                                                                                                 G
                                                                        0
                                                                        -
                                                                        6
                                                                        2
                                                                        1                v
                                                                        0
                                                                        1
                                                                        -
                                                                        4
                                                                        2                e
                                                                                         R

WRS-RTN Series Receivers for Many-to-One Wireless
Room Temperature Sensing Systems
Installation Instructions                                                         Part No. 24-10126-0, Rev. G
                                                                                           Issued February 2016
WRS-RTN0000-0, WRS-RTN0000-1

Application                                                 IMPORTANT: The WRS-RTN Series Receiver is
The WRS-RTN Series Receivers for the Many-to-One            intended to provide an input to equipment under
Wireless Room Temperature Sensing Systems are               normal operating conditions. Where failure or
designed to receive wireless Radio Frequency (RF)           malfunction of the receiver could lead to personal
temperature data from multiple WRS-TTx Series               injury or property damage to the controlled
Wireless Room Temperature Sensors for multiple              equipment or other property, additional precautions
temperature zones. Up to 60 WRS-TTx Series Sensors          must be designed into the control system.
can be associated with a single WRS-RTN Series              Incorporate and maintain other devices, such as
Receiver. The practical average due to typical              supervisory or alarm systems or safety or limit
application environments is 10 to 20 sensors per            controls, intended to warn of or protect against
receiver.                                                   failure or malfunction of the receiver.
Note: The WRS-RTN0000-1 Receiver (CE Mark                   IMPORTANT: Le WRS-RTN Series Receiver est
compliant model) has a reduced transmission power           destiné à transmettre des données entrantes à un
(10 dBm) and transmission range to comply with the          équipement dans des conditions normales de
requirements of select countries.                           fonctionnement. Lorsqu'une défaillance ou un
The WRS-RTN Series Receiver works in conjunction            dysfonctionnement du receiver risque de provoquer
with a Metasys® system Network Automation Engine            des blessures ou d'endommager l'équipement
(NAE) or Network Control Engine (NCE) and provides          contrôlé ou un autre équipement, la conception du
temperature data over Ethernet to the NAE or NCE.           système de contrôle doit intégrer des dispositifs de
The NAE or NCE processes the temperature data and           protection supplémentaires. Veiller dans ce cas à
distributes the data to various field controllers on the    intégrer de façon permanente d'autres dispositifs,
Metasys network.                                            tels que des systèmes de supervision ou d'alarme,
                                                            ou des dispositifs de sécurité ou de limitation, ayant
The receiver uses direct-sequence, spread-spectrum          une fonction d'avertissement ou de protection en
RF technology and operates on the 2.4 GHz ISM band.         cas de défaillance ou de dysfonctionnement du
The receiver meets the IEEE 802.15.4 standard for low       receiver.
power, low duty cycle RF transmitting systems.
The WRS-RTN Series Receiver operates as a                   IMPORTANT: The WRS-RTN Series Receiver is
transceiver to create a bidirectional association with      not designed or intended for use in mission-critical
the sensors, which allows the temperature sensing           or life/safety applications.
system to confirm and synchronize data transmissions
                                                           Refer to the WRS Series Many-to-One Wireless Room
between the sensors and the receiver.
                                                           Temperature Sensing System Technical Bulletin
                                                           (LIT-12011095) for information on commissioning and
                                                           configuring a WRS-RTN Series Receiver for operation
                                                           in a Many-to-One sensing system.

