Variable Speed Drives Series III

Quick Start Guide
Effective April 2018
New Information

CONTENTS
   Step 1—Variable Speed Drives Series III Overview . . . . 1
   Step 2—Keypad Operation Overview . . . . . . . . . . . . . . . 3
   Step 3—Menu Navigation . . . . . . . . . . . . . . . . . . . . . . . . 6
   Step 4—Startup Wizard . . . . . . . . . . . . . . . . . . . . . . . . . . 8
   Step 5—Standard Parameter List . . . . . . . . . . . . . . . . . . 10
   Appendix A—Fault and Warning Codes . . . . . . . . . . . . . 40
                                                                           Step 1—Variable Speed Drives Series III Overview

Step 1—Variable Speed Drives Series III Overview
This chapter describes the purpose and contents of this               Real Time Clock Battery Activation
manual, the receiving inspection recommendations and
the variable frequency drive catalog numbering system.                To activate the real time clock (RTC) functionality in the
                                                                      VFD, the RTC battery (already mounted in the drive) must
                                                                      be connected to the control board.
How to Use this Manual                                                Simply remove the primary drive cover, locate the RTC
                                                                      battery directly below the keypad, and connect the white
The purpose of this manual is to provide you with information         2-wire connector to the receptacle on the control board.
necessary to install, set and customize parameters, start up,
troubleshoot and maintain the variable frequency drive (VFD).         Figure 1. RTC Battery Connection
To provide for safe installation and operation of the
equipment, read the safety guidelines at the beginning of this
manual and follow the procedures outlined in the following
chapters before connecting power to the VFD. Keep this
operating manual handy and distribute to all users,
technicians and maintenance personnel for reference.

Receiving and Inspection
The Variable Speed Drives Series III has met a stringent
series of factory quality requirements before shipment. It is
possible that packaging or equipment damage may have
occurred during shipment. After receiving your VFD, please
check for the following:
Check to make sure that the package includes the Instruction
Leaflet, Quick Start Guide, and accessory packet. The
accessory packet includes:
●   Rubber grommets
●   Control cable grounding clamps
●   Additional grounding screw
Inspect the unit to ensure it was not damaged during
shipment.
Make sure that the part number indicated on the nameplate
corresponds with the catalog number on your order.                    Table 1. Common Abbreviations
If shipping damage has occurred, please contact and file a            Abbreviation       Definition
claim with the carrier involved immediately.                          CT                 Constant torque with high overload rating (150%)
If the delivery does not correspond to your order, please             VT                 Variable torque with low overload rating (110%)
contact your sales representative.
                                                                      IH                 High Overload (150%)
Note: Do not destroy the packing. The template printed on             IL                 Low Overload (110%)
      the protective cardboard can be used for marking the
      mounting points of the VFD on the wall or in a cabinet.         VFD                Variable Frequency Drive

                                            Variable Speed Drives Series III LIT-12012996—April 2018   www.johnsoncontrols.com              1
Step 1—Variable Speed Drives Series III Overview

Rating Label                                                                Keypad Overview
Figure 2. Rating Label                                                      Figure 3. Keypad and Display

                                                                               Programmable                                       Programmable
                                                                                   Soft Key 1                                     Soft Key 2

                                                                                  Increase
                                                                               Value Scroll                                       Change Control
                                                                                 Menu Up                                          Place to Auto

                                                                                 Back/Reset                                       Move Cursor
                                                                                    Button                                        Right

                                                                                                                                  Start/Hand Button
                                                                            Stop/Off Button

                                                                                          Move Cursor               Decrease Value
                                                                                          Left                      Scroll Menu Down
                                                                                                    Enter Menu
                                                                                                      Confirm Selection

Carton Labels (U.S. and Europe)
Same as rating label shown above.

2              Variable Speed Drives Series III   LIT-12012996—April 2018   www.johnsoncontrols.com
                                                                                                   Step 2—Keypad Operation Overview

Step 2—Keypad Operation Overview
The keypad is the interface between the drive and the user.
It features an LCD display, 3 LED lights and 11 buttons. With
the control keypad, it is possible to control the speed of a
motor, to supervise the state of the equipment and to set the
frequency converter’s parameters. See Figure 3.

