Текст документа

VSC Series III variable speed drives

Installation manual
Effective October 2016
New information
                                                                                                        VSC Variable Speed Drives

Support services
The goal of Johnson Controls is to ensure your greatest possible satisfaction with the
operation of our products. We are dedicated to providing fast, friendly, and accurate
assistance. Whether it’s by phone, fax, or email, you can access support information
listed below.
You should contact your local Johnson Controls Sales Representative for product pricing,
availability, ordering, expediting, and repairs.

Website
Use the Johnson Controls website to find product information.

Website address
www.johnsoncontrols.com –> HVAC Controls –> Variable Speed Drives

Johnson Controls product sales operation
Call the Johnson Controls PSO Team if you need assistance with placing an order, stock
availability or proof of shipment, expediting an existing order, emergency shipments,
product price information, and returns (including warranty returns).
Voice: 1-800-ASK-JNSN [275-5676] (US); 1-800-321-4023 (CA)
FAX: 1-800-356-1191 (US); 1-800-321-4024 (CA)
Support Hours of Operation: Monday–Friday, 6:30 a.m.–5:30 p.m. CST
                               (No evening or weekend Customer Service hours).
If you are in the U.S. or Canada, you can take advantage of our toll-free line for technical
assistance. Technical support engineers are available for calls during regular business hours.
Johnson Controls Field Support Center1-888-281-3792 Monday–Friday, 7:30 a.m.–5:30 p.m.
CSTemail: CGFieldSupportCenter@jci.com

For emergency assistance, contact:
johnsoncontrols technical resource center
Voice: 877-ETN-CARE (386-2273) (8:00 a.m.–5:00 p.m. EST)
FAX: 828-651-0549
email: TRC@johnsoncontrols.com

                                            VSC Variable Speed Drives   LIT-12012386—October 2016   www.johnsoncontrols.com     i
VSC Variable Speed Drives

Table of contents
SAFETY
      Before commencing the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                      iv
      Definitions and symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                v
      Hazardous high voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               v
      Warnings and cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                v

ABOUT THIS MANUAL
      Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         1
      List of revisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        1
      Mains supply voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              2
      Units of measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               2

VSC DEVICE SERIES
      Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       3
      System overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            4
      Checking the delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              5
      Rated operational data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             6
      Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       16
      Voltage categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          18
      Selection criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        20
      Output reduction (derating) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               21
      Proper use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      23
      Maintenance and inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  24
      Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     25
      Charging the internal DC link capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                      25

ENGINEERING
      Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      26
      Electrical power network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              28
      Cable cross-sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            29
      Safety and switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            30
      Mains chokes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          31
      Radio interference suppression filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                   31
      Braking resistances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           32
      Motor chokes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          34
      Sine filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   34
      Switching to the output side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                35
      Three-phase motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              37

INSTALLATION
      Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      40
      Mounting position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           40
      Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      40
      IP66 / NEMA4X degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                        45
      EMC installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        46
      Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         52
      Block diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          70
      Insulation testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        81
      Protection against electric shock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                 81

ii                 VSC Variable Speed Drives            LIT-12012386—October 2016            www.johnsoncontrols.com
                                                                                                                                     VSC Variable Speed Drives

Table of contents, continued
OPERATIONAL
    Checklist for commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                   82
    Operational hazard warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                   83
    Commissioning with control signal terminals (default settings) . . . . . . . . . . . . .                                    84
    Commissioning with local controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                       86
    Handling the keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               87
    Help leaflets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       91

CONTROL SIGNAL TERMINALS
    Correspondence between inputs/outputs and terminals . . . . . . . . . . . . . . . . . .                                     94
    Configuration of the control signal terminals . . . . . . . . . . . . . . . . . . . . . . . . . . .                         97

MESSAGES
    List of messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           111

ERROR MESSAGES
    Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       114
    Fault history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      114
    Fault list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   115
    Fault diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          117

TECHNICAL DATA
    General rating data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          118
    Specific rated operational data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                122
    Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         129
    Cable cross-sections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             132
    Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    134

ACCESSORIES
    Device-specific accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                135
    General accessories (list) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             143

PARAMETERS
    “Monitor” parameter group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  144
    “Extended” parameter group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                     150
    “Advanced” parameter group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                     157

                                                           VSC Variable Speed Drives            LIT-12012386—October 2016       www.johnsoncontrols.com     iii
VSC Variable Speed Drives

Safety
             Warning!
             Dangerous electrical voltage!