                           WRS-RTN Series Receivers for Many-to-One Wireless Room
                             Temperature Sensing Systems Installation Instructions
                                                     1
North American Compliance Statement                      Canada
United States                                            This Class (A) digital apparatus meets all the
                                                         requirements of the Canadian Interference-Causing
 This equipment has been tested and found to             Equipment Regulations.
 comply with the limits for a Class A digital device
 pursuant to Part 15 of the FCC Rules. These limits      Cet appareil numérique de la Classe (A) respecte
 are designed to provide reasonable protection           toutes les exigences du Règlement sur le matériel
 against harmful interference when this equipment is     brouilleur du Canada.
 operated in a commercial environment. This              RF Transmitters: Industry Canada Statements
 equipment generates, uses, and can radiate radio
 frequency energy and, if not installed and used in      The term IC before the certification/registration
 accordance with the instruction manual, may cause       number only signifies that the Industry Canada
 harmful interference to radio communications.           technical specifications were met.
 Operation of this equipment in a residential area is    This device has been designed to operate with an
 likely to cause harmful interference, in which case     antenna having a maximum gain of 2 dB. Antenna
 the user will be required to correct the interference   having a higher gain is strictly prohibited per
 at his/her own expense.                                 regulations of Industry Canada. The required
 RF Transmitters: Compliance Statement                   antenna impedance is 50 ohms.
 (Part 15.19)                                            To reduce potential radio interference to other users,
 This device complies with Part 15 of the FCC Rules.     the antenna type and its gain should be so chosen
 Operation is subject to the following two conditions:   that the Equivalent Isotropically Radiated Power
                                                         (EIRP) is not more than that required for successful
 1. This device may not cause harmful interference,      communication.
    and
                                                         Le terme « IC » précédant le numéro d'accréditation/
 2. This device must accept any interference             inscription signifie simplement que le produit est
    received, including interference that may cause      conforme aux spécifications techniques d'Industry
    undesired operation.                                 Canada.
 Warning (Part 15.21)
                                                         Cet appareil a été conçu pour fonctionner avec une
 Changes or modifications not expressly approved by      antenne d'un gain maximum de 2 dBi. En application
 the party responsible for compliance could void the     des réglementations d'Industry Canada, l'utilisation
 user’s authority to operate the equipment.              d'une antenne de gain supérieur est strictement
                                                         interdite. L'impédance d'antenne requise est de
 RF Exposure (OET Bulletin 65)
                                                         50 ohms.
 To comply with FCC RF exposure requirements for
                                                         Pour réduire les interférences radio potentielles
 mobile transmitting devices, this transmitter should
                                                         avec les dispositifs d'autres utilisateurs, le type
 only be used or installed at locations where there is
                                                         d'antenne et son gain doivent être choisis de façon à
 at least 20 cm separation distance between the
                                                         ce que la Puissance Isotrope Rayonnée Équivalente
 antenna and all persons.
                                                         (PIRE) ne soit pas supérieure à la puissance
                                                         nécessaire pour une bonne communication.

