VSD 575V Series II Variable Speed Open, IntelliPass®, and
IntelliDisconnect® Drives
Product Bulletin Code No. LIT-12012402
Issued August 2017
Introduction
The Johnson Controls® VSD 575V Series II Variable Figure 1: VSD Series II Open Drives
Speed Open, IntelliPass, and IntelliDisconnect drives,
powered by Eaton® technology, provide an intelligent
drive integrated with reliable bypass configuration. The
575V IntelliPass bypass is a three-contactor design
using Eaton contactors and power supplies. The
IntelliDisconnect variable speed drive combines a
premier quality drive with a fused disconnect.
The input/output (I/O) configuration is designed with
wiring ergonomics in mind by including removable
terminal blocks. Available I/O includes six digital IN,
two analog IN, one analog OUT, three relay OUT, and
two expansion slots for I/O or communications boards.
The available SA-Bus option card can be factory
installed on IntelliPass and IntelliDisconnect drives.
Features
• Patented Active Energy Control Algorithm—
Achieve an additional 2% to 8% energy savings
when compared to competitive products.
• HAND/OFF/AUTO and DRIVE/BYPASS Selector
on Keypad—Simplifies control.
• Copy/Paste Function—Allows the transfer of
parameter settings from one drive to the next.
• Versatile Type 12 Keypad—Displays up to nine
monitored parameters simultaneously.
• Closed-Loop Control Programmed with
Engineering —Provides software parameters
using engineering units common to the HVAC
industry.
• BACnet® MS/TP, BACnet IP, MODBUS®, and
N2 Network Protocols—Provide a wide variety of
communication protocols to meet the needs of
many applications.
• Drive Programming Capability Using Auxiliary
24 V Power Supply (VS-AUX24V)—Allows
variable speed drive programming (including
network communication validation) prior to wiring
three-phase power to the drive.
VSD 575V Series II Variable Speed Open, IntelliPass®, and
IntelliDisconnect® Drives Product Bulletin
1
• On-screen troubleshooting diagnostics with
embedded manual assistance.
IMPORTANT: Use this VSD Series II Variable
Speed Drive only as an operating control. Where • Quickstart wizard built into programming of drive
failure or malfunction of the drive could lead to ensures a smooth startup.
personal injury or property damage to the controlled • I/O connections with simple quick connection
equipment or other property, additional precautions terminals.
must be designed into the control system.
Incorporate and maintain other devices, such as • Standard I/O, 6DI, 2AI, 1AO 2 Form C RO (No/NC),
supervisory or alarm systems or safety or limit 1 Form A RO (NO).
controls, intended to warn of or protect against IntelliPass and IntelliDisconnect Features
failure or malfunction of the drive.
• Serial communication interface that can control the
IMPORTANT : Utiliser ce VSD Series II Variable drive and all bypass features so the remote
Speed Drive uniquement en tant que dispositif de operator can fully control the motor at all times.
contrôle de fonctionnement. Lorsqu'une défaillance
• Input surge protection against voltage spikes
ou un dysfonctionnement du drive risque de
varistor input.
provoquer des blessures ou d'endommager
l'équipement contrôlé ou un autre équipement, la • Hard-wired external/damper interlock.
conception du système de contrôle doit intégrer des
Additional IntelliPass Only Features
dispositifs de protection supplémentaires. Veiller
dans ce cas à intégrer de façon permanente d'autres • HAND/OFF/AUTO and DRIVE/BYPASS selector
dispositifs, tels que des systèmes de supervision ou on keypad that simplifies control.
d'alarme, ou des dispositifs de sécurité ou de • Electronic or Manual Bypass models.
limitation, ayant une fonction d'avertissement ou de
protection en cas de défaillance ou de • Programmable Automatic Restart Options
dysfonctionnement du drive. (automatically transfer to Bypass, reset drive only,
or reset drive and transfer to Bypass).
VSD Series II Open Drive Features • Fully rated, mechanically interlocked contacts.
• Integrated DC link choke standard on drives from
• Bypass circuit current interrupting rating up to
frame 4 through frame 9.
65 kAIC without fusing.
• Copy and paste keypad function allows you to
• Robust steel enclosure for simple installation.
transfer parameter settings from one drive to
another. Onboard Network Communication
• Standard Type 12 keypad on all drives. Metasys® System
• Keypad displays up to nine monitored parameters Each VSD Series II Variable Speed Open Drive
simultaneously. provides communication between the drive and a
Johnson Controls Metasys N2 Network. With this
• Anti-trip DC bus regulation.
connection, the drives can be controlled, monitored,
• Input surge protection against voltage spiked and programmed from the Metasys system. N2 can be
varistor input. selected and programmed by the drive keypad.
• Additional I/O and communication cards provide BACnet
plug-and-play functionality. The VSD Series II Variable Speed Open Drives provide
• Remote-mount keypad kit available. communication to the BACnet® networks. Data
transfer is MS/TP RS-485.
• NEMA Type 1 and NEMA Type 12 available.
BACnet IP
• Real-time clock with PLC functionality.
The drive provides a 100-base T interface.
• Two independent proportional-integral-derivative
MODBUS TCP
(PID) functions.
The drive includes Ethernet-based protocol.
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
2
MODBUS RTU
VSD Series II Variable Speed Open Drives provide communication to MODBUS RTU RS-485 as a
subordinate on a MODBUS network. Other communication parameters include an address range from 1 to
247, a parity of Non, Odd, or Even with a stop bit of 1.