Before commencing the installation                                           ●   Measures should be taken to ensure the proper restart of
                                                                                 programs interrupted after a voltage dip or failure. This
●    Disconnect the power supply of the device.
                                                                                 should not cause dangerous operating states even for a
●    Ensure that devices cannot be accidentally retriggered.                     short time. If necessary, emergency switching off devices
                                                                                 should be implemented.
●    Verify isolation from the supply.
                                                                             ●   Wherever faults in the automation system may cause
●    Ground and short-circuit.                                                   damage to persons or property, external measures must
●    Cover or enclose neighbouring units that are live.                          be implemented to ensure a safe operating state in the
                                                                                 event of a fault or malfunction (for example, by means of
●    Follow the engineering instructions (IL) of the device                      separate limit switches, mechanical interlocks, etc.).
     concerned.
                                                                             ●   During operation, and depending on their degree of
●    Only suitably qualified personnel in accordance with                        protection, variable speed drives may have live,
     EN 50110-1/-2 (VDE 0105 Part 100) may work on this                          uninsulated, moving, and/or rotating parts, as well as hot
     device/system.                                                              surfaces.
●    Before installation and before touching the device ensure               ●   The impermissible removal of the required cover, improper
     that you are free of electrostatic charge.                                  installation or incorrect operation of the motor or variable
                                                                                 speed drive can cause the failure of the device and serious
●    The functional earth (FE) must be connected to the
                                                                                 injury and/or material damage.
     protective earth (PE) or to the potential equalizing.
     The system installer is responsible for implementing this               ●   Comply with all applicable national accident prevention
     connection.                                                                 regulations (i.e., BGV A3) when working with energized
                                                                                 variable speed drives.
●    Connecting cables and signal lines should be installed so
     that inductive or capacitive interference do not impair the             ●   The electrical installation must be carried out in
     automation functions.                                                       accordance with the relevant regulations (i.e., with regard
                                                                                 to cable cross sections, fuses, PE).
●    Install automation devices and related operating elements
     in such a way that they are well protected against                      ●   All transport, installation, commissioning and maintenance
     unintentional operation.                                                    work must only be carried out by trained personnel
                                                                                 (observe IEC 60364, HD 384 or DIN VDE 0100 and national
●    Suitable safety hardware and software measures should
                                                                                 accident prevention regulations).
     be implemented for the I/O connection so that a cable or
     wire breakage on the signal side does not result in                     ●   If applicable, systems in which variable speed drives are
     undefined states in the automation device.                                  installed must be equipped with additional monitoring and
                                                                                 protective devices in accordance with the applicable safety
●    Ensure a reliable electrical isolation of the low voltage
                                                                                 regulations, i.e., the German Equipment and Product
     for the 24 V supply. Only use power supply units
                                                                                 Safety Act, accident prevention regulations, etc. Making
     complying with IEC 60364-4-41 or HD 384.4.41 S2
                                                                                 changes to the variable speed drives by using the
     (VDE 0100 part 410).
                                                                                 operating software is allowed.
●    Deviations of the mains voltage from the nominal value                  ●   Keep all covers and doors closed during operation.
     must not exceed the tolerance limits given in the technical
     data, otherwise this may cause malfunction and                          ●   When designing the machine, the user must incorporate
     dangerous operation.                                                        mechanisms and measures that limit the consequences of
                                                                                 a drive controller malfunction or failure (an increase in
●    Emergency-Stop devices complying with IEC/EN 60204-1
                                                                                 motor speed or the motor’s sudden stop) so as to prevent
     must be effective in all operating modes of the automation
                                                                                 hazards to people and property, i.e.:
     devices. Unlatching the emergency switching off devices
     must not cause restart.                                                     ●   Additional stand-alone devices for monitoring
                                                                                     parameters that are relevant to safety (speed, travel,
●    Built-in devices for enclosures or cabinets must only be
                                                                                     end positions, etc.)
     run and operated in an installed state, desk-top devices or
     portable devices only when the housing is closed.                           ●   Electrical and non-electrical safety devices (interlocks or
                                                                                     mechanical locks) for mechanisms that protect the
                                                                                     entire system

iv                  VSC Variable Speed Drives   LIT-12012386—October 2016   www.johnsoncontrols.com
                                                                                                          VSC Variable Speed Drives

  ●   Due to the possibility of there being capacitors that are       Hazardous high voltage
      still holding a charge, do not touch live device parts or
      terminals immediately after disconnecting the variable                                          WARNING
      speed drives from the supply voltage. Heed the
      corresponding labels on the variable speed drives               Motor control equipment and electronic controllers are
                                                                      connected to hazardous line voltages. When servicing
Read this manual thoroughly and make sure you understand              drives and electronic controllers, there may be exposed
the procedures before you attempt to install, set up, operate         components with housings or protrusions at or above
or carry out any maintenance work on this VSC Adjustable              line potential. Extreme care should be taken to protect
Speed Drive.                                                          against shock.

