SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

VAV Balancing Sensor User Guide

Вид документаКерівництво користувача
ВиробникJCI
Код документаvav-balancing-sensor-user-guide
Група обладнанняHandheld VAV Balancing Sensor/Tool
Сторінок2
Мова документаанглійська
Розмір файлу0.1 МБ

Текст документа

Error Codes                      Balancing Mode Operation                      Operation (continued)
Error #: Cause: Indication Recovery Action                                                     Upon entering the balancing mode of
ERR0: Firmware revision mismatch.                                                              operation, the address of the VAV Box
Get updated software for the VAV Box                                                           controller's Field Bus connection appears.
controller or replace the Balancing Sensor                                                     The Balancing Sensor presents the correct
with an updated version.                                                                       balancing functions and reacts to the use of
ERR1: Commissioning Session locked –                                                           the Enter and Cancel buttons depending on
unable to enter Balancing Mode because                                                         the configuration of the connected VAV Box
another tool/session is currently active.                                                      controller. Upon pressing either button the
Check to see if a commissioning session has                                                    next logical balancing menu item
already been started via the FX-PCT tool, or                                                   automatically appears. You may not need to
on another Balancing Sensor.                                                                   use the Dial to select the next command or       VAV Balancing Sensor User
ERR2: Communication error on SA Bus                                                            state.
Check the cables and connections between                                                                                                                 Guide
Balancing Sensor and the VAV Box                                                               The Balancing Sensor automatically cancels              Part No. 24-10159-13, Rev. A
                                                                                               the balancing mode if no user input is
controller.                                      To start balancing:                           provided for a default period of 60 minutes.
                                                                                                                                                                  For Models
ERR3: Control Sequence is currently
                                                 Assure proper connection. Press the Enter     Manual exiting of the balancing mode can be     FX-ATV7003-0 Handheld portable
disabled.
                                                 and the Cancel buttons simultaneously for 5   done either by selecting Exit command(s) or     NS-ATV7001-0 Surface mount with phone jack
Re-enable the Control Sequence from
                                                 seconds until the word BUSY appears. The      by pressing and holding the large and the       NS-ATV7002-0 Surface mount with terminal block
FX-PCT.
ERR4: Another operation (Auto Calibration        VAV Box controller's FC Bus address           small buttons simultaneously for 5 seconds.     NS-BTV7001-0 Wallbox mount with phone jack
or Gain Calculation) is currently being          appears.                                                                                      NS-BTV7002-0 Wallbox mount with terminal block
                                                                                               The backlighting stays on continuously while
performed in the Balancer Primitive.             General Operation                             in the balancing mode.                                           INSTALLATION
Wait for the other operation to complete, and    The display shows the operating parameters    For longer operations like Auto Calibration,
retry the desired operation. It may take a                                                                                                     For permanent mounting, see the Network Sensor
                                                 and/or the values for parameters.             the word BUSY appears. Do not press any         Installation instructions P/N 24-10094-9 for the
couple minutes to complete.                      •    The large Enter button allows you to     buttons during this time.                       surface mount models and P/N 24-10094-25 for the
ERR5: No flow override has been selected              enter a selection.                                                                       wall box mount models.
You must select a Flow Setpoint Override.                                                      We recommend that you exit the balance
                                                 •    The small Cancel button causes the                                                       For handheld, portable unit, plug one end of coiled
Then allow the flow to settle (watch the value                                                 mode before removing power. This returns
                                                      present selection to be canceled.                                                        cable into the modular jack on the balancing unit.
displayed on the Balancing Sensor), and then                                                   the VAV Box controller to normal operation.     Plug the other end of the coiled cable into the wall
retry calculating the gain.                      The adjustment dial changes a selection or    Otherwise a delay may result if you choose to   mounted Network Sensor associated with the
ERR6: Flow reading is unreliable.                varies an input parameter.                    resume the balancing mode.                      controller to be balanced.
The DP sensor is giving an unreliable value.
Check connections/integrity of the pneumatic
tubing, and check the pickup tubes for a
possible obstruction.
ERR7: Value out of range
Slightly increase or decrease the value.
ERR8: Auto Calibration Timed Out
Check all stroke time settings.
ERRx: Unknown Application Error
Reboot the VAV Box controller. If the problem
persists, get updated software for the VAV
Box controller, or replace the Balancing
Sensor with an updated version.
Johnson Controls, Inc. ©
SINGLE DUCT – supply/exhaust                        SINGLE DUCT – supply/exhaust              DUAL DUCT – supply/exhaust                                          Heating Min
Address appears                                                                               Address appears                             [HMIN]
                                                  Dial to Parameter Mode [PARM] and
Dial to Balance Mode [BAL] and press                                                                                                                                   Closed
                                                  press Enter.                                Dial to Balance Mode [BAL] and press
enter.                                                                                                                                    [OFF]
                                                  Flow Setpoints [FLSP], press Enter.         Enter.
                                                                                                                                          DUAL DUCT – supply/exhaust
Supply Duct [SPLY], press enter.                   Cooling Max Flow [CMAX]     0001 – 9999    Cold Duct [Cd], press Enter.
 dP Offset [dPO]            00.00 – 99.99                                                                                                 (Continued)
                                                   Cooling Min Flow [CMIN]     0000 – 9999     dP Offset [dPO]           00.00 – 99.99
 Auto Calibrate dP [ACAL]          No                                                                                                      Actual Flow [FLOW]          0001 – 9999