Keypad Buttons
Buttons Description
Table 2. Keypad Buttons
Icon               Button            Description
                   Soft Key 1,       Soft Key 1, Soft Key 2:
                   Soft Key 2        The functions of these two buttons shall be the following:
                                     Forward/Reverse, this shall change motor’s run direction.
                                     Reset, this shall ask MCU to reset after some parameters are modified.
                                     • Menu, this shall return to main menu.
                                     • Details, this shall display the details of the fault.
                                     • Bypass, this shall make drive go into bypass.
                                     • Jog, this shall activate jog.
                                     • Favorite, this shall add this parameter to the Favorite menu.
                                     • Delete, this shall delete this parameter from the Favorite menu.
                   Back/Reset        Back/Reset:
                                     This button has three integrated functions. The button operates as backward button during
                                     normal mode.
                                     In edit mode, it is used as cancel operate. It is also used to reset faults when faults occur.
                                     • Backs up one step.
                                     • Cancels Modify in edit mode.
                                     • Resets the active faults (all the active faults shall be reset by pressing this button
                                          more than 2s in any page).
                   Auto              Auto:
                                     This button switches the drive into the auto control place.

                   Up                Up and Down Arrows:
                   Down              • Move either up or down a menu list to select the desired menu item.
                                     • Editing a parameter bit by bit, while the active digit is scrolled.
                                     • Increase/decrease the reference value of the selected parameter.
                                     • In parameter comparison mode, scroll through the parameters of which current value
                                         is different from comparison parameter value.
                                     • In parameter page when in read mode, move to the previous or next brother
                                         parameter of this parameter.

                                            Variable Speed Drives Series III LIT-12012996—April 2018          www.johnsoncontrols.com   3
Step 2—Keypad Operation Overview

Table 2. Keypad Buttons, continued
Icon             Button                Description
                 Left                  Left Arrow:
                                       • Navigation button, movement to left when editing a parameter digit by digit.
                                       • Backs up one step.

                 Right                 Right Arrow:
                                       • Enter parameter group mode.
                                       • Enter parameter mode from group mode.
                                       • Enter parameter whole edit mode when this parameter can be written.
                                       • Enter parameter bit by bit edit mode from whole edit mode.
                                       • Navigation button, movement to right when editing a parameter bit by bit.

                 OK                    OK:
                                       • To clear all the Fault History if pressed for more than 5s (including 5s) in any page.
                                       • This button is used in the parameter edit mode to save the parameter setting.
                                       • To confirm the start-up list at the end of the Start-Up Wizard.
                                       • To confirm the comparison item in parameters comparison mode.
                                       The following is the same with Right key:
                                       • Enter parameter whole edit mode when this parameter can be written.
                                       • Enter parameter group mode.
                                       • Enter parameter mode from group mode.
                 Stop/Off              Stop/Off:
                                       This button operates as the motor stop button for normal operation and places the drive in the
                                       off control location. The Default is for this button to always be active. It can be changed in
                                       Parameter P4.1.3 to only when “Keypad” is selected as the control source.
                                       • Motor stop from the keypad.
                                       • Transitions drive into an Off control location preventing start from any control source.

                 Start/Hand            Start/Hand:
                                       This button operates as motor start button for normal operation when the “Keypad” is
                                       selected as the active control source, as well as selects the Hand control place location.
                                       • When Keypad is the reference place after hitting the start button, it will jump directly
                                            to the Keypad Ref Screen.
                                       • Places drive into Hand Control place. Hitting start again if keypad is in the control
                                            location will start the Drive.

4             Variable Speed Drives Series III   LIT-12012996—April 2018    www.johnsoncontrols.com
                                                                                                      Step 2—Keypad Operation Overview

