ZFR1800 Series Wireless Field Bus System
Product Bulletin
Code No. LIT-12011336
Release 10.1
Issued December 5, 2014
Refer to the QuickLIT Web site for the most up-to-date version of this document.
The ZFR1800 Series Wireless Field Bus System
provides a wireless platform for all Metasys® Field
Equipment Controller (FEC) family controllers using
BACnet® protocol over 2.4 GHz wireless ISM band.
One ZFR1811 router is required per field controller.
This pairing of a router and any FEC family device is
referred to as a Wireless-Enabled Field Controller
(WEFC). An FEC family device is an Advanced
Application Field Equipment Controller (FAC), FEC,
Input/Output Module (IOM), or VAV Modular Assembly
16 Series (VMA16) field controller.
A ZFR1800 Series system consists of:
Figure 1: ZFR1811 Routers (top left),
• up to eight ZFR1810 Wireless Field Bus ZFR1810 Coordinator (top center), and
Coordinators per field bus WRZ Series Sensors (bottom)
• up to 35 Wireless Enabled Field Controllers
(WEFCs) per coordinator
Together, these components create a wireless mesh
• up to 100 WEFCs per field bus, depending on the network that allows the exchange of data between the
network engine (32 with NCE, 50 with NAE35) collection of devices within the ZFR1800 Series
system’s wireless network and wired BACnet
• up to nine WRZ Sensors per FEC or VMA16 field
Multidrop Serial Bus/Token-Passing (MS/TP) devices.
controller
The wireless mesh network enhances reliability by
• additional ZFR1811 Wireless Field Bus Routers
providing redundant transmission paths for the data
connected to MS-ZFRRPT-0 Repeater
through other routers in the mesh network. The result
accessories, as required, acting as repeaters
is a resilient, self-healing network.
Note: Repeaters extend the wireless transmission
distance of the BACnet data communications, fill in any
gaps within the wireless mesh network, and provide
multiple wireless data transmission pathways.
Table 1: Features and Benefits (Part 1 of 2)
Features Benefits
Wireless Communications for a Metasys Provide a wireless platform for Metasys BACnet devices across multiple
System levels of a Metasys Building Automation System (BAS), from supervisory
engines, to field controllers, to room sensors; enable wireless devices to
coexist with hard-wired devices on the same Metasys network; offer simple
add-on hardware to seamlessly enable standard hard-wired Metasys
BACnet field controllers to function wirelessly.
Wireless Mesh Network Enables quick, economical, and low-maintenance installation; minimizes
MS/TP BACnet hardwiring; and enhances reliability through automatically
forming wireless links and redundant wireless data transmission paths.
ZFR1800 Series Wireless Field Bus System Product Bulletin 1
Table 1: Features and Benefits (Part 2 of 2)
Features Benefits
Improved Application Mobility and Provides a wireless alternative to hard-wired counterparts; facilitates easy
Flexibility initial location and relocation with minimal disruption to building occupants;
and cost-effectively extends Metasys systems to applications where
building aesthetics (such as solid walls or ceilings, temporary walls, or
decorative surfaces) normally hinder hardwiring.
Support of up to Nine WRZ Series Wireless Facilitates averaging and high/low selection to optimize comfort in larger
Room Sensors per Wirelessly Enabled Field zones. Installs easily; provides room temperature, setpoint temperature,
Controller occupancy status, and low battery status information to a Metasys system;
offers extensive battery life of up to 5 years.
Multiple Diagnostic Light-Emitting Diodes Provide quick and easy visual indication of power, FC bus activity, wireless
(LEDs) activity, wireless signal strength, and fault conditions; help locate optimum
device positions during installation and aid in troubleshooting.
Compact, Easy-to-Install, and Versatile Adapt easily to multiple mounting scenarios; serve multiple functions,
ZFR1811 Routers including providing wireless interface for numerous Metasys FEC, IOM, and
VMA16 controllers; and function as repeaters to extend wireless
transmission range.
Applications • stadiums, arenas, gymnasiums, convention
centers, airports, zoos, and other locations with
IMPORTANT: Use the ZFR1800 Series Wireless large, open spaces
Field Bus System only to provide an input to
• buildings with marble, granite, glass, mirrored,
equipment under normal operating conditions.
wood veneer, or other decorative surfaces that
Where failure or malfunction of the sensor could
present challenges to hard-wiring
lead to personal injury or property damage to the
controlled equipment or other property, additional • buildings with asbestos or other hazardous
precautions must be designed into the control materials that must not be disturbed
system. Incorporate and maintain other devices,
• buildings with occupants sensitive to disruptions to
such as supervisory or alarm systems or safety or
business
limit controls, intended to warn of or protect against
failure or malfunction of the ZFR1800 Series • regions with high labor costs
System.
