ZFR1800 Series Wireless Field Bus System
Product Bulletin
                                                                                               Code No. LIT-12011336
                                                                                                          Release 10.1
                                                                                               Issued December 5, 2014

                                               Refer to the QuickLIT Web site for the most up-to-date version of this document.

The ZFR1800 Series Wireless Field Bus System
provides a wireless platform for all Metasys® Field
Equipment Controller (FEC) family controllers using
BACnet® protocol over 2.4 GHz wireless ISM band.
One ZFR1811 router is required per field controller.
This pairing of a router and any FEC family device is
referred to as a Wireless-Enabled Field Controller
(WEFC). An FEC family device is an Advanced
Application Field Equipment Controller (FAC), FEC,
Input/Output Module (IOM), or VAV Modular Assembly
16 Series (VMA16) field controller.
A ZFR1800 Series system consists of:
                                                                       Figure 1: ZFR1811 Routers (top left),
•     up to eight ZFR1810 Wireless Field Bus                          ZFR1810 Coordinator (top center), and
      Coordinators per field bus                                          WRZ Series Sensors (bottom)
•     up to 35 Wireless Enabled Field Controllers
      (WEFCs) per coordinator
                                                              Together, these components create a wireless mesh
•     up to 100 WEFCs per field bus, depending on the         network that allows the exchange of data between the
      network engine (32 with NCE, 50 with NAE35)             collection of devices within the ZFR1800 Series
                                                              system’s wireless network and wired BACnet
•     up to nine WRZ Sensors per FEC or VMA16 field
                                                              Multidrop Serial Bus/Token-Passing (MS/TP) devices.
      controller
                                                              The wireless mesh network enhances reliability by
•     additional ZFR1811 Wireless Field Bus Routers
                                                              providing redundant transmission paths for the data
      connected to MS-ZFRRPT-0 Repeater
                                                              through other routers in the mesh network. The result
      accessories, as required, acting as repeaters
                                                              is a resilient, self-healing network.
Note: Repeaters extend the wireless transmission
distance of the BACnet data communications, fill in any
gaps within the wireless mesh network, and provide
multiple wireless data transmission pathways.
Table 1: Features and Benefits (Part 1 of 2)
    Features                                   Benefits
    Wireless Communications for a Metasys      Provide a wireless platform for Metasys BACnet devices across multiple
    System                                     levels of a Metasys Building Automation System (BAS), from supervisory
                                               engines, to field controllers, to room sensors; enable wireless devices to
                                               coexist with hard-wired devices on the same Metasys network; offer simple
                                               add-on hardware to seamlessly enable standard hard-wired Metasys
                                               BACnet field controllers to function wirelessly.
    Wireless Mesh Network                      Enables quick, economical, and low-maintenance installation; minimizes
                                               MS/TP BACnet hardwiring; and enhances reliability through automatically
                                               forming wireless links and redundant wireless data transmission paths.

                                                ZFR1800 Series Wireless Field Bus System Product Bulletin                    1
Table 1: Features and Benefits (Part 2 of 2)
    Features                                        Benefits
    Improved Application Mobility and               Provides a wireless alternative to hard-wired counterparts; facilitates easy
    Flexibility                                     initial location and relocation with minimal disruption to building occupants;
                                                    and cost-effectively extends Metasys systems to applications where
                                                    building aesthetics (such as solid walls or ceilings, temporary walls, or
                                                    decorative surfaces) normally hinder hardwiring.
    Support of up to Nine WRZ Series Wireless       Facilitates averaging and high/low selection to optimize comfort in larger
    Room Sensors per Wirelessly Enabled Field       zones. Installs easily; provides room temperature, setpoint temperature,
    Controller                                      occupancy status, and low battery status information to a Metasys system;
                                                    offers extensive battery life of up to 5 years.
    Multiple Diagnostic Light-Emitting Diodes       Provide quick and easy visual indication of power, FC bus activity, wireless
    (LEDs)                                          activity, wireless signal strength, and fault conditions; help locate optimum
                                                    device positions during installation and aid in troubleshooting.
    Compact, Easy-to-Install, and Versatile         Adapt easily to multiple mounting scenarios; serve multiple functions,
    ZFR1811 Routers                                 including providing wireless interface for numerous Metasys FEC, IOM, and
                                                    VMA16 controllers; and function as repeaters to extend wireless
                                                    transmission range.

Applications                                                       •     stadiums, arenas, gymnasiums, convention
                                                                         centers, airports, zoos, and other locations with
    IMPORTANT: Use the ZFR1800 Series Wireless                           large, open spaces
    Field Bus System only to provide an input to
                                                                   •     buildings with marble, granite, glass, mirrored,
    equipment under normal operating conditions.
                                                                         wood veneer, or other decorative surfaces that
    Where failure or malfunction of the sensor could
                                                                         present challenges to hard-wiring
    lead to personal injury or property damage to the
    controlled equipment or other property, additional             •     buildings with asbestos or other hazardous
    precautions must be designed into the control                        materials that must not be disturbed
    system. Incorporate and maintain other devices,
                                                                   •     buildings with occupants sensitive to disruptions to
    such as supervisory or alarm systems or safety or
                                                                         business
    limit controls, intended to warn of or protect against
    failure or malfunction of the ZFR1800 Series                   •     regions with high labor costs
    System.
                                                                   The ZFR1800 Series System is approved by national
The wireless Metasys products within a Metasys                     compliance agencies for use only in the United States
system are ideal for any location where it is                      and Canada. See Technical Specifications.
cost-prohibitive, difficult, or aesthetically unappealing to       Applications to Avoid
hardwire between Metasys products. Examples of
these locations include the following:                                 IMPORTANT: A Network Engine reports an offline
•      hospitals, office buildings, university campuses,               alarm within a certain period of time when an
       educational facilities, correctional facilities, and            associated FEC, IOM, or VMA16 field controller
       other commercial structures with brick or solid                 goes offline. For a hard-wired FEC, IOM, or VMA16
       concrete walls and/or ceilings that impede                      device, this time period is a nominal 20 seconds. For
       hard-wired applications                                         a wirelessly enabled FEC, IOM, or VMA16 device
                                                                       within the ZFR1800 Wireless Field Bus System, this
•      office buildings, retail stores, and other commercial           time period is 5 minutes.
       real estate where tenant turnover is frequent and
       temporary walls and ceilings are common                     Locations or applications that prohibit cellular
                                                                   telephones or Wi-Fi systems are unsuitable for the
•      museums, historical buildings, atriums, and other
                                                                   wireless Metasys products. Examples include:
       sites where building aesthetics and historical
       preservation are important                                  •     operating rooms or radiation therapy rooms
                                                                   •     validated environments
                                                                   •     UL 864 applications

