Cycle and response times     ___________________
                             Preface

                             ___________________
                             Documentation guide 1

                                              2
                             ___________________
                             Program processing
  SIMATIC
                             ___________________
                             Cyclic program processing 3
  S7-1500                    Event-driven program
  Cycle and response times   ___________________
                             processing           4

  Function Manual

  02/2014
  A5E03461504-02
Legal information
Warning notice system
             This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
             damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
             symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
             graded according to the degree of danger.

                  DANGER
              indicates that death or severe personal injury will result if proper precautions are not taken.

                  WARNING
              indicates that death or severe personal injury may result if proper precautions are not taken.

                  CAUTION
              indicates that minor personal injury can result if proper precautions are not taken.

              NOTICE
              indicates that property damage can result if proper precautions are not taken.
             If more than one degree of danger is present, the warning notice representing the highest degree of danger will
             be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
             property damage.
Qualified Personnel
             The product/system described in this documentation may be operated only by personnel qualified for the specific
             task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
             Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
             avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
             Note the following:

                  WARNING
              Siemens products may only be used for the applications described in the catalog and in the relevant technical
              documentation. If products and components from other manufacturers are used, these must be recommended
              or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
              maintenance are required to ensure that the products operate safely and without any problems. The permissible
              ambient conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks
             All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
             may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
             We have reviewed the contents of this publication to ensure consistency with the hardware and software
             described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
             information in this publication is reviewed regularly and any necessary corrections are included in subsequent
             editions.

             Siemens AG                             A5E03461504-02                                       Copyright © Siemens AG 2013 - 2014.
             Industry Sector                        Ⓟ 02/2014 Technical data subject to change           All rights reserved
             Postfach 48 48
             90026 NÜRNBERG
             GERMANY
Preface

Purpose of the documentation
                      The control system offers various options for program execution with different run priorities.
                      Cyclic and time-driven program execution have the largest share. The response times of a
                      control system are therefore significantly determined by the processing cycles.
                      Additionally there is also the possibility of event-driven program execution. The event-driven
                      program execution is normally limited to a few selected events.
                      This manual provides information on the following topics:
                      ● Types of program execution
                      ● Run priorities
                      ● Cycle and response times, and the influences to which they are subject
                      ● Configuration options for the optimization of your user program

Basic knowledge required
                      The following knowledge is required in order to understand the documentation:
                      ● General knowledge of automation technology
                      ● Knowledge of the industrial automation system SIMATIC
                      ● Knowledge about the use of Windows-based computers
                      ● Knowledge about how to use STEP 7/TIA Portal

Conventions
                      STEP 7: We refer to the configuration and programming software as "STEP 7" in this
                      documentation synonymously for "STEP 7 V12 (TIA Portal)" and subsequent versions.

                      Please also observe notes marked as follows:

                      Note
                      A note contains important information on the product described in the documentation, on the
                      handling of the product and on the section of the documentation to which particular attention
                      should be paid.

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                               3
Preface

Scope of the documentation
                 This documentation mainly includes the CPU components of the cycle and reaction times of
                 the S7-1500 automation system. You can find references at the corresponding instances for
                 more information on the ET 200MP and ET 200SP distributed I/O systems.

Additional support
                 Additional information on SIMATIC products is available on the Internet. The associated
                 documentation is likewise available on the Internet.
                 ● You can find the available technical documentation for the individual SIMATIC products
                   and systems in the internet (http://www.siemens.com/simatic-tech-doku-portal).
                 ● The online catalog and the ordering system are available on the Internet
                   (http://mall.automation.siemens.com).

Security information
                 Siemens provides products and solutions with industrial security functions that support the
                 secure operation of plants, solutions, machines, equipment and/or networks. They are
                 important components in a holistic industrial security concept. With this in mind, Siemens’
                 products and solutions undergo continuous development. Siemens recommends strongly
                 that you regularly check for product updates.
                 For the secure operation of Siemens products and solutions, it is necessary to take suitable
                 preventive action (e.g. cell protection concept) and integrate each component into a holistic,
                 state-of-the-art industrial security concept. Third-party products that may be in use should
                 also be considered. You can find more information about industrial security on the Internet
                 (http://www.siemens.com/industrialsecurity).
                 To stay informed about product updates as they occur, sign up for a product-specific
                 newsletter. You can find more information on the Internet
                 (http://support.automation.siemens.com).