The ZFR1800 Series System is approved by national
The wireless Metasys products within a Metasys compliance agencies for use only in the United States
system are ideal for any location where it is and Canada. See Technical Specifications.
cost-prohibitive, difficult, or aesthetically unappealing to Applications to Avoid
hardwire between Metasys products. Examples of
these locations include the following: IMPORTANT: A Network Engine reports an offline
• hospitals, office buildings, university campuses, alarm within a certain period of time when an
educational facilities, correctional facilities, and associated FEC, IOM, or VMA16 field controller
other commercial structures with brick or solid goes offline. For a hard-wired FEC, IOM, or VMA16
concrete walls and/or ceilings that impede device, this time period is a nominal 20 seconds. For
hard-wired applications a wirelessly enabled FEC, IOM, or VMA16 device
within the ZFR1800 Wireless Field Bus System, this
• office buildings, retail stores, and other commercial time period is 5 minutes.
real estate where tenant turnover is frequent and
temporary walls and ceilings are common Locations or applications that prohibit cellular
telephones or Wi-Fi systems are unsuitable for the
• museums, historical buildings, atriums, and other
wireless Metasys products. Examples include:
sites where building aesthetics and historical
preservation are important • operating rooms or radiation therapy rooms
• validated environments
• UL 864 applications
2 ZFR1800 Series Wireless Field Bus System Product Bulletin
• Department of Defense applications requiring The MS/TP trunk and device limits for supported
Diacap certification (for example, military bases NAE35/45/55 or NCE25 models are the same for
and military hospitals) hard-wired devices, wireless devices, or a combination
of hard-wired and wireless devices. For more
Do not use the wireless Metasys products in
information, refer to the ZFR1800 Series Wireless Field
applications that cannot tolerate intermittent
Bus System Technical Bulletin (LIT-12011295). For
interference, or where:
information on device quantity limits in a ZFR1800
• critical control features would impact life-safety or Series system, see Table 2.
result in large monetary loss, including secondary Table 2: ZFR1800 Series System Device Quantity
(backup) life-safety applications Limits
• data centers, production lines, or critical areas Device Quantity Limit
would be shut down ZFR1810 Coordinator Up to eight per NAE35/45/
• loss of critical control would result from loss of data 55 or NCE25 trunk
from humidity or temperature sensor ZFR1811 Router Paired Up to 35 WEFCs per
communications with an FEC, IOM, or ZFR1810 Coordinator
VMA16 Field Controller
• operation of exhaust fans or Air Handling Units ZFR1811 Router Used as Unlimited2
(AHUs) would impair a purge or pressurization Repeaters1
mode
WRZ Series Sensor Up to nine sensors per
• missing data would invalidate reporting required by wireless-enabled field
the customer controller
• security points are monitored 1. Requires use of the MS-ZFRRPT-0 optional repeater
accessory.
System Overview 2. Indiscriminate use of ZFR1811 Routers as repeaters can
lead to reduced performance.
Figure 2 illustrates a simple ZFR1800 Series Wireless
Field Bus System applied to BACnet field controllers on
Component Descriptions
a Metasys network.
Network Automation Engine (NAE) and Network
These devices provide wireless monitoring and control
Control Engine (NCE)
of HVAC equipment within multiple levels of a
Metasys BACnet system. NAE35/45/55s and NCE25s (NxEs) are Web-enabled,
Ethernet-based, supervisory controllers that connect
Refer to the ZFR1800 Series Wireless Field Bus BAS networks to Internet Protocol (IP) networks and
System Technical Bulletin (LIT-12011295) for the Web. NAEs and NCEs provide scheduling, alarm
information on commissioning and configuring a and event management, trending, energy
ZFR1800 Series Wireless Field Bus System for management, data exchange, dial-out capability, and
operation. password protection. With a computer running
Windows® Internet Explorer® Version 6.0 (or later),
you can browse to a configured NxE, and monitor and
control BAS field devices in the Metasys Site
Management Portal on the NxE.
ZFR1810 Coordinators
A ZFR1810 Wireless Field Bus Coordinator provides a
wireless interface between an NxE supervisory
controller on a wired BACnet MS/TP network and
wireless-enabled Metasys BACnet FEC, IOM, or VMA
field controllers.
Each wireless mesh network requires one ZFR1810
Coordinator, which initiates the formation of the
network. Each field bus can support up to eight
ZFR1810 Coordinators.
ZFR1800 Series Wireless Field Bus System Product Bulletin 3
A ZFR1810 Coordinator can operate from either of two Note: Wirelessly enabled FEC and VMA16 field
power sources: controllers can also use hard-wired NS Series network
sensors.
• a 24 VAC, Class 2 power source
WRZ Series Sensors
• 15 VDC power provided from the FC Bus Jack on
any Field Equipment or Supervisory Controller that Depending on the sensor model, the WRZ Series
is connected directly to the FC Bus Sensors transmit temperature, setpoint, humidity,
occupancy status, and low battery conditions to an
The ZFR1810 Coordinator features a remote-mount associated field controller by means of a ZFR1811
antenna and cable to allow transmission when the Router. If the field controller is mapped to the NxE, the
ZFR1810 Coordinator is mounted inside a metal panel. data sent by the wireless sensor can be displayed.