LED Lights                                                                       The lines definition is as below:
                                                                                 The first line is State line, shows:
Table 3. LED State Indicators                                                    ●   RUN / STP / NRD / FIM / TFM—If motor is running, the
Indicator    Description                                                             run state shall display “RUN”, otherwise the state display
                                                                                     “STP”. “RUN” blinks when the stop command is sent but
             Run:
                                                                                     the drive is decelerating. “NRD” is displayed if the drive is
             Indicates that the VFD is running and controlling the load in           not ready or does not have a signal. “FIM” is displayed to
Run          Drive or Bypass.
                                                                                     indicate it is in Fire Mode and the drive is in a Run state.
             Blinks when a stop command has been given but the drive is              “TFM” is displayed when in the Fire Mode Test Mode and
             still ramping down.
                                                                                     the drive is in a Run State.
             Fault:
             Turn on when there is one or more active drive fault(s).
                                                                                 ●   FWD / REV / JOG—If the motor running the direction is
Fault                                                                                clockwise, it displays “FWD”, otherwise displays “REV”
                                                                                     for counter clockwise. If “Jog” is displayed, it indicates
             Hand/OFF/Auto:                                                          Jog mode is active.
             Hand: If the Hand or Off control place is selected,
Auto         turn off the light.                                                 ●   KEY / I/O / BPS / RBP / BUS / OFF—If it is in bypass
             Auto: If the Auto control place is selected, turn on the light.         currently, display “BPS”; when run command is given, it
                                                                                     will go to “RBP”; otherwise, if the current control source
                                                                                     is I/O terminal, display “I/O”. If it is keypad, then display
                                                                                     “KEY”; otherwise display “BUS.” When indicates “OFF”, it
LCD Display                                                                          indicates the drive will not accept a command from the
The keypad LCD indicates the status of the motor and the                             Hand or Auto Control place.
drive and any faults in motor or drive functions. On the LCD,                    ●   PAR / MON / FLT / OPE / QSW / FAV / TPM / BUx—
the user sees information about the current location in the                          If the current page is parameter menu, display “PAR”;
menu structure and the item displayed.                                               If monitor menu, then display “MON”; If fault menu, then
                                                                                     display “FLT”; If operation menu, then display “OPE”;
                                                                                     If quick start wizard, then display “QSW”; If optional card
Overview
                                                                                     menu, then display “BOA”; If favorite menu, then display
Five lines shall be displayed in the screen. General view is as                      “FAV”; If main menu, then display “TPM”. “BUx” indicates
following in Figure 4.                                                               the drive being a backup drive when in the redundant drive
                                                                                     system.
Figure 4. General View of LCD
                                                                                 The second line is Code line, which shows the menu code.
                    Direction Status                        Menu Location
                                                                                 The third line is Name line, which shows the menu name or
        Drive Status                     Control Place
                                                                                 parameters name.
                                                                                 The fourth line is Value line, which shows the submenu
                                                                                 name or parameters value.
                                                                                 The fifth line is Soft key line, the functions of Soft key 1 and
                                                                                 Soft key 2 are changeable, and the real time is in the middle.

 Active
Selection

                                  Real Time Clock
                                     (hh:mm)
          Soft Key 1                                          Soft Key 2
        Function Label                                      Function Label

                                                       Variable Speed Drives Series III LIT-12012996—April 2018   www.johnsoncontrols.com         5
Step 3—Menu Navigation

Step 3—Menu Navigation

Menu Structure
Table 4. Keypad Menu
Item          Description                          Item                 Description
Monitor       M1—Basic                             Fault                F1—Active Fault
              M2—IO Status                                              F2—History Fault
              M3—Optional Boards                                        F3—Fault Log
              M4—Energy savings                    Option Boards        B1—Slot A
              M5—FB Monitor Menu                                        B2—Slot B
              M6—PID Monitor                       Favorite
              M7—Timer/Interval Control            Operate Mode         O1—Output Frequency
              M8—User Defined Output                                    O2—Freq Reference
              M9—MWH Monitor                                            O3—Motor Speed
              M10—Multi-Monitoring                                      O4—Motor Current
Parameters    P1—Basic Parameter                                        O5—Motor Torque
              P2—Inputs                                                 O6—Motor Power
              P3—Outputs                                                O7—Motor Voltage
              P4—Drive Control                                          O8—DC-link Voltage
              P5—Motor Control                                          O9—Unit Temperature
              P6—Protections                                            O10—Motor Temperature
              P7—PID Controller 1                                       R11—Keypad Reference
              P8—PID Controller 2                                       R12—PID1 Keypad Set Point 1
              P9—Fire Mode                                              R13—PID1 Keypad Set Point 2
              P10—Bypass                           Startup Wizard       S—Startup Wizard
              P11—Real Time Clock
              P12—Communication
              P13—System

Note: Will vary depending on application selected.

6               Variable Speed Drives Series III   LIT-12012996—April 2018   www.johnsoncontrols.com
                                                                                                                Step 3—Menu Navigation

Menu Navigation
This section provides basic instruction on navigating each
section in the menu structure.