          WRS-RTN Series Receivers for Many-to-One Wireless Room Temperature Sensing Systems
                                         Installation Instructions
                                                     2
Installation                                                                Mounting
                                                                            Location Considerations
    IMPORTANT: Before installing the WRS-RTN
    Series Receiver in plenum applications, verify                          Receivers Using the Omnidirectional Indoor
    acceptance of exposed plastic materials in plenum                       Antenna
    areas with the local building authority. Building                       Follow these guidelines when locating a
    codes for plenum requirements vary by location.                         WRS-RTN Series Receiver using the omnidirectional
    Some local building authorities accept compliance to                    antenna.
    UL 1995, Heating and Cooling Equipment, while
    others use different acceptance criteria.                               •   Locate the receiver so that it is easily accessible
                                                                                (typically just above the ceiling tiles).
Follow these guidelines:                                                    •   Locate the receiver near the center of the sensor
•     Transport the WRS-RTN Series Receiver in the                              array associated with the receiver.
      original container to minimize vibration and shock                    •   Locate the receiver on the same floor or building
      damage to the receiver.                                                   level as the associated sensors. (Transmissions
•     Verify that all the parts shipped with the receiver.                      may pass through floors. Test the transmission
                                                                                strength before installing associated sensors and
•     Do not drop the receiver or subject it to physical                        receivers on different floors or building levels.)
      shock.
                                                                            •   Locate the receiver in line-of-sight with as many
Parts Included                                                                  sensors as possible.
•     one WRS-RTN Series Receiver
                                                                            •   Mount the receiver in any orientation; but for best
•     one omnidirectional indoor antenna                                        signal transmission, the antenna should be
•     four No. 6 pan-head, sheet-metal screws                                   oriented vertically with at least 2 in. (50 mm) of the
                                                                                antenna tip exposed below and clear of any pipes,
•     one installation instructions sheet                                       duct work, or other metal obstructions, in direct
Dimensions                                                                      line-of-sight to the sensors.
                                                                            •   Avoid metal obstructions (including equipment
                                                                                rooms and elevator shafts) and concrete or brick
                                                 5-1/2
                                                  140
                                                                                walls between the receiver and sensors.
                               Omnidirectional
                                 Antenna                                    •   Do not mount the receiver in recessed areas, metal
                               5-3/4
                                                                                enclosures, or shelving units (unless the receiver
                                146                                             antenna is positioned as described in Installing the
                                                         2-1/16
                                                                                Omnidirectional Indoor Antenna on page 5).
                                                           52
                                                                            •   Do not point the tip of the omnidirectional antenna
                                                                                at any of the associated WRS-TTx Series Sensors.
                                                                            Note: For detailed information on estimating the
                                                                            number of WRS-RTN Series Receivers needed for a
                                                    4-31/32                 Many-to-One application and locating the
                                                      126
                                                                            WRS-RTN Series Receivers for optimum signal
                                                                            coverage, refer to the WRS Series Many-to-One
                 Link                                                       Wireless Room Temperature Sensing System
       24 VAC LED Activity                                                  Technical Bulletin (LIT-12011095).
       Class 2             LED
                               Parameter LED Receiver
                                                              FIG:frnt_vw
     Power Supply Ethernet       Reset Status Indicators
        Port          Port      Button

         Figure 1: WRS-RTN Series Receiver,
      Physical Features and Dimensions (in./mm)

             WRS-RTN Series Receivers for Many-to-One Wireless Room Temperature Sensing Systems
                                            Installation Instructions
                                                        3
Wireless RF Signal Transmission Considerations            To mount the receiver base with screws:
The maximum transmission range for indoor                 1. Remove the receiver from the mounting base
line-of-sight transmissions between a WRS-TTx Series         (Figure 2).
Sensor and a WRS-RTN0000-0 Receiver is
500 ft (152 m). Taking into consideration RF signal                                              2. Use the mounting base
                                                            3. Insert the four No. 6 screws into for screw hole template.
absorption and reflection due to metal objects, walls,      mount holes on mounting base and
and furniture found in typical building interiors, the      tighten them evenly to the surface.
practical average indoor (line-of-sight) transmission
range between a sensor and receiver is 200 ft (61 m).                                                                Slots

The maximum transmission range for indoor
line-of-sight transmissions between a WRS-TTx Series
Sensor and a WRS-RTN0000-1 Receiver is                      Locking
                                                            Tabs (4)
375 ft (114 m). Taking into consideration RF signal
absorption and reflection due to metal objects, walls,
and furniture found in typical building interiors, the

                                                                                                                          FIG:mntng_rcvr
practical average indoor (line-of-sight) transmission
range between a sensor and receiver is 165 ft (50 m).       4. Reinstall receiver
                                                            housing by aligning locking
The signal strength between an installed sensor and         tabs with slots on mounting   1. Remove receiver housing by
receiver can be tested by pressing and releasing the        base and pressing housing     pressing the locking tabs in at
                                                            until it locks on to base.    the slots in the mounting base to
occupancy button on the WRS-TTx Series Sensor.                                            release the receiver from base.
Refer to the WRS Series Many-to-One Wireless Room
                                                           Figure 2: Mounting the WRS-RTN Series Receiver
Temperature Sensing System Technical Bulletin
(LIT-12011095) for more information on determining
the signal strength between a WRS-TTx Series Sensor       2. Use the mounting base as a template; place the
and a WRS-RTN Series Receiver.                               mounting base against the mounting surface.
Use a WRS-SST Series Wireless Sensing System Tool         3. Drill pilot holes at the marked locations and secure
to determine the radio frequency signal strength             the mounting base to the surface with the (four)
between the sensor and receiver locations. Refer to the      No. 6 screws supplied.
WRS-SST Series Wireless Sensing System Tools
Technical Bulletin (Part No. 24-10139-16) for more         IMPORTANT: Do not overtighten the mounting
information on testing signal strength in your             screws. Overtightening the mounting screws may
application.                                               damage the mounting base or mounting surface.