ZFR1811 Routers Some applications that support the temperature or
A ZFR1811 Wireless Field Bus Router is used with any humidity control functions do not support the
model FEC, IOM, or VMA16 field controller to provide a occupancy/temperature setback function. Refer to a
wireless interface between a field controller and: field controller’s commissioning and operation literature
to determine if the application supports occupancy or
• the NAE/NCE supervisory controller (by means of
temperature setback functions.
a ZFR1810 Coordinator)
Note: Configure the Analog Inputs (AIs) on all WRZ
• its associated WRZ Series Sensors
Sensors as SA Bus devices (the same as with
The ZFR1811 Router can also be used as a repeater to hard-wired NS Series Sensors).
extend the range of the data communications within the
Note: The WRZ Series Sensors are designed for
wireless mesh network, or to fill any gaps within the
indoor, intra-building applications only.
mesh network, based on the physical layout of the
wireless devices, obstacles, and other characteristics The WRZ Series Sensors require two 1.5 VDC AA
of the installation site. alkaline batteries. The WRZ sensors minimize power
consumption by transmitting data only once per minute,
A ZFR1811 Router is powered directly from the
which yields an expected battery life of approximately
connected field controller’s 15 VDC output. It can also
4 to 5 years.
be powered by the ZFRRPT repeater accessory to
serve as a stand-alone repeater, extending the range ZFR Checkout Tool (ZCT)
of the BACnet data communications within the wireless The ZFR Checkout Tool is an optional tool, included
mesh network. with the installation of the Controller Configuration Tool
Supported Field Controllers (CCT), that allows you to validate the wireless
connectivity and health of wireless devices within a
The ZFR1800 Series Wireless Field Bus System
ZFR1800 Series Wireless Field Bus system, helping
enables wireless BACnet connectivity between all
ensure a reliable mesh network is in place. You can
FEC, IOM, or VMA16 controllers and Network
use the information provided by the ZCT to analyze
Automation Engines, including NAE/35/45/55 and
and troubleshoot the wireless mesh network created by
NCEs. In addition, the wireless field bus system
a ZFR1800 Series System.
provides wireless communication between FEC/
VMA16 controllers and WRZ Series wireless sensors. The ZCT gathers information by discovering the
wireless field controllers and wireless sensors on your
Note: The ZFR1811 Routers should be at the same
network and analyzing their status and wireless
Metasys system release version as the wirelessly
communication paths. The ZCT provides a simple
enabled FEC, IOM, or VMA16 field controller. If there is
report of wireless network performance, including
a version mismatch, the Controller Configuration Tool
online status verification and wireless signal strength
(CCT) provides indication of this, and the
information. The ZCT also provides wireless device
ZFR1811 Router is automatically updated during the
lists, signal strength information, and diagnostic
main code download to the field controller. For
measurements of the wireless mesh network.
information on uploading or downloading the devices to
match, refer to the Loading Devices chapter of the Refer to the Using the ZFR Checkout Tool (ZCT)
CCT Help (LIT-12011147). chapter of the CCT Help (LIT-12011147) for more
information on the ZCT.
Note: Some field controller applications do not
support the occupancy/temperature setback function.
4 ZFR1800 Series Wireless Field Bus System Product Bulletin
The ZCT requires a Universal Serial Bus (USB) WRZ-SST-120 Wireless Sensing System Tool
adaptor with ZFR driver. Use the optional, battery-operated WRZ-SST-120
Note: You must connect the adaptor to the computer Wireless Sensing System Tool with any model
running CCT/ZCT before attempting to scan the WRZ Series Sensor as a site survey tool to determine
network. the wireless signal strength between potential locations
of ZFR1800 system devices to survey your application
ZFR Repeater Kit and adjust ZFR1800 device locations before installing
The MS-ZFRRPT-0 is an optional repeater accessory the devices. Refer to the WRZ-SST-120 Wireless
for the ZFR1811 Router which allows remote mounting Sensing System Tool Installation Instructions
of the ZFR1811 Router without an FEC family (Part No. 24-10563-12) for more information on the
controller. The ZFRRPT Repeater contains a 4 x 4 inch tool.
(10.16 x 10.16 cm) electrical box with a 24 VAC to 15
VDC converter for powering the ZFR1811 Router.
ZFR Wireless USB Dongle
The ZFRRPT also contains a conduit sleeve for The ZFR Wireless USB Dongle allows a laptop
attaching a ZFR1811 to the 4 x 4 inch electrical box. computer to connect to a ZFR Field Router wireless
field bus for the purpose of commissioning and
USB Adaptor with ZFR Driver downloading applications to wirelessly enabled field
The ZFR connection type within CCT requires the USB controllers using the CCT or for analyzing a ZFR
adaptor with ZFR driver for your laptop computer. The wireless mesh using the ZFR Checkout Tool (ZCT).
USB adaptor provides a wireless connection to allow The ZFR Wireless USB Dongle requires a USB
wireless commissioning of the wireless-enabled field software driver which is installed automatically with
controllers and allows the use of the ZCT. CCT Version 5.3 or later. No user configuration is
required.
See Table 6 to order the ZFR USB adaptor (product
code ZFR-USBHA-0). This device is an IEEE 802.154 For more information, refer to the ZFR1800 Series
ZFR to USB Adaptor for the 2.4 GHz ISM Band. Wireless Field Bus System Technical Bulletin
(LIT-12011295).
Note: The software driver for the ZFR USB adaptor
installs automatically with the CCT.
ZFR1800 Series Wireless Field Bus System Product Bulletin 5
NAE
WRZ
Sensor A1 WRZ
Sensor A2
VMA16 ZFR1811
Device Address 4 Router B
ZFR1811
Router A
VMA16 IOM
Device Address 8 Device Address 9
FEC
Device Address 5
WRZ
Sensor A3
ZFR1810
IOM Coordinator
Device Address 6
WRZ
Sensor C4
Note: Signal range varies
depending on installation.
Signal range is shown as
a radius to illustrate
FEC ZFR1811 overlapping devices.