Table 1: 575V Series Open and Enclosed Drive Selection Chart
Code Number V S 3 D9 5 1 0 D 0 0 0 0 0
Base Product VS Series II
Amps, hp 3D9 = 3.9A, 3 hp
6D1 = 6.1A, 5 hp
9D0 = 9A, 7.5 hp
011 = 11A, 10 hp
018 = 18A, 15 hp
022 = 22A, 20 hp
027 = 27A, 25 hp
034 = 34A, 30 hp
041 = 41A, 40 hp
052 = 52A, 50 hp
062 = 62A, 60 hp
080 = 80A, 75 hp
100 =100A, 100 hp
125 = 125A, 125 hp
150 = 144A, 150 hp (IntelliPass & IntelliDisconnect)
200 = 208A, 200 hp (IntelliPass & IntelliDisconnect)
144 = 144A, 150 hp (Open drives)
208 = 208A, 208 hp (Open drives)
Voltage 5 = 575 V
Enclosure Rating 1 = Open NEMA 1 UL Type 1 (IP21)
2 = Open NEMA 12 UL Type 12 (IP54)
4 = Enclosed NEMA 1
5 = Enclosed NEMA 12
3 = Enclosed NEMA 3R
Drive Style 0 = Open
1 = IntelliPass
2 = IntelliDisconnect
Revision D = Canada
Communications 0 = BACnet MS/TP/MODBUS
S = SA Bus (factory installed on enclosed product)
Enclosed Configuration P9 = Fused electronic bypass
M1 = Fused mechanical bypass
P3 = Fused IntelliDisconnect
Output Filter 00 = No output filter
Enclosed Configuration OF = dV/dT filter
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
3
VSD Series II Open Drives Product Selection
Table 2: 575V Series II Open Drives—Frame Size 5
Code Number Description Current (A)
VS3D9510D-00000 VSD II, 3 hp (2.2 kW), 575 V, NEMA Type 1, N2 and BACnet comm 3.9
VS3D9520D-00000 VSD II, 3 hp (2.2 kW), 575 V, NEMA Type 12, N2 and BACnet comm
VS6D1510D-00000 VSD II, 5 hp (3.7 kW), 575 V, NEMA Type 1, N2 and BACnet comm 6.1
VS6D1520D-00000 VSD II, 5 hp (3.7 kW), 575 V, NEMA Type 12, N2 and BACnet comm
VS9D0510D-00000 VSD II, 7.5 hp (5 kW), 575 V, NEMA Type 1, N2 and BACnet comm 9
VS9D0520D-00000 VSD II, 7.5 hp (5 kW), 575 V, NEMA Type 12, N2 and BACnet comm
VS011510D-00000 VSD II, 10 hp (7.5 kW), 575 V, NEMA Type 1, N2 and BACnet comm 11
VS011520D-00000 VSD II, 10 hp (7.5 kW), 575 V, NEMA Type 12, N2 and BACnet comm
Table 3: 575V Series II Open Drives—Frame Size 6
Code Number Description Current (A)
VS018510D-00000 VSD II, 15 hp (11 kW), 575 V, NEMA Type 1, N2 and BACnet comm 18
VS018520D-00000 VSD II, 15 hp (11 kW), 575 V, NEMA Type 12, N2 and BACnet comm
VS022510D-00000 VSD II, 20 hp (15 kW), 575 V, NEMA Type 1, N2 and BACnet comm 22
VS022520D-00000 VSD II, 20 hp (15 kW), 575 V, NEMA Type 12, N2 and BACnet comm
VS027510D-00000 VSD II, 25 hp (18.5 kW), 575 V, NEMA Type 1, N2 and BACnet comm 27
VS027520D-00000 VSD II, 25 hp (18.5 kW), 575 V, NEMA Type 12, N2 and BACnet comm
VS034510D-00000 VSD II, 30 hp (22 kW), 575 V, NEMA Type 1, N2 and BACnet comm 34
VS034520D-00000 VSD II, 30 hp (22 kW), 575 V, NEMA Type 12, N2 and BACnet comm
Table 4: 575V Series II Open Drives—Frame Size 7
Code Number Description Current (A)
VS041510D-00000 VSD II, 40 hp (30 kW), 575 V, NEMA Type 1, N2 and BACnet comm 41
VS041520D-00000 VSD II, 40 hp (30 kW), 575 V, NEMA Type 12, N2 and BACnet comm
VS052510D-00000 VSD II, 50 hp (37 kW), 575 V, NEMA Type 1, N2 and BACnet comm 52
VS052520D-00000 VSD II, 50 hp (37 kW), 575 V, NEMA Type 12, N2 and BACnet comm
VS062510D-00000 VSD II, 60 hp (45 kW), 575 V, NEMA Type 1, N2 and BACnet comm 62
VS062520D-00000 VSD II, 60 hp (45 kW), 575 V, NEMA Type 12, N2 and BACnet comm
Table 5: 575V Series II Open Drives—Frame Size 8
Code Number Description Current (A)
VS080510D-00000 VSD II, 75 hp (55 kW), 575 V, NEMA Type 1, N2 and BACnet comm 80
VS080520D-00000 VSD II, 75 hp (55 kW), 575 V, NEMA Type 12, N2 and BACnet comm
VS100510D-00000 VSD II, 100 hp (75 kW), 575 V, NEMA Type 1, N2 and BACnet comm 100
VS100520D-00000 VSD II, 100 hp (75 kW), 575 V, NEMA Type 12, N2 and BACnet comm
VS125510D-00000 VSD II, 125 hp (90 kW), 575 V, NEMA Type 1, N2 and BACnet comm 125
VS125520D-00000 VSD II, 125 hp (90 kW), 575 V, NEMA Type 12, N2 and BACnet comm
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
4
Table 6: 575V Series II Open Drives—Frame Size 9
Code Number Description Current (A)
VS144510D-00000 VSD II, 150 hp (110 kW), 575 V, NEMA Type 1, N2 and BACnet comm 144
VS144520D-00000 VSD II, 150 hp (110 kW), 575 V, NEMA Type 12, N2 and BACnet comm
VS208510D-00000 VSD II, 200 hp (150 kW), 575 V, NEMA Type 1, N2 and BACnet comm 208
VS208520D-00000 VSD II, 200 hp (150 kW), 575 V, NEMA Type 12, N2 and BACnet comm
VSD Series II IntelliDisconnect Drives Product Selection
Table 7: 575V Series II IntelliDisconnect Drives—Box Type AX
Code Number Description Current Weight Drive
(A) (lb) Frame
VS3D9542D-0P300 VSD II with Disconnect, 3 hp (2.2 kW), 575 V, NEMA Type 1, N2 and 3.9 155 FS5
BACnet comm
VS3D9552D-0P300 VSD II with Disconnect, 3 hp (2.2 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS3D9532D-0P300 VSD II with Disconnect, 3 hp (2.2 kW), 575 V, NEMA Type 3R, N2 170
and BACnet comm
VS6D1542D-0P300 VSD II with Disconnect, 5 hp (3.7 kW), 575 V, NEMA Type 1, N2 and 6.1 155
BACnet comm
VS6D1552D-0P300 VSD II with Disconnect, 5 hp (3.7 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS6D1532D-0P300 VSD II with Disconnect, 5 hp (3.7 kW), 575 V, NEMA Type 3R, N2 170
and BACnet comm
VS9D0542D-0P300 VSD II with Disconnect, 7.5 hp (5 kW), 575 V, NEMA Type 1, N2 and 9 155
BACnet comm
VS9D0552D-0P300 VSD II with Disconnect, 7.5 hp (5 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS9D0532D-0P300 VSD II with Disconnect, 7.5 hp (5 kW), 575 V, NEMA Type 3R, N2 170
and BACnet comm
VS011542D-0P300 VSD II with Disconnect, 10 hp (7.5 kW), 575 V, NEMA Type 1, N2 11 155
and BACnet comm
VS011552D-0P300 VSD II with Disconnect, 10 hp (7.5 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS011532D-0P300 VSD II with Disconnect, 10 hp (7.5 kW), 575 V, NEMA Type 3R, N2 170
and BACnet comm
