Cycle and response times ___________________
Preface
___________________
Documentation guide 1
2
___________________
Program processing
SIMATIC
___________________
Cyclic program processing 3
S7-1500 Event-driven program
Cycle and response times ___________________
processing 4
Function Manual
02/2014
A5E03461504-02
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Siemens AG A5E03461504-02 Copyright © Siemens AG 2013 - 2014.
Industry Sector Ⓟ 02/2014 Technical data subject to change All rights reserved
Postfach 48 48
90026 NÜRNBERG
GERMANY
Preface
Purpose of the documentation
The control system offers various options for program execution with different run priorities.
Cyclic and time-driven program execution have the largest share. The response times of a
control system are therefore significantly determined by the processing cycles.
Additionally there is also the possibility of event-driven program execution. The event-driven
program execution is normally limited to a few selected events.
This manual provides information on the following topics:
● Types of program execution
● Run priorities
● Cycle and response times, and the influences to which they are subject
● Configuration options for the optimization of your user program
Basic knowledge required
The following knowledge is required in order to understand the documentation:
● General knowledge of automation technology
● Knowledge of the industrial automation system SIMATIC
● Knowledge about the use of Windows-based computers
● Knowledge about how to use STEP 7/TIA Portal
Conventions
STEP 7: We refer to the configuration and programming software as "STEP 7" in this
documentation synonymously for "STEP 7 V12 (TIA Portal)" and subsequent versions.
Please also observe notes marked as follows:
Note
A note contains important information on the product described in the documentation, on the
handling of the product and on the section of the documentation to which particular attention
should be paid.
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 3
Preface
Scope of the documentation
This documentation mainly includes the CPU components of the cycle and reaction times of
the S7-1500 automation system. You can find references at the corresponding instances for
more information on the ET 200MP and ET 200SP distributed I/O systems.
Additional support
Additional information on SIMATIC products is available on the Internet. The associated
documentation is likewise available on the Internet.
● You can find the available technical documentation for the individual SIMATIC products
and systems in the internet (http://www.siemens.com/simatic-tech-doku-portal).
● The online catalog and the ordering system are available on the Internet
(http://mall.automation.siemens.com).
Security information
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, solutions, machines, equipment and/or networks. They are
important components in a holistic industrial security concept. With this in mind, Siemens’
products and solutions undergo continuous development. Siemens recommends strongly
that you regularly check for product updates.
For the secure operation of Siemens products and solutions, it is necessary to take suitable
preventive action (e.g. cell protection concept) and integrate each component into a holistic,
state-of-the-art industrial security concept. Third-party products that may be in use should
also be considered. You can find more information about industrial security on the Internet
(http://www.siemens.com/industrialsecurity).
To stay informed about product updates as they occur, sign up for a product-specific
newsletter. You can find more information on the Internet
(http://support.automation.siemens.com).
Cycle and response times
4 Function Manual, 02/2014, A5E03461504-02
Table of contents
Preface ................................................................................................................................................... 3
1 Documentation guide .............................................................................................................................. 6
2 Program processing ................................................................................................................................ 8
3 Cyclic program processing .................................................................................................................... 11
3.1 Cycle ............................................................................................................................................11
3.2 Cycle time ....................................................................................................................................12
3.2.1 Different cycle times .....................................................................................................................12
3.2.2 Influences on the cycle time.........................................................................................................16
3.2.2.1 Update time for process images ..................................................................................................16
3.2.2.2 User program processing time .....................................................................................................17
3.2.2.3 Extension of cycle time due to communication load ....................................................................19
3.3 Time-driven program processing in cyclic interrupts ...................................................................21
3.4 Response time for cyclic and time-driven program processing ...................................................23
3.5 Summary of response time with cyclic and time-controlled program execution ..........................26
4 Event-driven program processing .......................................................................................................... 27
4.1 Response time of the CPUs when program execution is event-controlled .................................27
4.2 Process response time when program execution is event-driven ...............................................29
Glossary ............................................................................................................................................... 30
Index..................................................................................................................................................... 31
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 5
Documentation guide 1
Introduction
This modular documentation of the SIMATIC products covers diverse topics concerning your
automation system.