Figure 5. Main Menu Navigation
Back/left key          Right/OK key

           M – Monitor                M1 – Basic
 UP key                                                                    M1.1
                                      …                                    Output Frequency
                                      M10 – Multi-Monitoring               0.00 Hz

           P – Parameters             P1 – Basic Parameters             P1.1 – Min Frequency                  P1.1
                                      …                                 …                                     Min Frequency
Down key
                                      P13 – System                      P1.16 – Auto 2 Reference               0.00 Hz

           F – Fault                  F1 – Active Fault
                                      F2 – History Fault
                                      F3 – Fault Log
           B – Optional Boards

           T – Favorite

           O – Operate Mode

           S – Startup Wizard

                                                Variable Speed Drives Series III LIT-12012996—April 2018   www.johnsoncontrols.com   7
Step 4—Startup Wizard

Step 4—Startup Wizard

Startup Wizard                                                               Table 5. Startup Wizard Instructions
In the Startup Wizard, you will be prompted for essential                    Item       Description
information needed by the drive so that it can start                         1          Startup Wizard        Press OK?
controlling your process. In the Wizard, you will need
                                                                             2          Application           0 = Basic
the following keypad buttons:
                                                                                                              1 = PID
          Up/Down buttons.                                                                                    2 = Advanced
          Use these to change value.                                         3          Language              0 = English
                                                                                                              1 = ѝ᮷
                                                                                                              2 = Deutsch
                                                                             4          Real Time Clock       yy.mm.dd
                                                                                                              hh:mm:ss
                                                                             5           Daylight Saving      0 = Off
                                                                                                              1 = EU
                                                                                                              2 = US
          OK button.                                                         6          Min Frequency         Min: 0.00Hz
                                                                                                              Max: Max Frequency
          Confirm selection with this button, and enter into
          next question.                                                     7          Max Frequency         Min: Min Frequency
                                                                                                              Max: 400.00Hz
                                                                             8          Motor Nom Current     Min: 0.1A
          Back/Reset button.                                                                                  Max: 500.0A
          If this button was pressed at the first question,                  9          Current Limit         Min: Ih*1/10
          the Startup Wizard will be cancelled.                                                               Max: Ih*2
                                                                             10         Motor Nom Speed       Min: Ih*1/10
                                                                                                              Max: Ih*2
Once you have connected power to your frequency
converter, and the Startup Wizard is enabled, follow                         11         Motor PF              Min: 0.30
these instructions to easily set up your drive.                                                               Max: 1.0
                                                                             12         Motor Nom Voltage     Min: 180V
                                                                                                              Max: 690V
                                                                             13         Motor Nom Frequency   Min: 30.00 Hz
                                                                                                              Max: 400.00 Hz
                                                                             14         Accel Time 1          Min: 0.1 sec
                                                                                                              Max:3000.0 sec
                                                                             15         Decel Time 1          Min: 0.1 sec
                                                                                                              Max:3000.0 sec
                                                                             16         Hand Control Place    0 = Keypad
                                                                                                              1 = I/O Terminal Start 1
                                                                                                              2 = I/O Terminal Start 2
                                                                                                              3 = Fieldbus

8               Variable Speed Drives Series III   LIT-12012996—April 2018   www.johnsoncontrols.com
                                                                                                                       Step 4—Startup Wizard

Table 5. Startup Wizard Instructions, continued
Item     Description
17       Hand Reference             0 = AI1
                                    1 = AI2
                                    2 = Slot A: AI1
                                    3 = Slot B: AI1
                                    4 = AI1 Joystick
                                    5 = AI2 Joystick
                                    6 = Keypad
                                    7 = Fieldbus
                                    9 = Max Frequency
                                    10 = AI1 + AI2
                                    11 = AI1 –AI2
                                    12 = AI2 –AI1
                                    13 = AI1 * AI2
                                    14 = AI1 or AI2
                                    15 = Min(AI1,AI2)
                                    16 = Max(AI1,AI2)
                                    17 = PID1 Control Output
                                    18 = PID2 Control Output
18       Auto 1 Control Place       0 = I/O Terminal Start 1
                                    1 = Fieldbus
                                    2 = I/O Terminal Start 2
                                    3 = Keypad
19       Auto 1 Control Reference   0 = AI1
                                    1 = AI2
                                    2 = Slot A: AI1
                                    3 = Slot B: AI1
                                    4 = AI1 Joystick
                                    5 = AI2 Joystick
                                    6 = Keypad
                                    7 = Fieldbus
                                    9 = Max Frequency
                                    10 = AI1 + AI2
                                    11 = AI1 –AI2
                                    12 = AI2 –AI1
                                    13 = AI1 * AI2
                                    14 = AI1 or AI2
                                    15 = Min(AI1,AI2)
                                    16 = Max(AI1,AI2)
                                    17 = PID1 Control Output
                                    18 = PID2 Control Output
20       Bypass Enabled             0 = Disabled
                                    1 = Enabled
21       Application Mini-Wizard    Press OK?

Now the Startup Wizard is done. It won’t show again when
next power up. If you want to reset it, please set the Startup
Wizard (P13.1.17) or select it from the main menu screen to
enable and cycle the power to the drive.