                                                                                           Cycle and response times
4                                                                          Function Manual, 02/2014, A5E03461504-02
Table of contents

       Preface ................................................................................................................................................... 3
1      Documentation guide .............................................................................................................................. 6
2      Program processing ................................................................................................................................ 8
3      Cyclic program processing .................................................................................................................... 11
       3.1           Cycle ............................................................................................................................................11
       3.2           Cycle time ....................................................................................................................................12
       3.2.1         Different cycle times .....................................................................................................................12
       3.2.2         Influences on the cycle time.........................................................................................................16
       3.2.2.1       Update time for process images ..................................................................................................16
       3.2.2.2       User program processing time .....................................................................................................17
       3.2.2.3       Extension of cycle time due to communication load ....................................................................19
       3.3           Time-driven program processing in cyclic interrupts ...................................................................21
       3.4           Response time for cyclic and time-driven program processing ...................................................23
       3.5           Summary of response time with cyclic and time-controlled program execution ..........................26
4      Event-driven program processing .......................................................................................................... 27
       4.1           Response time of the CPUs when program execution is event-controlled .................................27
       4.2           Process response time when program execution is event-driven ...............................................29
       Glossary ............................................................................................................................................... 30
       Index..................................................................................................................................................... 31

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                                                                               5
Documentation guide                                                                                                  1
Introduction
                      This modular documentation of the SIMATIC products covers diverse topics concerning your
                      automation system.
                      The complete documentation for the S7-1500 system consists of a system manual, function
                      manuals and device manuals.
                      The STEP 7 information system (Online Help) also helps you configure and program your
                      automation system.

Overview of the additional documentation on the topic of cycle and response times
                      The following table lists additional documentation which supplements this description of
                      cycle and response times.

                      Table 1- 1     Documentation of cycle and response times

                       Topic               Documentation                                  Most important contents
                       System              System manual                                  •   Application planning
                       description         S7-1500 Automation System
                                                                                          •   Installation
                                           (http://support.automation.siemens.com/WW/vi
                                           ew/en/59191792)                                •   Wiring
                                           System manual                                  •   Commissioning
                                           ET 200SP distributed I/O system
                                           (http://support.automation.siemens.com/WW/vi
                                           ew/en/58649293)
                                           System manual
                                           ET 200MP distributed I/O system
                                           (http://support.automation.siemens.com/WW/vi
                                           ew/en/59193214)
                       CPU                 Device manual                                  •   Block diagram
                                           CPU 1511-1 PN
                                                                                          •   Wiring
                                           (http://support.automation.siemens.com/WW/vi
                                           ew/en/68020492)                                •   Parameter assignment/
                                           Device manual                                      addressing
                                           CPU 1513-1 PN                                  •   Diagnostics alarms/
                                           (http://support.automation.siemens.com/WW/vi       interrupts
                                           ew/en/59186494)
                                                                                          •   Technical specifications
                                           Device manual
                                                                                          •   Dimensional drawings
                                           CPU 1515-2 PN
                                           (http://support.automation.siemens.com/WW/vi
                                           ew/en/81162167)

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                                 6
                                                                                                   Documentation guide

                       Topic               Documentation                                  Most important contents
                                           Device manual
                                           CPU 1516-3 PN/DP
                                           (http://support.automation.siemens.com/WW/vi
                                           ew/en/59191914)
                                           Device manual
                                           CPU 1518-4 PN/DP
                                           (http://support.automation.siemens.com/WW/vi
                                           ew/en/81164632)
                       Isochronous mode Function manual                                   •   Isochronous mode for
                       for PROFINET     PROFINET with STEP 7 V13                              PROFINET
                                        (http://support.automation.siemens.com/WW/vi
                                        ew/en/49948856)                                   •   Instructions "SYNC_PI" and
                                                                                              "SYNC_PO"
                       Isochronous mode Function manual                                   •   Isochronous mode for
                       for PROFIBUS     PROFIBUS with STEP 7 V13                              PROFIBUS
                                        (http://support.automation.siemens.com/WW/vi
                                        ew/en/59193579)                                   •   Instructions "SYNC_PI" and
                                                                                              "SYNC_PO"

SIMATIC manuals
                      All current manuals for the SIMATIC products are available for download free of charge from
                      the Internet (http://www.siemens.com/automation/service&support).

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                                   7
Program processing                                                                                              2
Introduction
                      You often program your user program with a cyclic OB, usually in OB 1. With complex
                      applications, problems are often encountered in complying with the response time required
                      by the application. You can often solve the response time requirements by splitting the user
                      program up into several parts with different response time requirements. The CPU offers a
                      number of different OB types for this purpose, the properties (priority, frequency, etc.) of
                      which can be adapted to meet the requirements.

