3TK28 solid-state safety relays with contactor relay enabling circuits

Вид документаТехнічний паспорт
ВиробникSIEMENS
Моделі3TK28 50, 3TK28 51, 3TK28 52, 3TK28 53, 3TK28 56, 3TK28 57
Група обладнанняautomation
Мова документаанглійська
Розмір файлу0.2 МБ

Про документ

Solid-state safety relays combined with contactor relays in a single fully wired and tested unit for snapping onto a standard mounting rail. They are used in EMERGENCY-STOP circuits and safety circuits per EN 60204-1 (11.98), e.g. for moving covers and protective doors. Depending on device type and external circuit, up to Category 4 of EN 954-1 or SIL 3 per IEC 61508 can be achieved.

Ключові дані

max_categoryCategory 4 of EN 954-1 or SIL 3 according to IEC 61508 (depending on device type and external circuit)
basic_units_categoryUp to Category 3 according to EN 954-1
mountingSnap-on mounting on TH 35 standard mounting rail according to EN 60715; screw fixing with 2 additional 3RP19 03 push-in lugs

Застосування

  • EMERGENCY-STOP circuits
  • Safety circuits according to EN 60204-1 (11.98), e.g. moving covers and protective doors
  • Cascading with 3TK28 41, 3TK28 42, 3TK28 45, 3TK28 53 safety relays and 3RA7 11 load feeder via safe solid-state output (terminal 2)
  • Connection of expansion units 3TK28 30, 3TK28 56, 3TK28 57, 3RA7 11 to 3RA7 14, external actuators or loads via safe solid-state output (terminal 2)
  • Normal switching duty via connection of a PLC output

Особливості

  • Combination of solid-state safety relay and contactor relays with positively-driven contacts in one certified complete unit
  • Basic units 3TK28 50–52: two contactor relays as floating switch blocks, three LEDs for operating state and function
  • 3TK28 53: two contactor relays plus safe solid-state output, safe cascading input, input for normal switching duty
  • Cyclic monitoring of all internal circuit elements during operation; self-test at start-up
  • Automatic or monitored start depending on parameterization (AS/ÜS)
  • Optional crossover monitoring (QS)
  • 3TK28 57 offers delayed (OFF-delay tv) enabling circuits; 3TK28 56 instantaneous

Технічні дані

Parameter Value
Max achievable category Category 4 of EN 954-1 or SIL 3 according to IEC 61508 (depending on device type and external circuit)
Basic units 3TK28 50–52 category Up to Category 3 according to EN 954-1, depending on external circuit
Sensor inputs (basic units 3TK28 50–52) One sensor input each, varying number of contactor relay enabling circuits and signaling outputs
3TK28 53 One sensor input, one cascading input, one input for normal switching duty, solid-state and contactor relay enabling circuits
Expansion units 3TK28 56/57 One cascading input, one input for normal switching duty, solid-state enabling circuits or contactor relay enabling/signaling outputs
Start behavior Automatic start (AS) or automatic/monitored start (AS/ÜS) depending on parameterization
Time delay (3TK28 57) OFF-delay tv, time-delayed NO contacts (NOtv)
Mounting Snap-on TH 35 standard mounting rail per EN 60715; screw fixing via 2 × 3RP19 03 push-in lugs
Indication Three LEDs for operating state and function

Варіанти замовлення

  • 3TK28 50 – basic unit, 1-/2-channel AS/ÜS, FK hs (NO) enabling circuits
  • 3TK28 51 – basic unit, 1-/2-channel AS/ÜS, FK hs (NO), MK hs (NC)
  • 3TK28 52 – basic unit, 1-/2-channel AS/ÜS, multiple FK hs (NO)
  • 3TK28 53 – basic unit with cascading input (KAS), normal switching duty (BS), QS crossover monitoring option, FK hs / FK el / MK hs outputs
  • 3TK28 56 – expansion unit, instantaneous
  • 3TK28 57 – expansion unit, delayed (tv)

