR 60 F 12, 2 x SKR 141 F 15
Clamping cap on DC bus D 689S 20, V 72–26.120M

Варіанти замовлення

Selection is by nominal power rating row against the rectifier/regenerative unit order number (e.g. 6SE7022–1EC85–1AA0 for 7.5 kW). Each row lists matching order numbers for switch disconnectors, fuse switch-disconnectors, cable-protection fuses, semiconductor-protection fuses, contactors, commutating reactors (VD = 2 % / VD = 4 %), radio-interference suppression filters, regenerative autotransformers and free-wheeling diodes/clamping caps as tabulated above.

Допуски та стандарти

  • EN 61 800-3 (radio-interference suppression, with VD = 2 % commutating reactor)
  • Duty classes gL (cable-protection fuses) and aR (semiconductor-protection fuses)
  • Cable cross-section dimensioning per DIN VDE 0100, VDE 0298, Part 4

Текст документа

                                                      SIMOVERT MASTERDRIVES Motion Control
                                                                                                                   Selection and ordering data
                  Compact and                                    Compact
                  chassis units                                 PLUS units                              Recommended line-side power options

Rectifier/regenerative units, 25 % power-on duration in generating mode
Nominal Rectifier/                     Switch disconnector2)           Switch disconnectors with                           Fuse switch-disconnectors1)2)
power regenerative unit                                                fuse holders1)2)
rating                                                    Rated                             Rated           Max.                                  Rated     Max.
                                                          current                           current         fuse                                  current   fuse
                                                                                                            size                                            size
kW        Order No.                    Order No.          A            Order No.            A                              Order No.              A

Supply voltage 3-ph. 380 V to 480 V AC
  7.5     6SE7022–1EC85–1AA0           3KA50 30–1EE01       63         3KL55 30–1EB01       250             0; 1; 2        3NP42 70–0CA01         250       0; 1
 15       6SE7024–1EC85–1AA0           3KA50 30–1EE01       63         3KL55 30–1EB01       250             0; 1; 2        3NP42 70–0CA01         250       0; 1
 37       6SE7028–6EC85–1AA0           3KA51 30–1EE01       80         3KL55 30–1EB01       250             0; 1; 2        3NP42 70–0CA01         250       0; 1
 75       6SE7031–7EE85–1AA0           3KA53 30–1EE01     160          3KL55 30–1EB01       250             0; 1; 2        3NP42 70–0CA01         250       0; 1
 90       6SE7032–2EE85–1AA0           3KA55 30–1EE01     250          3KL55 30–1EB01       250             0; 1; 2        3NP42 70–0CA01         250       0; 1
132       6SE7033–1EE85–1AA0           3KA57 30–1EE01     400          3KL57 30–1EB01       400             1; 2           3NP53 60–0CA00         400       1; 2
160       6SE7033–8EE85–1AA0           3KA57 30–1EE01     400          3KL57 30–1EB01       400             1; 2           3NP53 60–0CA00         400       1; 2
200       6SE7034–6EE85–1AA0           3KA57 30–1EE01     400          3KL61 30–1AB0        630             2; 3           3NP54 60–0CA00         630       2; 3
250       6SE7036–1EE85–1AA0           3KA58 30–1EE01     630          3KL61 30–1AB0        630             2; 3           3NP54 60–0CA00         630       2; 3


Nominal Rectifier/                     Cable-protection fuses                       Semiconductor-protection fuses                     Main contactor/
power regenerative unit                Duty class gL3)4)                            Duty class aR4)                                    AC contactor5)
rating                                                                              (incl. cable protection)
                                                          Rated        Size                               Rated    Size                AC1                  Rated
                                                          current                                         current                      duty                 current
                                                                                                                                       55 °C
kW        Order No.                    Order No.          A                         Order No.               A                          Order No.            A

Supply voltage 3-ph. 380 V to 480 V AC
  7.5     6SE7022–1EC85–1AA0           3NA3 810             25         00           3NE4 101                 32            0           3RT10 25              35
 15       6SE7024–1EC85–1AA0           3NA3 820             50         00           3NE4 118                 63            0           3RT10 34              45
 37       6SE7028–6EC85–1AA0           3NA3 830           100          00           3NE4 122                125            0           3RT10 44              90
 75       6SE7031–7EE85–1AA0           3NA3 140           200          1            3NE3 227                250            1           3TK50                190
 90       6SE7032–2EE85–1AA0           3NA3 144           250          1            3NE3 230–0B             315            1           3TK52                315
132       6SE7033–1EE85–1AA0           3NA3 252           315          2            3NE3 233                450            1           3TK52                315
160       6SE7033–8EE85–1AA0           3NA3 260           400          2            3NE3 333                450            2           3TK54                380
200       6SE7034–6EE85–1AA0           3NA3 365           500          3            3NE3 335                560            2           3TK56                500
250       6SE7036–1EE85–1AA0           3NA3 372           630          3            3NE3 338–8              800            2           2 x 3TK52            567




1) Switch disconnectors: Please take into account       3) Does not ensure total protection for the input             5) Refer to Catalog NS K.
   the size of the cable-protection and semiconduc-        rectifier of the unit.
   tor-protection fuses!
                                                        4) The cable cross-sections must be dimensioned
2) Can be optionally used, depending on require-           according to DIN VDE 0100, VDE 0298, Part 4
   ments. For further information refer to Catalog         and as a function of the rated fuse currents.
   NS K.
        SIMOVERT MASTERDRIVES Motion Control
Selection and ordering data
                                                                                  Compact                                      Compact and
Recommended line-side power options                                               PLUS units                                   chassis units

Rectifier/regenerative units, 25 % power-on duration in generating mode
Nominal Rectifier/                 Commutating reactor                            Commutating reactor                                 Radio-interference
power regenerative unit            VD = 2 %                                       VD = 4 %                                            suppression filter1)2)
rating                             400/480 V                Pv       Rated        400/480 V                    Pv          Rated                               Class
                                   50/60 Hz                 50/60 Hz current      50/60 Hz                     50/60 Hz    current

kW       Order No.                 Order No.                W          A          Order No.                    W           A          Order No.