                                                    Variable Speed Drives Series III LIT-12012996—April 2018   www.johnsoncontrols.com     9
Step 5—Standard Parameter List

Step 5—Standard Parameter List
Introduction                                                                     I/O Controls
The Basic Application is designed for preloaded application
sets for use with HVAC specific terminology and functions.                       “Terminal To Function” (TTF) Programming
It has the patent Active Energy Control algorithm that will
improve your efficiency as well as minimize losses in your                       The design behind the programming of the digital inputs in
motor throughout the defined speed range. It provides the                        the DH1 drive is to use “Terminal To Function”
ability for the user to define its Hand and Auto control and                     programming, which is composed of multiple functions that
reference signals with the standard Off condition as well.                       get assigned a digital input to that function. The parameters
In addition there is the ability to scale the analog input and                   in the drive are set up with specific functions and by defining
output signals to be read based off the desired motor                            the digital input and slot in some cases, depending on which
response. There are also 8 digital inputs, 3 relay outputs, and                  options are available. For use of the drives control board
1 digital output that can be programmed to allow for control                     inputs, they will be referred to as DigIN:1 through DigIN:8.
schemes that require the drive to have certain functions. It                     When additional option cards are used, they will be defined
provides full customization on the motor control sequence                        as DigIN:X:IOY:Z. The X indicates the slot that the card is
with the ability to be in frequency or speed control mode, and                   being installed in, which will be either A or B. The IOY
tuning of the V/Hz curve can be selected. Drive/Motor                            determines the type of card it is, which would be IO1 or IO5.
protections can be customized to defined actions for added                       The Z indicates which input is being used on that available
user control. Below is a list of other features that are                         option card.
available in the Basic Application.
Basic Application includes functions:                                            “Function To Terminal” (FTT) Programming
●    Bypass control                                                              The design behind the programming of the relay outputs and
                                                                                 digital output in the DH1 drive is to use “Function To
●    Fire mode                                                                   Terminal” programming. It is composed of a terminal, be it a
●    Pre heat/cold weather mode                                                  relay output or a digital output, that is assigned a parameter.
                                                                                 Within that parameter, it has different functions that can be
●    Hand/Off/Auto in individual button for easy change of                       set.
     control mode
                                                                                 The parameters of the Standard Application are explained in
●    Programmable protections                                                    Appendix A of application manual.
●    Programmable digital/analog input/output function                           The explanations are arranged according to the parameter
                                                                                 number. For the DI function, we use Terminal programming
●    Programmable start/stop signal logic                                        method to function (TTF), where there is a fixed input that
●    Voltage and current limiters                                                gets programmed to a list of functions. This allows for
                                                                                 multiple inputs to be used for different functions. Connecting
●    Energy Savings Calculator                                                   a certain input with a certain parameter function is done by
●    Two independent set of Acceleration/Deceleration ramps                      give a parameter an appropriate value. The value is formed
                                                                                 by the location of the input, either being on the standard
●    Skip frequency                                                              control board or an external option board and the slot it is
                                                                                 located in.
●    Start source (Local/Remote control function)
●    Reference source
●    Flying start
●    Volts per Hertz control programmable
●    Real time clock—RTC time display
●    Auto restart on fault to drive or bypass
●    Programmable switching frequency
●    Multi-preset speeds
●    Fan control
●    DC brake

10                  Variable Speed Drives Series III   LIT-12012996—April 2018   www.johnsoncontrols.com
                                                                                                  Step 5—Standard Parameter List