The complete documentation for the S7-1500 system consists of a system manual, function
manuals and device manuals.
The STEP 7 information system (Online Help) also helps you configure and program your
automation system.
Overview of the additional documentation on the topic of cycle and response times
The following table lists additional documentation which supplements this description of
cycle and response times.
Table 1- 1 Documentation of cycle and response times
Topic Documentation Most important contents
System System manual • Application planning
description S7-1500 Automation System
• Installation
(http://support.automation.siemens.com/WW/vi
ew/en/59191792) • Wiring
System manual • Commissioning
ET 200SP distributed I/O system
(http://support.automation.siemens.com/WW/vi
ew/en/58649293)
System manual
ET 200MP distributed I/O system
(http://support.automation.siemens.com/WW/vi
ew/en/59193214)
CPU Device manual • Block diagram
CPU 1511-1 PN
• Wiring
(http://support.automation.siemens.com/WW/vi
ew/en/68020492) • Parameter assignment/
Device manual addressing
CPU 1513-1 PN • Diagnostics alarms/
(http://support.automation.siemens.com/WW/vi interrupts
ew/en/59186494)
• Technical specifications
Device manual
• Dimensional drawings
CPU 1515-2 PN
(http://support.automation.siemens.com/WW/vi
ew/en/81162167)
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 6
Documentation guide
Topic Documentation Most important contents
Device manual
CPU 1516-3 PN/DP
(http://support.automation.siemens.com/WW/vi
ew/en/59191914)
Device manual
CPU 1518-4 PN/DP
(http://support.automation.siemens.com/WW/vi
ew/en/81164632)
Isochronous mode Function manual • Isochronous mode for
for PROFINET PROFINET with STEP 7 V13 PROFINET
(http://support.automation.siemens.com/WW/vi
ew/en/49948856) • Instructions "SYNC_PI" and
"SYNC_PO"
Isochronous mode Function manual • Isochronous mode for
for PROFIBUS PROFIBUS with STEP 7 V13 PROFIBUS
(http://support.automation.siemens.com/WW/vi
ew/en/59193579) • Instructions "SYNC_PI" and
"SYNC_PO"
SIMATIC manuals
All current manuals for the SIMATIC products are available for download free of charge from
the Internet (http://www.siemens.com/automation/service&support).
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 7
Program processing 2
Introduction
You often program your user program with a cyclic OB, usually in OB 1. With complex
applications, problems are often encountered in complying with the response time required
by the application. You can often solve the response time requirements by splitting the user
program up into several parts with different response time requirements. The CPU offers a
number of different OB types for this purpose, the properties (priority, frequency, etc.) of
which can be adapted to meet the requirements.
Program organization
You can choose from the following types of program execution for running your user
program:
Program execution in the cyclic program of the CPU:
In the simplest case, you execute the entire user program in the cyclic program of the CPU.
All tasks in the user program are then processed with equal rank. This also results in the
same response times for all tasks.
In addition to program execution in the cyclic program, there is time-driven and event-driven
program execution.
Time-driven processing:
In a complex user program, there are frequently portions with different response time
requirements. You can optimize the response times by taking advantage of these differences
in the requirements. To do so you can move the program parts with higher response time
requirements to higher-priority OBs with shorter cycles, for example cyclic interrupt OBs.
The processing of these parts can thus occur with different frequencies and priorities.
Event-driven processing:
Depending on the I/O modules used, you can configure hardware interrupts for specific
process events (such as an edge change of a digital input) that result in the call of the
assigned hardware interrupt OB. The hardware interrupts have a higher priority and interrupt
the cyclic program of the CPU. You can achieve very short response time in the CPU with
hardware interrupts by directly triggering program execution.