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
5
Table 8: 575V Series II IntelliDisconnect Drives—Box Type BX
Code Number Description Current Weight Drive
(A) (lb) Frame
VS018542D-0P300 VSD II with Disconnect, 15 hp (11 kW), 575 V, NEMA Type 1, N2 and 18 215 FS6
BACnet comm
VS018552D-0P300 VSD II with Disconnect, 15 hp (11 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS018532D-0P300 VSD II with Disconnect, 15 hp (11 kW), 575 V, NEMA Type 3R, N2 235
and BACnet comm
VS022542D-0P300 VSD II with Disconnect, 20 hp (15 kW), 575 V, NEMA Type 1, N2 and 22 215
BACnet comm
VS022552D-0P300 VSD II with Disconnect, 20 hp (15 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS022532D-0P300 VSD II with Disconnect, 20 hp (15 kW), 575 V, NEMA Type 3R, N2 235
and BACnet comm
VS027542D-0P300 VSD II with Disconnect, 25 hp (18.5 kW), 575 V, NEMA Type 1, N2 27 215
and BACnet comm
VS027552D-0P300 VSD II with Disconnect, 25 hp (18.5 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS027532D-0P300 VSD II with Disconnect, 25 hp (18.5 kW), 575 V, NEMA Type 3R, N2 235
and BACnet comm
Table 9: 575V Series II IntelliDisconnect Drives—Box Type CX
Code Number Description Current Weight Drive
(A) (lb) Frame
VS034542D-0P300 VSD II with Disconnect, 30 hp (22 kW), 575 V, NEMA Type 1, N2 and 34 280 FS6
BACnet comm
VS034552D-0P300 VSD II with Disconnect, 30 hp (22 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS034532D-0P300 VSD II with Disconnect, 30 hp (22 kW), 575 V, NEMA Type 3R, N2 305
and BACnet comm
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
6
Table 9: 575V Series II IntelliDisconnect Drives—Box Type CX
Code Number Description Current Weight Drive
(A) (lb) Frame
VS041542D-0P300 VSD II with Disconnect, 40 hp (30 kW), 575 V, NEMA Type 1, N2 and 41 308 FS7
BACnet comm
VS041552D-0P300 VSD II with Disconnect, 40 hp (30 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS041532D-0P300 VSD II with Disconnect, 40 hp (30 kW), 575 V, NEMA Type 3R, N2 333
and BACnet comm
VS052542D-0P300 VSD II with Disconnect, 50 hp (37 kW), 575 V, NEMA Type 1, N2 and 52 308
BACnet comm
VS052552D-0P300 VSD II with Disconnect, 50 hp (37 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS052532D-0P300 VSD II with Disconnect, 50 hp (37 kW), 575 V, NEMA Type 3R, N2 333
and BACnet comm
VS062542D-0P300 VSD II with Disconnect, 60 hp (45 kW), 575 V, NEMA Type 1, N2 and 62 308
BACnet comm
VS062552D-0P300 VSD II with Disconnect, 60 hp (45 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS062532D-0P300 VSD II with Disconnect, 60 hp (45 kW), 575 V, NEMA Type 3R, N2 333
and BACnet comm
VS080542D-0P300 VSD II with Disconnect, 75 hp (55 kW), 575 V, NEMA Type 1, N2 and 80 368 FS8
BACnet comm
VS080552D-0P300 VSD II with Disconnect, 75 hp (55 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS080532D-0P300 VSD II with Disconnect, 75 hp (55 kW), 575 V, NEMA Type 3R, N2 393
and BACnet comm
VS100542D-0P300 VSD II with Disconnect, 100 hp (75 kW), 575 V, NEMA Type 1, N2 100 368
and BACnet comm
VS100552D-0P300 VSD II with Disconnect, 100 hp (75 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS100532D-0P300 VSD II with Disconnect, 100 hp (75 kW), 575 V, NEMA Type 3R, N2 393
and BACnet comm
VS125542D-0P300 VSD II with Disconnect, 125 hp (90 kW), 575 V, NEMA Type 1, N2 125 368
and BACnet comm
VS125552D-0P300 VSD II with Disconnect, 125 hp (90 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS125532D-0P300 VSD II with Disconnect, 125 hp (90 kW), 575 V, NEMA Type 3R, N2 393
and BACnet comm
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
7
Table 10: 575V Series II IntelliDisconnect Drives—Box Type DX
Code Number Description Current Weight Drive
(A) (lb) Frame
VS150542D-0P300 VSD II with Disconnect, 150 hp (110 kW), 575 V, NEMA Type 1, N2 144 820 FS9
and BACnet comm
VS150552D-0P300 VSD II with Disconnect, 150 hp (110 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS150532D-0P300 VSD II with Disconnect, 150 hp (110 kW), 575 V, NEMA Type 3R, N2 850
and BACnet comm
VS200542D-0P300 VSD II with Disconnect, 200 hp (150 kW), 575 V, NEMA Type 1, N2 208 820 FS9
and BACnet comm
VS200552D-0P300 VSD II with Disconnect, 200 hp (150 kW), 575 V, NEMA Type 12, N2
and BACnet comm
VS200532D-0P300 VSD II with Disconnect, 200 hp (150 kW), 575 V, NEMA Type 3R, N2 850
and BACnet comm
VSD Series II IntelliPass Drives Product Selection
Table 11: 575V Series II IntelliPass Drives—Box Type AX1
Code Number Description Current Weight Drive
(A) (lb) Frame
VS3D9541D-0_ _00 VSD II with Bypass, 3 hp (2.2 kW), 575 V, NEMA Type 1, N2 and 3.9 155 FS5
BACnet comm
VS3D9551D-0_ _00 VSD II with Bypass, 3 hp (2.2 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS3D9531D-0_ _00 VSD II with Bypass, 3 hp (2.2 kW), 575 V, NEMA Type 3R, N2 and 170
BACnet comm 170
VS6D1541D-0_ _00 VSD II with Bypass, 5 hp (3.7 kW), 575 V, NEMA Type 1, N2 and 6.1 155
BACnet comm
VS6D1551D-0_ _00 VSD II with Bypass, 5 hp (3.7 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS6D1531D-0_ _00 VSD II with Bypass, 5 hp (3.7 kW), 575 V, NEMA Type 3R, N2 and 170
BACnet comm
VS9D0541D-0_ _00 VSD II with Bypass, 7.5 hp (5 kW), 575 V, NEMA Type 1, N2 and 9 155
BACnet comm
VS9D0551D-0_ _00 VSD II with Bypass, 7.5 hp (5 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS9D0531D-0_ _00 VSD II with Bypass, 7.5 hp (5 kW), 575 V, NEMA Type 3R, N2 and 170
BACnet comm
VS011541D-0_ _00 VSD II with Bypass, 10 hp (7.5 kW), 575 V, NEMA Type 1, N2 and 11 155
BACnet comm
VS011551D-0_ _00 VSD II with Bypass, 10 hp (7.5 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS011531D-0_ _00 VSD II with Bypass, 10 hp (7.5 kW), 575 V, NEMA Type 3R, N2 and 170