Force Open/Force Close Selection                                       Option Board digIN Selection
The Force Open Selection would make the selected function              This allows Assignment of a hardware digital input on an
always off. Essentially this is a virtual switch that is always        option card to a function, this is set in a format of DigIN:
open. The Force Close Selection would make the selected                Y:IO1:X where Y is the slot the option card is inserted on the
function always on. Essentially this is a virtual switch that is       Main control board and X is the Input on the Board and IO1 is
always closed. These options are assigned to a function if we          the type of option board used.
want to force a state without using a hardware input.
The standard options are DigIn: Force Open—indication that             Example:
the parameter function is always going to be open, that being          If we set Run Enable to DigIN:A:IO5:6 the drive will be
said depending on the logic of the function this could mean            enabled when digital input 6 is closed on the IO5 option card
the function is always not active or always active. When the           which is inserted in Slot A, and would not be enabled when
selection of a function is DigIN: Force Closed—indication that         digital input 6 on the option card is open.
the parameter function is always going to be closed, that
being said again depending on the location of the function
this could mean the function is always active or not active.           Timer Channel Selection
Examples of these options would be ID190 Start Signal 1,
when set to “Force Open” and the drive is                              A Time Channel is a virtual path to link the digital output of a
                                                                       timer function to a digital input function. To utilize this feature
looking at I/O terminals for control, in this case the drive           a timer or interval would need to be assigned to a time
would never start since this Function is always Open. If this          channel 1 through 3, and the input function to be controlled
function is set to “Force closed” the drive would always be            would need to be assigned to the same time channel.
in a start mode when in that control location.
                                                                       Example:
Example:
                                                                       If we set Run Enable to DigIN:TimeChannel1 the drive will be
If we set Run Enable to Force Closed the drive is always               enabled when the timer assigned to Time Channel 1 is active
enabled. If we set the same function to Force Open the drive           or High, and would not be enabled when the Time Channel is
would never be Enabled. If a Digital input is to be used to            inactive or Low.
activate this Run Enable the function should be assigned to
a hardware input (See below for DIGIN Selections).
                                                                       Table 6. Drive Communication Ports
DIGIN Selection                                                        Port                                         Communication
                                                                       RJ45 Keypad Port
This allows Assignment of a hardware digital input to a
function, this is set in a format of DigIN:X where X is one            Upload/Download Parameters                   USB to RJ45
of the 8 Digital inputs on the Main control board.                     Remote Mount Keypad                          Ethernet
                                                                       Upgrade Drive Firmware                       USB to RJ45
Example:
                                                                       RJ45 Ethernet Port
If we set Run Enable to DigIN:6 the drive will be enabled
when digital input 6 (Terminal 8) is closed, and would not             Upload/Download Parameters                   Ethernet
be enabled when digital input 6 (Terminal 8) is open.                  BACnet/IP Communications                     Ethernet
                                                                       Modbus TCP Communications                    Ethernet
                                                                       RS-485 Serial Port 1
                                                                       Upload/Download Parameters
                                                                        Upgrade Drive Firmware                      Two-Wire Twisted Pair
                                                                        Modbus RTU Communications                   Two-Wire Twisted Pair
                                                                        BACnet MS/TP Communications                 Two-Wire Twisted Pair
                                                                        SA Bus                                      Two-Wire Twisted Pair
                                                                       Note
                                                                       1 Shielded wire recommended.

                                             Variable Speed Drives Series III LIT-12012996—April 2018   www.johnsoncontrols.com             11
Step 5—Standard Parameter List

Control I/O Configuration
●    Run 240 Vac and 24 Vdc control wiring in separate conduit
●    Communication wire to be shielded
Table 7. Analog Signals/Galaxy I/O Interface