Device Address 7 Router D The radius is 7.6 m
(Used as Repeater) (25 ft).
WRZ
Sensor C1
FC Bus
ZFR1811
Router C
Note: Sensor does not need WRZ
FEC Sensor C2
to be in the range of its
Device Address 10
target controller. WRZ
FIG:wrd_wrlss
Sensor C3
Note: The ZFR system supports
all FEC family controllers
including FECs, Advanced Application
Field Equipment Controllers (FACs), IOMs,
and VMAs.
Figure 2: ZFR1800 Series Wireless Field Bus System as Part of a Metasys Network
6 ZFR1800 Series Wireless Field Bus System Product Bulletin
ZFR1800 Series System Wireless Transmission ranges between ZFR1800 Series
Communication products can be less than the maximum distances
shown in Table 3.
The ZFR1800 Series System devices create a wireless
mesh network using ZFR technology. The mesh Table 3: Indoor Line-of-Sight Transmission
network provides redundant wireless paths, enabling Ranges
the BACnet data to traverse the network through Range Type Transmission Distance
alternate, automatically forming paths and arrive at the ZFR1810 WRZ Series
target destination device even if a ZFR1811 Router or Coordinator, Sensor
Repeater within the wireless mesh network ZFR1811 Router
experiences interference or drops out of the network.
Recommended 15.2 m (50 ft) 15.2 m (50 ft)
The ZFR1800 Series System uses Direct Sequence Maximum 76.2 m (250 ft) 30 m (100 ft)
Spread Spectrum (DSSS) Radio Frequency (RF)
technology and operates on the globally accepted Wireless Interference and Security
2.4 GHz Industrial, Scientific, and Medical (ISM) band.
All ZFR1800 Series System components use a The ZFR1800 Series Wireless Field Bus System is
transmission power of 10 mW. The WRZ Series designed to minimize the potential for wireless
sensors meet the Institute of Electrical and Electronics interference with other wireless applications. In most
Engineers, Inc. (IEEE) 802.15.4 standard for low commercial environments, the ZFR1800 Series
power, low duty-cycle wireless transmitting systems System does not encounter or generate wireless
and are compatible with wireless mesh networks interference, even in environments with cell phones
compliant with the ZigBee standard. and competing Wi-Fi applications.
For more information on wireless transmissions, signal ZFR1800 Series Wireless transmissions use different
strength, and locating devices for optimum signal modulation schemes than Wi-Fi applications and use
strength, refer to the ZFR1800 Series Wireless Field frequencies between popular Wi-Fi bands, enabling
Bus System Technical Bulletin (LIT-12011295). Wi-Fi and ZFR1800 Series Wireless networks to exist
in the same areas.
Wireless Signal Transmission Range
For more information on wireless interference and
The effective transmission range/distance for indoor security, refer to the ZFR1800 Series Wireless Field
applications varies because of wireless signal Bus System Technical Bulletin (LIT-12011295).
absorption and reflection due to metal obstructions,
walls (or floors), and furniture found in typical building
interiors.
ZFR1800 Series Wireless Field Bus System Product Bulletin 7
Physical Features and Dimensions Figure 4 shows the ZFR1811 Router.
Figure 3 shows the ZFR1810 Coordinator with the
remote-mounted antenna.
Figure 4: ZFR1811 Wireless Field Bus Router,
Physical Features and Dimensions, mm (in.)
Figure 5 shows the WRZ Series Sensor.
Figure 3: ZFR1810 Wireless Field Bus Coordinator,
Physical Features and Dimensions, mm (in.)
Figure 5: WRZ Series Sensor,
Physical Features and Dimensions, mm (in.)
8 ZFR1800 Series Wireless Field Bus System Product Bulletin
Ordering Information Refer to the Network Automation Engine (NAE)
Product Bulletin (LIT-1201160) and the Metasys
For ZFR1800 Series System product ordering
System Field Equipment Controllers and Related
information, see Table 4 and Table 5. For ZFR1800
Products Product Bulletin (LIT-12011042) for additional
Series System accessories product ordering
information on related products.
information, see Table 6. For supported models of the
Metasys BACnet field controllers, see Table 7. Repair Information
Contact the nearest Johnson Controls® representative If a ZFR1800 Series Wireless Field Bus System
to order the products in Table 4 through Table 7. component fails to operate within its specifications,
Specify the desired product code number from these replace the unit. For a replacement ZFR1800 Series
tables. System component, contact the nearest
Johnson Controls representative.