Mounting the Base                                         4. Reinstall the receiver housing to the mounting
The WRS-RTN Series Receiver can be surface                   base.
mounted using the four No. 6 self-tapping, pan-head
screws supplied.

          WRS-RTN Series Receivers for Many-to-One Wireless Room Temperature Sensing Systems
                                         Installation Instructions
                                                     4
Wiring                                                       Note: Transformers not manufactured by
                                                             Johnson Controls may have different color wires.
Wiring Considerations and Guidelines                         Follow the manufacturer’s instructions when mounting
                                                             and wiring transformers.
                                                                                          24V~

    Risk of Property Damage.                                              Power
    Do not apply power to the system before checking all              Terminal Block
    wiring connections. Short circuited or improperly
    connected wires may result in permanent damage to                    Power Terminal
                                                                           Block Plug
    the equipment.
                                                                          Wires from
                                                                                           COM   HOT
                                                                       Johnson Controls

                                                                                                                FIG:pwr_prt
                                                                        24 VAC Class 2
                                                                      Power Transformer

    Risque de dégâts matériels.                                                        Brown Wire Orange Wire
    Ne pas mettre le système sous tension avant d'avoir                                  (COM)     (24 VAC)
    vérifié tous les raccords de câblage. Des fils formant
                                                               Figure 3: WRS-RTN Power Supply Connection
    un court-circuit ou connectés de façon incorrecte
    risquent d'endommager irrémédiablement
    l'équipement.                                            Connecting to the Ethernet Network
                                                             The (10 or 100 Mbps) Ethernet connection is an
                                                             eight-pin RJ-45 network port (Figure 1). Use the
    IMPORTANT: Use copper conductors only. Make              Ethernet port to connect to the Internet Protocol (IP)
    all wiring in accordance with local, national, and       network on which the associated NAE or NCE resides.
    regional regulations. The WRS-RTN Series
    Receiver is a low-voltage (less than 30 VAC) device.      IMPORTANT: You must assign an Internet
    Do not exceed the receiver’s electrical ratings.          Protocol (IP) address to the WRS-RTN Series
                                                              Receiver before connecting the receiver to the
    IMPORTANT: Prevent any static electric discharge          network the first time. Refer to the WRS Series
    to the WRS-RTN Series Receiver. Static electric           Many-to-One Wireless Room Temperature Sensing
    discharge can damage the receiver and void any            System Technical Bulletin (LIT-12011095) for more
    warranties.                                               information on assigning an IP address to the
                                                              receiver.
Follow these guidelines when wiring a receiver:
•      Route the power supply wires and Ethernet cables
                                                             Setup and Adjustments
       at least 2 in. (50 mm) away from the vent slots on    Installing the Omnidirectional Indoor Antenna
       the sides of the receiver housing.                    The omnidirectional indoor antenna, supplied with the
•      Provide slack in the wires and cables. Keep cables    receiver, fits the reverse polarity male Sub-Miniature
       routed neatly around the receiver to promote good     version A (SMA) connector.
       ventilation, Light-Emitting Diode (LED) visibility,   To install the omnidirectional antenna:
       and ease of service.
                                                             1. Screw the omnidirectional antenna onto the
Connecting the Power Supply                                     antenna port on the WRS-RTN Series Receiver.
The WRS-RTN Series Receiver requires a nominal
                                                             2. Position the antenna in a vertical position with at
24 VAC, 50/60 Hz, 4.5 VA (minimum), Class 2 power
                                                                least 2 in. (50 mm) of the antenna tip exposed and
supply. The required minimum voltage is 20.4 VAC.
                                                                unobstructed by any pipes, duct work, or other
See Table 1 for recommended Johnson Controls®
                                                                metal obstructions and in direct line-of-sight to the
transformers.
                                                                sensors.
1. Connect the 24 VAC supply power wires from the
   transformer to the removable three-terminal plug
   as shown in Figure 3. The middle terminal is not
   used.