Program organization
                      You can choose from the following types of program execution for running your user
                      program:
                      Program execution in the cyclic program of the CPU:
                      In the simplest case, you execute the entire user program in the cyclic program of the CPU.
                      All tasks in the user program are then processed with equal rank. This also results in the
                      same response times for all tasks.
                      In addition to program execution in the cyclic program, there is time-driven and event-driven
                      program execution.
                      Time-driven processing:
                      In a complex user program, there are frequently portions with different response time
                      requirements. You can optimize the response times by taking advantage of these differences
                      in the requirements. To do so you can move the program parts with higher response time
                      requirements to higher-priority OBs with shorter cycles, for example cyclic interrupt OBs.
                      The processing of these parts can thus occur with different frequencies and priorities.
                      Event-driven processing:
                      Depending on the I/O modules used, you can configure hardware interrupts for specific
                      process events (such as an edge change of a digital input) that result in the call of the
                      assigned hardware interrupt OB. The hardware interrupts have a higher priority and interrupt
                      the cyclic program of the CPU. You can achieve very short response time in the CPU with
                      hardware interrupts by directly triggering program execution.
                      Keep in mind that the time characteristics of your application becomes less predictable with
                      intense use of hardware interrupts. The reason being that the time at which the triggering
                      events occur can result in drastically different response times.
                      Tip: Use hardware interrupts only for a few, select events.

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                              8
                                                                                                  Program processing

Using process image partitions
                      If a program is distributed to various OBs, for example, due to differing response time
                      requirements, it is advisable and often necessary to assign the update of the used I/O data
                      directly to these OBs. You can use process image partitions for this purpose.
                      You group the input and output data in a process image partition according to their use in the
                      program and assign the data to the corresponding OB.
                      You optimize the response times this way, because the update of the affected I/O modules is
                      directly synchronized with the processing in the program.
                      A process image partition of the inputs (PIPI) permits the associated input data for an
                      OB program to be updated immediately before the OB program starts.
                      A process image partition of the outputs (PIPQ) permits the output data associated with an
                      OB program to become effective on the outputs immediately after the OB program runs.
                      You have 32 (0 … 31) process image partitions at your disposal. The default assignment for
                      the I/O is process image partition 0 (setting: "Automatic updating"). Process image partition 0
                      is permanently assigned to cyclic processing.
                      You have to configure this "system-side update of process image partitions". You can find
                      additional information on configuration of process image partitions in the online help for
                      STEP 7 under the keyword "Assign process image/process image partition".

Interruptability of program run
                      Each organization block is processed with a priority. You can adapt the priority according to
                      the response time requirements for most organization blocks.
                      All cycle OBs always have the lowest priority of 1. The highest priority is 26.
                      Communication tasks always have priority 15. If necessary, you can change the priority of
                      your blocks and select a higher priority than the communication.
                      Organization blocks or system activities with higher priority interrupt those with lower priority,
                      and thus extend the run time of the interrupted organization blocks or system activities. If two
                      pending tasks have the same priority, these tasks are processed in the order in which the
                      tasks occurred.

                      Note
                      Higher priority OBs
                      Communication functionality is strongly influenced by too many or runtime-intensive OBs
                      with a priority > 15.
                      When using OBs with a priority > 15, you should consider the runtime load that they cause in
                      order to keep communication functionality at a reasonable level.

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                              9
Program processing

Reference
                 You can find additional information on the subject of priorities in the system manual for the
                 S7-1500 Automation System
                 (http://support.automation.siemens.com/WW/view/en/59191792), in the Events and OBs
                 section.

                                                                                           Cycle and response times
10                                                                         Function Manual, 02/2014, A5E03461504-02
Cyclic program processing                                                                                            3
3.1               Cycle

Introduction
                      In this section, you will learn about the concept of the "cycle".

Definition of cycle
                      A cycle in the S7-1500 automation system encompasses the following:
                      ● Update of process image partition 0 of the inputs (PIPI 0)
                      ● Processing of the cyclic program
                      ● Update of process image partition 0 of the outputs (PIPQ 0)
                      The process image partition 0 is permanently assigned to the cycle. You assign
                      I/O addresses to this process image partition using the "Automatic updating" setting (default)
                      in the TIA Portal in HW Config for the I/O modules.
                      The figure below illustrates the phases that are passed through during a cycle.