Допуски та стандарти

  • EN 418 (Category 4 devices)
  • EN 954-1 (Category 3 / Category 4)
  • EN 60204-1 (11.98)
  • IEC 61508 (SIL 3)
  • EN 60715 (TH 35 mounting rail)
  • Certified by the appropriate authorities as a complete unit

Текст документа

               3TK28 Safety Relays

      With contactor relay enabling circuits

    ■ Design
      The solid-state safety relays can be used in EMERGENCY-STOP                     Basic units, Category 4
      devices according to EN 418 and in safety circuits according to
      EN 60204-1 (11.98), for example, for moving covers and protec-                  The 3TK28 53 solid-state safety relay has two contactor relays
      tive doors. Depending on the device type and the external                       snapped onto the safety solid-state units as floating switch
      circuit, the maximum category that can be achieved is Category                  blocks, as well as a safe solid-state output, a safe input for
      4 of EN 954-1 or SIL 3 according to IEC 61508.                                  cascading and one input for normal switching duty. Three LEDs
                                                                                      indicate the operating state and the function.
      With these devices, solid-state safety relays are connected with
      contactor relays. The combination is supplied as a complete                     During start-up, the device runs through a self-test in which the
      unit, fully wired up and tested, for snapping onto a standard                   internal electronics are checked for correct functioning. During
      mounting rail. This unit combines the advantages of a solid-state               operation, all internal circuit elements are monitored cyclically
      safety relay and those of contactor relays with positively-driven               for faults.
      contacts in a single device. It has been certified by the                       Expansion units, namely 3TK28 30, 3TK28 56, 3TK28 57,
      appropriate authorities as a complete unit.                                     3RA7 11 to 3RA7 14, as well as external actuators or loads can
                                                                                      be connected using the safe solid-state output (terminal 2).
      Basic units, Category 3                                                         Cascading with the 3TK28 41, 3TK28 42, 3TK28 45 and
      The solid-state safety relays 3TK28 50, 3TK28 51 and 3TK28 52                   3TK28 53 safety relays as well as with the 3RA7 11 load feeder
      have two contactor relays snapped onto the safety solid-state                   is also possible using the safe solid-state output (terminal 2).
      unit as floating switch blocks. Three LEDs indicate the operating
      state and the function. During operation, all internal circuit                  Installation
      elements are monitored cyclically for faults. Up to Category 3                  For snap-on mounting on TH 35 standard mounting rail
      according to EN 954-1 is achieved, depending on the external                    according to EN 60715. Screw fixing is also possible for the
      circuit.                                                                        devices by means of 2 additional 3RP19 03 push-in lugs.

    ■ Function
      Basic units
                                                                                                                   3TK28 52 basic unit
      3TK28 50 to 3TK28 52                                                                                                                            FK hs
                                                                                             S1
                                                                                                           AS/ÜS                                       (NO)
      The devices 3TK28 50 to 3TK28 52 each have one sensor input
      and a varying number of contactor relay enabling circuits and                                                                                   FK hs
      signaling outputs. If the signal is no longer applied to the sensor                                                                              (NO)
      input, the enabling circuits are isolated immediately.
                                                                                                                                                      FK hs
                                                                                                                                                       (NO)

                                                                                                                                                      FK hs
                                 3TK28 50 basic unit                                                                                                   (NO)

            S1                                                  FK hs                                                                                 FK hs
                         AS/ÜS                                   (NO)                                                                                  (NO)

                                                                FK hs                                                                                 FK hs
                                                                 (NO)                                                                                  (NO)

                                                                FK hs                                                                                 MKhs
                                                                 (NO)                                                                                 (NO)
7
                                                                        NSC0_00689a
                       1-/2-channel AS/ÜS                                                                                                                     NSC0_00691a
                                                                                                        1-/2-channel AS/ÜS



                                                                                      Legend
                                                                                      Sensor interface
                                                                                      Sx:           Sensor input
                                 3TK28 51 basic unit                                  Safety logic
                                                                FK hs                 AS/ÜS:       Automatic or monitored start depending on the parameterization
            S1
                         AS/ÜS                                   (NO)
                                                                                      Parameters
                                                                FK hs                 1-/2-channel: One-channel / two-channel sensor connection
                                                                 (NO)                 AS/ÜS:        Automatic or monitored start depending on the
                                                                                                    parameterization
                                                                MK hs                 Actuator interface
                                                                (NC)
                                                                                      FKhs:          Enabling circuit, contactor relay (floating)

