Code No. LIT-1928275
Issued March 27, 2009
VMA1400 Series
Variable Air Volume Modular Assembly
Description Features
The Variable Air Volume Modular Assembly • easy-to-handle unit with a compact
(VMA) is a family of configurable digital footprint
controllers. Differing models in the VMA1400 • pre-wired controller with pressure sensor
series combine a controller, pressure sensor and actuator for reduced installation time
and/or actuator housed in one pre-assembled (VMA1430 uses external actuator,
unit. VMA1440 has no pressure sensor)
The VMA1400 series is available in four • fast response actuator that drives the
models: damper from full open to full closed (90°) in
30 seconds (VMA1410, VMA1420,
• Cooling Only (VMA1410) VMA1440) for reduced commissioning time
• Cooling with Reheat and/or Fan • continuous loop tuning through
(VMA1420) proportional adaptive algorithms using
• External Actuator (VMA1430) patented P-Adaptive and Pattern
• Metasys Zoning Package (VMA1440) Recognition Adaptive Control (PRAC)
The VMA1410, VMA1420, and VMA1440 use technologies
an integrated actuator with a stepper motor • advanced diagnostics that identify and
drive for quick and accurate damper correct system deviations related to flow,
positioning. damper travel, and energy
The VMA1410, 1420, 1430 are designed for • N2 network communications for integrating
pressure-independent, single duct systems. VMA as a part of a facility management
The VMA1420 and VMA1430 can also be system with an NCM or N30 Series
used with parallel or series fan-powered Supervisory Controller VMA1400
boxes, supply/exhaust applications, and dual • simple question/answer software format for
duct systems. quick, easy configuration of project-specific
applications. Software - The VMA can be configured,
The VMA1440 is used exclusively as part of downloaded, and commissioned with
the Metasys Zoning Package. See the The VMA1400 Balancing Tool (VBT) software
can be used with handheld interfaces (such as HVAC PRO software, Release 7.00 or later,
Metasys Zoning Package Product Bulletin which uses a simple Q/A format. Dual duct
(LIT-639050) for details. 3Com® PalmPilot™) to easily read and adjust
parameters (not available for VMA1440). VBT applications, and TMZ1600 room sensor and
software is included in M-Tools or can be supply/exhaust applications require
ordered separately. HVAC PRO Rel. 8.01. The TE-7700 RF
Temperature Sensor Application requires
HVAC PRO Software Release 8.04 or later.
VMA Functionality
Inputs/Outputs Points Rating VMA1400 Model
1410 1420 1430 1440
Zone Temperature AI-1 1 K Ni, Si, Pt, or 2.25 K NTC 9 9 9 9
Zone Setpoint AI-2 1.6 K ohm Potentiometer 9 9 9 9
Sideloop (humidity, dew point) (for 1410, 1420, 1430) AI-3 0-10 VDC 9 9 9
Analog Inputs or Static Pressure (for 1440)
Supply Air Temperature or Supplemental Heat AI-4 1 K Ni, Si, Pt, or 2.25 K NTC 9 9 9
Temperature
Velocity Pressure Internal 0-374 pa (0-1.5 in. W.C.) 9 9 9
Temporary Occupied Button BI-1 Dry contact 9 9 9 9
Occupied or User Configurable (for 1440) BI-2 Dry contact 9 9 9 9
Binary Inputs
Off or Window or Shutdown (for 1410, 1420, 1430) or BI-3 Dry contact 9 9 9 9
User Configurable (for 1440)
Proportional Heat or External Damper (for 1440, AO-1 0-10 VDC @ 10 mA 9 9 9
Analog Outputs AO-2 is Bypass/Subordinate Damper) AO-2 0-10 VDC @ 10 mA 9 9 9
Lights, Fan, External Damper, Box Heat - On/Off Valve BO-1 - BO-5 24 VAC Triac @ 0.5 A each 9 9 9
or 1- 3 stage Electric, Supplemental Heat - On/Off (BO-1 - BO-4
Binary Outputs Valve or Single Stage Electric Heat for 1440)
Stepper Motor with Position Feedback Internal 2-phase Stepper (up to 9 9 9 9
93° rotation at 4 N.m [35 lb.in])
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2009 Johnson Controls, Inc. www.johnsoncontrols.com
1 of 2
Variable Air Volume Modular Assembly (Continued)
Selection Chart VMA1400 Series Variable Air Volume Modular Assembly
(Part 2 of 2)
Code Number Description
Ambient -40 to 70°C (-40 to 158°F)
AP-VMA1410-0 Integrated VAV Controller/Actuator/Pressure Sensor
Storage
(Cooling only) Single pack
Conditions
AP-VMA1410-OD AP-VMA1410 Bulk pack (10 maximum/pack)1
Terminations 6.3 mm (1/4 inch) spade lugs
AP-VMA1420-0 Integrated VAV Controller/Actuator/Pressure Sensor (with (Communications has removable screw terminals included)
Reheat and Fan-Powered) Single pack
Optional 2, 3 or 4-position screw terminals that plug into spade lugs
AP-VMA1420-OD AP-VMA1420 Bulk pack (10 maximum/pack)1 Terminations (accessories)
AP-VMA1430-0 Similar to AP-VMA1420 without internal actuator RS-485 Serial N2 Bus and Zone Bus
Single pack Interfaces
AP-VMA1430-0D AP-VMA1430 Bulk pack (10 maximum/pack)1 N2 DIP switch set (1 to 253) or through software
AP-VMA1440-0 VMA1440 for Metasys Zoning Package Single Pack Controller
Addressing
1. The VMA is bulk packed in 2-10 unit increments, depending on the order. A
Communicati N2 between VMA controller and N3x or NCM
single Variable Air Volume Modular Assembly (VMA) Installation Bulletin is
ons Bus Zone Bus between VMA controller and room sensor (either 8-
included in each order. Order quantity as you would for the standard single
pack VMA. pin phone jack or spade lugs)
(not available when TE-7700 used)
Mounting One screw mounts the VMA to the VAV box
Accessories
One screw attaches damper shaft to the actuator, 8 mm
Description Code Numbers (5/16 in.) square-head set screw with 44 N.m (375 lb.in) of axial
holding power for 13 mm (1/2 in.) round damper shaft
Transformer AS-XFR050, AS-XFR100,
Y63 through Y66 Series Minimum damper shaft length is 44.5 mm (1-3/4 in.)