Supply voltage 3-ph. 380 V to 480 V AC
  7.5    6SE7022–1EC85–1AA0        4EP36 00–4US00           52/ 57     18         4EP37 00–7US00                57/ 60      18        6SE7023–4ES87–0FB1 B1
 15      6SE7024–1EC85–1AA0        4EP37 00–2US00           57/ 60     35.5       4EP39 00–5US00                82/ 87      35.5      6SE7023–4ES87–0FB1 B1
 37      6SE7028–6EC85–1AA0        4EP39 00–2US00           82/ 87     80         4EU24 52–4UA00–0AA0 154/163               80        6SE7027–2ES87–0FB1 B1
 75      6SE7031–7EE85–1AA0        4EU24 52–2UA00–0AA0 154/163         160        4EU27 52–1UB00–0AA0 253/275              160        6SE7031–8ES87–0FA1 A1
 90      6SE7032–2EE85–1AA0        4EU25 52–4UA00–0AA0 187/201         200        4EU27 52–2UB00–0AA0 253/275              200        6SE7031–8ES87–0FA1 A1
132      6SE7033–1EE85–1AA0        4EU27 52–0UB00–0AA0 253/275         280        4EU30 52–7UA00–0AA0 334/367              280        6SE7033–2ES87–0FA1 A1
160      6SE7033–8EE85–1AA0        4EU27 52–7UA00–0AA0 253/275         315        4EU30 52–8UA00–0AA0 334/367              355        6SE7033–2ES87–0FA1 A1
200      6SE7034–6EE85–1AA0        4EU27 52–8UA00–0AA0 253/275         400        4EU36 52–3UB00–0AA0 450/495              400        6SE7036–0ES87–0FA1 A1
250      6SE7036–1EE85–1AA0        4EU30 52–5UA00–0AA0 334/367         560        4EU36 52–4UB00–0AA0 450/495              560        6SE7036–0ES87–0FA1 A1


Nominal Rectifier/                 Regenerative autotransformer3)                                                         Free-wheeling diode     Clamping cap
power regenerative unit                                                                                                   on the DC bus4)
rating                             25 % power-on duration   Pv               25 % power-on duration     Pv                Diode
                                   380 V to 415 V           50/60 Hz         440 V to 480 V             50/60 Hz
                                   50/60 Hz                                  60 Hz
kW       Order No.                 Order No.                kW               Order No.                  kW                Order No.               Order No.

Supply voltage 3-ph. 380 V to 480 V AC
  7.5    6SE7022–1EC85–1AA0        4AP25 95–0UA11–8AN2 0.35                  4AP25 95–0UA21–8AN2 0.35                     SKR 3 F 20/12
 15      6SE7024–1EC85–1AA0        4AP27 95–0UA01–8AN2 0.45                  4AP27 95–0UA51–8AN2 0.45                     SKR 3 F 20/12
 37      6SE7028–6EC85–1AA0        4AP30 95–0UA01–8AN2 0.65                  4AP30 95–0UA71–8AN2 0.65                     SKR 60 F 12
 75      6SE7031–7EE85–1AA0        4AU39 95–0UA51–8AN2 2.20                  4AU36 95–0UA21–8AN2 1.70                     SKR 60 F 12
 90      6SE7032–2EE85–1AA0        4AU39 95–0UA61–8AN2 2.20                  4AU39 95–0UB01–8AN2 2.20                     SKR 60 F 12
132      6SE7033–1EE85–1AA0        4BU43 95–0UA41–8A        2.70             4BU43 95–0UA51–8A          2.70              2 x SKR 141 F 15
160      6SE7033–8EE85–1AA0        4BU45 95–0UA61–8A        2.80             4BU45 95–0UA71–8A          2.80              2 x SKR 141 F 15
200      6SE7034–6EE85–1AA0        4BU47 95–0UA61–8A        3.00             4BU47 95–0UA71–8A          3.00              2 x SKR 141 F 15
250      6SE7036–1EE85–1AA0        4BU51 95–0UA31–8A        6.00             4BU51 95–0UA41–8A          6.00              D 689S 205)6)           V 72–26.120M5)6)




1) Compliance with radio-interference suppression   3) Transformer: Cycle duration of 22 min, i.e. with         5) Diode supplied as a disc diode with a clamping
   to EN 61 800-3 can only be ensured in               25 % power-on duration, maximum 5.5 min in                  cap for mounting on a copper plate or copper rail.
   conjunction with a line commutating reactor of      regenerating mode, 16.5 min in rectifying mode.
                                                                                                                6) The diodes referred to are from
   VD = 2 % .
                                                    4) The diodes referred to are from                             from the product range supplied
2) Can only be used with TT and TN systems             the range of products supplied                              by EUPEC GmbH u. Co. KG,
   (earthed systems).                                  by SEMIKRON GmbH u. Co. KG,                                 Max-Planck-Str. 5, D-59581 Warstein,
                                                       Sigmundstr. 200, D-90431 Nuremberg,                         Germany. Internet: www.eupec.com
                                                       Germany. Internet: www.semikron.com


Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.