                                                                        NSC0_00690a
                                                                                      MKhs:          Signaling circuit, contactor relay (floating)
                                                                                      NO:            NO contact
                       1-/2-channel AS/ÜS                                             NC:            NC contact




       7/116        Siemens LV 1 T · 2007
                                                                                                              3TK28 Safety Relays

                                                                                                             With contactor relay enabling circuits
Basic units                                                                                Expansion units
3TK28 53                                                                                   3TK28 56 and 3TK28 57
The 3TK28 53 has one sensor input and one one input for normal                             The 3TK28 56 and 3TK28 57 devices each have one one input
switching duty and one cascading input. On the output side is a                            for normal switching duty and one cascading input. On the
varying number number of solid-state enabling circuits or                                  output side is a varying number number of solid-state enabling
contactor relay enabling circuits. If the signal is no longer                              circuits or contactor relay enabling circuits and signaling
applied to one of the inputs, the enabling circuits are isolated                           outputs. If the signal is no longer applied to one of the inputs, the
immediately. Autostart or monitored start can be selected in the                           enabling circuits are isolated immediately or according to the set
parameterization.                                                                          delay time.

                            3TK28 53 Basic unit                                                          3TK28 56 expansion unit instantaneous
                                                                      FK hs                                                                           FK hs
      BS                                                                                        BS
                       AS         &                                   (NO)                                     &                                      ( NO)

                    AS/ÜS                                             FK hs                                                                           FK hs
      KAS                                                                                      KAS
                                                                      (NO)                                                                            (NO)
                    AS/ÜS
                                                                      FK hs                                                                           FK hs
      S1
                                                                      (NO)                                                                            (NO)

                                                                      FK el                                                                           FK hs
                                                                      (NO)                                                                            (NO)


                                                                              NSC0_00692
                                                                                                                                                      FK hs
                  QS   AS/ÜS                                                                                                                          (NO)

                                                                                                                                                      FK hs
                                                                                                                                                      (NO)
Legend
Sensor interface                                                                                                                                       FK el
Sx:          Sensor input                                                                                                                             (NO)
KAS/BS:      Cascading input or normal switching duty..
             Normal switching duty: Connection of a PLC output for example.                                                                           MK hs
             The enabling circuits and hence the connected loads can then                                                                             (NC)
             be operated by the machine control.

                                                                                                                                                                   NSC0_00693
             The safety function is on a higher level.
Safety logic
AS:          Automatic start. Device starts automatically once the
             enabling conditions are fulfilled. If a START button is integrated in
             the feedback circuit, a manual start is also possible (up to
             Category 3 according to EN 954-1).
AS/ÜS:       Automatic or monitored start depending on the parameterization
Parameters
QS:        With or without crossover monitoring
AS/ÜS:     Automatic or monitored start depending on the parameterization                                  3TK28 57 expansion unit delayed
                                                                                                                                                        FK hs
                                                                                                 BS                                          tv
                                                                                                                                                       (NOtv )
 tv          Time delay, OFF-delay                                                                             &

                                                                                                                                                        FK hs
Actuator interface                                                                              KAS                                          tv
                                                                                                                                                         tv tv )
                                                                                                                                                       (NO                         7
FKel:        Enabling circuit, solid-state (non-floating)
FKhs:        Enabling circuit, contactor relay (floating)                                                                                               FK hs
MKhs:        Signaling circuit, contactor relay (floating)                                                                                   tv
                                                                                                                                                       (NO tv)
NO:          NO contact

                                                                                                                                                                      NSC0_00694
NOtv:        NO contact, time-delayed                                                                                                                  FK el
NC:          NC contact
                                                                                                                                                       (NO)




                                                                                                                              Siemens LV 1 T · 2007      7/117