Keep in mind that the time characteristics of your application becomes less predictable with
intense use of hardware interrupts. The reason being that the time at which the triggering
events occur can result in drastically different response times.
Tip: Use hardware interrupts only for a few, select events.
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 8
Program processing
Using process image partitions
If a program is distributed to various OBs, for example, due to differing response time
requirements, it is advisable and often necessary to assign the update of the used I/O data
directly to these OBs. You can use process image partitions for this purpose.
You group the input and output data in a process image partition according to their use in the
program and assign the data to the corresponding OB.
You optimize the response times this way, because the update of the affected I/O modules is
directly synchronized with the processing in the program.
A process image partition of the inputs (PIPI) permits the associated input data for an
OB program to be updated immediately before the OB program starts.
A process image partition of the outputs (PIPQ) permits the output data associated with an
OB program to become effective on the outputs immediately after the OB program runs.
You have 32 (0 … 31) process image partitions at your disposal. The default assignment for
the I/O is process image partition 0 (setting: "Automatic updating"). Process image partition 0
is permanently assigned to cyclic processing.
You have to configure this "system-side update of process image partitions". You can find
additional information on configuration of process image partitions in the online help for
STEP 7 under the keyword "Assign process image/process image partition".
Interruptability of program run
Each organization block is processed with a priority. You can adapt the priority according to
the response time requirements for most organization blocks.
All cycle OBs always have the lowest priority of 1. The highest priority is 26.
Communication tasks always have priority 15. If necessary, you can change the priority of
your blocks and select a higher priority than the communication.
Organization blocks or system activities with higher priority interrupt those with lower priority,
and thus extend the run time of the interrupted organization blocks or system activities. If two
pending tasks have the same priority, these tasks are processed in the order in which the
tasks occurred.
Note
Higher priority OBs
Communication functionality is strongly influenced by too many or runtime-intensive OBs
with a priority > 15.
When using OBs with a priority > 15, you should consider the runtime load that they cause in
order to keep communication functionality at a reasonable level.
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 9
Program processing
Reference
You can find additional information on the subject of priorities in the system manual for the
S7-1500 Automation System
(http://support.automation.siemens.com/WW/view/en/59191792), in the Events and OBs
section.
Cycle and response times
10 Function Manual, 02/2014, A5E03461504-02
Cyclic program processing 3
3.1 Cycle
Introduction
In this section, you will learn about the concept of the "cycle".
Definition of cycle
A cycle in the S7-1500 automation system encompasses the following:
● Update of process image partition 0 of the inputs (PIPI 0)
● Processing of the cyclic program
● Update of process image partition 0 of the outputs (PIPQ 0)
The process image partition 0 is permanently assigned to the cycle. You assign
I/O addresses to this process image partition using the "Automatic updating" setting (default)
in the TIA Portal in HW Config for the I/O modules.
The figure below illustrates the phases that are passed through during a cycle.
① The operating system starts measurement of the cycle time.
② The CPU reads the status of the inputs at the input module and writes the input data to the
process image partition of the inputs.
③ The CPU processes the user program and executes the instructions specified in the program.
④ The CPU writes the states from the process image outputs to the output modules.
⑤ The operating system evaluates the determined cycle time and starts the measurement again.
Figure 3-1 Cycle
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 11
Cyclic program processing
3.2 Cycle time
3.2 Cycle time
Introduction
In this section you will learn about the concept of "cycle time", and how to estimate the cycle
time.
Definition of cycle time
The cycle time is the time the CPU need to execute the cyclic program, to update the
process image of the inputs and outputs as well as for all program parts and system
activities that interrupt this cycle.
