SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Molded case motor starter protectors SIRIUS 3RV1

Вид документаКаталожна сторінка
ВиробникSIEMENS
Моделі3RV10 63, 3RV10 73, 3RV10 83, 3RV13 53, 3RV13 63, 3RV13 73, 3RV13 83, 3RV13 64
Група обладнанняelectrical
Мова документаанглійська
Розмір файлу0.2 МБ

Про документ

Siemens SIRIUS 3RV1 molded case motor starter protectors up to 800 A. Type 3RV10 provides motor protection with standard switching capacity; type 3RV13 is used for starter combinations and offers standard or increased switching capacity.

Ключові дані

Rated current In100 ... 200 A / 400 A / 630 A (3RV10); 1 ... 32 A to 630, 800 A (3RV13)
Rated operational voltage Ue690 V AC
Rated frequency50/60 Hz
Short-circuit breaking capacity Icu at 400 V AC85 ... 200 kA depending on size
Trip classCLASS 10A, 10, 20, 30 (3RV10)

Застосування

  • Motor protection (3RV10)
  • Starter combinations (3RV13)

Особливості

  • Standard switching capacity (3RV10 63/73/83; 3RV13 53/63/73/83) or increased switching capacity (3RV13 64/74)
  • Thermal overload release CLASS 10A, 10, 20, 30 (3RV10)
  • Electronic release, adjustable multiple of rated current (6 … 13 times for 3RV10; 1 … 10 times non-adjustable or adjustable for 3RV13)
  • Trip units TU 1, TU 2, TU 3, TU 4
  • Wide accessory range: auxiliary switches, undervoltage releases, shunt releases, rotary operating mechanisms
  • Connection methods: extended terminals on the front, cable terminals on the front, rear terminals

Технічні дані

Parameter Value
Rated current In (3RV10 63) 100 ... 200 A
Rated current In (3RV10 73) 400 A
Rated current In (3RV10 83) 630 A
Rated current In (3RV13 53) 1 ... 32 A
Rated current In (3RV13 63) 100 ... 250 A
Rated current In (3RV13 73) 400, 630 A
Rated current In (3RV13 83) 630, 800 A
Rated current In (3RV13 64) 100 ... 250 A
Rated current In (3RV13 74) 400 A
Rated operational voltage Ue according to IEC 690 V AC
Rated frequency 50/60 Hz
Trip class (3RV10) CLASS 10A, 10, 20, 30
Thermal overload release (3RV10) 40 ... 100 to 252 ... 630 A
Electronic release, multiple of rated current (3RV10) Adjustable, 6 ... 13 times
Electronic release, multiple of rated current (3RV13) Non-adjustable 1 ... 10 times; adjustable: 1 ... 12.5 A: 13 times; 20 A, 32 A: 6 ... 12 times
Short-circuit breaking capacity Icu at 400 V AC (3RV10 63) 120 kA
Short-circuit breaking capacity Icu at 400 V AC (3RV10 73) 120 kA
Short-circuit breaking capacity Icu at 400 V AC (3RV10 83) 100 kA
Short-circuit breaking capacity Icu at 400 V AC (3RV13 53) 85 kA
Short-circuit breaking capacity Icu at 400 V AC (3RV13 63) 120 kA
Short-circuit breaking capacity Icu at 400 V AC (3RV13 73) 120 kA
Short-circuit breaking capacity Icu at 400 V AC (3RV13 83) 100 kA
Short-circuit breaking capacity Icu at 400 V AC (3RV13 64) 200 kA
Short-circuit breaking capacity Icu at 400 V AC (3RV13 74) 200 kA
Trip unit (release) TU 4; TU 1: 1 ... 12.5 A; TU 2: 20 A, 32 A; TU 3

Варіанти замовлення

Accessories available for all sizes: auxiliary switches ✓, undervoltage releases ✓, shunt releases ✓, rotary operating mechanisms ✓. Connection methods per model:

  • Extended terminals on the front: 3RV10 63 ✓, 3RV10 73 ✓, 3RV10 83 --, 3RV13 53 ✓, 3RV13 63 ✓, 3RV13 73 ✓, 3RV13 83 --, 3RV13 64 ✓, 3RV13 74 ✓
  • Cable terminals on the front: all models ✓
  • Rear terminals: all models ✓

Note: For overload protection of the motors, appropriate overload relays must be used.

Текст документа

                                                                           © Siemens AG 2013

               Protection Equipment

      Introduction

    ■ Overview




      Type                              3RV10                                   3RV13
      SIRIUS 3RV1 molded case motor starter protectors up to 800 A
      Applications
      • Motor protection                ✓                                       --
      • Starter combinations            --                                      ✓
      Switching capacity                Standard switching capacity             Standard switching capacity                                 Increased switching
                                                                                                                                            capacity
      Size                              3RV10 63        3RV10 73     3RV10 83   3RV13 53           3RV13 63         3RV13 73   3RV13 83     3RV13 64      3RV13 74
      Rated current In              A   100 ... 200     400          630        1 ... 32           100 ... 250      400, 630   630, 800     100 ... 250   400
      Rated operational voltage V       690 AC                                  690 AC
      Ue according to IEC
      Rated frequency               Hz 50/60                                    50/60
      Trip class                        CLASS 10A, 10, 20, 30                   --1)
      Thermal overload release A        40 ... 100 to                           Without1)
7                              A        252 ... 630
      Electronic release
      A multiple of the rated           Adjustable, 6 ... 13 times              Non-               1 ... 10 times
      current                                                                   adjustable
                                                                                1 ... 12.5 A:
                                                                                13 times;
                                                                                Adjustable
                                                                                20 A, 32 A:
                                                                                6 ... 12 times
      Short-circuit breaking        kA 120              120          100        85                 120              120        100          200           200
      capacity Icu at 400 V AC
      Trip unit (release)               TU 4                                    TU 1:              TU 3
                                                                                1 ... 12.5 A;
                                                                                TU 2:
                                                                                20 A, 32 A

      Accessories
      For molded case motor             3RV10 63        3RV10 73     3RV10 83   3RV13 53          3RV13 63          3RV13 73   3RV13 83     3RV13 64      3RV13 74
      starter protectors
      Auxiliary switches                ✓               ✓            ✓          ✓                 ✓                 ✓          ✓            ✓             ✓
      Undervoltage releases             ✓               ✓            ✓          ✓                 ✓                 ✓          ✓            ✓             ✓
      Shunt releases                    ✓               ✓            ✓          ✓                 ✓                 ✓          ✓            ✓             ✓
      Rotary operating mechanisms       ✓               ✓            ✓          ✓                 ✓                 ✓          ✓            ✓             ✓
      Connection methods
      • Extended terminals on the       ✓               ✓            --         ✓                 ✓                 ✓          --           ✓             ✓
        front
      • Cable terminals on the          ✓               ✓            ✓          ✓                 ✓                 ✓          ✓            ✓             ✓
        front
      • Rear terminals                  ✓               ✓            ✓          ✓                 ✓                 ✓          ✓            ✓             ✓
                                                                                        1)
      ✓ Has this function or can use this accessory                                          For overload protection of the motors, appropriate overload relays must be
      -- Does not have this function or cannot use this accessory                            used.




        7/4          Siemens IC 10 · 2013


Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.