2        ZFR1800 Series Wireless Field Bus System Product Bulletin
•   Department of Defense applications requiring              The MS/TP trunk and device limits for supported
    Diacap certification (for example, military bases         NAE35/45/55 or NCE25 models are the same for
    and military hospitals)                                   hard-wired devices, wireless devices, or a combination
                                                              of hard-wired and wireless devices. For more
Do not use the wireless Metasys products in
                                                              information, refer to the ZFR1800 Series Wireless Field
applications that cannot tolerate intermittent
                                                              Bus System Technical Bulletin (LIT-12011295). For
interference, or where:
                                                              information on device quantity limits in a ZFR1800
•   critical control features would impact life-safety or     Series system, see Table 2.
    result in large monetary loss, including secondary        Table 2: ZFR1800 Series System Device Quantity
    (backup) life-safety applications                                  Limits
•   data centers, production lines, or critical areas          Device                        Quantity Limit
    would be shut down                                         ZFR1810 Coordinator           Up to eight per NAE35/45/
•   loss of critical control would result from loss of data                                  55 or NCE25 trunk
    from humidity or temperature sensor                        ZFR1811 Router Paired         Up to 35 WEFCs per
    communications                                             with an FEC, IOM, or          ZFR1810 Coordinator
                                                               VMA16 Field Controller
•   operation of exhaust fans or Air Handling Units            ZFR1811 Router Used as        Unlimited2
    (AHUs) would impair a purge or pressurization              Repeaters1
    mode
                                                               WRZ Series Sensor             Up to nine sensors per
•   missing data would invalidate reporting required by                                      wireless-enabled field
    the customer                                                                             controller

•   security points are monitored                             1.   Requires use of the MS-ZFRRPT-0 optional repeater
                                                                   accessory.
System Overview                                               2.   Indiscriminate use of ZFR1811 Routers as repeaters can
                                                                   lead to reduced performance.
Figure 2 illustrates a simple ZFR1800 Series Wireless
Field Bus System applied to BACnet field controllers on
                                                              Component Descriptions
a Metasys network.
                                                              Network Automation Engine (NAE) and Network
These devices provide wireless monitoring and control
                                                              Control Engine (NCE)
of HVAC equipment within multiple levels of a
Metasys BACnet system.                                        NAE35/45/55s and NCE25s (NxEs) are Web-enabled,
                                                              Ethernet-based, supervisory controllers that connect
Refer to the ZFR1800 Series Wireless Field Bus                BAS networks to Internet Protocol (IP) networks and
System Technical Bulletin (LIT-12011295) for                  the Web. NAEs and NCEs provide scheduling, alarm
information on commissioning and configuring a                and event management, trending, energy
ZFR1800 Series Wireless Field Bus System for                  management, data exchange, dial-out capability, and
operation.                                                    password protection. With a computer running
                                                              Windows® Internet Explorer® Version 6.0 (or later),
                                                              you can browse to a configured NxE, and monitor and
                                                              control BAS field devices in the Metasys Site
                                                              Management Portal on the NxE.
                                                              ZFR1810 Coordinators
                                                              A ZFR1810 Wireless Field Bus Coordinator provides a
                                                              wireless interface between an NxE supervisory
                                                              controller on a wired BACnet MS/TP network and
                                                              wireless-enabled Metasys BACnet FEC, IOM, or VMA
                                                              field controllers.
                                                              Each wireless mesh network requires one ZFR1810
                                                              Coordinator, which initiates the formation of the
                                                              network. Each field bus can support up to eight
                                                              ZFR1810 Coordinators.