Table 4: ZFR1800 Series Wireless Field Bus System Components
Product Code Product Description
Number
MS-ZFR1810-x Wireless Field Bus Coordinator, 10 mW Transmission Power; functions with NAE35, NAE45, NAE55,
and NCE25 Models
MS-ZFR1811-x Wireless Field Bus Router, 10 mW Transmission Power; functions with Metasys BACnet FECs, IOMs,
VMA16s, and WRZ Series Sensors
WRZ-MHN0100-0 Wireless Remote Transmitter with Temperature, Relative Humidity (RH) and Occupancy Motion
Detector (PIR) only, No Display
WRZ-MNN0100-0 Wireless Remote Transmitter with Occupancy Detection (PIR), No Display
WRZ-MTB0100-0 Wireless Remote Transmitter with Display, Temperature, Relative Humidity (RH), and Occupancy
Detection only, Warmer/Cooler (+/-) Setpoint Adjustment (setpoint configured in the Metasys system)
WRZ-MTN0100-0 Wireless Remote Transmitter with Temperature and Occupancy Detection only, No Display
WRZ-RMT10K-0 Wireless Remote Temperature Transmitter designed to operate with a TE-6300 Series 10k ohm
Johnson Controls® Type II Thermistor Sensor (order separately) to sense temperature in warmer
applications up to 158°F (70°C). Includes one Transmitter, one Mounting Base, strips of Double-Sided
Adhesive Foam Tape (all factory assembled), and one Strain Relief
WRZ-STR0000-0 Wireless Transmitter and Temperature Sensor with Display and F/C Button. Includes Temperature
Probe encased in a Clear Acrylic Cylinder, 9 ft (2.7 m) Wire Lead, one Probe Mounting Strap, and a strip
of Double-Sided Adhesive Foam Tape, 10 mW Transmission Power
WRZ-STRNIST-0 NIST Rated Wireless Transmitter and Temperature Sensor with Display and F/C Button. Includes
Temperature Probe encased in a Clear Acrylic Cylinder, 9 ft (2.7 m) Wire Lead, one Probe Mounting
Strap, and a strip of Double-Sided Adhesive Foam Tape, 10 mW Transmission Power
WRZ-THB0000-0 Wireless Temperature/Humidity Sensor with Display, Warmer/Cooler (+/-) Setpoint Adjustment or
Setpoint Adjustment Scale: 13 to 29°C/55 to 85°F, F/C Button, Relative Humidity (RH) Button and
Occupancy Button, 10 mW Transmission Power
WRZ-THN0000-0 Wireless Temperature/Humidity Sensor, Occupancy Button, No Temperature adjustment and No LCD
temperature/humidity display, 10 mW Transmission Power
WRZ-THP0000-0 Wireless Temperature/Humidity Sensor, Warmer/Cooler (+/-) Setpoint Adjustment and Occupancy
Button, No LCD temperature/humidity display, 10 mW Transmission Power
WRZ-TTB0000-0 Wireless Temperature Sensor with Display and F/C Button, 10 mW Transmission Power
WRZ-TTD0000-0 Wireless Temperature Sensor with Display, F/C Button and Fan Speed Control, 10 mW Transmission
Power
WRZ-TTP0000-0 Wireless Room Temperature Sensor, Warmer/Cooler (+/-) Setpoint Adjustment, 10 mW Transmission
Power
WRZ-TTR0000-0 Wireless Room Temperature Sensor, No Setpoint Adjustment, 10 mW Transmission Power
WRZ-TTS0000-0 Wireless Room Temperature Sensor, Setpoint Adjustment Scale: 13 to 29°C/55 to 85°F, 10 mW
Transmission Power
ZFR1800 Series Wireless Field Bus System Product Bulletin 9
Table 5: WRZ Sensor Model Comparison
Sensor Model Temperature 3% Display F/C Fan Occupancy Occupancy Setpoint
Humidity Button Control Motion Override Adjustment
Detection (PIR) Dial1
WRZ-MHN0100-0 x x x
WRZ-MNN0100-0 x
WRZ-MTB0100-0 x x
WRZ-MTN0100-0 x x x ABSOL
WRZ-RMT10K-0 x
WRZ-STR0000-0 x x x
WRZ-STRNIST-0 x x x
WRZ-THB0000-0 x x x x x Both
WRZ-THN0000-0 x x x
WRZ-THP0000-0 x x x W/C
WRZ-TTB0000-0 x x x x Both
WRZ-TTD0000-0 x x x x x Both
WRZ-TTP0000-0 x x W/C
WRZ-TTR0000-0 x x
WRZ-TTS0000-0 x x ABSOL
1. Either Absolute Scale (ABSOL), Warmer/Cooler (W/C), or Both (BOTH).
Table 6: Accessories
Product Code Number Product Description
MS-ZFRRPT-0 Optional Repeater Accessory for use with ZFR1811 Router as a repeater. Includes 20 to 28
VAC or 16 to 30 VDC input power, 12 VDC output power supply (regulated at 500 mA
maximum, 6 VA), and 4 x 4 in. (10.16 x 10.16 cm) electrical box with cover. Kit does not
include a ZFR1811 Router.
MS-ZFRCBL-0 Wire Harness with Connectors for use with MS-ZFR1811-x Router for Wireless Field Bus.
Allows ZFR1811 Router to function with FEC1620 controller; and with FEC1610, VMA1610,
or VMA1620 controllers in conjunction with NS Series Sensors, MS-BTCVT-1 Wireless
Commissioning Converter, or DIS1710 Local Controller Display.
ZFR-USBHA-0 Universal Serial Bus (USB) Dongle with ZFR Driver provides a wireless connection through
the CCT to allow wireless commissioning of the wirelessly enabled FEC, IOM, and VMA16
Series Field Controllers. Also used for the ZFR Checkout Tool (ZCT) in CCT.
ZFR-1810ANT-700 Replacement antenna kit for ZFR1810 Wireless Field Bus Coordinator. Includes antenna,
coaxial cable, and mounting hardware
WRZ-SST-120 Optional Wireless Sensing System Tool to be used with a WRZ Series Sensor to indicate
wireless signal strength between potential locations of ZFR1800 System devices.