                      ①     The operating system starts measurement of the cycle time.
                      ②     The CPU reads the status of the inputs at the input module and writes the input data to the
                            process image partition of the inputs.
                      ③     The CPU processes the user program and executes the instructions specified in the program.
                      ④     The CPU writes the states from the process image outputs to the output modules.
                      ⑤     The operating system evaluates the determined cycle time and starts the measurement again.

                      Figure 3-1   Cycle

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                                  11
Cyclic program processing
3.2 Cycle time

3.2            Cycle time

Introduction
                  In this section you will learn about the concept of "cycle time", and how to estimate the cycle
                  time.

Definition of cycle time
                  The cycle time is the time the CPU need to execute the cyclic program, to update the
                  process image of the inputs and outputs as well as for all program parts and system
                  activities that interrupt this cycle.

3.2.1          Different cycle times

Introduction
                  The cycle time (Tcyc) is not equally long for every cycle, because the processing times can
                  vary. Causes for this are, for example:
                  ● Different program runtimes
                     (e.g. program loops, conditional commands, conditional block calls, or different program
                     paths)
                  ● Lengthening due to interruptions
                     (e.g. time-driven interrupt processing, processing of hardware interrupts or
                     communication)

                                                                                            Cycle and response times
12                                                                          Function Manual, 02/2014, A5E03461504-02
                                                                                          Cyclic program processing
                                                                                                      3.2 Cycle time

Causes for different cycle times
                      The cycle time Tcyc2 is longer than Tcyc1, because the cyclic program is interrupted by a cyclic
                      interrupt OB in this example (e.g: OB 30). The cyclic interrupt OB in turn is interrupted by
                      communication.
                      The figure below shows the different cycle times Tcyc1 and Tcyc2.

                      Figure 3-2   Possible causes of differing cycle times

Minimum cycle time
                      In STEP 7, you can set a minimum cycle time for a CPU. The default for the minimum cycle
                      time is one millisecond. It may be advisable to increase this setting in the following cases:
                      ● To reduce the cycle time's fluctuation range.
                      ● To make remaining computing time available for communication tasks.

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                            13
Cyclic program processing
3.2 Cycle time

Maximum cycle time
                  The cycle time is monitored by the CPU. By default, the maximum cycle time is 150 ms. This
                  value can be changed by setting CPU parameters. When the cycle time is longer than the
                  maximum cycle time, the time error OB (OB 80) is called.
                  You have the option of restarting the maximum cycle time using the "RE_TRIGR" instruction,
                  and thus extending it.
                  With the user program in OB 80 you specify how the CPU responds to the time error. Under
                  the following conditions the CPU goes to STOP.
                  ● If you have not loaded an OB 80.
                  ● If the cycle is still not completed after an additional maximum cycle time
                  Keep in mind that the cycle time is extended by interruptions as shown in the previous figure.

                                                                                           Cycle and response times
14                                                                         Function Manual, 02/2014, A5E03461504-02
                                                                                           Cyclic program processing
                                                                                                       3.2 Cycle time

Cycle time statistics
                      In STEP 7 and in the TIA Portal, you have the option of viewing the cycle time statistics, and
                      of determining the minimum and maximum cycle time with the instruction "RT_INFO". You
                      need this information to determine the response times of the user program in the cycle.
                      To view the cycle time statistics, follow these steps:
                      1. Establish an online connection with the TIA Portal.
                      2. Select the Online tools task card on the very right.
                      Result: The diagram of the cycle time statistics is displayed in the cycle time section.
                      The following figure shows an extract from the TIA Portal with the cycle time statistics. In this
                      example, the cycle time ranges from 7 ms to 12 ms. The current cycle time is 10 ms. The
                      maximum cycle time that can be set in this example is 40 ms.

                      Figure 3-3   Cycle time statistics

                      You can find additional information on the runtime characteristics of the CPU with the
                      "RT_INFO" instruction in the user program. You can read the utilization of the CPU in
                      percentage with the control program and communication, and you can also read the runtime
                      statistics of individual OBs.

Reference
                      You can find additional information on the "RT_INFO" instruction in the STEP 7 online help.

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                            15
Cyclic program processing
3.2 Cycle time

3.2.2          Influences on the cycle time

3.2.2.1        Update time for process images

Introduction
                  In this section, you will learn how you can estimate the update time of process image
                  partitions.