External                   Signal                                                Default
Wiring 1          Pin      Name             Signal                               Setting                   Description
                  1        +10V             Ref. Output Voltage                  —                         10 Vdc Supply Source
        Res       2        AI1+ 2           Analog Input 1                       0–10V                     Voltage Speed Reference (Programmable to 4 mA to 20 mA)
                  3        AI1–             Analog Input 1 Ground                —                         Analog Input 1 Common (Ground)
                  4        AI2+ 2           Analog Input 2                       4 mA to 20 mA             Current Speed Reference (Programmable to 0–10V)
              i
                  5        AI2–             Analog Input 2 Ground                —                         Analog Input 2 Common (Ground)
                  6        GND              I/O Signal Ground                    —                         I/O Ground for Reference and Control
                  7        DIN5             Digital Input 5                      Preset Speed B0           Sets frequency output to Preset Speed 1
                  8        DIN6             Digital Input 6                      Fire Mode                 Enables drive into Fire Mode
                  9        DIN7             Digital Input 7                      Bypass Start (TI–)        Enables drive into Bypass mode waiting for drive start
                  10       DIN8             Digital Input 8                      Force Auto (TI+)          Input forces drive into Auto Control place
                  11       CMB              DI5 to DI8 Common                    Grounded                  Allows source input
                  12       GND              I/O Signal Ground                    —                         I/O Ground for Reference and Control
                  13       24V              +24 Vdc Output                       —                         Control voltage output (100 mA max.)
                  14       DO1              Digital Output 1                     Ready                     Shows the drive is ready to run
                  15       24Vo             +24 Vdc Output                       —                         Control voltage output (100 mA max.)
                  16       GND              I/O Signal Ground                    —                         I/O Ground for Reference and Control
                  17       AO1+             Analog Output 1                      Output Frequency          Shows Output frequency to motor 0–60 Hz (4 mA to 20 mA)
                  18       AO2+             Analog Output 2                      Motor Current             Shows Motor current of motor 0–FLA (4 mA to 20 mA)
                  19       24Vi             +24 Vdc Input                        —                         External control voltage input
                  20       DIN1             Digital Input 1                      Run Forward               Input starts drive in forward direction (start enable)
                  21       DIN2             Digital Input 2                      Run Reverse               Input starts drive in reverse direction (start enable)
                  22       DIN3             Digital Input 3                      External Fault            Input causes drive to fault
                  23       DIN4             Digital Input 4                      Fault Reset               Input resets active faults
                  24       CMA              DI1 to DI4 Common                    Grounded                  Allows source input
                  25       A/+              RS-485 Signal A                      —                         Fieldbus Communication (Modbus, BACnet, SA Bus)
                  26       B/–              RS-485 Signal B                      —                         Fieldbus Communication (Modbus, BACnet, SA Bus)
                  27       R3NO             Relay 3 Normally Open                Fault                     Relay output 3 shows VFD is Faulted
                  28       R1NC             Relay 1 Normally Closed              Bypass Run                Relay output 1 shows VFD is in a bypass run state
                  29       R1CM             Relay 1 Common
                  30       R1NO             Relay 1 Normally Open
                  31       R3CM             Relay 3 Common                       Fault                     Relay output 3 shows VFD is Faulted
                  32       R2NC             Relay 2 Normally Closed              Run                       Relay output 2 shows VFD is in a drive run state
                  33       R2CM             Relay 2 Common
                  34       R2NO             Relay 2 Normally Open
Notes
1 The above wiring demonstrates a SINK configuration. It is important that CMA and CMB are wired to ground (as shown by dashed line).
  If a SOURCE configuration is desired, wire 24 V to CMA and CMB and close the inputs to ground. When using the +10 V for AI1, it is
  important to wire AI1—ground (as shown by dashed line). If using +10 V for AI1 or AI2, terminals 3, 5, and 6 need to be jumpered together.
2 AI1+ and AI2+ support 10K potentiometer.

12                      Variable Speed Drives Series III        LIT-12012996—April 2018      www.johnsoncontrols.com
                                                                                                              Step 5—Standard Parameter List

Basic Application—Parameters List
On the next pages you will find the lists of parameters within the respective parameter
groups. The parameter descriptions are given in Appendix A of application manual. The
descriptions are arranged according to the parameter number.
Column explanations:
Code = Location indication on the keypad; shows the operator the present parameter number
Parameter = Name of parameter
Min = Minimum value of parameter
Max = Maximum value of parameter
Unit = Unit of parameter value; given if available
Default = Value preset by factory
ID = ID number of the parameter

Monitor

Table 8. Basic—M1
Code          Parameter                    Min.            Max.            Unit           Default              ID              Note
M1.1          Output Frequency                                             Hz                                  1
M1.2          Freq Reference                                               Hz                                  24
M1.3          Motor Speed                                                  rpm                                 2
M1.4          Motor Current                                                A                                   3
M1.5          Motor Torque                                                 %                                   4
M1.6          Motor Power                                                  %                                   5
M1.7          Motor Voltage                                                V                                   6
M1.8          DC-link Voltage                                              V                                   7
M1.9          Unit Temperature                                             °C                                  8
M1.10         Motor Temperature                                            %                                   9
M1.11         Latest Fault Code                                                                                28
M1.12         Instant Motor Power                                          kW                                  1686
M1.13         RTC Battery Status                                                                               583             0 = Not Installed
                                                                                                                               1 = Installed
                                                                                                                               2 = Change Battery
                                                                                                                               3 = OverVoltage

Notes                                                                             3 Input function is Level sensed.
1 Parameter value can only be changed after the drive has stopped.                4 Input function is Edge sensed.
2 Parameter value will be set to be default when changing macros.                 5 Input function is Edge sensed when using StartP/StopP start logic.

                                                     Variable Speed Drives Series III LIT-12012996—April 2018         www.johnsoncontrols.com            13
Step 5—Standard Parameter List

Table 9. IO Status—M2
Code          Parameter                      Min.          Max.            Unit           Default              ID           Note
M2.1          Analog Input 1                                               Varies                              10
M2.2           Analog Input 2                                              Varies                              11
M2.3           Analog Output 1                                             Varies                              25
M2.4           Analog Output 2                                             Varies                              575
M2.5          DI1, DI2, DI3                                                                                    12
M2.6          DI4, DI5, DI6                                                                                    13
M2.7          DI7, DI8                                                                                         576
M2.8           DO1,Virtual RO1,Virtual RO2                                                                     14
M2.9           RO1, RO2, RO3                                                                                   557

