| Вид документа | Каталожна сторінка |
|---|---|
| Виробник | SIEMENS |
| Моделі | 3RV10 63, 3RV10 73, 3RV10 83, 3RV13 53, 3RV13 63, 3RV13 73, 3RV13 83, 3RV13 64 |
| Група обладнання | electrical |
| Мова документа | англійська |
| Розмір файлу | 0.2 МБ |
Про документ
Siemens SIRIUS 3RV1 molded case motor starter protectors up to 800 A. Type 3RV10 provides motor protection with standard switching capacity; type 3RV13 is used for starter combinations and offers standard or increased switching capacity.
Ключові дані
| Rated current In | 100 ... 200 A / 400 A / 630 A (3RV10); 1 ... 32 A to 630, 800 A (3RV13) |
|---|---|
| Rated operational voltage Ue | 690 V AC |
| Rated frequency | 50/60 Hz |
| Short-circuit breaking capacity Icu at 400 V AC | 85 ... 200 kA depending on size |
| Trip class | CLASS 10A, 10, 20, 30 (3RV10) |
Застосування
- Motor protection (3RV10)
- Starter combinations (3RV13)
Особливості
- Standard switching capacity (3RV10 63/73/83; 3RV13 53/63/73/83) or increased switching capacity (3RV13 64/74)
- Thermal overload release CLASS 10A, 10, 20, 30 (3RV10)
- Electronic release, adjustable multiple of rated current (6 … 13 times for 3RV10; 1 … 10 times non-adjustable or adjustable for 3RV13)
- Trip units TU 1, TU 2, TU 3, TU 4
- Wide accessory range: auxiliary switches, undervoltage releases, shunt releases, rotary operating mechanisms
- Connection methods: extended terminals on the front, cable terminals on the front, rear terminals
Технічні дані
| Parameter | Value |
|---|---|
| Rated current In (3RV10 63) | 100 ... 200 A |
| Rated current In (3RV10 73) | 400 A |
| Rated current In (3RV10 83) | 630 A |
| Rated current In (3RV13 53) | 1 ... 32 A |
| Rated current In (3RV13 63) | 100 ... 250 A |
| Rated current In (3RV13 73) | 400, 630 A |
| Rated current In (3RV13 83) | 630, 800 A |
| Rated current In (3RV13 64) | 100 ... 250 A |
| Rated current In (3RV13 74) | 400 A |
| Rated operational voltage Ue according to IEC | 690 V AC |
| Rated frequency | 50/60 Hz |
| Trip class (3RV10) | CLASS 10A, 10, 20, 30 |
| Thermal overload release (3RV10) | 40 ... 100 to 252 ... 630 A |
| Electronic release, multiple of rated current (3RV10) | Adjustable, 6 ... 13 times |
| Electronic release, multiple of rated current (3RV13) | Non-adjustable 1 ... 10 times; adjustable: 1 ... 12.5 A: 13 times; 20 A, 32 A: 6 ... 12 times |
| Short-circuit breaking capacity Icu at 400 V AC (3RV10 63) | 120 kA |
| Short-circuit breaking capacity Icu at 400 V AC (3RV10 73) | 120 kA |
| Short-circuit breaking capacity Icu at 400 V AC (3RV10 83) | 100 kA |
| Short-circuit breaking capacity Icu at 400 V AC (3RV13 53) | 85 kA |
| Short-circuit breaking capacity Icu at 400 V AC (3RV13 63) | 120 kA |
| Short-circuit breaking capacity Icu at 400 V AC (3RV13 73) | 120 kA |
| Short-circuit breaking capacity Icu at 400 V AC (3RV13 83) | 100 kA |
| Short-circuit breaking capacity Icu at 400 V AC (3RV13 64) | 200 kA |
| Short-circuit breaking capacity Icu at 400 V AC (3RV13 74) | 200 kA |
| Trip unit (release) | TU 4; TU 1: 1 ... 12.5 A; TU 2: 20 A, 32 A; TU 3 |
Варіанти замовлення
Accessories available for all sizes: auxiliary switches ✓, undervoltage releases ✓, shunt releases ✓, rotary operating mechanisms ✓. Connection methods per model:
- Extended terminals on the front: 3RV10 63 ✓, 3RV10 73 ✓, 3RV10 83 --, 3RV13 53 ✓, 3RV13 63 ✓, 3RV13 73 ✓, 3RV13 83 --, 3RV13 64 ✓, 3RV13 74 ✓
- Cable terminals on the front: all models ✓
- Rear terminals: all models ✓
Note: For overload protection of the motors, appropriate overload relays must be used.
Текст документа
© Siemens AG 2013
Protection Equipment
Introduction
■ Overview
Type 3RV10 3RV13
SIRIUS 3RV1 molded case motor starter protectors up to 800 A
Applications
• Motor protection ✓ --
• Starter combinations -- ✓
Switching capacity Standard switching capacity Standard switching capacity Increased switching
capacity
Size 3RV10 63 3RV10 73 3RV10 83 3RV13 53 3RV13 63 3RV13 73 3RV13 83 3RV13 64 3RV13 74
Rated current In A 100 ... 200 400 630 1 ... 32 100 ... 250 400, 630 630, 800 100 ... 250 400
Rated operational voltage V 690 AC 690 AC
Ue according to IEC
Rated frequency Hz 50/60 50/60
Trip class CLASS 10A, 10, 20, 30 --1)
Thermal overload release A 40 ... 100 to Without1)
7 A 252 ... 630
Electronic release
A multiple of the rated Adjustable, 6 ... 13 times Non- 1 ... 10 times
current adjustable
1 ... 12.5 A:
13 times;
Adjustable
20 A, 32 A:
6 ... 12 times
Short-circuit breaking kA 120 120 100 85 120 120 100 200 200
capacity Icu at 400 V AC
Trip unit (release) TU 4 TU 1: TU 3
1 ... 12.5 A;
TU 2:
20 A, 32 A
Accessories
For molded case motor 3RV10 63 3RV10 73 3RV10 83 3RV13 53 3RV13 63 3RV13 73 3RV13 83 3RV13 64 3RV13 74
starter protectors
Auxiliary switches ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Undervoltage releases ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Shunt releases ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Rotary operating mechanisms ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Connection methods
• Extended terminals on the ✓ ✓ -- ✓ ✓ ✓ -- ✓ ✓
front
• Cable terminals on the ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
front
• Rear terminals ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
1)
✓ Has this function or can use this accessory For overload protection of the motors, appropriate overload relays must be
-- Does not have this function or cannot use this accessory used.
7/4 Siemens IC 10 · 2013