Definitions and symbols                                               ●   Stand on an insulating pad and make it a habit to use
                                                                          only one hand when checking components.
                           WARNING                                    ●   Always work with another person in case an
                                                                          emergency occurs.
This symbol indicates high voltage. It calls your attention
to items or operations that could be dangerous to you                 ●   Disconnect power before checking controllers or
and other persons operating this equipment. Read the                      performing maintenance.
message and follow the instructions carefully.
                                                                      ●   Be sure equipment is properly earthed.
                                                                      ●   Wear safety glasses whenever working on electronic
                                                                          controllers or rotating machinery.
This symbol is the “Safety Alert Symbol.” It occurs with
either of two signal words: CAUTION or WARNING, as
described below.
                                                                                                      WARNING
                                                                      The components in the drive’s power section remain
                           WARNING                                    energized after the supply voltage has been switched off.
                                                                      After disconnecting the supply, wait at least five minutes
Indicates a potentially hazardous situation which, if not             before removing the cover to allow the intermediate
avoided, can result in serious injury or death.                       circuit capacitors to discharge.
                                                                      Pay attention to hazard warnings!
                            CAUTION
Indicates a potentially hazardous situation which, if not
avoided, can result in minor to moderate injury, or serious
damage to the product. The situation described in the                 DANGER
CAUTION may, if not avoided, lead to serious results.                 5 MIN
Important safety measures are described in CAUTION (as
well as WARNING).
                                                                                                      WARNING
                                                                      Electric shock hazard—risk of injuries! Carry out wiring
                                                                      work only if the unit is de-energized.

                                                                                                      WARNING
                                                                      Do not perform any modifications on the AC drive when
                                                                      it is connected to mains.

                                                                      Warnings and cautions
                                                                      This manual contains clearly marked cautions and warnings
                                                                      which are intended for your personal safety and to avoid any
                                                                      unintentional damage to the product or connected
                                                                      appliances.
                                                                      Please read the information included in cautions and
                                                                      warnings carefully.

                                              VSC Variable Speed Drives   LIT-12012386—October 2016   www.johnsoncontrols.com     v
VSC Variable Speed Drives

vi           VSC Variable Speed Drives   LIT-12012386—October 2016   www.johnsoncontrols.com
                                                                                                                          About this manual

About this manual
This manual (LIT-12012386) is used in the installation and
programming of the Series III VSC variable speed drives.

Target group
This LIT-12012386 manual is intended for engineers and
electricians. Electrical engineering and physics-related
knowledge and skills will be required in order to be able
to commission the corresponding devices.
We assume that you have a good knowledge of engineering
basics and that you are familiar with handling electrical
systems and machines, as well as with reading technical
drawings.

List of revisions
The following significant amendments have been introduced
since previous issues:

Publication date          Page        Keyword                                 New           Modified       Deleted
10/16                                 Initial issue

Writing conventions                                                      Tips
Symbols with the following meaning are used in this manual:              Note: Indicates useful tips.
●   Indicates instructions to be followed.                               In order to make it easier to understand some of the figures
                                                                         included in this manual, the variable speed drive housing, as
Hazard warnings of material damages                                      well as other safety-relevant parts, has been left out.
                                                                         However, it is important to note that the variable speed drive
                                                                         must always be operated with its housing in its proper place,
                            Notice                                       as well as with all required safety-relevant parts.
Warns about the possibility of material damage.                          All the specifications in this manual refer to the hardware and
                                                                         software versions documented in it.
Hazard warnings of personal injury
                                                                         Documents with additional information
                             CAUTION                                     Note: More information on the devices described here can
Warns of the possibility of hazardous situations that may                      be found on the Internet under:
possibly cause slight injury.
                                                                         www.johnsoncontrols.com

                            WARNING
Warns of the possibility of hazardous situations that
could result in serious injury or even death.

                            DANGER
Warns of hazardous situations that result in serious
injury or death.