BACnet comm
1. Complete IntelliPass order code with P9 (Electronic Bypass) or M1 (Mechanical Bypass).
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
8
Table 12: 575V Series II IntelliPass Drives—Box Type BX1
Code Number Description Current Weight Drive
(A) (lb) Frame
VS018541D-0_ _00 VSD II with Bypass, 15 hp (11 kW), 575 V, NEMA Type 1, N2 and 18 215 FS6
BACnet comm
VS018551D-0_ _00 VSD II with Bypass, 15 hp (11 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS018531D-0_ _00 VSD II with Bypass, 15 hp (11 kW), 575 V, NEMA Type 3R, N2 and 235
BACnet comm
VS022541D-0_ _00 VSD II with Bypass, 20 hp (15 kW), 575 V, NEMA Type 1, N2 and 22 215
BACnet comm
VS022551D-0_ _00 VSD II with Bypass, 20 hp (15 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS022531D-0_ _00 VSD II with Bypass, 20 hp (15 kW), 575 V, NEMA Type 3R, N2 and 235
BACnet comm
VS027541D-0_ _00 VSD II with Bypass, 25 hp (18.5 kW), 575 V, NEMA Type 1, N2 and 27 215
BACnet comm
VS027551D-0_ _00 VSD II with Bypass, 25 hp (18.5 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS027531D-0_ _00 VSD II with Bypass, 25 hp (18.5 kW), 575 V, NEMA Type 3R, N2 and 235
BACnet comm
1. Complete IntelliPass order code with P9 (Electronic Bypass) or M1 (Mechanical Bypass).
Table 13: 575V Series II IntelliPass Drives—Box Type CX1
Code Number Description Current Weight Drive
(A) (lb) Frame
VS034541D-0_ _00 VSD II with Bypass, 30 hp (22 kW), 575 V, NEMA Type 1, N2 and 34 280 FS6
BACnet comm
VS034551D-0_ _00 VSD II with Bypass, 30 hp (22 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS034531D-0_ _00 VSD II with Bypass, 30 hp (22 kW), 575 V, NEMA Type 3R, N2 and 305
BACnet comm
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
9
Table 13: 575V Series II IntelliPass Drives—Box Type CX1
Code Number Description Current Weight Drive
(A) (lb) Frame
VS041541D-0_ _00 VSD II with Bypass, 40 hp (30 kW), 575 V, NEMA Type 1, N2 and 41 308 FS7
BACnet comm
VS041551D-0_ _00 VSD II with Bypass, 40 hp (30 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS041531D-0_ _00 VSD II with Bypass, 40 hp (30 kW), 575 V, NEMA Type 3R, N2 and 333
BACnet comm
VS052541D-0_ _00 VSD II with Bypass, 50 hp (37 kW), 575 V, NEMA Type 1, N2 and 52 308
BACnet comm
VS052551D-0_ _00 VSD II with Bypass, 50 hp (37 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS052531D-0_ _00 VSD II with Bypass, 50 hp (37 kW), 575 V, NEMA Type 3R, N2 and 333
BACnet comm
VS062541D-0_ _00 VSD II with Bypass, 60 hp (45 kW), 575 V, NEMA Type 1, N2 and 62 308
BACnet comm
VS062551D-0_ _00 VSD II with Bypass, 60 hp (45 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS062531D-0_ _00 VSD II with Bypass, 60 hp (45 kW), 575 V, NEMA Type 3R, N2 and 333
BACnet comm
1. Complete IntelliPass order code with P9 (Electronic Bypass) or M1 (Mechanical Bypass).
Table 14: 575V Series II IntelliPass Drives—Box Type DX1
Code Number Description Current Weight Drive
(A) (lb) Frame
VS080541D-0_ _00 VSD II with Bypass, 75 hp (55 kW), 575 V, NEMA Type 1, N2 and 80 820 FS8
BACnet comm
VS080551D-0_ _00 VSD II with Bypass, 75 hp (55 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS080531D-0_ _00 VSD II with Bypass, 75 hp (55 kW), 575 V, NEMA Type 3R, N2 and 850
BACnet comm
VS100541D-0_ _00 VSD II with Bypass, 100 hp (75 kW), 575 V, NEMA Type 1, N2 and 100 820
BACnet comm
VS100551D-0_ _00 VSD II with Bypass, 100 hp (75 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS100531D-0_ _00 VSD II with Bypass, 100 hp (75 kW), 575 V, NEMA Type 3R, N2 and 850
BACnet comm
VS125541D-0_ _00 VSD II with Bypass, 125 hp (90 kW), 575 V, NEMA Type 1, N2 and 125 820
BACnet comm
VS125551D-0_ _00 VSD II with Bypass, 125 hp (90 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS125531D-0_ _00 VSD II with Bypass, 5 hp (90 kW), 575 V, NEMA Type 3R, N2 and 850
BACnet comm
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
10
Table 14: 575V Series II IntelliPass Drives—Box Type DX1
Code Number Description Current Weight Drive
(A) (lb) Frame
VS150541D-0_ _00 VSD II with Bypass, 150 hp (110 kW), 575 V, NEMA Type 1, N2 and 144 820 FS9
BACnet comm
VS150551D-0_ _00 VSD II with Bypass, 150 hp (110 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS150531D-0_ _00 VSD II with Bypass, 150 hp (110 kW), 575 V, NEMA Type 3R, N2 850
and BACnet comm
VS200541D-0_ _00 VSD II with Bypass, 200 hp (150 kW), 575 V, NEMA Type 1, N2 and 208 820
BACnet comm
VS200551D-0_ _00 VSD II with Bypass, 200 hp (150 kW), 575 V, NEMA Type 12, N2 and
BACnet comm
VS200531D-0_ _00 VSD II with Bypass, 200 hp (150 kW), 575 V, NEMA Type 3R, N2 850