Table 10. Optional Boards—M3
Code          Parameter                      Min.          Max.            Unit           Default              ID           Note
M3.1          PT100 Temperature                                            °C             1000.0               27

Table 11. Energy Savings—M4
Code          Parameter                      Min.          Max.            Unit           Default              ID           Note
M4.1 2        Energy Savings                                               Varies         0.000                2120

Table 12. FB Monitor Menu—M5
Code          Parameter                      Min.          Max.            Unit           Default              ID           Note
M5.1           Control Board DIDO Status                                                                       2209         Bit 0 = DIN1 Status
                                                                                                                            Bit 1 = DIN2 Status
                                                                                                                            Bit 2 = DIN3 Status
                                                                                                                            Bit 3 = DIN4 Status
                                                                                                                            Bit 4 = DIN5 Status
                                                                                                                            Bit 5 = DIN6 Status
                                                                                                                            Bit 6 = DIN7 Status
                                                                                                                            Bit 7 = DIN8 Status
                                                                                                                            Bit 8 = DO1 Status
                                                                                                                            Bit 9 = RO1 Status
                                                                                                                            Bit 10 = RO2 Status
                                                                                                                            Bit 11 = RO3 Status
                                                                                                                            Bit 12 = Slot A with Board
                                                                                                                            Bit 13 = Slot B with Board
                                                                                                                            Bit 14–15 = Not used

Notes                                                                             3 Input function is Level sensed.
1 Parameter value can only be changed after the drive has stopped.                4 Input function is Edge sensed.
2 Parameter value will be set to be default when changing macros.                 5 Input function is Edge sensed when using StartP/StopP start logic.

14                  Variable Speed Drives Series III   LIT-12012996—April 2018    www.johnsoncontrols.com
                                                                                                              Step 5—Standard Parameter List

Table 11. FB Monitor Menu—M5, continued
Code          Parameter                    Min.            Max.            Unit           Default              ID              Note
M5.2          SlotA DIDO Status                                                                                2210            Bit 0 = IO1_DIN1 Status
                                                                                                                               Bit 1 = IO1_DIN2 Status
                                                                                                                               Bit 2 = IO1_DIN3 Status
                                                                                                                               Bit 3 = IO1_DO1 Status
                                                                                                                               Bit 4 = IO1_DO2 Status
                                                                                                                               Bit 5 = IO1_DO3 Status
                                                                                                                               Bite 6 = IO3_RO1 Status
                                                                                                                               Bit 7 = IO3_RO2 Status
                                                                                                                               Bit 8 = IO3_RO3 Status
                                                                                                                               Bit 9 = IO5_AC1 Status
                                                                                                                               Bit 10 = IO5_AC2 Status
                                                                                                                               Bit 11 = IO5_AC3 Status
                                                                                                                               Bit 12 = IO5_AC4 Status
                                                                                                                               Bit 13 = IO5_AC5 Status
                                                                                                                               Bit 14 = IO5_AC6 Status
                                                                                                                               Bit 15 = Not Used
M5.3          SlotB DIDO Status                                                                                2211            Bit 0 = IO1_DIN1 Status
                                                                                                                               Bit 1 = IO1_DIN2 Status
                                                                                                                               Bit 2 = IO1_DIN3 Status
                                                                                                                               Bit 3 = IO1_DO1 Status
                                                                                                                               Bit 4 = IO1_DO2 Status
                                                                                                                               Bit 5 = IO1_DO3 Status
                                                                                                                               Bite 6 = IO3_RO1 Status
                                                                                                                               Bit 7 = IO3_RO2 Status
                                                                                                                               Bit 8 = IO3_RO3 Status
                                                                                                                               Bit 9 = IO5_AC1 Status
                                                                                                                               Bit 10 = IO5_AC2 Status
                                                                                                                               Bit 11 = IO5_AC3 Status
                                                                                                                               Bit 12 = IO5_AC4 Status
                                                                                                                               Bit 13 = IO5_AC5 Status
                                                                                                                               Bit 14 = IO5_AC6 Status
                                                                                                                               Bit 15 = Not Used
M5.4          Application Status Word                                                                          29              Bit 0 = MC Ready
                                                                                                                               Bit 1 = MC_Run
                                                                                                                               Bit 2 = MC_Fault
                                                                                                                               Bit 3 = FB_Ref_Active
                                                                                                                               Bit 4 = MC_Stopping
                                                                                                                               Bit 5 = MC_Reverse
                                                                                                                               Bit 6 