                                                 VSC Variable Speed Drives   LIT-12012386—October 2016   www.johnsoncontrols.com          1
About this manual

Abbreviations                                                                       Mains supply voltages
The following abbreviations are used in this manual:                                The rated operating voltages stated in the following table are
                                                                                    based on the standard values for networks with a grounded
Abbreviation       Description                                                      star point.
dec                Decimal (base-10 numeral system)                                 In ring networks (as found in Europe) the rated operating
DS                 Default settings                                                 voltage at the transfer point of the power supply companies
EMC                Electromagnetic compatibility                                    is the same as the value in the consumer networks (i.e.,
                                                                                    230 V, 400 V).
FE                 Functional earth
                                                                                    In star networks (as found in North America), the rated
FS                 Frame Size                                                       operating voltage at the transfer point of the utility
FWD                Forward run (clockwise rotating field)                           companies is higher than in the consumer network.
GND                Ground (0-V-potential)                                           Example: 120 V R 115 V, 240 V R 230 V, 480 V R 460 V.

hex                Hexadecimal (base-16 numeral system)                             The VSC variable speed drive’s wide tolerance range takes
                                                                                    into account a permissible voltage drop of 10% (i.e.
ID                 Identifier (unique ID)                                           ULN –10%) while, in the 400-V category, it takes into
IGBT               Insulated gate bipolar transistor                                account the North American mains voltage of 480 V +10 %
LED                Light Emitting Diode (LED)                                       (60 Hz).

OLED               Organic Light Emitting Diode                                     The rated mains voltage operational data is always based on
                                                                                    mains frequencies of 50/60 Hz within a range of 48 to 62 Hz.
PC                 Personal Computer
PDS                Power Drive System                                               The permissible power supply for the VSC series can be
                                                                                    found in “Features” on Page 9.
PE                 Protective earth
PES                EMC connection to PE for screened lines
PNU                Parameter number
REV                Reverse run (counterclockwise rotation field active)
ro                 Read Only (read access only)
rw                 Read/Write (read/write access)
SCCR               Short Circuit Current Rating
UL                 Underwriters Laboratories

Units of measurement
Every physical dimension included in this manual uses
international metric system units, otherwise known as SI
(Système International d’Unités) units. For the purpose of the
equipment’s UL certification, some of these dimensions are
accompanied by their equivalents in imperial units.

Table 1. Unit conversion examples
                            US-American                   US-American
Designation                 designation                   value                    SI value                  Conversion value
Length                      inch                          1 in (")                 25.4 mm                   0.0394
Performance                 horsepower                    1 hp = 1.014 PS          0.7457 kW                 1.341
Torque                      pound-force inches            1 lbf in                 0.113 Nm                  8.851
Temperature                 Fahrenheit                    1 °F (TF)                –17.222 °C (TC)           TF = TC × 9/5 + 32
Rotational speed            Revolutions per minute        1 rpm                    1 min-1                   1
Weight                      pound                         1 lb                     0.4536 kg                 2.205
Flow rate                   cubic feed per minute         1 cfm                    1.698 m3/min              0.5889

2                    VSC Variable Speed Drives         LIT-12012386—October 2016   www.johnsoncontrols.com
                                                                                                                                                VSC device series

VSC device series

Introduction                                                                                  For distributed local installations, there are three sizes
                                                                                              covering a performance range of 0.37 (for 230 V) to 7.5 kW
Due to their ease of use and high reliability, VSC Series III                                 (for 400 V) and featuring a degree of protection of IP66.
variable speed drives are ideal for general applications                                      These models come in two versions: with and without local
involving three-phase motors. In addition, an integrated radio                                controls. These local controls include a setpoint
interference suppression filter and a flexible interface ensure                               potentiometer, a selector switch for switching operating
that the inverters meet a number of important needs in the                                    directions, and a lockable main switch on the mains side.
machine building industry when it comes to the optimization
of production and manufacturing processes.                                                    The computer-based drivesConnect parameter configuration
                                                                                              program ensures data integrity and reduces the time
For installations in control panels, devices with a                                           required for commissioning and maintenance.
performance range of 0.37 (for 230 V) to 22 kW (for 400 V)
are available in a compact and sturdy design featuring three                                  In addition, the comprehensive accessories available
available sizes (FS1, FS2, FS3, FS4) and a degree of                                          increase the inverters’ flexibility in all scopes of application.
protection of IP20.

