Code No. LIT-1928275
                                                                                                                                                  Issued March 27, 2009

VMA1400 Series
Variable Air Volume Modular Assembly
Description                                                     Features
The Variable Air Volume Modular Assembly                        •  easy-to-handle unit with a compact
(VMA) is a family of configurable digital                          footprint
controllers. Differing models in the VMA1400                    • pre-wired controller with pressure sensor
series combine a controller, pressure sensor                       and actuator for reduced installation time
and/or actuator housed in one pre-assembled                        (VMA1430 uses external actuator,
unit.                                                              VMA1440 has no pressure sensor)
The VMA1400 series is available in four                         • fast response actuator that drives the
models:                                                            damper from full open to full closed (90°) in
                                                                   30 seconds (VMA1410, VMA1420,
•  Cooling Only (VMA1410)                                          VMA1440) for reduced commissioning time
•  Cooling with Reheat and/or Fan                               • continuous loop tuning through
   (VMA1420)                                                       proportional adaptive algorithms using
• External Actuator (VMA1430)                                      patented P-Adaptive and Pattern
• Metasys Zoning Package (VMA1440)                                 Recognition Adaptive Control (PRAC)
The VMA1410, VMA1420, and VMA1440 use                              technologies
an integrated actuator with a stepper motor                     • advanced diagnostics that identify and
drive for quick and accurate damper                                correct system deviations related to flow,
positioning.                                                       damper travel, and energy
The VMA1410, 1420, 1430 are designed for                        • N2 network communications for integrating
pressure-independent, single duct systems.                         VMA as a part of a facility management
The VMA1420 and VMA1430 can also be                                system with an NCM or N30 Series
used with parallel or series fan-powered                           Supervisory Controller                                                                VMA1400
boxes, supply/exhaust applications, and dual                    • simple question/answer software format for
duct systems.                                                      quick, easy configuration of project-specific
                                                                   applications.                                                 Software - The VMA can be configured,
The VMA1440 is used exclusively as part of                                                                                       downloaded, and commissioned with
the Metasys Zoning Package. See the                             The VMA1400 Balancing Tool (VBT) software
                                                                can be used with handheld interfaces (such as                    HVAC PRO software, Release 7.00 or later,
Metasys Zoning Package Product Bulletin                                                                                          which uses a simple Q/A format. Dual duct
(LIT-639050) for details.                                       3Com® PalmPilot™) to easily read and adjust
                                                                parameters (not available for VMA1440). VBT                      applications, and TMZ1600 room sensor and
                                                                software is included in M-Tools or can be                        supply/exhaust applications require
                                                                ordered separately.                                              HVAC PRO Rel. 8.01. The TE-7700 RF
                                                                                                                                 Temperature Sensor Application requires
                                                                                                                                 HVAC PRO Software Release 8.04 or later.

VMA Functionality
               Inputs/Outputs                                                            Points             Rating                                         VMA1400 Model
                                                                                                                                                1410        1420        1430       1440
                       Zone Temperature                                                  AI-1               1 K Ni, Si, Pt, or 2.25 K NTC       9           9           9          9
                       Zone Setpoint                                                     AI-2               1.6 K ohm Potentiometer             9           9           9          9
                       Sideloop (humidity, dew point) (for 1410, 1420, 1430)             AI-3               0-10 VDC                                        9           9          9
Analog Inputs          or Static Pressure (for 1440)
                       Supply Air Temperature or Supplemental Heat                       AI-4               1 K Ni, Si, Pt, or 2.25 K NTC                   9           9          9
                       Temperature
                       Velocity Pressure                                                 Internal           0-374 pa (0-1.5 in. W.C.)           9           9           9
                       Temporary Occupied Button                                         BI-1               Dry contact                         9           9           9          9
                       Occupied or User Configurable (for 1440)                          BI-2               Dry contact                         9           9           9          9
Binary Inputs
                       Off or Window or Shutdown (for 1410, 1420, 1430) or               BI-3               Dry contact                         9           9           9          9
                       User Configurable (for 1440)
                       Proportional Heat or External Damper (for 1440,                   AO-1               0-10 VDC @ 10 mA                                9           9          9
Analog Outputs         AO-2 is Bypass/Subordinate Damper)                                AO-2               0-10 VDC @ 10 mA                                9           9          9
                       Lights, Fan, External Damper, Box Heat - On/Off Valve BO-1 - BO-5                    24 VAC Triac @ 0.5 A each                       9           9          9
                       or 1- 3 stage Electric, Supplemental Heat - On/Off    (BO-1 - BO-4
Binary Outputs         Valve or Single Stage Electric Heat                   for 1440)
                       Stepper Motor with Position Feedback                              Internal           2-phase Stepper (up to            9             9           9          9
                                                                                                            93° rotation at 4 N.m [35 lb.in])