                                                   ZFR1800 Series Wireless Field Bus System Product Bulletin             3
A ZFR1810 Coordinator can operate from either of two       Note: Wirelessly enabled FEC and VMA16 field
power sources:                                             controllers can also use hard-wired NS Series network
                                                           sensors.
•   a 24 VAC, Class 2 power source
                                                           WRZ Series Sensors
•   15 VDC power provided from the FC Bus Jack on
    any Field Equipment or Supervisory Controller that     Depending on the sensor model, the WRZ Series
    is connected directly to the FC Bus                    Sensors transmit temperature, setpoint, humidity,
                                                           occupancy status, and low battery conditions to an
The ZFR1810 Coordinator features a remote-mount            associated field controller by means of a ZFR1811
antenna and cable to allow transmission when the           Router. If the field controller is mapped to the NxE, the
ZFR1810 Coordinator is mounted inside a metal panel.       data sent by the wireless sensor can be displayed.
ZFR1811 Routers                                            Some applications that support the temperature or
A ZFR1811 Wireless Field Bus Router is used with any       humidity control functions do not support the
model FEC, IOM, or VMA16 field controller to provide a     occupancy/temperature setback function. Refer to a
wireless interface between a field controller and:         field controller’s commissioning and operation literature
                                                           to determine if the application supports occupancy or
•   the NAE/NCE supervisory controller (by means of
                                                           temperature setback functions.
    a ZFR1810 Coordinator)
                                                           Note: Configure the Analog Inputs (AIs) on all WRZ
•   its associated WRZ Series Sensors
                                                           Sensors as SA Bus devices (the same as with
The ZFR1811 Router can also be used as a repeater to       hard-wired NS Series Sensors).
extend the range of the data communications within the
                                                           Note: The WRZ Series Sensors are designed for
wireless mesh network, or to fill any gaps within the
                                                           indoor, intra-building applications only.
mesh network, based on the physical layout of the
wireless devices, obstacles, and other characteristics     The WRZ Series Sensors require two 1.5 VDC AA
of the installation site.                                  alkaline batteries. The WRZ sensors minimize power
                                                           consumption by transmitting data only once per minute,
A ZFR1811 Router is powered directly from the
                                                           which yields an expected battery life of approximately
connected field controller’s 15 VDC output. It can also
                                                           4 to 5 years.
be powered by the ZFRRPT repeater accessory to
serve as a stand-alone repeater, extending the range       ZFR Checkout Tool (ZCT)
of the BACnet data communications within the wireless      The ZFR Checkout Tool is an optional tool, included
mesh network.                                              with the installation of the Controller Configuration Tool
Supported Field Controllers                                (CCT), that allows you to validate the wireless
                                                           connectivity and health of wireless devices within a
The ZFR1800 Series Wireless Field Bus System
                                                           ZFR1800 Series Wireless Field Bus system, helping
enables wireless BACnet connectivity between all
                                                           ensure a reliable mesh network is in place. You can
FEC, IOM, or VMA16 controllers and Network
                                                           use the information provided by the ZCT to analyze
Automation Engines, including NAE/35/45/55 and
                                                           and troubleshoot the wireless mesh network created by
NCEs. In addition, the wireless field bus system
                                                           a ZFR1800 Series System.
provides wireless communication between FEC/
VMA16 controllers and WRZ Series wireless sensors.         The ZCT gathers information by discovering the
                                                           wireless field controllers and wireless sensors on your
Note: The ZFR1811 Routers should be at the same
                                                           network and analyzing their status and wireless
Metasys system release version as the wirelessly
                                                           communication paths. The ZCT provides a simple
enabled FEC, IOM, or VMA16 field controller. If there is
                                                           report of wireless network performance, including
a version mismatch, the Controller Configuration Tool
                                                           online status verification and wireless signal strength
(CCT) provides indication of this, and the
                                                           information. The ZCT also provides wireless device
ZFR1811 Router is automatically updated during the
                                                           lists, signal strength information, and diagnostic
main code download to the field controller. For
                                                           measurements of the wireless mesh network.
information on uploading or downloading the devices to
match, refer to the Loading Devices chapter of the         Refer to the Using the ZFR Checkout Tool (ZCT)
CCT Help (LIT-12011147).                                   chapter of the CCT Help (LIT-12011147) for more
                                                           information on the ZCT.
Note: Some field controller applications do not
support the occupancy/temperature setback function.

4     ZFR1800 Series Wireless Field Bus System Product Bulletin
The ZCT requires a Universal Serial Bus (USB)              WRZ-SST-120 Wireless Sensing System Tool
adaptor with ZFR driver.                                   Use the optional, battery-operated WRZ-SST-120
Note: You must connect the adaptor to the computer         Wireless Sensing System Tool with any model
running CCT/ZCT before attempting to scan the              WRZ Series Sensor as a site survey tool to determine
network.                                                   the wireless signal strength between potential locations
                                                           of ZFR1800 system devices to survey your application
ZFR Repeater Kit                                           and adjust ZFR1800 device locations before installing
The MS-ZFRRPT-0 is an optional repeater accessory          the devices. Refer to the WRZ-SST-120 Wireless
for the ZFR1811 Router which allows remote mounting        Sensing System Tool Installation Instructions
of the ZFR1811 Router without an FEC family                (Part No. 24-10563-12) for more information on the
controller. The ZFRRPT Repeater contains a 4 x 4 inch      tool.
(10.16 x 10.16 cm) electrical box with a 24 VAC to 15
VDC converter for powering the ZFR1811 Router.
                                                           ZFR Wireless USB Dongle

The ZFRRPT also contains a conduit sleeve for              The ZFR Wireless USB Dongle allows a laptop
attaching a ZFR1811 to the 4 x 4 inch electrical box.      computer to connect to a ZFR Field Router wireless
                                                           field bus for the purpose of commissioning and
USB Adaptor with ZFR Driver                                downloading applications to wirelessly enabled field
The ZFR connection type within CCT requires the USB        controllers using the CCT or for analyzing a ZFR
adaptor with ZFR driver for your laptop computer. The      wireless mesh using the ZFR Checkout Tool (ZCT).
USB adaptor provides a wireless connection to allow        The ZFR Wireless USB Dongle requires a USB
wireless commissioning of the wireless-enabled field       software driver which is installed automatically with
controllers and allows the use of the ZCT.                 CCT Version 5.3 or later. No user configuration is
                                                           required.
See Table 6 to order the ZFR USB adaptor (product
code ZFR-USBHA-0). This device is an IEEE 802.154          For more information, refer to the ZFR1800 Series
ZFR to USB Adaptor for the 2.4 GHz ISM Band.               Wireless Field Bus System Technical Bulletin
                                                           (LIT-12011295).
Note: The software driver for the ZFR USB adaptor
installs automatically with the CCT.