and BACnet comm
1. Complete IntelliPass order code with P9 (Electronic Bypass) or M1 (Mechanical Bypass).
VSD Series II IntelliDisconnect Drives with dV/dT Filter Product Selection
Table 15: 575V Series II IntelliDisconnect Drives with dV/dT Filter—Box Type BX
Code Number Description Current Weight Drive
(A) (lb) Frame
VS3D9542D-0P3OF VSD II with Disconnect, 3 hp (2.2 kW), 575 V, NEMA Type 1, N2 3.9 226 FS5
and BACnet DVDT filter
VS3D9552D-0P3OF VSD II with Disconnect, 3 hp (2.2 kW), 575 V, NEMA Type 12, N2
and BACnet DVDT filter
VS3D9532D-0P3OF VSD II with Disconnect, 3 hp (2.2 kW), 575 V, NEMA Type 3R, N2 247
and BACnet DVDT filter
VS6D1542D-0P3OF VSD II with Disconnect, 5 hp (3.7 kW), 575 V, NEMA Type 1, N2 6.1 226
and BACnet DVDT filter
VS6D1552D-0P3OF VSD II with Disconnect, 5 hp (3.7 kW), 575 V, NEMA Type 12, N2
and BACnet DVDT filter
VS6D1532D-0P3OF VSD II with Disconnect, 5 hp (3.7 kW), 575 V, NEMA Type 3R, N2 247
and BACnet DVDT filter
VS9D0542D-0P3OF VSD II with Disconnect, 7.5 hp (5 kW), 575 V, NEMA Type 1, N2 9 226
and BACnet DVDT filter
VS9D0552D-0P3OF VSD II with Disconnect, 7.5 hp (5 kW), 575 V, NEMA Type 12, N2
and BACnet DVDT filter
VS9D0532D-0P3OF VSD II with Disconnect, 7.5 hp (5 kW), 575 V, NEMA Type 3R, N2 247
and BACnet DVDT filter 247
VS011542D-0P3OF VSD II with Disconnect, 10 hp (7.5 kW), 575 V, NEMA Type 1, N2 11 226
and BACnet DVDT filter
VS011552D-0P3OF VSD II with Disconnect, 10 hp (7.5 kW), 575 V, NEMA Type 12, N2
and BACnet DVDT filter
VS011532D-0P3OF VSD II with Disconnect, 10 hp (7.5 kW), 575 V, NEMA Type 3R, N2 247
and BACnet DVDT filter
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
11
Table 16: 575V Series II IntelliDisconnect Drives with dV/dT Filter—Box Type CX
Code Number Description Current Weight Drive
(A) (lb) Frame
VS018542D-0P3OF VSD II with Disconnect, 15 hp (11 kW), 575 V, NEMA Type 1, N2 18 235 FS6
and BACnet DVDT filter
VS018552D-0P3OF VSD II with Disconnect, 15 hp (11 kW), 575 V, NEMA Type 12, N2
and BACnet DVDT filter
VS018532D-0P3OF VSD II with Disconnect, 15 hp (11 kW), 575 V, NEMA Type 3R, N2 247
and BACnet DVDT filter
VS022542D-0P3OF VSD II with Disconnect, 20 hp (15 kW), 575 V, NEMA Type 1, N2 22 235
and BACnet DVDT filter
VS022552D-0P3OF VSD II with Disconnect, 20 hp (15 kW), 575 V, NEMA Type 12, N2
and BACnet DVDT filter
VS022532D-0P3OF VSD II with Disconnect, 20 hp (15 kW), 575 V, NEMA Type 3R, N2 247
and BACnet DVDT filter
VS027542D-0P3OF VSD II with Disconnect, 25 hp (18.5 kW), 575 V, NEMA Type 1, N2 27 265
and BACnet DVDT filter
VS027552D-0P3OF VSD II with Disconnect, 25 hp (18.5 kW), 575 V, NEMA Type 12, N2
and BACnet DVDT filter
VS027532D-0P3OF VSD II with Disconnect, 25 hp (18.5 kW), 575 V, NEMA Type 3R, 350
N2 and BACnet DVDT filter
VS034542D-0P3OF VSD II with Disconnect, 30 hp (22 kW), 575 V, NEMA Type 1, N2 34 294
and BACnet DVDT filter
VS034552D-0P3OF VSD II with Disconnect, 30 hp (22 kW), 575 V, NEMA Type 12, N2
and BACnet DVDT filter
VS034532D-0P3OF VSD II with Disconnect, 30 hp (22 kW), 575 V, NEMA Type 3R, N2 250
and BACnet DVDT filter
VS041542D-0P3OF VSD II with Disconnect, 40 hp (30 kW), 575 V, NEMA Type 1, N2 41 323 FS7
and BACnet DVDT filter
VS041552D-0P3OF VSD II with Disconnect, 40 hp (30 kW), 575 V, NEMA Type 12, N2
and BACnet DVDT filter
VS041532D-0P3OF VSD II with Disconnect, 40 hp (30 kW), 575 V, NEMA Type 3R, N2 350
and BACnet DVDT filter
VS052542D-0P3OF VSD II with Disconnect, 50 hp (37 kW), 575 V, NEMA Type 1, N2 52 323
and BACnet DVDT filter
VS052552D-0P3OF VSD II with Disconnect, 50 hp (37 kW), 575 V, NEMA Type 12, N2
and BACnet DVDT filter
VS052532D-0P3OF VSD II with Disconnect, 50 hp (37 kW), 575 V, NEMA Type 3R, N2 350
and BACnet DVDT filter
VS062542D-0P3OF VSD II with Disconnect, 60 hp (45 kW), 575 V, NEMA Type 1, N2 62 323
and BACnet DVDT filter
VS062552D-0P3OF VSD II with Disconnect, 60 hp (45 kW), 575 V, NEMA Type 12, N2
and BACnet DVDT filter
VS062532D-0P3OF VSD II with Disconnect, 60 hp (45 kW), 575 V, NEMA Type 3R, N2 350
and BACnet DVDT filter
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
12
Table 17: 575V Series II IntelliDisconnect Drives with dV/dT Filter—Box Type DX
Code Number Description Current Weight Drive
(A) (lb) Frame
VS080542D-0P3OF VSD II with Disconnect, 75 hp (55 kW), 575 V, NEMA Type 1, N2 80 861 FS8
and BACnet DVDT filter
VS080552D-0P3OF VSD II with Disconnect, 75 hp (55 kW), 575 V, NEMA Type 12, N2
and BACnet DVDT filter
VS080532D-0P3OF VSD II with Disconnect, 75 hp (55 kW), 575 V, NEMA Type 3R, N2 893