MS-BTCVT-1 Wireless Commissioning Converter, with Bluetooth® technology
MS-DIS1710-0 Local Controller Display for FEC1610 and FEC2610 models
TP-2420 Transformer, Wall Plug Mount, 120 VAC to 24 VAC, 20 VA, Class 2
Y65T31-01 Transformer, 120/208/240 VAC to 24 VAC, 40 VA, Class 2, Foot Mount, 20 cm (8 in.) Primary
Leads and Secondary Screw Terminals
T-4000-119 1.6 mm (1/16 in.) Allen-Head Adjustment Tool (30 per Bag) for Accessing and Securing
WRZ Series Sensors
MAGNET-BASE-PLW Magnetic Backplate for Mounting a Transmitter on Metal Surfaces; 5 Magnetic Backplates per
Package
1.5 VDC, AA Alkaline Battery Replacement Battery for WRZ Series Sensors (Purchase Locally)
1. Additional Y60 Series Transformers are available from Johnson Controls.
10 ZFR1800 Series Wireless Field Bus System Product Bulletin
Table 7: Related Field Controllers
Product Code Product Description1
Number
MS-FAC2611-0 17-Point Field Equipment Controller with 6 UI, 2 BI, 3 BO, 2 AO, 4 CO, 24 VAC, and SA Bus with
Real-Time Clock
MS-FAC2612-1 18-Point Advanced Application Field Equipment Controller with 5 UI, 4 BI, 4 CO, and 5 RO
MS-FAC2612-2 18-Point Advanced Application Field Equipment Controller with 5 UI, 4 BI, 4 CO, and 5 RO. Line voltage
input power 90 VAC to 230 VAC.
MS-FAC3611-0 26-Point Advanced Application Field Equipment Controller with 8 UI, 6 BI, 6 BO, and 6 AO; 24 VAC;
SA Bus; FC Bus; Integral Real-time Clock; Improved Fast Persistence
MS-FEC1611-0 10-Point Field Equipment Controller with 2 UI, 1 BI, 3 BO, 4 CO, 24 VAC, and SA Bus
MS-FEC1621-0 Field Equipment Controller Cover with 2 UI, 1 BI, 3 BO, 4 CO, 24 VAC, and SA Bus with LCD Screen,
with Mounting Base
MS-FEC2611-0 17-Point Field Equipment Controller with 6 UI, 2 BI, 3 BO, 2 AO, 4 CO, 24 VAC, and SA Bus
MS-FEC2621-0 17-Point Field Equipment Controller with 6 UI, 2 BI, 3 BO, 2 AO, 4 CO, 24 VAC, and SA Bus with LCD
Screen
MS-IOM1711-0 4-Point IOM with 4 BI, FC Bus, and SA Bus Support
MS-IOM2711-0 6-Point IOM with 2 UI, 2 UO, 2 BO, FC Bus, and SA Bus Support
MS-IOM2721-0 10-Point Analog IOM with 8 UI, 2 AO, FC Bus, and SA Bus Support
MS-IOM3711-0 12-Point IOM with 4 UI, 4 UO, 4 BO, FC Bus, and SA Bus Support
MS-IOM3721-0 16-Point Binary IOM with 16 BI, FC Bus, and SA Bus Support
MS-IOM3731-0 16-Point Binary IOM with 8 BI, 8 BO, FC Bus, and SA Bus Support
MS-IOM4711-0 17-Point IOM with 6 UI, 2 BI, 3 BO, 2 AO, 4 CO, 24 VAC, and SA Bus with Mounting Base
MS-VMA1610-0 Integrated VAV Controller/Actuator/Pressure Sensor (Cooling Only), FC Bus, and SA Bus
MS-VMA1620-0 Integrated VAV Controller/Actuator/Pressure Sensor (with Reheat and Fan Control), FC Bus, and SA Bus
1. Universal Input (UI), Binary Input (BI), Binary Output (BO), Analog Output (AO), Configurable Output (CO), Sensor Actuator
(SA), and Relay Output (RO).
ZFR1800 Series Wireless Field Bus System Product Bulletin 11
Technical Specifications
ZFR1810 Wireless Field Bus Coordinator (Part 1 of 2)
Product Code Number MS-ZFR1810-x
ZFR1810-x Power Supply Input One of the following:
• 24 VAC +10%/-15%, 50/60 Hz, Class 2. Transformer allowance should be 2.5 VA
maximum, 2 VA typical. Provided through the three-position 24 V~ screw terminal
pluggable block.
• 15 VDC, 180 mA (7 to 18 VDC, 185 mA maximum current draw) on the FC Bus
provided through the FC BUS IN RJ-12 jack from the FC Bus jack on a field controller
or NxE Supervisory Engine.
Power Supply Output 15 VDC; Provided through the FC/SA BUS OUT RJ-12 jack for external devices.
Note: You can only use the power supply output when the ZFR1810 device is powered
from the 24 VAC power supply input.
Addressing DIP Switches, Field Adjustable
Wireless Band Direct-Sequence Spread-Spectrum, 2.4 GHz ISM Bands
Transmission Power 10 mW Maximum
Transmission Range 76.2 m (250 ft) Maximum Line-of-Sight
15 m (50 ft) Recommended
Ambient Conditions Operating: 0 to 50°C (32 to 122°F), 5 to 95% RH, Noncondensing
Storage: -20 to 70°C (-4 to 158°F), 5 to 90% RH, Noncondensing
Materials White Plastic Housing with Plenum rating per UL1995 UL94-5VB Flammability Rating
Terminations Two spade terminals with three-position screw terminal pluggable block for 24 VAC power
supply input.