3.2.1 Different cycle times
Introduction
The cycle time (Tcyc) is not equally long for every cycle, because the processing times can
vary. Causes for this are, for example:
● Different program runtimes
(e.g. program loops, conditional commands, conditional block calls, or different program
paths)
● Lengthening due to interruptions
(e.g. time-driven interrupt processing, processing of hardware interrupts or
communication)
Cycle and response times
12 Function Manual, 02/2014, A5E03461504-02
Cyclic program processing
3.2 Cycle time
Causes for different cycle times
The cycle time Tcyc2 is longer than Tcyc1, because the cyclic program is interrupted by a cyclic
interrupt OB in this example (e.g: OB 30). The cyclic interrupt OB in turn is interrupted by
communication.
The figure below shows the different cycle times Tcyc1 and Tcyc2.
Figure 3-2 Possible causes of differing cycle times
Minimum cycle time
In STEP 7, you can set a minimum cycle time for a CPU. The default for the minimum cycle
time is one millisecond. It may be advisable to increase this setting in the following cases:
● To reduce the cycle time's fluctuation range.
● To make remaining computing time available for communication tasks.
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 13
Cyclic program processing
3.2 Cycle time
Maximum cycle time
The cycle time is monitored by the CPU. By default, the maximum cycle time is 150 ms. This
value can be changed by setting CPU parameters. When the cycle time is longer than the
maximum cycle time, the time error OB (OB 80) is called.
You have the option of restarting the maximum cycle time using the "RE_TRIGR" instruction,
and thus extending it.
With the user program in OB 80 you specify how the CPU responds to the time error. Under
the following conditions the CPU goes to STOP.
● If you have not loaded an OB 80.
● If the cycle is still not completed after an additional maximum cycle time
Keep in mind that the cycle time is extended by interruptions as shown in the previous figure.
Cycle and response times
14 Function Manual, 02/2014, A5E03461504-02
Cyclic program processing
3.2 Cycle time
Cycle time statistics
In STEP 7 and in the TIA Portal, you have the option of viewing the cycle time statistics, and
of determining the minimum and maximum cycle time with the instruction "RT_INFO". You
need this information to determine the response times of the user program in the cycle.
To view the cycle time statistics, follow these steps:
1. Establish an online connection with the TIA Portal.
2. Select the Online tools task card on the very right.
Result: The diagram of the cycle time statistics is displayed in the cycle time section.
The following figure shows an extract from the TIA Portal with the cycle time statistics. In this
example, the cycle time ranges from 7 ms to 12 ms. The current cycle time is 10 ms. The
maximum cycle time that can be set in this example is 40 ms.
Figure 3-3 Cycle time statistics
You can find additional information on the runtime characteristics of the CPU with the
"RT_INFO" instruction in the user program. You can read the utilization of the CPU in
percentage with the control program and communication, and you can also read the runtime
statistics of individual OBs.
Reference
You can find additional information on the "RT_INFO" instruction in the STEP 7 online help.
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 15
Cyclic program processing
3.2 Cycle time
3.2.2 Influences on the cycle time
3.2.2.1 Update time for process images
Introduction
In this section, you will learn how you can estimate the update time of process image
partitions.
Update time for process image partitions
The update time of the process image partitions depends on the quantity of assigned central
and distributed I/O module data.
You can estimate the update time using the following formula:
Base load for process image update
+ Number of words in the process image x copy time for central I/O modules
+ Number of words in the process image via DP x copy time for PROFIBUS I/O
+ Number of words in the process image via PROFINET x copy time for PROFINET I/O
__________________________________________________________________________________
= Update time of the process image partition
The following table includes the times for estimating the typical update time of the process
image partitions.