                                                ZFR1800 Series Wireless Field Bus System Product Bulletin          5
                                   NAE

                                                     WRZ
                                                   Sensor A1              WRZ
                                                                        Sensor A2

                     VMA16                                                           ZFR1811
                 Device Address 4                                                    Router B

                                          ZFR1811
                                          Router A

                                                         VMA16                             IOM
                                                     Device Address 8                Device Address 9
                      FEC
                Device Address 5
                                                                                                          WRZ
                                                                                                        Sensor A3

                                                                             ZFR1810
                     IOM                                                    Coordinator
               Device Address 6
                                                WRZ
                                              Sensor C4

                                                                                     Note: Signal range varies
                                                                                          depending on installation.
                                                                                          Signal range is shown as
                                                                                          a radius to illustrate
                      FEC                                        ZFR1811                  overlapping devices.
                Device Address 7                                 Router D                 The radius is 7.6 m
                                                             (Used as Repeater)           (25 ft).

                                                                                WRZ
                                                                              Sensor C1

                                     FC Bus
                                                                 ZFR1811
                                                                 Router C

        Note: Sensor does not need                                                                    WRZ
                                                                               FEC                  Sensor C2
             to be in the range of its
                                                                        Device Address 10
             target controller.                      WRZ
                                                                                                                FIG:wrd_wrlss
                                                   Sensor C3
        Note: The ZFR system supports
              all FEC family controllers
              including FECs, Advanced Application
              Field Equipment Controllers (FACs), IOMs,
              and VMAs.

          Figure 2: ZFR1800 Series Wireless Field Bus System as Part of a Metasys Network

6   ZFR1800 Series Wireless Field Bus System Product Bulletin
ZFR1800 Series System Wireless                                Transmission ranges between ZFR1800 Series
Communication                                                 products can be less than the maximum distances
                                                              shown in Table 3.
The ZFR1800 Series System devices create a wireless
mesh network using ZFR technology. The mesh                   Table 3: Indoor Line-of-Sight Transmission
network provides redundant wireless paths, enabling                    Ranges
the BACnet data to traverse the network through                Range Type             Transmission Distance
alternate, automatically forming paths and arrive at the                        ZFR1810              WRZ Series
target destination device even if a ZFR1811 Router or                           Coordinator,         Sensor
Repeater within the wireless mesh network                                       ZFR1811 Router
experiences interference or drops out of the network.
                                                               Recommended      15.2 m (50 ft)        15.2 m (50 ft)
The ZFR1800 Series System uses Direct Sequence                 Maximum          76.2 m (250 ft)       30 m (100 ft)
Spread Spectrum (DSSS) Radio Frequency (RF)
technology and operates on the globally accepted              Wireless Interference and Security
2.4 GHz Industrial, Scientific, and Medical (ISM) band.
All ZFR1800 Series System components use a                    The ZFR1800 Series Wireless Field Bus System is
transmission power of 10 mW. The WRZ Series                   designed to minimize the potential for wireless
sensors meet the Institute of Electrical and Electronics      interference with other wireless applications. In most
Engineers, Inc. (IEEE) 802.15.4 standard for low              commercial environments, the ZFR1800 Series
power, low duty-cycle wireless transmitting systems           System does not encounter or generate wireless
and are compatible with wireless mesh networks                interference, even in environments with cell phones
compliant with the ZigBee standard.                           and competing Wi-Fi applications.

For more information on wireless transmissions, signal        ZFR1800 Series Wireless transmissions use different
strength, and locating devices for optimum signal             modulation schemes than Wi-Fi applications and use
strength, refer to the ZFR1800 Series Wireless Field          frequencies between popular Wi-Fi bands, enabling
Bus System Technical Bulletin (LIT-12011295).                 Wi-Fi and ZFR1800 Series Wireless networks to exist
                                                              in the same areas.
Wireless Signal Transmission Range
                                                              For more information on wireless interference and
The effective transmission range/distance for indoor          security, refer to the ZFR1800 Series Wireless Field
applications varies because of wireless signal                Bus System Technical Bulletin (LIT-12011295).
absorption and reflection due to metal obstructions,
walls (or floors), and furniture found in typical building
interiors.

                                                   ZFR1800 Series Wireless Field Bus System Product Bulletin           7
Physical Features and Dimensions                       Figure 4 shows the ZFR1811 Router.
Figure 3 shows the ZFR1810 Coordinator with the
remote-mounted antenna.

                                                         Figure 4: ZFR1811 Wireless Field Bus Router,
                                                         Physical Features and Dimensions, mm (in.)

                                                       Figure 5 shows the WRZ Series Sensor.

Figure 3: ZFR1810 Wireless Field Bus Coordinator,
   Physical Features and Dimensions, mm (in.)

                                                                 Figure 5: WRZ Series Sensor,
                                                           Physical Features and Dimensions, mm (in.)