Four spade terminals with four-position screw terminal pluggable block for RS-485
communications.
RJ-12 IN jack for 15 VDC power supply and communications connection from an NxE or
FEC FC Bus jack.
RJ-12 OUT jack supplies 15 VDC and communications to BTCVT Wireless
Commissioning Converter.
Dimensions 146 x 122 x 52 mm (5.8 x 4.8 x 2.1 in.)
12 ZFR1800 Series Wireless Field Bus System Product Bulletin
ZFR1810 Wireless Field Bus Coordinator (Part 2 of 2)
Mounting Hardware Four No. 6 Trade Size Sheet Metal Screws
Shipping Weights 0.45 kg (1.0 lb)
Compliance United States:
Intended for Connection to an NEC Class 2 Power Source;
UL 916 Energy Management
Plenum rated per UL1995 UL94-5VB Flammability Rating
FCC Compliant to CFR47, Part 15, Subpart B, Class A
Transmission Complies with FCC Part 15.247 Regulations for Low Power Unlicensed
Transmitters
Transmitter Identification ZFR1810-0: FCC: TFB-MATRIXL
Transmitter Identification ZFR1810-1: FCC: OEJ-WRZRADIO
Canada:
CAN/CSA C22.2 No. 205, Signal Equipment
Industry Canada (IC) Compliant to Canadian ICES-003, Class B Limits
Industry Canada (IC) RSS-210
Transmitter Identification ZFR1810-0: 5969A-MATRIXLP
Transmitter Identification ZFR1810-1: 279A-WRZRADIO
Europe:
CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the
essential requirements and other relevant provisions of the R&TTE Directive 1999/05/EC
and the EMC Directive 2004/108/EC.
Australia and New Zealand: C-Tick Mark, Australia/NZ Emissions Compliant
ZFR1811 Wireless Field Bus Router (Part 1 of 2)
Product Code Number MS-ZFR1811-x
Supply Voltage 8 to 18 VDC, 15 VDC nominal, provided from the FC/SA BUS RJ-12 jack on the FEC,
IOM, or VMA1600
Current Consumption 90 mA maximum
Addressing DIP Switches, Field Adjustable
Wireless Band Direct-Sequence Spread-Spectrum, 2.4 GHz ISM Bands
Transmission Power 10 mW Maximum
Transmission Range 76.2 m (250 ft) Maximum Line-of-Sight
15 m (50 ft) Recommended
Ambient Conditions Operating: 0 to 50°C (32 to 122°F), 5 to 95% RH, Noncondensing
Storage: -20 to 70°C (-4 to 158°F), 5 to 90% RH, Noncondensing
Materials Translucent Plastic Housing with Plenum rating per UL1995 UL94-5VB Flammability
Rating
Terminations RJ-12 plug for connection to FEC or VMA1600 FC/SA Bus jack
Dimensions 136 x 100 x 18 mm (5-3/8 x 3-15/16 x 3/4 in.)
Mounting Hardware 1/2 in. trade size Electrical Mechanical Tubing (EMT) connector
Shipping Weights 0.095 kg (0.21 lb)
ZFR1800 Series Wireless Field Bus System Product Bulletin 13
ZFR1811 Wireless Field Bus Router (Part 2 of 2)
Compliance United States:
Intended for Connection to an NEC Class 2 Power Source;
UL 916 Energy Management
Plenum rated per UL1995 UL94-5VB Flammability Rating
FCC Compliant to CFR47, Part 15, Subpart B, Class A
Transmission Complies with FCC Part 15.247 Regulations for Low Power Unlicensed
Transmitters
Transmitter Identification ZFR1811-0: FCC: TFB-MATRIXL;
Transmitter Identification ZFR1811-1: FCC: OEJ-WRZRADIO;
Canada:
CAN/CSA C22.2 No. 205, Signal Equipment
Industry Canada (IC) Compliant to Canadian ICES-003, Class B Limits
Industry Canada (IC) RSS-210
Transmitter Identification ZFR1810-0: 5969A-MATRIXLP
Transmitter Identification ZFR1810-1: 279A-WRZRADIO
Europe:
CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the
essential requirements and other relevant provisions of the R&TTE Directive 1999/05/EC
and the EMC Directive 2004/108/EC.