Update time for process image partitions
                  The update time of the process image partitions depends on the quantity of assigned central
                  and distributed I/O module data.
                  You can estimate the update time using the following formula:

                     Base load for process image update
                  + Number of words in the process image x copy time for central I/O modules
                  + Number of words in the process image via DP x copy time for PROFIBUS I/O
                  + Number of words in the process image via PROFINET x copy time for PROFINET I/O
                  __________________________________________________________________________________
                  = Update time of the process image partition
                  The following table includes the times for estimating the typical update time of the process
                  image partitions.

                  Table 3- 1    Data for estimating the typical update time of the process image partition

                  Components                                         Update time of the CPU
                                      1511-1 PN        1513-1 PN         1515-2 PN       1516-3 PN/DP 1518-4 PN/DP
                  Base load for       35 μs            35 μs             30 μs           30 μs               5 μs
                  process image
                  partition update
                  Copy time for       9 μs/word        9 μs/word         8 μs/word       8 μs/word           4 μs/word
                  central I/O
                  modules
                  Copy time for       0.5 μs/word      0.5 μs/word       0.5 μs/word     0.5 μs/word         0.3 μs/word
                  distributed I/O
                  modules via
                  PROFIBUS
                  Copy time for       0.5 μs/word      0.5 μs/word       0.5 μs/word     0.5 μs/word         0.3 μs/word
                  distributed I/O
                  modules via
                  PROFINET

                                                                                                   Cycle and response times
16                                                                                Function Manual, 02/2014, A5E03461504-02
                                                                                            Cyclic program processing
                                                                                                        3.2 Cycle time

3.2.2.2           User program processing time

Introduction
                      Organization blocks or system activities with higher priority interrupt those with lower priority,
                      and thus extend the run time of the lower-priority organization blocks or system activities.

Program execution time without interruptions
                      The user program has a certain runtime without interruptions. The length of the run time
                      depends on the number of operations that are executed in the user program.
                      The following table contains the times for how long an operation lasts.

                      Table 3- 2     Duration of an operation

                       CPU                 1511-1 PN       1513-1 PN     1515-2 PN       1516-3 PN/DP 1518-4 PN/DP
                       Bit operations,     60 ns           40 ns         30 ns           10 ns           1 ns
                       typ.
                       Word operations,    72 ns           48 ns         36 ns           12 ns           2 ns
                       typ.
                       Fixed-point         96 ns           64 ns         48 ns           16 ns           2 ns
                       arithmetic, typ.
                       Floating-point      384 ns          256 ns        192 ns          64 ns           6 ns
                       arithmetic, typ.

                      Note
                      Instruction "RUNTIME"
                      You can measure the run times of program sequences with the instruction "RUNTIME".

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                              17
Cyclic program processing
3.2 Cycle time

Extension due to nesting of higher-priority OBs and/or interrupts
                  The interruption of a user program by a higher-priority OB causes a certain basic time
                  expenditure. Take account of this basic time expenditure in addition to the update time of the
                  assigned process image partitions and the processing time of the contained user program.
                  The following tables include the corresponding times for the various interrupts and error
                  events.

                  Table 3- 3    Basic time expenditure for an interrupt

                  CPU                 1511-1 PN        1513-1 PN          1515-2 PN      1516-3 PN/DP 1518-4 PN/DP
                  Hardware            90 μs            90 μs              80 μs          80 μs            12 μs
                  interrupt
                  Time-of-day         90 μs            90 μs              80 μs          80 μs            12 μs
                  interrupt
                  Time-delay          90 μs            90 μs              80 μs          80 μs            12 μs
                  interrupt
                  Cyclic interrupt    90 μs            90 μs              80 μs          80 μs            12 μs

                  Table 3- 4    Basic time expenditure for an error OB

                  CPU                 1511-1 PN        1513-1 PN          1515-2 PN      1516-3 PN/DP 1518-4 PN/DP
                  Programming         90 μs            90 μs              80 μs          80 μs            12 μs
                  error
                  I/O access error    90 μs            90 μs              80 μs          80 μs            12 μs
                  Time error          90 μs            90 μs              80 μs          80 μs            12 μs
                  Diagnostic          90 μs            90 μs              80 μs          80 μs            12 μs
                  interrupt
                  Module              90 μs            90 μs              80 μs          80 μs            12 μs
                  failure/recovery
                  CPU stop/           90 μs            90 μs              80 μs          80 μs            12 μs
                  recovery

Reference
                  You can find additional information on the subject of error handling in the system manual for
                  the S7-1500 Automation System
                  (http://support.automation.siemens.com/WW/view/en/59191792), in the Events and OBs
                  section.

