Error Codes Balancing Mode Operation Operation (continued)
Error #: Cause: Indication Recovery Action Upon entering the balancing mode of
ERR0: Firmware revision mismatch. operation, the address of the VAV Box
Get updated software for the VAV Box controller's Field Bus connection appears.
controller or replace the Balancing Sensor The Balancing Sensor presents the correct
with an updated version. balancing functions and reacts to the use of
ERR1: Commissioning Session locked – the Enter and Cancel buttons depending on
unable to enter Balancing Mode because the configuration of the connected VAV Box
another tool/session is currently active. controller. Upon pressing either button the
Check to see if a commissioning session has next logical balancing menu item
already been started via the FX-PCT tool, or automatically appears. You may not need to
on another Balancing Sensor. use the Dial to select the next command or VAV Balancing Sensor User
ERR2: Communication error on SA Bus state.
Check the cables and connections between Guide
Balancing Sensor and the VAV Box The Balancing Sensor automatically cancels Part No. 24-10159-13, Rev. A
the balancing mode if no user input is
controller. To start balancing: provided for a default period of 60 minutes.
For Models
ERR3: Control Sequence is currently
Assure proper connection. Press the Enter Manual exiting of the balancing mode can be FX-ATV7003-0 Handheld portable
disabled.
and the Cancel buttons simultaneously for 5 done either by selecting Exit command(s) or NS-ATV7001-0 Surface mount with phone jack
Re-enable the Control Sequence from
seconds until the word BUSY appears. The by pressing and holding the large and the NS-ATV7002-0 Surface mount with terminal block
FX-PCT.
ERR4: Another operation (Auto Calibration VAV Box controller's FC Bus address small buttons simultaneously for 5 seconds. NS-BTV7001-0 Wallbox mount with phone jack
or Gain Calculation) is currently being appears. NS-BTV7002-0 Wallbox mount with terminal block
The backlighting stays on continuously while
performed in the Balancer Primitive. General Operation in the balancing mode. INSTALLATION
Wait for the other operation to complete, and The display shows the operating parameters For longer operations like Auto Calibration,
retry the desired operation. It may take a For permanent mounting, see the Network Sensor
and/or the values for parameters. the word BUSY appears. Do not press any Installation instructions P/N 24-10094-9 for the
couple minutes to complete. • The large Enter button allows you to buttons during this time. surface mount models and P/N 24-10094-25 for the
ERR5: No flow override has been selected enter a selection. wall box mount models.
You must select a Flow Setpoint Override. We recommend that you exit the balance
• The small Cancel button causes the For handheld, portable unit, plug one end of coiled
Then allow the flow to settle (watch the value mode before removing power. This returns
present selection to be canceled. cable into the modular jack on the balancing unit.
displayed on the Balancing Sensor), and then the VAV Box controller to normal operation. Plug the other end of the coiled cable into the wall
retry calculating the gain. The adjustment dial changes a selection or Otherwise a delay may result if you choose to mounted Network Sensor associated with the
ERR6: Flow reading is unreliable. varies an input parameter. resume the balancing mode. controller to be balanced.
The DP sensor is giving an unreliable value.
Check connections/integrity of the pneumatic
tubing, and check the pickup tubes for a
possible obstruction.
ERR7: Value out of range
Slightly increase or decrease the value.
ERR8: Auto Calibration Timed Out
Check all stroke time settings.
ERRx: Unknown Application Error
Reboot the VAV Box controller. If the problem
persists, get updated software for the VAV
Box controller, or replace the Balancing
Sensor with an updated version.
Johnson Controls, Inc. ©
SINGLE DUCT – supply/exhaust SINGLE DUCT – supply/exhaust DUAL DUCT – supply/exhaust Heating Min
Address appears Address appears [HMIN]
Dial to Parameter Mode [PARM] and
Dial to Balance Mode [BAL] and press Closed
press Enter. Dial to Balance Mode [BAL] and press
enter. [OFF]
Flow Setpoints [FLSP], press Enter. Enter.
DUAL DUCT – supply/exhaust
Supply Duct [SPLY], press enter. Cooling Max Flow [CMAX] 0001 – 9999 Cold Duct [Cd], press Enter.
dP Offset [dPO] 00.00 – 99.99 (Continued)
Cooling Min Flow [CMIN] 0000 – 9999 dP Offset [dPO] 00.00 – 99.99
Auto Calibrate dP [ACAL] No Actual Flow [FLOW] 0001 – 9999
Heating Flow [Htg] 0000 – 9999 Auto Calibrate dP [ACAL] No [NO]
[NO] Pickup Gain – K Factor [K] 0.001 – 9.999
Differential Flow [dIFF] -999 to 999 Yes
Yes [YES] [YES]
Dial Exit and press Enter.