              WRS-RTN Series Receivers for Many-to-One Wireless Room Temperature Sensing Systems
                                             Installation Instructions
                                                         5
Refer to the WRS Series Many-to-One Wireless Room                 Repair Information
Temperature Sensing System Technical Bulletin
                                                                  If the WRS-RTN Series Receiver fails to operate within
(LIT-12011095) and the WRS-SST Series Wireless
                                                                  its specifications, replace the unit. For a replacement
Sensing System Tools Technical Bulletin
                                                                  receiver, contact the nearest Johnson Controls
(Part No. 24-10139-16) for more information.
                                                                  representative.
Accessories
Table 1: Accessories Ordering Information
 Product Code Number                Product Description
 WRS-TTP0000-0                      Wireless Room Temperature Sensor, Warmer/Cooler Setpoint Adjustment,
                                    15 dBm Transmission Power
 WRS-TTP0000-1                      Wireless Room Temperature Sensor, Warmer/Cooler Setpoint Adjustment,
                                    10 dBm Transmission Power (CE Mark)
 WRS-TTR0000-0                      Wireless Room Temperature Sensor, No Setpoint Adjustment, 15 dBm Transmission
                                    Power
 WRS-TTR0000-1                      Wireless Room Temperature Sensor, No Setpoint Adjustment, 10 dBm Transmission
                                    Power (CE Mark)
 WRS-TTS0000-0                      Wireless Room Temperature Sensor, Setpoint Adjustment Scale: 55 to 85°F/13 to 29°C,
                                    15 dBm Transmission Power
 WRS-TTS0000-1                      Wireless Room Temperature Sensor, Setpoint Adjustment Scale: 55 to 85°F/13 to 29°C,
                                    10 dBm Transmission Power (CE Mark)
 WRS-SST-100                        Wireless Sensing System Tool (Monitors RF Signal Strength and Temperature Data
                                    between a WRS-TTx0000-0 Series Sensor and the Associated WRS-RTN0000-0 Series
                                    or TE-7800 Series Receiver), 15 dBm Transmission Power
 WRS-SST-101                        Wireless Sensing System Tool (Monitors RF Signal Strength and Temperature Data
                                    between a WRS-TTx0000-1 Series Sensor and the Associated WRS-RTN0000-1 Series
                                    or TE-7800 Series Receiver), 10 dBm Transmission Power (CE Mark)
 TP-2420                            Transformer, Wall Plug Mount, 120 VAC to 24 VAC, 20 VA, Class 2

 Y65T31-0  1                        Transformer, 102/208/240 VAC to 24 VAC, 40 VA, Class 2, Foot Mount, 8 in. (20 cm)
                                    Primary Leads and Secondary Screw Terminals

1.   Additional Y60 Series Transformers are available from Johnson Controls.

Technical Specifications
WRS-RTN Series Receivers for Many-to-One Wireless Room Temperature Sensing
Systems (Part 1 of 2)
 Power Requirements                  24 VAC (+10%/-15%), 50/60 Hz, 4.5 VA (Minimum) Class 2 Power Supply
 Addressing                          Configurable via the NAE or NCE for up to 511 Unique Transmitter ID Addresses and up
                                     to 31 Property Code Addresses.
 Ambient Operating                   32 to 122°F (0 to 50°C )
 Temperature Limits
 Ambient Operating                   5 to 95% RH, Noncondensing
 Humidity Limits
 Ambient Storage                     -40 to 160°F (-40 to 71°C)
 Temperature Limits
 Ambient Storage                     5 to 90% RH, Noncondensing
 Humidity Limits
 RF Band                             Direct-Sequence, Spread-Spectrum, 2.4 GHz ISM Bands
 Transmission Power                  WRS-RTN0000-0 Receiver: 15 dBm Maximum
                                     WRS-RTN0000-1 Receiver: 10 dBm Maximum