                                                                                                  Cycle and response times
18                                                                                Function Manual, 02/2014, A5E03461504-02
                                                                                        Cyclic program processing
                                                                                                    3.2 Cycle time

3.2.2.3           Extension of cycle time due to communication load

Impact of communication on the cycle time
                      In the sequence model of the CPU, communication tasks are processed with priority 15. All
                      program parts with priority > 15 are not influenced by communication.

Configured communication load
                      The CPU operating system provides the maximum specified percentage of total CPU
                      processing power for communication tasks. The default setting for the communication load of
                      the S7-1500 automation system is 50% in the TIA Portal. If the processing power is not
                      needed for communication, then the processing power is available to the operating system
                      and the user program.
                      Communication is allocated the requisite processing time in 1-ms increments, with
                      priority 15. At 50% communication load, 500 μs of each 1 millisecond are used for
                      communication.
                      The following formula may be used to estimate the extension of the cycle time by
                      communication.

                      Figure 3-4   Formula: Impact of communication load

                      With a complete use of the communication load of 50% (default), the following value results:

                      Figure 3-5   Extension of cycle time due to communication load

                      The actual cycle time is up to twice as long as the cycle time without communication when
                      you use the default communication load.

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                          19
Cyclic program processing
3.2 Cycle time

Dependency of maximum cycle time on the configured communication load
                  The diagram shows the nonlinear relationship between maximum cycle time and configured
                  communication load with a pure cycle time of 10 ms, which means without interruptions.

                  Figure 3-6   Maximum cycle time depending on the configured communication load

                  The shown influence of the communication load on the processing time applies to all OBs
                  with a priority ≤ 15.

Reducing the cycle time through low communication load
                  You can reduce the setting for the communication load in the hardware configuration. If you
                  set a communication load of 20%, for example, instead of the default 50%, the cycle time is
                  reduced from 2 x cycle time without communication to 1.25 x cycle time without
                  communication.

                                                                                            Cycle and response times
20                                                                          Function Manual, 02/2014, A5E03461504-02
                                                                                         Cyclic program processing
                                                              3.3 Time-driven program processing in cyclic interrupts

Effect on the actual cycle time
                      Communication is only one cause for extension of the cycle time. All cycle time extending
                      settings lead to the result that more asynchronous events can occur within a cycle, which
                      additionally extend the cyclic program. This extension depends on the number of events that
                      occur in the cyclic program and the time required to process these events.

                      Note
                      Checking parameter changes
                      • Check the effects of a value change on the "Cycle load due to communication" parameter
                        during system operation.
                      • To prevent time errors, take account of the communication load when setting the
                        maximum cycle time.

Tips
                      Whenever possible, use the default setting for the configured communication load.
                      If you reduce the value of the communication load, keep in mind that communication tasks
                      are interrupted by higher-priority OBs. This means it will also take longer to process the
                      communication.

3.3               Time-driven program processing in cyclic interrupts
                      With a cyclic interrupt, you can have a particular program processed in a defined cycle. This
                      program is run at a higher priority (user-assigned) and is thus independent of the execution
                      time of the cyclic program.
                      Tip: By shifting program sections to cyclic interrupts, you can reduce the corresponding
                      response times or better adapt them to your requirements.
                      In STEP 7, the organization blocks OB 30 to OB 38 are provided for the processing of cyclic
                      interrupts. You can create additional cyclic interrupts starting with organization block OB 123.
                      The number of available organization blocks depends on the CPU used.

Definition
                      A cyclic interrupt is an interrupt initiated according to a defined cycle that causes a cyclic
                      interrupt OB to be processed.

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                               21
Cyclic program processing
3.3 Time-driven program processing in cyclic interrupts

Cycle of a cyclic interrupt
                   The cycle of a cyclic interrupt is defined as the time from the call of a cyclic interrupt OB to
                   the next call of a cyclic interrupt OB.
                   The following figure shows an example of the cycle of a cyclic interrupt.

                   Figure 3-7     Call interval of a cyclic interrupt

Accuracy of a cyclic interrupt
                   If a cyclic interrupt is not delayed by a higher-priority OB or communication activities, the
                   accuracy with which it is started is nevertheless subject to system-dependent fluctuations.
                   The following table shows the accuracy with which a cyclic interrupt is triggered:

                   Table 3- 5     Accuracy of cyclic interrupts

                    CPU                1511-1 PN         1513-1 PN      1515-2 PN      1516-3 PN/DP     1518-4 PN/DP
                    Cyclic interrupt   ±90 μs            ±90 μs         ±80 μs         ±80 μs           ±25 μs

                                                                                                 Cycle and response times
22                                                                               Function Manual, 02/2014, A5E03461504-02
                                                                                        Cyclic program processing
                                                  3.4 Response time for cyclic and time-driven program processing

3.4               Response time for cyclic and time-driven program processing

Introduction
                      In this section you will learn about the concept of "response time", and how to calculate the
                      response time.