8     ZFR1800 Series Wireless Field Bus System Product Bulletin
Ordering Information                                          Refer to the Network Automation Engine (NAE)
                                                              Product Bulletin (LIT-1201160) and the Metasys
For ZFR1800 Series System product ordering
                                                              System Field Equipment Controllers and Related
information, see Table 4 and Table 5. For ZFR1800
                                                              Products Product Bulletin (LIT-12011042) for additional
Series System accessories product ordering
                                                              information on related products.
information, see Table 6. For supported models of the
Metasys BACnet field controllers, see Table 7.                Repair Information
Contact the nearest Johnson Controls® representative          If a ZFR1800 Series Wireless Field Bus System
to order the products in Table 4 through Table 7.             component fails to operate within its specifications,
Specify the desired product code number from these            replace the unit. For a replacement ZFR1800 Series
tables.                                                       System component, contact the nearest
                                                              Johnson Controls representative.
Table 4: ZFR1800 Series Wireless Field Bus System Components
 Product Code        Product Description
 Number
 MS-ZFR1810-x        Wireless Field Bus Coordinator, 10 mW Transmission Power; functions with NAE35, NAE45, NAE55,
                     and NCE25 Models
 MS-ZFR1811-x        Wireless Field Bus Router, 10 mW Transmission Power; functions with Metasys BACnet FECs, IOMs,
                     VMA16s, and WRZ Series Sensors
 WRZ-MHN0100-0       Wireless Remote Transmitter with Temperature, Relative Humidity (RH) and Occupancy Motion
                     Detector (PIR) only, No Display
 WRZ-MNN0100-0       Wireless Remote Transmitter with Occupancy Detection (PIR), No Display
 WRZ-MTB0100-0       Wireless Remote Transmitter with Display, Temperature, Relative Humidity (RH), and Occupancy
                     Detection only, Warmer/Cooler (+/-) Setpoint Adjustment (setpoint configured in the Metasys system)
 WRZ-MTN0100-0       Wireless Remote Transmitter with Temperature and Occupancy Detection only, No Display
 WRZ-RMT10K-0        Wireless Remote Temperature Transmitter designed to operate with a TE-6300 Series 10k ohm
                     Johnson Controls® Type II Thermistor Sensor (order separately) to sense temperature in warmer
                     applications up to 158°F (70°C). Includes one Transmitter, one Mounting Base, strips of Double-Sided
                     Adhesive Foam Tape (all factory assembled), and one Strain Relief
 WRZ-STR0000-0       Wireless Transmitter and Temperature Sensor with Display and F/C Button. Includes Temperature
                     Probe encased in a Clear Acrylic Cylinder, 9 ft (2.7 m) Wire Lead, one Probe Mounting Strap, and a strip
                     of Double-Sided Adhesive Foam Tape, 10 mW Transmission Power
 WRZ-STRNIST-0       NIST Rated Wireless Transmitter and Temperature Sensor with Display and F/C Button. Includes
                     Temperature Probe encased in a Clear Acrylic Cylinder, 9 ft (2.7 m) Wire Lead, one Probe Mounting
                     Strap, and a strip of Double-Sided Adhesive Foam Tape, 10 mW Transmission Power
 WRZ-THB0000-0       Wireless Temperature/Humidity Sensor with Display, Warmer/Cooler (+/-) Setpoint Adjustment or
                     Setpoint Adjustment Scale: 13 to 29°C/55 to 85°F, F/C Button, Relative Humidity (RH) Button and
                     Occupancy Button, 10 mW Transmission Power
 WRZ-THN0000-0       Wireless Temperature/Humidity Sensor, Occupancy Button, No Temperature adjustment and No LCD
                     temperature/humidity display, 10 mW Transmission Power
 WRZ-THP0000-0       Wireless Temperature/Humidity Sensor, Warmer/Cooler (+/-) Setpoint Adjustment and Occupancy
                     Button, No LCD temperature/humidity display, 10 mW Transmission Power
 WRZ-TTB0000-0       Wireless Temperature Sensor with Display and F/C Button, 10 mW Transmission Power
 WRZ-TTD0000-0       Wireless Temperature Sensor with Display, F/C Button and Fan Speed Control, 10 mW Transmission
                     Power
 WRZ-TTP0000-0       Wireless Room Temperature Sensor, Warmer/Cooler (+/-) Setpoint Adjustment, 10 mW Transmission
                     Power
 WRZ-TTR0000-0       Wireless Room Temperature Sensor, No Setpoint Adjustment, 10 mW Transmission Power
 WRZ-TTS0000-0       Wireless Room Temperature Sensor, Setpoint Adjustment Scale: 13 to 29°C/55 to 85°F, 10 mW
                     Transmission Power

                                                 ZFR1800 Series Wireless Field Bus System Product Bulletin                 9
Table 5: WRZ Sensor Model Comparison
 Sensor Model          Temperature      3%            Display    F/C       Fan       Occupancy         Occupancy    Setpoint
                                        Humidity                 Button    Control   Motion            Override     Adjustment
                                                                                     Detection (PIR)                Dial1
 WRZ-MHN0100-0                x              x                                              x
 WRZ-MNN0100-0                                                                              x
 WRZ-MTB0100-0                x                                                             x
 WRZ-MTN0100-0                x                           x                                 x                       ABSOL
 WRZ-RMT10K-0                 x
 WRZ-STR0000-0                x                           x          x
 WRZ-STRNIST-0                x                           x          x
 WRZ-THB0000-0                x              x            x          x                                     x        Both
 WRZ-THN0000-0                x              x                                                             x
 WRZ-THP0000-0                x              x                                                             x        W/C
 WRZ-TTB0000-0                x                           x          x                                     x        Both
 WRZ-TTD0000-0                x                           x          x        x                            x        Both
 WRZ-TTP0000-0                x                                                                            x        W/C
 WRZ-TTR0000-0                x                                                                            x
 WRZ-TTS0000-0                x                                                                            x        ABSOL
1.   Either Absolute Scale (ABSOL), Warmer/Cooler (W/C), or Both (BOTH).