                                                                                                   REV     0
                                                                                                               FWD

                                                                                                   PWR   OFF

                                                                                                                     ON

     DC- L1/L
                             L2/N L3

     1   2   3   4   5   6   7   8   9 10 11

   DC+ BR
                             U       V     W

IP20 degree                                    IP66 degree of protection                      IP66 degree of protection,
of protection                                                                                 with local controls

Figure 1. Designs and enclosure versions

                                                                      VSC Variable Speed Drives   LIT-12012386—October 2016   www.johnsoncontrols.com             3
VSC device series

System overview

                                                           1   2     3   4   5 6   7   8   9 10 11

                                                               ffj                 U       V    W

                       Ready

               I       A
                   O

Figure 2. System overview (example: size FS1, degree of protection IP20)
1 VSC… variable speed drives
2 Extern radio interference suppression filter DX-EMC…
3 DX-LN… mains choke, DX-LM3-… motor choke, DX-SIN3-… sine filter
4 DX-BR… braking resistance
5 DXC-EXT-… expansion module
6 DX-NET-ETHERNET2-2 EtherNet/IP interface
7 DX-COM-STICK2 communication module and accessories
    (i.e., DX-CBL-… connection cable)
8 DE-KEY-… keypad (external)

4                              VSC Variable Speed Drives   LIT-12012386—October 2016                 www.johnsoncontrols.com
                                                                                                                        VSC device series

Checking the delivery                                                 Open the packaging with adequate tools and inspect the
                                                                      contents immediately after receipt in order to ensure that
Note: Before opening the package, please check the                    they are complete and undamaged.
      nameplate on it to make sure that you received the
      correct variable speed drive.                                   The packaging must contain the following parts:
                                                                      ●   VSC series variable speed drive
The VSC series variable speed drives are carefully packaged
and prepared for delivery. The devices should be shipped              ●   an instructional leaflet
only in their original packaging with suitable transportation
materials. Please take note of the labels and instructions on
the packaging, as well as of those meant for the unpacked
device.

                              L1/L L2/N
                                         L3

   1   2   3   4   5   6   7    8   9 10 11

                          U        V     W

Figure 3. Equipment supplied (example: devices with IP20 / IP66 degree of protection with instruction leaflet)

                                              VSC Variable Speed Drives   LIT-12012386—October 2016   www.johnsoncontrols.com           5
VSC device series

Rated operational data

Rated operational data on the nameplate
The device-specific rated operational data of the VSC variable
speed drive is listed on the nameplate of the device.

2
                                   L1/L L2/N
                                              L3

                                                              1                                                             1

        1   2   3   4   5   6   7    8   9 10 11

                               U        V     W

Figure 4. Nameplate location
The nameplate on top (nameplate 2) is a simplified version
that can be used to clearly identify the device if the main
nameplate (nameplate 1) is blocked by other devices.

6                                         VSC Variable Speed Drives   LIT-12012386—October 2016   www.johnsoncontrols.com
                                                                                                                                    VSC device series

Nameplate inscription
The inscription of the nameplate has the following
meaning (example):

Table 2. Nameplate inscription
Inscription              Meaning
VSC344D1FBA20C           Part no.:
                         VSC = VSC series variable speed drive
                         3 = Three-phase mains connection / three-phase motor connection
                         4 = 400 V mains voltage category
                         4D1 = 4.1 A rated operational current (4-decimal-1, output current)
                         F = Integrated radio interference suppression filter
                         B = Integrated brake chopper
                         A = LED display (7-segment text display)
                         20 = IP20 degree of protection
                         C = Coated boards
Input                    Rated operational data of mains connection
                         Three-phase AC voltage (Ue 3~ AC),
                         380–480 V voltage, 50/60 Hz frequency, input phase current (5.6 A).
Output                   Load side (motor) rated operational data:
                         Three-phase AC voltage (0–Ue), output phase current (4.1 A), output frequency
                         (0–500 Hz)
                         Assigned motor output:
                         1.5 kW with a voltage of 400 V/2 hp with a voltage of 460 V for a four-pole, internally cooled
                         or surface-cooled three-phase asynchronous motor (1500 rpm at 50 Hz / 1800 rpm at 60 Hz)
Serial No.:              Serial number
IP20                     Degree of protection of the housing: IP 20, UL (cUL) Open Type
Software                 Software version (2.0)
25072016                 Manufacturing date: 07-25-2016
Max amb. 50 °C           Maximum permissible ambient air temperature (50 °C)

                 Variable speed drive is an electrical apparatus.
a                Read the manual (in this case LIT-12012386) before making any electrical
                 connections and commissioning.