Table 3- 1 Data for estimating the typical update time of the process image partition
Components Update time of the CPU
1511-1 PN 1513-1 PN 1515-2 PN 1516-3 PN/DP 1518-4 PN/DP
Base load for 35 μs 35 μs 30 μs 30 μs 5 μs
process image
partition update
Copy time for 9 μs/word 9 μs/word 8 μs/word 8 μs/word 4 μs/word
central I/O
modules
Copy time for 0.5 μs/word 0.5 μs/word 0.5 μs/word 0.5 μs/word 0.3 μs/word
distributed I/O
modules via
PROFIBUS
Copy time for 0.5 μs/word 0.5 μs/word 0.5 μs/word 0.5 μs/word 0.3 μs/word
distributed I/O
modules via
PROFINET
Cycle and response times
16 Function Manual, 02/2014, A5E03461504-02
Cyclic program processing
3.2 Cycle time
3.2.2.2 User program processing time
Introduction
Organization blocks or system activities with higher priority interrupt those with lower priority,
and thus extend the run time of the lower-priority organization blocks or system activities.
Program execution time without interruptions
The user program has a certain runtime without interruptions. The length of the run time
depends on the number of operations that are executed in the user program.
The following table contains the times for how long an operation lasts.
Table 3- 2 Duration of an operation
CPU 1511-1 PN 1513-1 PN 1515-2 PN 1516-3 PN/DP 1518-4 PN/DP
Bit operations, 60 ns 40 ns 30 ns 10 ns 1 ns
typ.
Word operations, 72 ns 48 ns 36 ns 12 ns 2 ns
typ.
Fixed-point 96 ns 64 ns 48 ns 16 ns 2 ns
arithmetic, typ.
Floating-point 384 ns 256 ns 192 ns 64 ns 6 ns
arithmetic, typ.
Note
Instruction "RUNTIME"
You can measure the run times of program sequences with the instruction "RUNTIME".
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 17
Cyclic program processing
3.2 Cycle time
Extension due to nesting of higher-priority OBs and/or interrupts
The interruption of a user program by a higher-priority OB causes a certain basic time
expenditure. Take account of this basic time expenditure in addition to the update time of the
assigned process image partitions and the processing time of the contained user program.
The following tables include the corresponding times for the various interrupts and error
events.
Table 3- 3 Basic time expenditure for an interrupt
CPU 1511-1 PN 1513-1 PN 1515-2 PN 1516-3 PN/DP 1518-4 PN/DP
Hardware 90 μs 90 μs 80 μs 80 μs 12 μs
interrupt
Time-of-day 90 μs 90 μs 80 μs 80 μs 12 μs
interrupt
Time-delay 90 μs 90 μs 80 μs 80 μs 12 μs
interrupt
Cyclic interrupt 90 μs 90 μs 80 μs 80 μs 12 μs
Table 3- 4 Basic time expenditure for an error OB
CPU 1511-1 PN 1513-1 PN 1515-2 PN 1516-3 PN/DP 1518-4 PN/DP
Programming 90 μs 90 μs 80 μs 80 μs 12 μs
error
I/O access error 90 μs 90 μs 80 μs 80 μs 12 μs
Time error 90 μs 90 μs 80 μs 80 μs 12 μs
Diagnostic 90 μs 90 μs 80 μs 80 μs 12 μs
interrupt
Module 90 μs 90 μs 80 μs 80 μs 12 μs
failure/recovery
CPU stop/ 90 μs 90 μs 80 μs 80 μs 12 μs
recovery
Reference
You can find additional information on the subject of error handling in the system manual for
the S7-1500 Automation System
(http://support.automation.siemens.com/WW/view/en/59191792), in the Events and OBs
section.
Cycle and response times
18 Function Manual, 02/2014, A5E03461504-02
Cyclic program processing
3.2 Cycle time
3.2.2.3 Extension of cycle time due to communication load
Impact of communication on the cycle time
In the sequence model of the CPU, communication tasks are processed with priority 15. All
program parts with priority > 15 are not influenced by communication.
Configured communication load
The CPU operating system provides the maximum specified percentage of total CPU
processing power for communication tasks. The default setting for the communication load of
the S7-1500 automation system is 50% in the TIA Portal. If the processing power is not
needed for communication, then the processing power is available to the operating system
and the user program.