Dial Exit and press Enter.
Flow Setpoint Override [FLSP] None Flow Setpoint Override [FLSP] None [EXIT]
[EXIT]
[NONE] [NONE] Dial Exit and press Enter. [EXIT]
Cooling Max Supply Duct [SPLY], press Enter. Max
[CMAX] Box Area [AREA] 0.001 – 9.999 [CMAX] Dial to Parameter Mode [PARM] and
Cooling Min [CMIN] Pickup Gain – K Factor [K] 0.001 – 9.999 Min press Enter.
Heating [Htg] dP Offset [dPO] 00.00 – 99.99 [CMIN] Flow Setpoints [FLSP], press Enter.
Closed [OFF] Dial Exit and press Enter. Closed Cooling Max Flow [CMAX] 0001 – 9999
Actual Flow [FLOW] 0001 – 9999 [EXIT] [OFF] Cooling Min Flow [CMIN] 0000 – 9999
Box Gain – K Factor [K] 0.001 – 9.999 Actual Flow [FLOW] 0001 – 9999 Heating Max Flow [HMAX] 0001 – 9999
Dial Exit and press enter. Exhaust Duct [EXH], press Enter. Box Gain – K Factor [K] 0.001 – 9.999 Heating Min Flow [HMIN] 0000 – 9999
[EXIT] Box Area [AREA] 0.001 – 9.999 Dial Exit and press Enter. Differential Flow [dIFF] -999 to 999
Pickup Gain – K Factor [K] 0.001 – 9.999 [EXIT] Dial Exit and press Enter.
Exhaust Duct [EXH], press enter. dP Offset [dPO] 00.00 – 99.99 [EXIT]
Hot Duct [Hd], press Enter.
dP Offset [dPO] 00.00 – 99.99 Dial Exit and press Enter. [EXIT] Cold Duct [Cd], press Enter.
dP Offset [dPO] 00.00 – 99.99
Auto Calibrate dP [ACAL] No Box Area [AREA] 0.001 – 9.999
Dial Exit and press Enter. [EXIT] Auto Calibrate dP [ACAL] No
[NO] [NO] Pickup Gain – K Factor [K] 0.001 – 9.999
Yes [YES] Dial Exit (balance mode) and press Yes dP Offset [dPO] 00.00 – 99.99
Flow Setpoint Override [FLSP] None Enter. [EXIT] [YES] Dial Exit and press Enter.
[NONE] Flow Setpoint Override [FLSP] None [EXIT]
[NONE] [NONE] Hot Duct [Hd], press Enter.
Cooling Max Max Box Area [AREA] 0.001 – 9.999
[CMAX] [HMAX] Pickup Gain – K Factor [K] 0.001 – 9.999
Cooling Min [CMIN] Min dP Offset [dPO] 00.00 – 99.99
Heating [Htg] [HMIN] Dial Exit and press Enter.
Closed [OFF] Closed [EXIT]
Actual Flow [FLOW] 0001 – 9999 [OFF] Exhaust Duct [EXH], press Enter.
Pickup Gain – K Factor [K] 0.001 – 9.999 Actual Flow [FLOW] 0001 – 9999 Box Area [AREA] 0.001 – 9.999
Dial Exit and press enter. Box Gain – K Factor [K] 0.001 – 9.999 Pickup Gain – K Factor [K] 0.001 – 9.999
[EXIT] Dial Exit and press Enter. dP Offset [dPO] 00.00 – 99.99
[EXIT] Dial Exit and press Enter.
Dial Exit and press enter. [EXIT]
[EXIT] Exhaust Duct [EXH], press Enter.
dP Offset [dPO] 00.00 – 99.99 Dial Exit and press Enter.
Dial in selection or value and press Enter
OR Auto Calibrate dP [ACAL] No [EXIT]
Accept selection or value presented by pressing [NO] Dial Exit (balance mode) and press
Enter. Yes Enter.
Use the Cancel button to back up to the last
display.
[YES] [EXIT]
Flow Setpoint Override [FLSP] None
[NONE]
Cooling Max
[CMAX]
Cooling Min
[CMIN]
Heating Max