Table 6: Accessories
 Product Code Number                  Product Description
 MS-ZFRRPT-0                          Optional Repeater Accessory for use with ZFR1811 Router as a repeater. Includes 20 to 28
                                      VAC or 16 to 30 VDC input power, 12 VDC output power supply (regulated at 500 mA
                                      maximum, 6 VA), and 4 x 4 in. (10.16 x 10.16 cm) electrical box with cover. Kit does not
                                      include a ZFR1811 Router.
 MS-ZFRCBL-0                          Wire Harness with Connectors for use with MS-ZFR1811-x Router for Wireless Field Bus.
                                      Allows ZFR1811 Router to function with FEC1620 controller; and with FEC1610, VMA1610,
                                      or VMA1620 controllers in conjunction with NS Series Sensors, MS-BTCVT-1 Wireless
                                      Commissioning Converter, or DIS1710 Local Controller Display.
 ZFR-USBHA-0                          Universal Serial Bus (USB) Dongle with ZFR Driver provides a wireless connection through
                                      the CCT to allow wireless commissioning of the wirelessly enabled FEC, IOM, and VMA16
                                      Series Field Controllers. Also used for the ZFR Checkout Tool (ZCT) in CCT.
 ZFR-1810ANT-700                      Replacement antenna kit for ZFR1810 Wireless Field Bus Coordinator. Includes antenna,
                                      coaxial cable, and mounting hardware
 WRZ-SST-120                          Optional Wireless Sensing System Tool to be used with a WRZ Series Sensor to indicate
                                      wireless signal strength between potential locations of ZFR1800 System devices.
 MS-BTCVT-1                           Wireless Commissioning Converter, with Bluetooth® technology
 MS-DIS1710-0                         Local Controller Display for FEC1610 and FEC2610 models
 TP-2420                              Transformer, Wall Plug Mount, 120 VAC to 24 VAC, 20 VA, Class 2
 Y65T31-01                            Transformer, 120/208/240 VAC to 24 VAC, 40 VA, Class 2, Foot Mount, 20 cm (8 in.) Primary
                                      Leads and Secondary Screw Terminals
 T-4000-119                           1.6 mm (1/16 in.) Allen-Head Adjustment Tool (30 per Bag) for Accessing and Securing
                                      WRZ Series Sensors
 MAGNET-BASE-PLW                      Magnetic Backplate for Mounting a Transmitter on Metal Surfaces; 5 Magnetic Backplates per
                                      Package
 1.5 VDC, AA Alkaline Battery         Replacement Battery for WRZ Series Sensors (Purchase Locally)

1.   Additional Y60 Series Transformers are available from Johnson Controls.

10     ZFR1800 Series Wireless Field Bus System Product Bulletin
Table 7: Related Field Controllers
 Product Code        Product Description1
 Number
 MS-FAC2611-0        17-Point Field Equipment Controller with 6 UI, 2 BI, 3 BO, 2 AO, 4 CO, 24 VAC, and SA Bus with
                     Real-Time Clock
 MS-FAC2612-1        18-Point Advanced Application Field Equipment Controller with 5 UI, 4 BI, 4 CO, and 5 RO
 MS-FAC2612-2        18-Point Advanced Application Field Equipment Controller with 5 UI, 4 BI, 4 CO, and 5 RO. Line voltage
                     input power 90 VAC to 230 VAC.
 MS-FAC3611-0        26-Point Advanced Application Field Equipment Controller with 8 UI, 6 BI, 6 BO, and 6 AO; 24 VAC;
                     SA Bus; FC Bus; Integral Real-time Clock; Improved Fast Persistence
 MS-FEC1611-0        10-Point Field Equipment Controller with 2 UI, 1 BI, 3 BO, 4 CO, 24 VAC, and SA Bus
 MS-FEC1621-0        Field Equipment Controller Cover with 2 UI, 1 BI, 3 BO, 4 CO, 24 VAC, and SA Bus with LCD Screen,
                     with Mounting Base
 MS-FEC2611-0        17-Point Field Equipment Controller with 6 UI, 2 BI, 3 BO, 2 AO, 4 CO, 24 VAC, and SA Bus
 MS-FEC2621-0        17-Point Field Equipment Controller with 6 UI, 2 BI, 3 BO, 2 AO, 4 CO, 24 VAC, and SA Bus with LCD
                     Screen
 MS-IOM1711-0        4-Point IOM with 4 BI, FC Bus, and SA Bus Support
 MS-IOM2711-0        6-Point IOM with 2 UI, 2 UO, 2 BO, FC Bus, and SA Bus Support
 MS-IOM2721-0        10-Point Analog IOM with 8 UI, 2 AO, FC Bus, and SA Bus Support
 MS-IOM3711-0        12-Point IOM with 4 UI, 4 UO, 4 BO, FC Bus, and SA Bus Support
 MS-IOM3721-0        16-Point Binary IOM with 16 BI, FC Bus, and SA Bus Support
 MS-IOM3731-0        16-Point Binary IOM with 8 BI, 8 BO, FC Bus, and SA Bus Support
 MS-IOM4711-0        17-Point IOM with 6 UI, 2 BI, 3 BO, 2 AO, 4 CO, 24 VAC, and SA Bus with Mounting Base
 MS-VMA1610-0        Integrated VAV Controller/Actuator/Pressure Sensor (Cooling Only), FC Bus, and SA Bus
 MS-VMA1620-0        Integrated VAV Controller/Actuator/Pressure Sensor (with Reheat and Fan Control), FC Bus, and SA Bus

1.   Universal Input (UI), Binary Input (BI), Binary Output (BO), Analog Output (AO), Configurable Output (CO), Sensor Actuator
     (SA), and Relay Output (RO).

                                                     ZFR1800 Series Wireless Field Bus System Product Bulletin                11
Technical Specifications
ZFR1810 Wireless Field Bus Coordinator (Part 1 of 2)
Product Code Number            MS-ZFR1810-x
ZFR1810-x Power Supply Input   One of the following:
                               • 24 VAC +10%/-15%, 50/60 Hz, Class 2. Transformer allowance should be 2.5 VA
                                 maximum, 2 VA typical. Provided through the three-position 24 V~ screw terminal
                                 pluggable block.
                               • 15 VDC, 180 mA (7 to 18 VDC, 185 mA maximum current draw) on the FC Bus
                                 provided through the FC BUS IN RJ-12 jack from the FC Bus jack on a field controller
                                 or NxE Supervisory Engine.
Power Supply Output            15 VDC; Provided through the FC/SA BUS OUT RJ-12 jack for external devices.
                               Note: You can only use the power supply output when the ZFR1810 device is powered
                               from the 24 VAC power supply input.
Addressing                     DIP Switches, Field Adjustable
Wireless Band                  Direct-Sequence Spread-Spectrum, 2.4 GHz ISM Bands
Transmission Power             10 mW Maximum
Transmission Range             76.2 m (250 ft) Maximum Line-of-Sight
                               15 m (50 ft) Recommended
Ambient Conditions             Operating: 0 to 50°C (32 to 122°F), 5 to 95% RH, Noncondensing
                               Storage: -20 to 70°C (-4 to 158°F), 5 to 90% RH, Noncondensing
Materials                      White Plastic Housing with Plenum rating per UL1995 UL94-5VB Flammability Rating
Terminations                   Two spade terminals with three-position screw terminal pluggable block for 24 VAC power
                               supply input.
                               Four spade terminals with four-position screw terminal pluggable block for RS-485
                               communications.
                               RJ-12 IN jack for 15 VDC power supply and communications connection from an NxE or
                               FEC FC Bus jack.
                               RJ-12 OUT jack supplies 15 VDC and communications to BTCVT Wireless
                               Commissioning Converter.
Dimensions                     146 x 122 x 52 mm (5.8 x 4.8 x 2.1 in.)