Communication is allocated the requisite processing time in 1-ms increments, with
priority 15. At 50% communication load, 500 μs of each 1 millisecond are used for
communication.
The following formula may be used to estimate the extension of the cycle time by
communication.
Figure 3-4 Formula: Impact of communication load
With a complete use of the communication load of 50% (default), the following value results:
Figure 3-5 Extension of cycle time due to communication load
The actual cycle time is up to twice as long as the cycle time without communication when
you use the default communication load.
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 19
Cyclic program processing
3.2 Cycle time
Dependency of maximum cycle time on the configured communication load
The diagram shows the nonlinear relationship between maximum cycle time and configured
communication load with a pure cycle time of 10 ms, which means without interruptions.
Figure 3-6 Maximum cycle time depending on the configured communication load
The shown influence of the communication load on the processing time applies to all OBs
with a priority ≤ 15.
Reducing the cycle time through low communication load
You can reduce the setting for the communication load in the hardware configuration. If you
set a communication load of 20%, for example, instead of the default 50%, the cycle time is
reduced from 2 x cycle time without communication to 1.25 x cycle time without
communication.
Cycle and response times
20 Function Manual, 02/2014, A5E03461504-02
Cyclic program processing
3.3 Time-driven program processing in cyclic interrupts
Effect on the actual cycle time
Communication is only one cause for extension of the cycle time. All cycle time extending
settings lead to the result that more asynchronous events can occur within a cycle, which
additionally extend the cyclic program. This extension depends on the number of events that
occur in the cyclic program and the time required to process these events.
Note
Checking parameter changes
• Check the effects of a value change on the "Cycle load due to communication" parameter
during system operation.
• To prevent time errors, take account of the communication load when setting the
maximum cycle time.
Tips
Whenever possible, use the default setting for the configured communication load.
If you reduce the value of the communication load, keep in mind that communication tasks
are interrupted by higher-priority OBs. This means it will also take longer to process the
communication.
3.3 Time-driven program processing in cyclic interrupts
With a cyclic interrupt, you can have a particular program processed in a defined cycle. This
program is run at a higher priority (user-assigned) and is thus independent of the execution
time of the cyclic program.
Tip: By shifting program sections to cyclic interrupts, you can reduce the corresponding
response times or better adapt them to your requirements.
In STEP 7, the organization blocks OB 30 to OB 38 are provided for the processing of cyclic
interrupts. You can create additional cyclic interrupts starting with organization block OB 123.
The number of available organization blocks depends on the CPU used.
Definition
A cyclic interrupt is an interrupt initiated according to a defined cycle that causes a cyclic
interrupt OB to be processed.
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 21
Cyclic program processing
3.3 Time-driven program processing in cyclic interrupts
Cycle of a cyclic interrupt
The cycle of a cyclic interrupt is defined as the time from the call of a cyclic interrupt OB to
the next call of a cyclic interrupt OB.
The following figure shows an example of the cycle of a cyclic interrupt.
Figure 3-7 Call interval of a cyclic interrupt
Accuracy of a cyclic interrupt
If a cyclic interrupt is not delayed by a higher-priority OB or communication activities, the
accuracy with which it is started is nevertheless subject to system-dependent fluctuations.
The following table shows the accuracy with which a cyclic interrupt is triggered:
Table 3- 5 Accuracy of cyclic interrupts
CPU 1511-1 PN 1513-1 PN 1515-2 PN 1516-3 PN/DP 1518-4 PN/DP
Cyclic interrupt ±90 μs ±90 μs ±80 μs ±80 μs ±25 μs
Cycle and response times
22 Function Manual, 02/2014, A5E03461504-02
Cyclic program processing
3.4 Response time for cyclic and time-driven program processing
3.4 Response time for cyclic and time-driven program processing
Introduction
In this section you will learn about the concept of "response time", and how to calculate the
response time.