and BACnet DVDT filter
VS100542D-0P3OF VSD II with Disconnect, 100 hp (75 kW), 575 V, NEMA Type 1, N2 100 861
and BACnet DVDT filter
VS100552D-0P3OF VSD II with Disconnect, 100 hp (75 kW), 575 V, NEMA Type 12, N2
and BACnet DVDT filter
VS100532D-0P3OF VSD II with Disconnect, 100 hp (75 kW), 575 V, NEMA Type 3R, N2 893
and BACnet DVDT filter
VS125542D-0P3OF VSD II with Disconnect, 125 hp (90 kW), 575 V, NEMA Type 1, N2 125 861
and BACnet DVDT filter
VS125552D-0P3OF VSD II with Disconnect, 125 hp (90 kW), 575 V, NEMA Type 12, N2
and BACnet DVDT filter
VS125532D-0P3OF VSD II with Disconnect, 5 hp (90 kW), 575 V, NEMA Type 3R, N2 893
and BACnet DVDT filter
VS150542D-0P3OF VSD II with Disconnect, 150 hp (110 kW), 575 V, NEMA Type 1, N2 144 861 FS9
and BACnet DVDT filter
VS150552D-0P3OF VSD II with Disconnect, 150 hp (110 kW), 575 V, NEMA Type 12,
N2 and BACnet DVDT filter
VS150532D-0P3OF VSD II with Disconnect, 150 hp (110 kW), 575 V, NEMA Type 3R, 893
N2 and BACnet DVDT filter
VS200542D-0P3OF VSD II with Disconnect, 200 hp (150 kW), 575 V, NEMA Type 1, N2 208 861
and BACnet DVDT filter
VS200552D-0P3OF VSD II with Disconnect, 200 hp (150 kW), 575 V, NEMA Type 12,
N2 and BACnet DVDT filter
VS200532D-0P3OF VSD II with Disconnect, 200 hp (150 kW), 575 V, NEMA Type 3R, 893
N2 and BACnet DVDT filter
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
13
VSD Series II IntelliPass Drives with dV/dT Filter Product Selection
Table 18: 575V Series II IntelliPass Drives with dV/dT Filter—Box Type CX
Code Number Description Current Weight Drive
(A) (lb) Frame
VS3D9541D-0_ _OF VSD II with Bypass, 3 hp (2.2 kW), 575 V, NEMA Type 1, N2 and 3.9 294 FS5
BACnet Comm DVDT filter
VS3D9551D-0_ _OF VSD II with Bypass, 3 hp (2.2 kW), 575 V, NEMA Type 12, N2 and
BACnet Comm DVDT filter
VS3D9531D-0_ _OF VSD II with Bypass, 3 hp (2.2 kW), 575 V, NEMA Type 3R, N2 and 320
BACnet Comm DVDT filter
VS6D1541D-0_ _OF VSD II with Bypass, 5 hp (3.7 kW), 575 V, NEMA Type 1, N2 and 6.1 294
BACnet Comm DVDT filter
VS6D1551D-0_ _OF VSD II with Bypass, 5 hp (3.7 kW), 575 V, NEMA Type 12, N2 and
BACnet Comm DVDT filter
VS6D1531D-0_ _OF VSD II with Bypass, 5 hp (3.7 kW), 575 V, NEMA Type 3R, N2 and 320
BACnet Comm DVDT filter
VS9D0541D-0_ _OF VSD II with Bypass, 7.5 hp (5 kW), 575 V, NEMA Type 1, N2 and 9 294
BACnet Comm DVDT filter
VS9D0551D-0_ _OF VSD II with Bypass, 7.5 hp (5 kW), 575 V, NEMA Type 12, N2 and
BACnet Comm DVDT filter
VS9D0531D-0_ _OF VSD II with Bypass, 7.5 hp (5 kW), 575 V, NEMA Type 3R, N2 and 320
BACnet Comm DVDT filter
VS011541D-0_ _OF VSD II with Bypass, 10 hp (7.5 kW), 575 V, NEMA Type 1, N2 and 11 294
BACnet Comm DVDT filter
VS011551D-0_ _OF VSD II with Bypass, 10 hp (7.5 kW), 575 V, NEMA Type 12, N2 and
BACnet Comm DVDT filter
VS011531D-0_ _OF VSD II with Bypass, 10 hp (7.5 kW), 575 V, NEMA Type 3R, N2 and 320
BACnet Comm DVDT filter
VS018541D-0_ _OF VSD II with Bypass, 15 hp (11 kW), 575 V, NEMA Type 1, N2 and 18 294 FS6
BACnet Comm DVDT filter
VS018551D-0_ _OF VSD II with Bypass, 15 hp (11 kW), 575 V, NEMA Type 12, N2 and
BACnet Comm DVDT filter
VS018531D-0_ _OF VSD II with Bypass, 15 hp (11 kW), 575 V, NEMA Type 3R, N2 and 320
BACnet Comm DVDT filter
VS022541D-0_ _OF VSD II with Bypass, 20 hp (15 kW), 575 V, NEMA Type 1, N2 and 22 294
BACnet Comm DVDT filter
VS022551D-0_ _OF VSD II with Bypass, 20 hp (15 kW), 575 V, NEMA Type 12, N2 and
BACnet Comm DVDT filter
VS022531D-0_ _OF VSD II with Bypass, 20 hp (15 kW), 575 V, NEMA Type 3R, N2 and 320
BACnet Comm DVDT filter
VS027541D-0_ _OF VSD II with Bypass, 25 hp (18.5 kW), 575 V, NEMA Type 1, N2 and 27 294
BACnet Comm DVDT filter
VS027551D-0_ _OF VSD II with Bypass, 25 hp (18.5 kW), 575 V, NEMA Type 12, N2 and
BACnet Comm DVDT filter
VS027531D-0_ _OF VSD II with Bypass, 25 hp (18.5 kW), 575 V, NEMA Type 3R, N2 and 320
BACnet Comm DVDT filter
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
14
Table 19: 575V Series II IntelliPass Drives dV/dT Filter—Box Type DX
Code Number Description Current Weight Drive
(A) (lb) Frame
VS034541D-0_ _OF VSD II with Bypass, 30 hp (22 kW), 575 V, NEMA Type 1, N2 and 34 294 FS6
BACnet DVDT filter
VS034551D-0_ _OF VSD II with Bypass, 30 hp (22 kW), 575 V, NEMA Type 12, N2 and
BACnet DVDT filter
VS034531D-0_ _OF VSD II with Bypass, 30 hp (22 kW), 575 V, NEMA Type 3R, N2 and 320
BACnet DVDT filter
VS041541D-0_ _OF VSD II with Bypass, 40 hp (30 kW), 575 V, NEMA Type 1, N2 and 41 861 FS7
BACnet DVDT filter
VS041551D-0_ _OF VSD II with Bypass, 40 hp (30 kW), 575 V, NEMA Type 12, N2 and