Definition
                      The response time in the case of cyclic or time-controlled program execution is the time
                      between the detection of an input signal and the change of a connected output signal.

Fluctuation of the response time of the CPU
                      The actual response time of the CPU fluctuates between one and two cycle times for cyclic
                      program execution and between one and two cyclic interrupt cycles for time-controlled
                      program execution.
                      You must always reckon with the longest response time when configuring your system.
                      The following figure shows the shortest and longest response times of the CPU to an event.

                      Figure 3-8   Shortest and longest response times of the CPU

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                          23
Cyclic program processing
3.4 Response time for cyclic and time-driven program processing

Factors
                  To determine the process response time, you must take account of the following factors in
                  addition to the CPU response time described above:
                  ● Delay of the inputs and outputs at the I/O module
                  ● Update times for PROFINET IO or DP cycle times on PROFIBUS DP
                  ● Switching times of the sensors and actuators used

Delay at the inputs and outputs of the modules
                  Delays in the response time occur at the inputs and outputs of the modules and as a result of
                  device-internal delays (e.g., interface modules).
                  The delay and cycle times can be found in the technical specifications for the I/O modules.

Update time with distributed I/O
                  When distributed I/O are used, the maximum response time is also extended by the bus
                  transmission times of PROFIBUS or PROFINET. These bus transmission times occur when
                  process image partitions are read in and output. The bus transmission times correspond to
                  the bus update cycle of the distributed device.
                  PROFINET IO
                  If you use STEP 7 to configure your PROFINET IO system, STEP 7 calculates the update
                  time. Select the PROFINET interface of the I/O module. In the General tab, select "Advanced
                  options > Real time settings > I/O cycle". The update time is displayed in the field "Update
                  time".
                  PROFIBUS DP
                  If you use STEP 7 to configure your PROFIBUS DP master system, STEP 7 calculates the
                  DP cycle time. Select the PROFIBUS subnet in the network view. In the Inspector window,
                  navigate to the bus parameter in the General tab. The DP cycle time is typically displayed in
                  the "Parameters" field at "Ttr typical".
                  The following figure illustrates the additional bus runtimes using distributed I/O.

                  Figure 3-9   Additional bus runtimes with distributed I/O

                  You can achieve a further optimization of the response times using isochronous mode.

                                                                                              Cycle and response times
24                                                                            Function Manual, 02/2014, A5E03461504-02
                                                                                        Cyclic program processing
                                                  3.4 Response time for cyclic and time-driven program processing

Reference
                      The following links provide additional information:
                      ● Tool for calculating the reaction time on PROFINET
                        (http://support.automation.siemens.com/WW/view/en/21869080)
                      ● Tool for calculating the reaction time on PROFIBUS
                        (http://support.automation.siemens.com/WW/view/en/21178141)
                      ● Transmission times and isochronous mode in Function Manual PROFINET with STEP 7
                        V13 (http://support.automation.siemens.com/WW/view/en/49948856); note also the
                        chapter "Tips on assembly"
                      ● Transmission times and isochronous mode in Function Manual PROFIBUS with STEP 7
                        V13 (http://support.automation.siemens.com/WW/view/en/59193579); note also the
                        chapter "Network settings"
                      ● Delays at the input or output of the modules can be found in the manual for the respective
                        device.
                      ● Device-internal delays can be found in the manuals for the ET 200MP and ET 200SP
                        distributed I/O systems.

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                       25
Cyclic program processing
3.5 Summary of response time with cyclic and time-controlled program execution

3.5            Summary of response time with cyclic and time-controlled program
               execution

Estimation of the shortest and longest response time
                  The following formulas may be used to estimate the shortest and longest response time:

Estimation of the shortest response time
                  The shortest response time is the sum of:

                     1 x delay in the I/O module for inputs
                  + 1 x (update PROFINET IO or PROFIBUS DP)*
                  + 1 x transfer time of the process image inputs
                  + 1 x processing of the user program
                  + 1 x transfer time of the process image outputs
                  + 1 x (update PROFINET IO or PROFIBUS DP)*
                  + 1 x delay in the I/O module for outputs
                  _________________________________________________________________________________
                  = Shortest response time
                  * Time is dependent on the configuration and the extent of the network.
                  The shortest response time is equivalent to the sum of the cycle time plus the input and
                  output delay times.