Definition
The response time in the case of cyclic or time-controlled program execution is the time
between the detection of an input signal and the change of a connected output signal.
Fluctuation of the response time of the CPU
The actual response time of the CPU fluctuates between one and two cycle times for cyclic
program execution and between one and two cyclic interrupt cycles for time-controlled
program execution.
You must always reckon with the longest response time when configuring your system.
The following figure shows the shortest and longest response times of the CPU to an event.
Figure 3-8 Shortest and longest response times of the CPU
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 23
Cyclic program processing
3.4 Response time for cyclic and time-driven program processing
Factors
To determine the process response time, you must take account of the following factors in
addition to the CPU response time described above:
● Delay of the inputs and outputs at the I/O module
● Update times for PROFINET IO or DP cycle times on PROFIBUS DP
● Switching times of the sensors and actuators used
Delay at the inputs and outputs of the modules
Delays in the response time occur at the inputs and outputs of the modules and as a result of
device-internal delays (e.g., interface modules).
The delay and cycle times can be found in the technical specifications for the I/O modules.
Update time with distributed I/O
When distributed I/O are used, the maximum response time is also extended by the bus
transmission times of PROFIBUS or PROFINET. These bus transmission times occur when
process image partitions are read in and output. The bus transmission times correspond to
the bus update cycle of the distributed device.
PROFINET IO
If you use STEP 7 to configure your PROFINET IO system, STEP 7 calculates the update
time. Select the PROFINET interface of the I/O module. In the General tab, select "Advanced
options > Real time settings > I/O cycle". The update time is displayed in the field "Update
time".
PROFIBUS DP
If you use STEP 7 to configure your PROFIBUS DP master system, STEP 7 calculates the
DP cycle time. Select the PROFIBUS subnet in the network view. In the Inspector window,
navigate to the bus parameter in the General tab. The DP cycle time is typically displayed in
the "Parameters" field at "Ttr typical".
The following figure illustrates the additional bus runtimes using distributed I/O.
Figure 3-9 Additional bus runtimes with distributed I/O
You can achieve a further optimization of the response times using isochronous mode.
Cycle and response times
24 Function Manual, 02/2014, A5E03461504-02
Cyclic program processing
3.4 Response time for cyclic and time-driven program processing
Reference
The following links provide additional information:
● Tool for calculating the reaction time on PROFINET
(http://support.automation.siemens.com/WW/view/en/21869080)
● Tool for calculating the reaction time on PROFIBUS
(http://support.automation.siemens.com/WW/view/en/21178141)
● Transmission times and isochronous mode in Function Manual PROFINET with STEP 7
V13 (http://support.automation.siemens.com/WW/view/en/49948856); note also the
chapter "Tips on assembly"
● Transmission times and isochronous mode in Function Manual PROFIBUS with STEP 7
V13 (http://support.automation.siemens.com/WW/view/en/59193579); note also the
chapter "Network settings"
● Delays at the input or output of the modules can be found in the manual for the respective
device.
● Device-internal delays can be found in the manuals for the ET 200MP and ET 200SP
distributed I/O systems.
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 25
Cyclic program processing
3.5 Summary of response time with cyclic and time-controlled program execution
3.5 Summary of response time with cyclic and time-controlled program
execution
Estimation of the shortest and longest response time
The following formulas may be used to estimate the shortest and longest response time:
Estimation of the shortest response time
The shortest response time is the sum of:
1 x delay in the I/O module for inputs
+ 1 x (update PROFINET IO or PROFIBUS DP)*
+ 1 x transfer time of the process image inputs
+ 1 x processing of the user program
+ 1 x transfer time of the process image outputs
+ 1 x (update PROFINET IO or PROFIBUS DP)*
+ 1 x delay in the I/O module for outputs
_________________________________________________________________________________
= Shortest response time
* Time is dependent on the configuration and the extent of the network.