                                                   Heating Flow [Htg]          0000 – 9999     Auto Calibrate dP [ACAL]         No [NO]
[NO]                                                                                                                                       Pickup Gain – K Factor [K] 0.001 – 9.999
                                                   Differential Flow [dIFF]     -999 to 999                                   Yes
                                Yes [YES]                                                     [YES]
                                                                                                                                          Dial Exit and press Enter.
                                                  Dial Exit and press Enter.
 Flow Setpoint Override [FLSP] None                                                            Flow Setpoint Override [FLSP] None         [EXIT]
                                                  [EXIT]
[NONE]                                                                                        [NONE]                                      Dial Exit and press Enter. [EXIT]
                       Cooling Max                Supply Duct [SPLY], press Enter.                                           Max
[CMAX]                                             Box Area [AREA]            0.001 – 9.999   [CMAX]                                      Dial to Parameter Mode [PARM] and
                       Cooling Min [CMIN]          Pickup Gain – K Factor [K] 0.001 – 9.999                                   Min         press Enter.
                            Heating [Htg]          dP Offset [dPO]            00.00 – 99.99   [CMIN]                                      Flow Setpoints [FLSP], press Enter.
                             Closed [OFF]         Dial Exit and press Enter.                                               Closed          Cooling Max Flow [CMAX]     0001 – 9999
 Actual Flow [FLOW]          0001 – 9999          [EXIT]                                      [OFF]                                        Cooling Min Flow [CMIN]     0000 – 9999
 Box Gain – K Factor [K]    0.001 – 9.999                                                     Actual Flow [FLOW]           0001 – 9999     Heating Max Flow [HMAX]     0001 – 9999
Dial Exit and press enter.                        Exhaust Duct [EXH], press Enter.            Box Gain – K Factor [K]     0.001 – 9.999    Heating Min Flow [HMIN]     0000 – 9999
[EXIT]                                             Box Area [AREA]            0.001 – 9.999   Dial Exit and press Enter.                   Differential Flow [dIFF]      -999 to 999
                                                   Pickup Gain – K Factor [K] 0.001 – 9.999   [EXIT]                                      Dial Exit and press Enter.
Exhaust Duct [EXH], press enter.                   dP Offset [dPO]            00.00 – 99.99                                               [EXIT]
                                                                                              Hot Duct [Hd], press Enter.
 dP Offset [dPO]            00.00 – 99.99         Dial Exit and press Enter. [EXIT]                                                       Cold Duct [Cd], press Enter.
                                                                                               dP Offset [dPO]            00.00 – 99.99
 Auto Calibrate dP [ACAL]          No                                                                                                      Box Area [AREA]            0.001 – 9.999
                                                  Dial Exit and press Enter. [EXIT]            Auto Calibrate dP [ACAL]         No
[NO]                                                                                          [NO]                                         Pickup Gain – K Factor [K] 0.001 – 9.999
                                Yes [YES]         Dial Exit (balance mode) and press                                          Yes          dP Offset [dPO]            00.00 – 99.99
 Flow Setpoint Override [FLSP] None               Enter.                     [EXIT]           [YES]                                       Dial Exit and press Enter.
[NONE]                                                                                         Flow Setpoint Override [FLSP] None         [EXIT]
                                   [NONE]                                                     [NONE]                                      Hot Duct [Hd], press Enter.
                       Cooling Max                                                                                           Max           Box Area [AREA]            0.001 – 9.999
[CMAX]                                                                                        [HMAX]                                       Pickup Gain – K Factor [K] 0.001 – 9.999
                       Cooling Min [CMIN]                                                                                     Min          dP Offset [dPO]            00.00 – 99.99
                            Heating [Htg]                                                     [HMIN]                                      Dial Exit and press Enter.
                             Closed [OFF]                                                                                  Closed         [EXIT]
 Actual Flow [FLOW]          0001 – 9999                                                      [OFF]                                       Exhaust Duct [EXH], press Enter.
 Pickup Gain – K Factor [K] 0.001 – 9.999                                                      Actual Flow [FLOW]          0001 – 9999     Box Area [AREA]            0.001 – 9.999
Dial Exit and press enter.                                                                     Box Gain – K Factor [K]    0.001 – 9.999    Pickup Gain – K Factor [K] 0.001 – 9.999
[EXIT]                                                                                        Dial Exit and press Enter.                   dP Offset [dPO]            00.00 – 99.99
                                                                                              [EXIT]                                      Dial Exit and press Enter.
Dial Exit and press enter.                                                                                                                [EXIT]
[EXIT]                                                                                        Exhaust Duct [EXH], press Enter.
                                                                                               dP Offset [dPO]            00.00 – 99.99   Dial Exit and press Enter.
   Dial in selection or value and press Enter
                       OR                                                                      Auto Calibrate dP [ACAL]         No        [EXIT]
Accept selection or value presented by pressing                                               [NO]                                        Dial Exit (balance mode) and press
                      Enter.                                                                                                  Yes         Enter.
  Use the Cancel button to back up to the last
                     display.
                                                                                              [YES]                                       [EXIT]
                                                                                               Flow Setpoint Override [FLSP] None
                                                                                              [NONE]
                                                                                                                     Cooling Max
                                                                                              [CMAX]
                                                                                                                      Cooling Min
                                                                                              [CMIN]
                                                                                                                     Heating Max
                                                                                              [HMAX]

Позиції каталогу з цим документом

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.