12   ZFR1800 Series Wireless Field Bus System Product Bulletin
ZFR1810 Wireless Field Bus Coordinator (Part 2 of 2)
Mounting Hardware           Four No. 6 Trade Size Sheet Metal Screws
Shipping Weights            0.45 kg (1.0 lb)
Compliance                  United States:
                            Intended for Connection to an NEC Class 2 Power Source;
                            UL 916 Energy Management
                            Plenum rated per UL1995 UL94-5VB Flammability Rating
                            FCC Compliant to CFR47, Part 15, Subpart B, Class A
                            Transmission Complies with FCC Part 15.247 Regulations for Low Power Unlicensed
                            Transmitters
                            Transmitter Identification ZFR1810-0: FCC: TFB-MATRIXL
                            Transmitter Identification ZFR1810-1: FCC: OEJ-WRZRADIO
                            Canada:
                            CAN/CSA C22.2 No. 205, Signal Equipment
                            Industry Canada (IC) Compliant to Canadian ICES-003, Class B Limits

                            Industry Canada (IC) RSS-210
                            Transmitter Identification ZFR1810-0: 5969A-MATRIXLP
                            Transmitter Identification ZFR1810-1: 279A-WRZRADIO
                            Europe:
                            CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the
                            essential requirements and other relevant provisions of the R&TTE Directive 1999/05/EC
                            and the EMC Directive 2004/108/EC.
                            Australia and New Zealand: C-Tick Mark, Australia/NZ Emissions Compliant

ZFR1811 Wireless Field Bus Router (Part 1 of 2)
Product Code Number         MS-ZFR1811-x
Supply Voltage              8 to 18 VDC, 15 VDC nominal, provided from the FC/SA BUS RJ-12 jack on the FEC,
                            IOM, or VMA1600
Current Consumption         90 mA maximum
Addressing                  DIP Switches, Field Adjustable
Wireless Band               Direct-Sequence Spread-Spectrum, 2.4 GHz ISM Bands
Transmission Power          10 mW Maximum
Transmission Range          76.2 m (250 ft) Maximum Line-of-Sight
                            15 m (50 ft) Recommended
Ambient Conditions          Operating: 0 to 50°C (32 to 122°F), 5 to 95% RH, Noncondensing
                            Storage: -20 to 70°C (-4 to 158°F), 5 to 90% RH, Noncondensing
Materials                   Translucent Plastic Housing with Plenum rating per UL1995 UL94-5VB Flammability
                            Rating
Terminations                RJ-12 plug for connection to FEC or VMA1600 FC/SA Bus jack
Dimensions                  136 x 100 x 18 mm (5-3/8 x 3-15/16 x 3/4 in.)
Mounting Hardware           1/2 in. trade size Electrical Mechanical Tubing (EMT) connector
Shipping Weights            0.095 kg (0.21 lb)

                                           ZFR1800 Series Wireless Field Bus System Product Bulletin            13
ZFR1811 Wireless Field Bus Router (Part 2 of 2)
Compliance                    United States:
                              Intended for Connection to an NEC Class 2 Power Source;
                              UL 916 Energy Management
                              Plenum rated per UL1995 UL94-5VB Flammability Rating
                              FCC Compliant to CFR47, Part 15, Subpart B, Class A
                              Transmission Complies with FCC Part 15.247 Regulations for Low Power Unlicensed
                              Transmitters
                              Transmitter Identification ZFR1811-0: FCC: TFB-MATRIXL;
                              Transmitter Identification ZFR1811-1: FCC: OEJ-WRZRADIO;
                              Canada:
                              CAN/CSA C22.2 No. 205, Signal Equipment
                              Industry Canada (IC) Compliant to Canadian ICES-003, Class B Limits
                              Industry Canada (IC) RSS-210
                              Transmitter Identification ZFR1810-0: 5969A-MATRIXLP
                              Transmitter Identification ZFR1810-1: 279A-WRZRADIO
                              Europe:
                              CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the
                              essential requirements and other relevant provisions of the R&TTE Directive 1999/05/EC
                              and the EMC Directive 2004/108/EC.
                              Australia and New Zealand: C-Tick Mark, Australia/NZ Emissions Compliant