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2009 Johnson Controls, Inc.                  www.johnsoncontrols.com

                                                                                       1 of 2
Variable Air Volume Modular Assembly (Continued)

Selection Chart                                                                                         VMA1400 Series Variable Air Volume Modular Assembly
                                                                                                                            (Part 2 of 2)
Code Number             Description
                                                                                                 Ambient            -40 to 70°C (-40 to 158°F)
AP-VMA1410-0            Integrated VAV Controller/Actuator/Pressure Sensor
                                                                                                 Storage
                        (Cooling only) Single pack
                                                                                                 Conditions
AP-VMA1410-OD AP-VMA1410 Bulk pack (10 maximum/pack)1
                                                                                                 Terminations 6.3 mm (1/4 inch) spade lugs
AP-VMA1420-0            Integrated VAV Controller/Actuator/Pressure Sensor (with                              (Communications has removable screw terminals included)
                        Reheat and Fan-Powered) Single pack
                                                                                                 Optional     2, 3 or 4-position screw terminals that plug into spade lugs
AP-VMA1420-OD AP-VMA1420 Bulk pack (10 maximum/pack)1                                            Terminations (accessories)
AP-VMA1430-0            Similar to AP-VMA1420 without internal actuator                          RS-485 Serial N2 Bus and Zone Bus
                        Single pack                                                              Interfaces
AP-VMA1430-0D           AP-VMA1430 Bulk pack (10 maximum/pack)1                                  N2                 DIP switch set (1 to 253) or through software
AP-VMA1440-0            VMA1440 for Metasys Zoning Package Single Pack                           Controller
                                                                                                 Addressing
1. The VMA is bulk packed in 2-10 unit increments, depending on the order. A
                                                                                                 Communicati N2 between VMA controller and N3x or NCM
   single Variable Air Volume Modular Assembly (VMA) Installation Bulletin is
                                                                                                 ons Bus     Zone Bus between VMA controller and room sensor (either 8-
   included in each order. Order quantity as you would for the standard single
   pack VMA.                                                                                                 pin phone jack or spade lugs)
                                                                                                             (not available when TE-7700 used)
                                                                                                 Mounting           One screw mounts the VMA to the VAV box
Accessories
                                                                                                                    One screw attaches damper shaft to the actuator, 8 mm
Description                    Code Numbers                                                                         (5/16 in.) square-head set screw with 44 N.m (375 lb.in) of axial
                                                                                                                    holding power for 13 mm (1/2 in.) round damper shaft
Transformer                    AS-XFR050, AS-XFR100,
                               Y63 through Y66 Series                                                               Minimum damper shaft length is 44.5 mm (1-3/4 in.)
Screw Terminal Kit             AP-TBK1002-0 - Removable 2-position screw                         Housing            Plastic housing for controller, sensor, and actuator with
                               terminal kit (100 pcs) 1                                                             UL 94-5VB Plenum Flammability Rating
                               AP-TBK1003-0 - Removable 3-position screw                         Dimensions         VMA1410/1420/1440: 153 x 102 x 102 mm (6 x 4 x 4 in.)
                               terminal kit (100 pcs) 1                                          (L x W x H)        VMA1430: 153 x 102 x 83 mm (6 x 4 x 3.25 in.)
                               M9000-106 - Removable 4-position screw terminal                   Actuator           4 N·m minimum (35 lb·in)
                               (1 piece)                                                         Rating
                               AP-TBK4N2-0 - Replacement N2 Bus 4-position
                                                                                                 Shipping           VMA1410/1420/1440: 13.1 kg (29 lb) for a box of ten,
                               screw terminal kit (10 pcs)