BACnet DVDT filter
VS041531D-0_ _OF VSD II with Bypass, 40 hp (30 kW), 575 V, NEMA Type 3R, N2 and 893
BACnet DVDT filter
VS052541D-0_ _OF VSD II with Bypass, 50 hp (37 kW), 575 V, NEMA Type 1, N2 and 52 861
BACnet DVDT filter
VS052551D-0_ _OF VSD II with Bypass, 50 hp (37 kW), 575 V, NEMA Type 12, N2 and
BACnet DVDT filter
VS052531D-0_ _OF VSD II with Bypass, 50 hp (37 kW), 575 V, NEMA Type 3R, N2 and 893
BACnet DVDT filter
VS062541D-0_ _OF VSD II with Bypass, 60 hp (45 kW), 575 V, NEMA Type 1, N2 and 62 861
BACnet DVDT filter
VS062551D-0_ _OF VSD II with Bypass, 60 hp (45 kW), 575 V, NEMA Type 12, N2 and
BACnet DVDT filter
VS062531D-0_ _OF VSD II with Bypass, 60 hp (45 kW), 575 V, NEMA Type 3R, N2 and 893
BACnet DVDT filter
VS080541D-0_ _OF VSD II with Bypass, 75 hp (55 kW), 575 V, NEMA Type 1, N2 and 80 861 FS8
BACnet DVDT filter
VS080551D-0_ _OF VSD II with Bypass, 75 hp (55 kW), 575 V, NEMA Type 12, N2 and
BACnet DVDT filter
VS080531D-0_ _OF VSD II with Bypass, 75 hp (55 kW), 575 V, NEMA Type 3R, N2 and 893
BACnet DVDT filter
VS100541D-0_ _OF VSD II with Bypass, 100 hp (75 kW), 575 V, NEMA Type 1, N2 and 100 861
BACnet DVDT filter
VS100551D-0_ _OF VSD II with Bypass, 100 hp (75 kW), 575 V, NEMA Type 12, N2 and
BACnet DVDT filter
VS100531D-0_ _OF VSD II with Bypass, 100 hp (75 kW), 575 V, NEMA Type 3R, N2 and 893
BACnet DVDT filter
VS125541D-0_ _OF VSD II with Bypass, 125 hp (90 kW), 575 V, NEMA Type 1, N2 and 125 861
BACnet DVDT filter
VS125551D-0_ _OF VSD II with Bypass, 125 hp (90 kW), 575 V, NEMA Type 12, N2 and
BACnet DVDT filter
VS125531D-0_ _OF VSD II with Bypass, 5 hp (90 kW), 575 V, NEMA Type 3R, N2 and 893
BACnet DVDT filter
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
15
Table 19: 575V Series II IntelliPass Drives dV/dT Filter—Box Type DX
Code Number Description Current Weight Drive
(A) (lb) Frame
VS150541D-0_ _OF VSD II with Bypass, 150 hp (110 kW), 575 V, NEMA Type 1, N2 and 144 861 FS9
BACnet DVDT filter
VS150551D-0_ _OF VSD II with Bypass, 150 hp (110 kW), 575 V, NEMA Type 12, N2 and
BACnet DVDT filter
VS150531D-0_ _OF VSD II with Bypass, 150 hp (110 kW), 575 V, NEMA Type 3R, N2 893
and BACnet DVDT filter
VS200541D-0_ _OF VSD II with Bypass, 200 hp (150 kW), 575 V, NEMA Type 1, N2 and 208 861
BACnet DVDT filter
VS200551D-0_ _OF VSD II with Bypass, 200 hp (150 kW), 575 V, NEMA Type 12, N2 and
BACnet DVDT filter
VS200531D-0_ _OF VSD II with Bypass, 200 hp (150 kW), 575 V, NEMA Type 3R, N2 893
and BACnet DVDT filter
VSD 575V Series II Accessories and Replacement Parts
Table 20: Conversion Kits
Code Number Description
VS-FS5-N12KIT Frame 5, Type 1 to Type 12 Conversion Kit—Type 12/IP54 Cover with Gasket and Plastic Plugs
VS-FS6-N12KIT Frame 6, Type 1 to Type 12 Conversion Kit—Type 12/IP54 Cover with Gasket and Plastic Plugs
Table 21: Keypads and Cables
Code Number Description
VS-KEYPAD-SER2 VSD Series II Graphic Hands-Off/Auto Keypad
VS-RMT-KEYPAD2 VSD Series II Remote Keypad Kit
VS-REM-USB-LOAD Remote Download USB to RJ-485 Cable with Software Driver Disk
Table 22: Flange Kits
Code Number Description
VS-FS5-N12FLKIT Frame 5, Type 12/IP54 Flange Kit
VS-FS6-N12FLKIT Frame 6, Type 12/IP54 Flange Kit
VS-FS7-N12FLKIT Frame 7, Type 12/IP54 Flange Kit
Table 23: Communication and I/O Option Cards
Code Number Description
VS-XMX-B1 I/O Expander Card, 6 DI/DO, Slot D/E
VS-XMX-B2 I/O Expander Card, 2 RO and Thermistor, Slot D/E
VS-XMX-B4 I/O Expander Card, 1 AI, 2 AO (Isolated), Slot D/E
VS-XMX-B5 I/O Expander Card, 3 RO, Slot D/E
VS-XMX-B9 I/O Expander Card, 1 RO, 5 DI (42 to 240 VAC), Slot D/E
VS-XMX-BF I/O Expander Card, 1 AO, 1 DO, 1 RO, Slot D/E
VS-XMX-C4 LONWORKS® Communications Card, Slot D/E
VS-XMX-CS SA Bus Communications Card
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
16
Table 23: Communication and I/O Option Cards
Code Number Description
VS-XMX-F1 I/O Expander Card, 3 RO, Slot B
VS-XMX-F2 I/O Expander Card, 2 RO and Thermistor Input, Slot B
Table 24: Replacement Cooling Fans
Code Number Description
VS-FS5-FAN Frame 5, Main Fan
VS-FS6-FAN Frame 6, Main Fan
VS-FS7-FAN Frame 7, Main Fan
VS-FS8-FAN Frame 8, Main Fan
VS-FS9-FAN Frame 9, Main Fan
VS-FS5-INT-FAN Frame 5, Internal Fan
VS-FS6-INT-FAN Frame 6, Internal Fan
VS-FS7-INT-FAN Frame 7, Internal Fan
VS-FS8-INT-FAN Frame 8, Internal Fan
VS-FS9-INT-FAN Frame 9, Internal Fan
Power Rating for Open Drives
Table 25: Base Drive Ratings with Input Current and Temperature De-Rating