                                                   VSC Variable Speed Drives      LIT-12012386—October 2016       www.johnsoncontrols.com           7
VSC device series

Catalog number selection
The catalog no. or part no. for the VSC series of variable
speed drives is made up of four sections.
Series — Power section — Model — Version
The following figure shows it in greater detail:

                                                      VSC 1 2 4D1 F N A 20 C
          Device series                                                                                                                          Type
    VSC = Series III variable                                                                                                         C = Additional PCB
          speed drive, compact                                                                                                            protection (coated
                                                                                                                                          board)

              Connection in power section
          1 = Single-phase mains connection /                                                                                    Degree of protection
              three-phase motor connection                                                                                     20 = IP20 / NEMA 0
          3 = Three-phase mains connection /                                                                                   66 = IP66 / NEMA 4X
              three-phase motor connection                                                                                     6S = IP66 with switch /
          S = Single-phase mains connection /                                                                                       NEMA 4X, switched
              single-phase motor connection

                                                                                                                            Display unit (display)
                     Mains voltage category                                                                                A = LED display
          1 = 115 V (110 - 115 V ±10 %)
          2 = 230 V (200 - 240 V ±10 %)
          4 = 400 V (380 - 480 V ±10 %)
          D = 115 V input / 230 V output (voltage doubler)                                                                 Brake chopper
                                                                                                                      N = No internal brake
                                                                                                                          chopper
                                                                                                                      B = Brake chopper
                                                          Rated operational current        EMC (radio interference
                                                                  (examples)                  suppression filter)
                                                         2D2 = 2.2 A                     N = No internal RFI filter
                                                         4D1 = 4.1 A                     F = Internal RFI filter
                                                         046 = 46 A

Figure 5. Catalog number selection

8                    VSC Variable Speed Drives               LIT-12012386—October 2016   www.johnsoncontrols.com
                                                                                                                                 VSC device series

Features

VSC1D… device series
Mains voltage: 1 AC 110–115 V (±10 %), 50/60 Hz
Output voltage: 3 AC 230 V, 50/60 Hz
Note: An internal voltage doubler will increase the mains
      supply voltage to 230 V (output voltage).

Table 3. VSC1D… features
                           Rated
                           operational     Assigned instance
                           current         motor power
                                                                                                    Radio
                                           P1               P2               Display                interference
                           Ie              (230 V, 50 Hz)   (230 V, 60 Hz)   (operating Local       suppression       Degree of            Brake
Part no.                   A               kW               hp               unit)      controls    filter            protection    Size   chopper
VSC1D2D3NNA20C             2.3             0.37             1/2              LED          —         —                 IP20          FS1    —
VSC1D2D3NNA66C             2.3             0.37             1/2              LED          —         —                 IP66_x        FS1    —
VSC1D2D3NNA6SC             2.3             0.37             1/2              LED          ✔         —                 IP66_x        FS1    —
VSC1D4D3NNA20C             4.3             0.75             1                LED          —         —                 IP20          FS1    —
VSC1D4D3NNA66C             4.3             0.75             1                LED          —         —                 IP66_x        FS1    —
VSC1D4D3NNA6SC             4.3             0.75             1                LED          ✔         —                 IP66_x        FS1    —
VSC1D5D8NNA20C             5.8             1.1              1-1/2            LED          —         —                 IP20          FS2    ✔
VSC1D5D8NNA66C             5.8             1.1              1-1/2            LED          —         —                 IP66_x        FS2    ✔
VSC1D5D8NNA6SC             5.8             1.1              1-1/2            LED          ✔         —                 IP66_x        FS2    ✔
Notes
1 As per IEC standards.
2 As per UL 61800-5-1, Table DVE.1, March 6, 2015.

                                                     VSC Variable Speed Drives     LIT-12012386—October 2016   www.johnsoncontrols.com               9
VSC device series