Estimation of the longest response time
                  The longest response time is comprised of:

                     1 x delay in the I/O module for inputs
                  + 2 x (update PROFINET IO or PROFIBUS DP)*
                  + 2 x transfer time of the process image inputs
                  + 2 x processing of the user program
                  + 2 x transfer time of the process image outputs
                  + 2 x (update PROFINET IO or PROFIBUS DP)*
                  + 1 x delay in the I/O module for outputs
                  _________________________________________________________________________________
                  = Longest response time
                  * Time is dependent on the configuration and the extent of the network.
                  The longest response time is equivalent to the sum of twice the cycle time plus the delay
                  times of the inputs and outputs. The longest reaction time includes twice the update time for
                  PROFINET IO or twice the DP cycle time on PROFIBUS DP.

                                                                                            Cycle and response times
26                                                                         Function Manual, 02/2014, A5E03461504-02
Event-driven program processing                                                                              4
4.1               Response time of the CPUs when program execution is event-
                  controlled

Introduction
                      In order to detect events in the process immediately in the user program and to react to them
                      with an appropriate program, you use hardware interrupts. In STEP 7, organization blocks
                      OB 40 to OB 47 are provided for processing a hardware interrupt. You can create additional
                      hardware interrupts starting with organization block OB 123. The number of available
                      organization blocks depends on the CPU used.

Definition
                      A hardware interrupt is an interrupt that occurs during the running program processing, due
                      to an interrupt-triggering process event. The operating system calls the assigned interrupt
                      OB; as a result, the processing of the program cycle or of lower priority program parts is
                      interrupted.

Interrupt response times of the CPUs
                      The interrupt response times of the CPUs start with the occurrence of a hardware interrupt
                      event in the CPU and end with the start of the assigned hardware interrupt OB.
                      This time is subject to system-inherent fluctuations, and this is expressed using a minimum
                      and maximum interrupt response time.
                      The following table contains the length of the response times of the CPUs for hardware
                      interrupts.

                      Table 4- 1   Response times of the CPUs for hardware interrupts

                       CPU                 1511-1 PN      1513-1 PN      1515-2 PN      1516-3 PN/DP 1518-4 PN/DP
                       Interrupt   Min.    100 μs         100 μs         90 μs          90 μs        20 μs
                       response    Max.    400 μs         400 μs         360 μs         360 μs       90 μs
                       times

                      Note that the times are extended if higher-priority interrupts are queued up for processing,
                      and if the hardware interrupt OB is assigned to a process image partition. You can find these
                      times in the table Times for interrupts (Page 18).

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                           27
Event-driven program processing
4.1 Response time of the CPUs when program execution is event-controlled

Impact of communication on interrupts
                  Communication tasks are always processed by the CPU with priority 15. If you do not want
                  the interrupt processing to be delayed or interrupted by communication, configure the
                  interrupt processing with priority > 15. The default setting for interrupt processing is
                  priority 16.

Reference
                  You can find additional information on the number of available organization blocks in the
                  S7-1500 Automation System (http://support.automation.siemens.com/WW/view/en/59191792)
                  system manual, in the Events and OBs chapter.
                  You can find additional information on the topic of "Configuring hardware interrupts" in the
                  STEP 7 online help.

See also
                  User program processing time (Page 17)

                                                                                            Cycle and response times
28                                                                          Function Manual, 02/2014, A5E03461504-02
                                                                                Event-driven program processing
                                                4.2 Process response time when program execution is event-driven

4.2               Process response time when program execution is event-driven
                      When program execution is event-driven, the process response time is determined by the
                      following:
                      ● Delay times of the input and output modules used
                      ● Update times for PROFIBUS/PROFINET, if distributed modules are used
                      ● Interrupt response time of CPU
                      ● Runtimes of the interrupt OB including update of the process image partition
                      The following figure shows the individual processing steps for event-driven program
                      processing.

                      Figure 4-1   Schematic representation of event-driven program processing

Cycle and response times
Function Manual, 02/2014, A5E03461504-02                                                                       29
Glossary

Automation system
                      An automation system in the context of SIMATIC S7 is a programmable logic controller.

Cycle time
                      The cycle time represents the time a CPU requires to process the user program once.

Cyclic interrupt
        