                                                                                                 Weight             1.3 kg (2.8 lb) each
Room Sensors                   TE-6700, TE-7000 (Europe only), TE-7700 (using                                       VMA1430: 5 kg (10.6 lb) for a box of ten, 0.5 kg (1.06 lb) each
                               HVAC PRO Rel. 8.04 or later), and
                               AP-TMZ1600-0 (using HVAC PRO Rel. 8.01)                           Velocity           Velocity Pressure for 0 to 374 Pascal (0 to 1.5 inch W.C.)
                                                                                                 Pressure
8-pin Room Sensor    Length                        Part Number
Communication Cables 7.5 m (25 ft.)                                                              Electrical         Analog Inputs:
                                                   CBL-STAT25-SW
                                                                                                 Inputs             Nickel, silicon, or platinum (1K ohm) or NTC (2.25K) RTD room
                     15 m (50 ft.)                 CBL-STAT50-SW
                                                                                                                    sensors, 1.6K setpoint potentiometer (2-wire)
                     22.5 m (75 ft.)               CBL-STAT75-SW
                                                                                                                    Voltage input for 0-10 VDC (humidity or pressure sensor)
                     30 m (100 ft.)                CBL-STAT100-SW
                                                                                                                    Binary Inputs: Dry contacts
Electronic Fan Speed           S66AA-1C or S66DC-1C For specifications, refer to                                    Input configurations vary based on model type.
Controller                     S66 Series Electronic Fan Speed Control Product/
                               Technical Bulletin, LIT-121605                                    Outputs            No outputs on AP-VMA1410-0, except Stepper Motor
                                                                                                                    Binary Outputs: 24 VAC triac switched; 25 to 500 mA loads
VBT Software                   AP-VMAVBT1-0
                                                                                                                    Stepper Drive: 2 to 767 steps per second
                               MW-MTOOL-0, -6 Rel. 5.1 or later                                                     (23,000 step resolution)
HVAC PRO Software              WS-EUROPRO-0, Release 8.04 in Europe                                                 Analog Outputs: 0 to 10 VDC at 10 mA
Release 8.04 or later          MW-MTOOL-0 (New User) or                                          Agency             CSA 22.2 No. 205
                               MW-MTOOL-6 (Upgrade), Rel 5.1 or later                            Compliance         UL 916 UL 94-5VB
Converters                     AS-CVTPROx00-0, AS-CBLPRO-2,                                                         FCC Part 15, Subpart B, Class A and B
                               IU-9100-0 (Europe), MM-CVT101-0 (US)                                                 C-tick Australia/NZ, AS/NZS 4251.1, CISPR 22, Residential
1. These terminals fit over the existing I/O spade lugs.                                                            Class B
                                                                                                                    CE Directive (89/336/EEC, EN50081/1, EN50082/2) Industrial
                                                                                                                    and Residential
Technical Specifications                                                                                            IEEE 472 ANSI C62.41 A/B (IEEE 587 Category A/B)
      VMA1400 Series Variable Air Volume Modular Assembly                                                           IEC 950 IEC 801-2, -3, -4, -6, -7, -8
                          (Part 1 of 2)
                                                                                                 For wiring details, refer to VMA Installation Bulletin Part No. 24-8740-1
Supply             20 to 30 VAC at 50 or 60 Hz
                                                                                                 (VMA1410 and VMA1420), P/N24-8986-18 (VMA1430), and
Voltage
                                                                                                 Part No. 24-9590-0 (VMA1440).
Optional     0.6 ampere for VMA1410; 2.0 ampere for a VMA1420 and
Fuse Current 1440;
             1.2 ampere for VMA1430
Power       VMA1410/1420/1440:10 VA maximum
Consumption (Relay and valve requirements not included.)
            VMA1430:3 VA maximum
            (Damper actuator, relay, and valve requirements not included.)
Ambient            0 to 50°C (32 to 122°F)
Operating          10 to 90% RH non-condensing,
Conditions         limited by a 30°C (86°F) maximum dew point

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2009 Johnson Controls, Inc.                  www.johnsoncontrols.com

                                                                                       2 of 2