Frame Drive Rating 600V 60Hz Drives De-Rated Low Overload Catalog Number
Size Low Overload Full Horsepower Input Full Load Amps
Load Amps 104°F (40°C) Amps 122°F (50°C)
FR5 3.9 3 4.6 3.3 VS3D95_0B-00000
6.1 5 6.8 5.2 VS6D15_0B-00000
9 7.5 9 7.7 VS9D05_0B-00000
11 10 10.5 9.4 VS0115_0B-00000
FR6 18 15 19.9 15.3 VS0185_0B-00000
22 20 23.3 18.7 VS0225_0B-00000
27 25 27.2 23 VS0275_0B-00000
34 30 32.8 28.9 VS0345_0B-00000
FR7 41 40 45.3 34.9 VS0415_0B-00000
52 50 53.8 44.2 VS0525_0B-00000
62 60 62.2 52.7 VS0625_0B-00000
FR8 80 75 90 68 VS0805_0B-00000
100 100 106 85 VS1005_0B-00000
125 125 127 106.3 VS1255_0B-00000
FR9 144 150 156 122.4 VS1445_0B-00000
208 200 212 176.8 VS2085_0B-00000
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
17
VSD Series II Dimensions
Table 26: 575V Series II Open Frames 5-9 Approximate Dimensions and Weight
HP Range Frame Size Height, in. (mm) Width, in. (mm) Depth, in. (mm) Weight, lb
3 to 10 FS5 16.5 (419.0) 5.67 (144) 8.73 (221.6) 10
15 to 30 FS6 21.93 (557.0) 7.68 (195.0) 9.29 (236.0) 20
40 to 60 FS7 25.98 (660.0) 9.06 (230.0) 10.40 (266.5) 38
75 to 125 FS8 38.02 (965.6) 11.26 (268.1) 12.02 (305.4) 70
150 to 200 FS9 45.28 (1150.0) 18.9 (480.0) 12.52 (318.0) 108
Table 27: 575V Series II Enclosed Box Size by HP and Configuration
HP Fused Electronic Mechanical Fused Electronic Mechanical
Disconnect Bypass Bypass Disconnect & Bypass & Bypass & DVDT
DVDT DVDT
3
5 AX
7.5
10
15
20 BX
25
30 CX
40
50
60
75
100
125 DX
150
200
Table 28: 575V Series II Enclosed Approximate Dimensions, in. (mm)
NEMA 1/12 NEMA 3R
Box H W D H
AX 26 (661.4) 21 (534.2) 19 (483.4) +8 (203.5)
BX 37 (941.3)
CX 49 (1246.6) 31 (788.6)
DX 82 (2086.1) 24 (610.6)
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
18
Wiring for Open Drives
Figure 2: I/O and Main Connections
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
19
Table 29: Technical Specifications
Description Specification
Input Voltage 525 to 600 V, -10 to +10%
Input Frequency 50 to 60 Hz, -5 to +10%
Connection to Mains Once per minute or less
Continuous Output Current Ambient temperature max. 40°C, up to 50°C with derating, overload 1.1 x IL
Output Frequency 0 to 320 Hz
Frequency Resolution 0.01 Hz
Switching Frequency FS5 to FS9: 1.5-6 kHz, Default: 2 kHz automatic switching frequency derating in
case of overload
Frequency Reference Analog Input Resolution 0.1% (10-bit), accuracy +1%
Acceleration/Deceleration Time 0.1 to 3000 s
Ambient Operating Temperature IL: -10°C (no frost) to 40°C, up to 50°C with derating
Storage Temperature -40° to 70°C
Relative Humidity 0 to 95% RH, non-condensing, non-corrosive
Altitude 100% load capacity (no derating) up to 1000m, 1% derating for each 100 m
above 1000 m. Max. 2000 m (TN and IT systems, no corner grounding)
EMC Immunity (As Default Settings) Fulfills EN61800-3 (2004), first and second environment
Analog Input Voltage 0 to 10 V, R = 200 k ohms Differential Resolution 0.1%; Accuracy ±1%, Dip
Switch Selection (voltage/current)
Analog Input Current 0 (4) to 20 mA; Ri - 250 ohms Differential
Digital Inputs Positive or negative logic; 18 to 30 VDC
Auxiliary Voltage 24 V ±10%, Maximum 250 mA
Output Reference Voltage 10 V +3%, Maximum Load 10 mA
Analog Output 0 to 10 V, 0 (4) to 20 mA; RL max. 500 ohms; resolution 10 bit; accuracy ± 2%,
Dip switch selection (voltage/current)
Relay Outputs 3 Programmable, 2 Form C, 1 Form A relay outputs switching capacity: 24
VDC/8 A, 250 VAC/8 A, 125 VDC/0.4 A
Dip Switch Settings Default AI1: V, AI2: mA, AO: mA, RS-485: Off
Noise Level dB A (Cooling Fan FS5: 65, FS6: 72, FS7: 73, FS8: 73, FS9: 75
Sounds Pressure)
Voltage Trip Limit (High/Low) 600 V drives: 1094 Vdc / 0.8775 x supply voltage (527 V)
Protections Overvoltage, Undervoltage, Earth Fault, Overcurrent, Overtemperature, Motor
Overload, Motor Stall, Motor Underload
Compliance UL Listed File No 508C; cUL Listed
Safety – EN 61800-5-1 (2007)
CE Mark – Johnson Controls declares that this product is in compliance with the
essential requirements and other relevant provisions of EMC Directive and Low
Voltage Directive
IntelliPass and IntelliDisconnect certified to CAN/CSA Std C22.2 No 14
Building Technologies & Solutions
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.
All other marks herein are the marks of their respective owners. © 2017 Johnson Controls.
VSD 575V Series II Variable Speed Open, IntelliPass®, and IntelliDisconnect® Drives Product Bulletin
Published in U.S.A. 20 www.johnsoncontrols.comДокумент виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.