The shortest response time is equivalent to the sum of the cycle time plus the input and
output delay times.
Estimation of the longest response time
The longest response time is comprised of:
1 x delay in the I/O module for inputs
+ 2 x (update PROFINET IO or PROFIBUS DP)*
+ 2 x transfer time of the process image inputs
+ 2 x processing of the user program
+ 2 x transfer time of the process image outputs
+ 2 x (update PROFINET IO or PROFIBUS DP)*
+ 1 x delay in the I/O module for outputs
_________________________________________________________________________________
= Longest response time
* Time is dependent on the configuration and the extent of the network.
The longest response time is equivalent to the sum of twice the cycle time plus the delay
times of the inputs and outputs. The longest reaction time includes twice the update time for
PROFINET IO or twice the DP cycle time on PROFIBUS DP.
Cycle and response times
26 Function Manual, 02/2014, A5E03461504-02
Event-driven program processing 4
4.1 Response time of the CPUs when program execution is event-
controlled
Introduction
In order to detect events in the process immediately in the user program and to react to them
with an appropriate program, you use hardware interrupts. In STEP 7, organization blocks
OB 40 to OB 47 are provided for processing a hardware interrupt. You can create additional
hardware interrupts starting with organization block OB 123. The number of available
organization blocks depends on the CPU used.
Definition
A hardware interrupt is an interrupt that occurs during the running program processing, due
to an interrupt-triggering process event. The operating system calls the assigned interrupt
OB; as a result, the processing of the program cycle or of lower priority program parts is
interrupted.
Interrupt response times of the CPUs
The interrupt response times of the CPUs start with the occurrence of a hardware interrupt
event in the CPU and end with the start of the assigned hardware interrupt OB.
This time is subject to system-inherent fluctuations, and this is expressed using a minimum
and maximum interrupt response time.
The following table contains the length of the response times of the CPUs for hardware
interrupts.
Table 4- 1 Response times of the CPUs for hardware interrupts
CPU 1511-1 PN 1513-1 PN 1515-2 PN 1516-3 PN/DP 1518-4 PN/DP
Interrupt Min. 100 μs 100 μs 90 μs 90 μs 20 μs
response Max. 400 μs 400 μs 360 μs 360 μs 90 μs
times
Note that the times are extended if higher-priority interrupts are queued up for processing,
and if the hardware interrupt OB is assigned to a process image partition. You can find these
times in the table Times for interrupts (Page 18).
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 27
Event-driven program processing
4.1 Response time of the CPUs when program execution is event-controlled
Impact of communication on interrupts
Communication tasks are always processed by the CPU with priority 15. If you do not want
the interrupt processing to be delayed or interrupted by communication, configure the
interrupt processing with priority > 15. The default setting for interrupt processing is
priority 16.
Reference
You can find additional information on the number of available organization blocks in the
S7-1500 Automation System (http://support.automation.siemens.com/WW/view/en/59191792)
system manual, in the Events and OBs chapter.
You can find additional information on the topic of "Configuring hardware interrupts" in the
STEP 7 online help.
See also
User program processing time (Page 17)
Cycle and response times
28 Function Manual, 02/2014, A5E03461504-02
Event-driven program processing
4.2 Process response time when program execution is event-driven
4.2 Process response time when program execution is event-driven
When program execution is event-driven, the process response time is determined by the
following:
● Delay times of the input and output modules used
● Update times for PROFIBUS/PROFINET, if distributed modules are used
● Interrupt response time of CPU
● Runtimes of the interrupt OB including update of the process image partition
The following figure shows the individual processing steps for event-driven program
processing.
Figure 4-1 Schematic representation of event-driven program processing
Cycle and response times
Function Manual, 02/2014, A5E03461504-02 29
Glossary
Automation system
An automation system in the context of SIMATIC S7 is a programmable logic controller.
Cycle time
The cycle time represents the time a CPU requires to process the user program once.
Cyclic interrupt