VSC12… device series
Mains voltage: 1 AC 220–240 V (±10 %), 50/60 Hz
Output voltage: 3 AC 220–240 V, 50/60 Hz
Table 4. VSC12… features
                            Rated
                            operational     Assigned instance
                            current         motor power
                                                                                                          Radio
                                            P1                P2               Display                    interference
                            Ie              (230 V, 50 Hz)    (230 V, 60 Hz)   (operating Local           suppression    Degree of           Brake
Part no.                    A               kW                hp               unit)      controls        filter         protection   Size   chopper
VSC122D3NNA20C              2.3             0.37              1/2              LED          —             —              IP20         FS1    —
VSC122D3FNA20C              2.3             0.37              1/2              LED          —             ✔              IP20         FS1    —
VSC122D3NNA66C              2.3 3           0.37              1/2              LED          —             —              IP66_x       FS1    —
VSC122D3FNA66C              2.3 3           0.37              1/2              LED          —             ✔              IP66_x       FS1    —
VSC122D3NNA6SC              2.3 3           0.37              1/2              LED          ✔             –              IP66_x       FS1    —
VSC122D3FNA6SC              2.3 3           0.37              1/2              LED          ✔             ✔              IP66_x       FS1    —
VSC124D3NNA20C              4.3             0.75              1                LED          —             —              IP20         FS1    —
VSC124D3FNA20C              4.3             0.75              1                LED          —             ✔              IP20         FS1    —
VSC124D3NNA66C              4.3 3           0.75              1                LED          —             —              IP66_x       FS1    —
VSC124D3FNA66C              4.3 3           0.75              1                LED          —             ✔              IP66_x       FS1    —
VSC124D3NNA6SC              4.3 3           0.75              1                LED          ✔             —              IP66_x       FS1    —
VSC124D3FNA6SC              4.3 3           0.75              1                LED          ✔             ✔              IP66_x       FS1    —
VSC127D0NNA20C              7               1.5               2                LED          —             —              IP20         FS1    —
VSC127D0FNA20C              7               1.5               2                LED          —             ✔              IP20         FS1    —
VSC127D0NBA20C              7               1.5               2                LED          —             —              IP20         FS2    ✔
VSC127D0FBA20C              7               1.5               2                LED          —             ✔              IP20         FS2    ✔
VSC127D0NNA66C              73              1.5               2                LED          —             —              IP66_x       FS1    —
VSC127D0FNA66C              73              1.5               2                LED          —             ✔              IP66_x       FS1    —
VSC127D0NBA66C              73              1.5               2                LED          —             —              IP66_x       FS2    ✔
VSC127D0FBA66C              73              1.5               2                LED          —             ✔              IP66_x       FS2    ✔
VSC127D0NNA6SC              73              1.5               2                LED          ✔             —              IP66_x       FS1    —
VSC127D0FNA6SC              73              1.5               2                LED          ✔             ✔              IP66_x       FS1    —
VSC127D0NBA6SC              73              1.5               2                LED          ✔             —              IP66_x       FS2    ✔
VSC127D0FBA6SC              73              1.5               2                LED          ✔             ✔              IP66_x       FS2    ✔
Notes
1 As per IEC standards.
2 As per UL 61800-5-1, Table DVE.1, March 6, 2015.
3 Rated operational current at switching frequencies of up to 16 kHz and
  ambient temperatures of up to +40 °C.

10                  VSC Variable Speed Drives      LIT-12012386—October 2016    www.johnsoncontrols.com
                                                                                                                                   VSC device series

Table 4. VSC12… features, continued
                            Rated
                            operational     Assigned instance
                            current         motor power
                                                                                                      Radio
                                            P1                P2               Display                interference
                            Ie              (230 V, 50 Hz)    (230 V, 60 Hz)   (operating Local       suppression       Degree of            Brake
Part no.                    A               kW                hp               unit)      controls    filter            protection    Size   chopper
VSC12011NBA20C              10.5 6          2.2               3                LED          —         —                 IP20          FS2    ✔
VSC12011FBA20C              10.5 6          2.2               3                LED          —         ✔                 IP20          FS2    ✔
VSC12011NBA66C              10.5 3          2.2               3                LED          —         —                 IP66_x        FS2    ✔
VSC12011FBA66C              10.5 3          2.2               3                LED          —         ✔                 IP66_x        FS2    ✔
VSC12011NBA6SC              10.5 3          2.2               3                LED          ✔         —                 IP66_x        FS2    ✔
VSC12011FBA6SC              10.5 3          2.2               3                LED          ✔         ✔                 IP66_x        FS2    ✔
VSC12015NBA20C              15.3 5          4                 5                LED          —         —                 IP20          FS3    ✔
VSC12015NBA66C              15.3 5          4                 5                LED          —         —                 IP66_x        FS3    ✔
VSC12015NBA6SC              15.3 5          4                 5                LED          ✔         —                 IP66_x        FS3    ✔
Notes
1 As per IEC standards
2 As per UL 61800-5-1, Table DVE.1, March 6, 2015
3 Rated operational current at switching frequencies of up to 16 kHz and
  ambient temperatures of up to +40 °C
4 Rated operational current at switching frequencies of up to 8 kHz and
  ambient temperatures of up to +50 °C
5 Rated operational current at switching frequencies of up to 8 kHz and
  ambient temperatures of up to +40 °C
6 For UL conformity: Rated operational current at ambient temperatures
  of up to +45 °C over a period of 24 hours

                                                       VSC Variable Speed Drives     LIT-12012386—October 2016   www.johnsoncontrols.com               11
VSC device series