            WRS-RTN Series Receivers for Many-to-One Wireless Room Temperature Sensing Systems
                                           Installation Instructions
                                                       6
WRS-RTN Series Receivers for Many-to-One Wireless Room Temperature Sensing
Systems (Part 2 of 2)
 Transmission Range                        WRS-RTN0000-0 Receiver: 500 ft (152 m) Maximum Indoor Line-of-Sight;
                                           200 ft (61 m) Practical Average Indoor
                                           WRS-RTN0000-1 Receiver: 375 ft (114 m) Maximum Indoor Line-of-Sight;
                                           165 ft (50 m) Practical Average Indoor
 Receiver Outputs                          One Ethernet Connection for Communicating Temperature, Setpoint, Occupancy Status,
                                           Field Strength Measurements, and Low Battery Conditions
 Temperature System Accuracy               1F° (0.6C°) Over the Range of 55 to 85°F (13 to 29°C);
                                           1.5F° (0.9C°) Over a Range of 32 to 55°F (0 to 13°C) and 85 to 110°F (29 to 43°C)
 Wiring Terminations and                   One Three-Position Terminal Block with Removable Terminal Plug for 24 VAC Supply
 Network Interfaces                        Power; One 10/100 Mbps, Eight-Pin, RJ-45 Ethernet Port
 Network Bandwidth                         Less than 0.02% on a 10 Mbps Ethernet Connection
 Requirement
 Materials                                 Gray Plastic Housing with UL94-5VB Flammability Rating
 Mounting                                  Screw Mount; Four No. 6 Pan-Head, Sheet-Metal Screws Included
 Compliance (WRS-RTN0000-0                 United States: Intended for NEC Class 2 Connection
 Receiver)
                                           UL Listed, File E107041, CCN PAZX
                                           UL 94-5VB Flammability Rating
                                           FCC Compliant to CFR 47, Part 15, Subpart B, Class A
                                           Transmission Complies with FCC Part 15.247 Regulations for Low Power Unlicensed
                                           Transmitters
                                           Transmitter FCC Identification: CB2-TMPSENS2400A
                                           Canada: Intended for CEC Class 2 Connection
                                           UL Listed, File E107041, CCN PAZX7
                                           UL 94-5VB Flammability Rating
                                           Industry Canada IC: 279A-TSENS24A
                                           Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
 Compliance (WRS-RTN0000-1                 Europe: CE Mark – Johnson Controls, Inc., declares that this product is in
 Receiver)                                 compliance with the essential requirements and other relevant provisions of the
                                           R&TTE Directive.
                                           South Africa: Accepts Directives for Europe

 Shipping Weight                           1.0 lb (0.45 kg)

European Single Point of Contact:               NA/SA Single Point of Contact:                   APAC Single Point of Contact:
JOHNSON CONTROLS                                JOHNSON CONTROLS                                 JOHNSON CONTROLS
WESTENDHOF 3                                    507 E MICHIGAN ST                                C/O CONTROLS PRODUCT
45143 ESSEN                                     MILWAUKEE WI 53202                               MANAGEMENT
GERMANY                                         USA                                              NO. 22 BLOCK D NEW DISTRICT
                                                                                                 WUXI JIANGSU PROVINCE 214142
                                                                                                 CHINA

The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.

                                                                                                                     Building Efficiency
                                                                                            507 E. Michigan Street, Milwaukee, WI 53202
                                             Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                    All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.

            WRS-RTN Series Receivers for Many-to-One Wireless Room Temperature Sensing Systems
                                           Installation Instructions
Published in U.S.A.                                    7                          www.johnsoncontrols.com