Screw Terminal Kit AP-TBK1002-0 - Removable 2-position screw Housing Plastic housing for controller, sensor, and actuator with
terminal kit (100 pcs) 1 UL 94-5VB Plenum Flammability Rating
AP-TBK1003-0 - Removable 3-position screw Dimensions VMA1410/1420/1440: 153 x 102 x 102 mm (6 x 4 x 4 in.)
terminal kit (100 pcs) 1 (L x W x H) VMA1430: 153 x 102 x 83 mm (6 x 4 x 3.25 in.)
M9000-106 - Removable 4-position screw terminal Actuator 4 N·m minimum (35 lb·in)
(1 piece) Rating
AP-TBK4N2-0 - Replacement N2 Bus 4-position
Shipping VMA1410/1420/1440: 13.1 kg (29 lb) for a box of ten,
screw terminal kit (10 pcs)
Weight 1.3 kg (2.8 lb) each
Room Sensors TE-6700, TE-7000 (Europe only), TE-7700 (using VMA1430: 5 kg (10.6 lb) for a box of ten, 0.5 kg (1.06 lb) each
HVAC PRO Rel. 8.04 or later), and
AP-TMZ1600-0 (using HVAC PRO Rel. 8.01) Velocity Velocity Pressure for 0 to 374 Pascal (0 to 1.5 inch W.C.)
Pressure
8-pin Room Sensor Length Part Number
Communication Cables 7.5 m (25 ft.) Electrical Analog Inputs:
CBL-STAT25-SW
Inputs Nickel, silicon, or platinum (1K ohm) or NTC (2.25K) RTD room
15 m (50 ft.) CBL-STAT50-SW
sensors, 1.6K setpoint potentiometer (2-wire)
22.5 m (75 ft.) CBL-STAT75-SW
Voltage input for 0-10 VDC (humidity or pressure sensor)
30 m (100 ft.) CBL-STAT100-SW
Binary Inputs: Dry contacts
Electronic Fan Speed S66AA-1C or S66DC-1C For specifications, refer to Input configurations vary based on model type.
Controller S66 Series Electronic Fan Speed Control Product/
Technical Bulletin, LIT-121605 Outputs No outputs on AP-VMA1410-0, except Stepper Motor
Binary Outputs: 24 VAC triac switched; 25 to 500 mA loads
VBT Software AP-VMAVBT1-0
Stepper Drive: 2 to 767 steps per second
MW-MTOOL-0, -6 Rel. 5.1 or later (23,000 step resolution)
HVAC PRO Software WS-EUROPRO-0, Release 8.04 in Europe Analog Outputs: 0 to 10 VDC at 10 mA
Release 8.04 or later MW-MTOOL-0 (New User) or Agency CSA 22.2 No. 205
MW-MTOOL-6 (Upgrade), Rel 5.1 or later Compliance UL 916 UL 94-5VB
Converters AS-CVTPROx00-0, AS-CBLPRO-2, FCC Part 15, Subpart B, Class A and B
IU-9100-0 (Europe), MM-CVT101-0 (US) C-tick Australia/NZ, AS/NZS 4251.1, CISPR 22, Residential
1. These terminals fit over the existing I/O spade lugs. Class B
CE Directive (89/336/EEC, EN50081/1, EN50082/2) Industrial
and Residential
Technical Specifications IEEE 472 ANSI C62.41 A/B (IEEE 587 Category A/B)
VMA1400 Series Variable Air Volume Modular Assembly IEC 950 IEC 801-2, -3, -4, -6, -7, -8
(Part 1 of 2)
For wiring details, refer to VMA Installation Bulletin Part No. 24-8740-1
Supply 20 to 30 VAC at 50 or 60 Hz
(VMA1410 and VMA1420), P/N24-8986-18 (VMA1430), and
Voltage
Part No. 24-9590-0 (VMA1440).
Optional 0.6 ampere for VMA1410; 2.0 ampere for a VMA1420 and
Fuse Current 1440;
1.2 ampere for VMA1430
Power VMA1410/1420/1440:10 VA maximum
Consumption (Relay and valve requirements not included.)
VMA1430:3 VA maximum
(Damper actuator, relay, and valve requirements not included.)
Ambient 0 to 50°C (32 to 122°F)
Operating 10 to 90% RH non-condensing,
Conditions limited by a 30°C (86°F) maximum dew point
The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2009 Johnson Controls, Inc. www.johnsoncontrols.com