VSC32… device series
Mains voltage: 3 AC 220–240 V (±10 %), 50/60 Hz
Output voltage: 3 AC 220–240 V, 50/60 Hz
Table 5. VSC32… features
                            Rated
                            operational     Assigned instance
                            current         motor power
                                                                                                          Radio
                                            P1                P2               Display                    interference
                            Ie              (230 V, 50 Hz)    (230 V, 60 Hz)   (operating Local           suppression    Degree of           Brake
Part no.                    A               kW                hp               unit)      controls        filter         protection   Size   chopper
VSC322D3NNA20C              2.3             0.37              1/2              LED          —             —              IP20         FS1    —
VSC322D3NNA66C              2.3 3           0.37              1/2              LED          —             —              IP66_x       FS1    —
VSC322D3NNA6SC              2.3 3           0.37              1/2              LED          ✔             —              IP66_x       FS1    —
VSC324D3NNA20C              4.3             0.75              1                LED          —             —              IP20         FS1    —
VSC324D3NNA66C              4.3 3           0.75              1                LED          —             —              IP66_x       FS1    —
VSC324D3NNA6SC              4.3 3           0.75              1                LED          ✔             —              IP66_x       FS1    —
VSC327D0NNA20C              7               1.5               2                LED          —             —              IP20         FS1    —
VSC327D0NBA20C              7               1.5               2                LED          —             —              IP20         FS2    ✔
VSC327D0FBA20C              7               1.5               2                LED          —             ✔              IP20         FS2    ✔
VSC327D0NNA66C              73              1.5               2                LED          —             —              IP66_x       FS1    —
VSC327D0NBA66C              73              1.5               2                LED          —             —              IP66_x       FS2    ✔
VSC327D0FBA66C              73              1.5               2                LED          —             ✔              IP66_x       FS2    ✔
VSC327D0NNA6SC              73              1.5               2                LED          ✔             —              IP66_x       FS1    —
VSC327D0NBA6SC              73              1.5               2                LED          ✔             —              IP66_x       FS2    ✔
VSC327D0FBA6SC              73              1.5               2                LED          ✔             ✔              IP66_x       FS2    ✔
VSC32011NBA20C              10.5 6          2.2               3                LED          —             —              IP20         FS2    ✔
VSC32011FBA20C              10.5 6          2.2               3                LED          —             ✔              IP20         FS2    ✔
VSC32011NBA66C              10.5 6          2.2               3                LED          —             —              IP66_x       FS2    ✔
VSC32011FBA66C              10.5 6          2.2               3                LED          —             ✔              IP66_x       FS2    ✔
VSC32011NBA6SC              10.5 6          2.2               3                LED          ✔             —              IP66_x       FS2    ✔
VSC32011FBA6SC              10.5 6          2.2               3                LED          ✔             ✔              IP66_x       FS2    ✔
VSC32018NBA20C              18              4                 5                LED          —             —              IP20         FS3    ✔
VSC32018FBA20C              18              4                 5                LED          —             ✔              IP20         FS3    ✔
VSC32018NBA66C              18 5            4                 5                LED          —             —              IP66_x       FS3    ✔
VSC32018FBA66C              18 5            4                 5                LED          —             ✔              IP66_x       FS3    ✔
VSC32018NBA6SC              18 5            4                 5                LED          ✔             —              IP66_x       FS3    ✔
VSC32018FBA6SC              18 5            4                 5                LED          ✔             ✔              IP66_x       FS3    ✔
Notes
1 As per IEC standards.
2 As per UL 61800-5-1, Table DVE.1, March 6, 2015.
3 Rated operational current at switching frequencies of up to 16 kHz and
  ambient temperatures of up to +40 °C.
4 Rated operational current at switching frequencies of up to 8 kHz and
  ambient temperatures of up to +50 °C.
5 Rated operational current at switching frequencies of up to 8 kHz and
  ambient temperatures of up to +40 °C.
6 For UL conformity: Rated operational current at ambient temperatures
  of up to +45 °C over a period of 24 hours.

12                  VSC Variable Speed Drives      LIT-12012386—October 2016    www.johnsoncontrols.com
                                                                                                                                   VSC device series

Table 5. VSC32… features, continued
                            Rated
                            operational     Assigned instance
                            current         motor power
                                                                                                      Radio
                                            P1                P2               Display                interference
                            Ie              (230 V, 50 Hz)    (230 V, 60 Hz)   (operating Local       suppression       Degree of            Brake
Part no.                    A               kW                hp               unit)      controls    filter            protection    Size   chopper
VSC32024NBA20C              24              5.5               7-1/2            LED          —         —                 IP20          FS3    ✔
VSC32024FBA20C              24              5.5               7-1/2            LED          —         ✔                 IP20          FS3    ✔
VSC32030NBA20C              30              7.5  