WRZ Series Sensors (Part 1 of 2)
Product Codes                 WRZ-MHN0100-0: Temperature/Humidity Sensor with Occupancy Motion Detection
                              (PIR)
                              WRZ-MNN0100-0: Occupancy Sensor with Occupancy Motion Detection (PIR)
                              WRZ-MTB0100-0: Temperature/Humidity Sensor with Display and Occupancy Motion
                              Detection (PIR) with Warmer/Cooler (+/-) Setpoint Adjustment (setpoint configured in the
                              Metasys system)
                              WRZ-MTN0100-0: Temperature Sensor with Occupancy Motion Detection (PIR) with No
                              Display
                              WRZ-RMT10K-0: Temperature Transmitter designed to operate with a TE-6300 Series
                              10k ohm Johnson Controls® Type II Thermistor Sensor (order separately) to sense
                              temperature in warmer applications up to 158°F (70°C)
                              WRZ-STR0000-0: Transmitter and Temperature Sensor with Display and F/C Button
                              WRZ-STRNIST-0: NIST Rated Transmitter and Temperature Sensor with Display and
                              F/C Button
                              WRZ-THB0000-0: Temperature/Humidity Sensor with Display, Warmer/Cooler (+/-)
                              Setpoint Adjustment or Setpoint Adjustment Scale: 13 to 29°C/55 to 85°F, F/C Button, RH
                              Button and Occupancy Button
                              WRZ-THN0000-0: Temperature/Humidity Sensor with Occupancy Button
                              WRZ-THP0000-0: Temperature/Humidity Sensor with Warmer/Cooler (+/-) Setpoint
                              Adjustment and Occupancy Button
                              WRZ-TTB0000-0: Temperature Sensor with Display and F/C Button
                              WRZ-TTD0000-0: Temperature Sensor with Display, F/C Button and Fan Speed Control
                              WRZ-TTP0000-0: Temperature Sensor with Warmer/Cooler (+/-) Setpoint Adjustment
                              WRZ-TTR0000-0: Temperature Sensor with No Setpoint Adjustment
                              WRZ-TTS0000-0: Temperature Sensor with Setpoint Adjustment Scale: 13 to 29°C
                                                 (55 to 85°F)
Power Requirements            3 VDC Supplied by Two 1.5 VDC AA Alkaline Batteries (Included with Sensor);
                              Typical Battery Life: 48 Months (36 Months Minimum)
Addressing                    DIP Switches, Field Adjustable.
                              MS/TP Address, PAN Number, and Zone Address
Ambient Conditions            Operating: 0 to 50C (32 to 122F), 5 to 95% RH, Noncondensing
                              Storage: -40 to 71C (-40 to 160F), 5 to 95% RH, Noncondensing

14   ZFR1800 Series Wireless Field Bus System Product Bulletin
WRZ Series Sensors (Part 2 of 2)
 Wireless Band                             Direct-Sequence Spread-Spectrum, 2.4 GHz ISM Band
 Transmission Power                        10 mW Maximum
 Transmission Range                        30 m (100 ft) Maximum Line-of-Sight;
                                           15 m (50 ft) Recommended
 Transmissions                             Every 60 Seconds (±20 Seconds)
 Temperature System Accuracy               0.6C/1.0F Over the Range of 13 to 29C (55 to 85F);
                                           0.9C/1.5F Over a Range of 0 to 13C (32 to 55F) and 29 to 43C (85 to 110F)
 Temperature Sensor Type                   Internal 10k ohm Negative Temperature Coefficient (NTC) Thermistor
 Humidity Calibrated Range                 10% to 90% RH at 23C (73F)
 Humidity Accuracy                         ±3% RH across the Range of 20% to 80% RH, ±6% RH across the Range of 10% to
                                           20% RH and 80% to 90% RH; within the Temperature Range of 13 to 29°C (55 to 85°F)
 Materials                                 NEMA 1 White Plastic Housing
 Mounting                                  Screw Mount or Double-Sided Adhesive Foam Tape Mount;
                                           Double-Sided Adhesive Foam Tape Included
 Dimensions                                120 x 80 x 38 mm (4.7 x 3.1 x 1.5 in.)
 Shipping Weight                           0.14 kg (0.3 lb)
 Compliance                                United States:
                                           Transmission Complies with FCC Part 15.247 Regulations for Low Power Unlicensed
                                           Transmitters
                                           Transmitter FCC Identification: TFB-MATRIXL
                                           Canada:
                                           Industry Canada IC: 5969A-MATRIXL
                                           Europe:
                                           CE Mark – Johnson Controls, Inc., declares that this product is in compliance with the
                                           essential requirements and other relevant provisions of the R&TTE Directive 1999/05/EC
                                           and the EMC Directive 2004/108/EC.
                                           Australia and New Zealand: C-Tick Mark, Australia/NZ Emissions Compliant
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.

                                                            ZFR1800 Series Wireless Field Bus System Product Bulletin                          15
USB ZFR Dongle
 Product Code Number                ZFR-USBHA-0
 Electrical Specifications          Operating Voltage: USB std 5 VDC
                                    Standby Current: 50 mA
                                    Tx Current: 190 mA
                                    Rx Current: 50 mA
 RF Specifications                  RF Frequency: 2.4 - 2.4835 GH
                                    Channels: 16
                                    Modulation: DSSS (O-QPSK)
                                    Data Rate: 250 Kbps
                                    Tx Power: 8 dBm
                                    Rx Sensitivity:- 85 dBm
                                    Antenna Type: Built-in Antenna
                                    Coverage Range: 100 meter (328 feet) line of sight. This distance is limited by the maximum
                                    line of sight transmission distance of the ZFR system. Actual line of sight distances may be
                                    lower.
 Physical Specifications            Dimensions: 63.5 mm x 27.5mm x 10.5 mm
                                    Operating Temperature: Range -10°C (14°F) to 50°C (122°F)
United States Emissions Compliance
Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the
equipment.
RF Exposure (OET Bulletin 65) To comply with FCC RF exposure requirements for mobile transmitting devices, this transmitter should only be
used or installed at locations where there is at least 20cm separation distance between the antenna and all persons.
Canadian Emissions Compliance
Industry Canada Statement
The term IC before the certification/registration number only signifies that the Industry Canada technical specifications were met.
Le terme « IC » précédant le numéro d'accréditation/inscription signifie simplement que le produit est conforme aux spécifications techniques
d'Industry Canada.
Section 5.5 of RSS-210This device has been designed to operate with an antenna having a max

Показано початок документа. Повний текст — у PDF за посиланням вище.

Позиції каталогу з цим документом

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.