Australia and New Zealand: C-Tick Mark, Australia/NZ Emissions Compliant
WRZ Series Sensors (Part 1 of 2)
Product Codes WRZ-MHN0100-0: Temperature/Humidity Sensor with Occupancy Motion Detection
(PIR)
WRZ-MNN0100-0: Occupancy Sensor with Occupancy Motion Detection (PIR)
WRZ-MTB0100-0: Temperature/Humidity Sensor with Display and Occupancy Motion
Detection (PIR) with Warmer/Cooler (+/-) Setpoint Adjustment (setpoint configured in the
Metasys system)
WRZ-MTN0100-0: Temperature Sensor with Occupancy Motion Detection (PIR) with No
Display
WRZ-RMT10K-0: Temperature Transmitter designed to operate with a TE-6300 Series
10k ohm Johnson Controls® Type II Thermistor Sensor (order separately) to sense
temperature in warmer applications up to 158°F (70°C)
WRZ-STR0000-0: Transmitter and Temperature Sensor with Display and F/C Button
WRZ-STRNIST-0: NIST Rated Transmitter and Temperature Sensor with Display and
F/C Button
WRZ-THB0000-0: Temperature/Humidity Sensor with Display, Warmer/Cooler (+/-)
Setpoint Adjustment or Setpoint Adjustment Scale: 13 to 29°C/55 to 85°F, F/C Button, RH
Button and Occupancy Button
WRZ-THN0000-0: Temperature/Humidity Sensor with Occupancy Button
WRZ-THP0000-0: Temperature/Humidity Sensor with Warmer/Cooler (+/-) Setpoint
Adjustment and Occupancy Button
WRZ-TTB0000-0: Temperature Sensor with Display and F/C Button
WRZ-TTD0000-0: Temperature Sensor with Display, F/C Button and Fan Speed Control
WRZ-TTP0000-0: Temperature Sensor with Warmer/Cooler (+/-) Setpoint Adjustment
WRZ-TTR0000-0: Temperature Sensor with No Setpoint Adjustment
WRZ-TTS0000-0: Temperature Sensor with Setpoint Adjustment Scale: 13 to 29°C
(55 to 85°F)
Power Requirements 3 VDC Supplied by Two 1.5 VDC AA Alkaline Batteries (Included with Sensor);
Typical Battery Life: 48 Months (36 Months Minimum)
Addressing DIP Switches, Field Adjustable.
MS/TP Address, PAN Number, and Zone Address
Ambient Conditions Operating: 0 to 50C (32 to 122F), 5 to 95% RH, Noncondensing
Storage: -40 to 71C (-40 to 160F), 5 to 95% RH, Noncondensing
14 ZFR1800 Series Wireless Field Bus System Product Bulletin
WRZ Series Sensors (Part 2 of 2)
Wireless Band Direct-Sequence Spread-Spectrum, 2.4 GHz ISM Band
Transmission Power 10 mW Maximum
Transmission Range 30 m (100 ft) Maximum Line-of-Sight;
15 m (50 ft) Recommended
Transmissions Every 60 Seconds (±20 Seconds)
Temperature System Accuracy 0.6C/1.0F Over the Range of 13 to 29C (55 to 85F);
0.9C/1.5F Over a Range of 0 to 13C (32 to 55F) and 29 to 43C (85 to 110F)
Temperature Sensor Type Internal 10k ohm Negative Temperature Coefficient (NTC) Thermistor
Humidity Calibrated Range 10% to 90% RH at 23C (73F)
Humidity Accuracy ±3% RH across the Range of 20% to 80% RH, ±6% RH across the Range of 10% to
20% RH and 80% to 90% RH; within the Temperature Range of 13 to 29°C (55 to 85°F)
Materials NEMA 1 White Plastic Housing
Mounting Screw Mount or Double-Sided Adhesive Foam Tape Mount;
Double-Sided Adhesive Foam Tape Included
Dimensions 120 x 80 x 38 mm (4.7 x 3.1 x 1.5 in.)
Shipping Weight 0.14 kg (0.3 lb)
Compliance United States:
Transmission Complies with FCC Part 15.247 Regulations for Low Power Unlicensed
Transmitters
Transmitter FCC Identification: TFB-MATRIXL
Canada:
Industry Canada IC: 5969A-MATRIXL
Europe:
CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the
essential requirements and other relevant provisions of the R&TTE Directive 1999/05/EC
and the EMC Directive 2004/108/EC.
Australia and New Zealand: C-Tick Mark, Australia/NZ Emissions Compliant
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
ZFR1800 Series Wireless Field Bus System Product Bulletin 15
USB ZFR Dongle
Product Code Number ZFR-USBHA-0
Electrical Specifications Operating Voltage: USB std 5 VDC
Standby Current: 50 mA
Tx Current: 190 mA
Rx Current: 50 mA
RF Specifications RF Frequency: 2.4 - 2.4835 GH
Channels: 16
Modulation: DSSS (O-QPSK)
Data Rate: 250 Kbps
Tx Power: 8 dBm
Rx Sensitivity:- 85 dBm
Antenna Type: Built-in Antenna
Coverage Range: 100 meter (328 feet) line of sight. This distance is limited by the maximum
line of sight transmission distance of the ZFR system. Actual line of sight distances may be
lower.
Physical Specifications Dimensions: 63.5 mm x 27.5mm x 10.5 mm
Operating Temperature: Range -10°C (14°F) to 50°C (122°F)
United States Emissions Compliance
Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the
equipment.
RF Exposure (OET Bulletin 65) To comply with FCC RF exposure requirements for mobile transmitting devices, this transmitter should only be
used or installed at locations where there is at least 20cm separation distance between the antenna and all persons.
Canadian Emissions Compliance
Industry Canada Statement
The term IC before the certification/registration number only signifies that the Industry Canada technical specifications were met.
Le terme « IC » précédant le numéro d'accréditation/inscription signifie simplement que le produit est conforme aux spécifications techniques
d'Industry Canada.
Section 5.5 of RSS-210This device has been designed to operate with an antenna having a maxПоказано початок документа. Повний текст — у PDF за посиланням вище.
Позиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.