VA9204-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators Installation Guide

Вид документаІнструкція з монтажу
ВиробникJCI
Код документаva9204-agx-2z-series-on-off-and-floating-point-electric-spring-return-valve
Група обладнанняM9000-342 Weather Shield
Сторінок12
Мова документаанглійська
Розмір файлу3.1 МБ

Текст документа

VA9204-AGA-2Z, VA9204-AGB-2Z
VA9204-AGx-2Z Series On/Off and Floating Point Electric Spring
Return Valve Actuators
Installation Guide                                                                                          LIT-12014316 Rev. —
                                                                                                                      July 2023

Applications                                                     Installation
VA9204-AGx-2Z Series on/off and floating point electric spring Install the ball valve with the actuator at or above the center
return actuators are direct-mount valve actuators that operate line of the horizontal piping (see Figure 1).
on 24 VAC/VDC power. These bidirectional actuators are
used to provide accurate positioning on Johnson Controls®        IMPORTANT: In steam applications, install the valve with
VG1000 Series 1/2 in., 3/4 in., and 1 in. (DN15, DN20, and       the stem horizontal to the piping. Failure to follow this
DN25) ball valves in HVAC applications.                          precaution may shorten the life of the actuator.
                                                               Figure 1: Mounting positions for chilled water and
An integral line voltage auxiliary switch, available only on   condensing atmosphere applications
the VA9204-AGB-2Z models, indicates end-stop position,
or performs switching functions within the selected rotation
range.

VA9204-AGA-2Z actuators includes plenum-rated cables and
are specially configured for installation in spaces used for
environmental air-handling purposes other than ducts and
plenums as specified in National Fire Protection Association
(NFPA) 70: National Electrical Code (NEC) section 300.22(C),
Other Space Used for Environmental Air. The space over a
hung ceiling used for environmental air handling purposes is
an example of the type of space for which these actuators are
configured.
 IMPORTANT: Use this VA9204 Series valve actuator only
 to control equipment under normal operating conditions.
 Where failure or malfunction of the VA9204 Series
 valve actuator could lead to personal injury or property
 damage to the controlled equipment or other property,
 additional precautions must be designed into the control
 system. Incorporate and maintain other devices, such as
 supervisory or alarm systems or safety or limit controls,
 intended to warn of or protect against failure or malfunction
 of the VA9204 Series valve actuator.

 IMPORTANT : Utiliser ce VA9204 Series valve actuator                IMPORTANT: Do not install or use this VA9204 Series
 uniquement pour commander des équipements dans                      valve actuator in or near environments where corrosive
 des conditions normales de fonctionnement. Lorsqu’une               substances or vapors could be present. Exposure of
 défaillance ou un dysfonctionnement du VA9204 Series                the actuator to corrosive environments may damage the
 valve actuator risque de provoquer des blessures                    device’s internal components, and will void the warranty.
 ou d’endommager l’équipement contrôlé ou un autre
 équipement, la conception du système de contrôle doit           Special tools needed
 intégrer des dispositifs de protection supplémentaires.         • Digital voltmeter
 Veiller dans ce cas à intégrer de façon permanente              • T-20 TORX® driver
 d’autres dispositifs, tels que des systèmes de supervision
 ou d’alarme, ou des dispositifs de sécurité ou de limitation,
 ayant une fonction d’avertissement ou de protection en cas
 de défaillance ou de dysfonctionnement du
 VA9204 Series valve actuator.

                                                                 1                                          LIT-12014316 Rev. —
VA9204-AGA-2Z, VA9204-AGB-2Z
Dimensions
Valve actuator
See Table 1, Table 2, and Figure 2 for the dimensions of the VA9204 Series-actuated ball valves.
Figure 2: Spring return VA9204-actuated VG1241, VG1245, VG1841, and VG1845 Series ball valve dimensions,
in. (mm)

                                                                         3 1/2 (89)

                                                                         Clearance required

       3 1/4 (82)                                  2 7/8 (73)

                                                                                                           F
                                A
                                                                                                                            Port marking
                                                                                                                            locations

                                                                                                       C

                                                                 D
                                                                                                                       E                   G
                                                                                                                                                               B
Table 1: VA9204-actuated VG1241, VG1245, VG1841, and VG1845 Series ball valve dimensions, in. (mm)
Valve size,                 A                  B                        C                      D                   E                 F                  G
in. (DN)
1/2 (DN15)                                                                             6 31/32 (177)       2 33/64 (64)                         1 1/4 (32)
                    4 5/8 (117)     21/32 (17)                  1 7/32 (31)
3/4 (DN20)                                                                             7 1/8 (181)         2 51/64 (71)    11/32 (9)            1 13/32 (36)
1 (DN25)            4 11/16 (119)   3/4 (19)                    1 19/64 (33)           7 31/64 (190)       3 13/32 (87)                         1 45/64 (43)

Note: Port A must always be connected to the coil.
Table 2: VA9204-actuated VG1271, VG1275, VG1871, and VG1875 Series sweat ball valve and VA9204-actuated
VG1291, VG1295, VG1891, and VG1895 Series press ball valve dimensions, in. (mm)
Valve size,                 A                  B                        C                      D                   E                 F                  G
in. (DN)
1/2 (DN15)                                                                             7 13/64 (183)       3 25/32 (96)                         1 1/4 (32)
                    4 5/8 (117)     21/32 (17)                  1 7/32 (31)
3/4 (DN20)                                                                             7 3/4 (197)         4 3/32 (104)    11/32 (9)            1 13/32 (36)
1 (DN25)            4 11/16 (119)   3/4 (19)                    1 19/64 (33)           8 3/16 (208)        4 41/64 (118)                        1 45/64 (43)

Note: Port A must always be connected to the coil.

                                                                                       2                                                   LIT-12014316 Rev. —
VA9204-AGA-2Z, VA9204-AGB-2Z
Valve actuator with thermal barrier
See Figure 3 and Table 3 for valve actuator dimensions with the optional M9000-561 Thermal Barrier installed.
Figure 3: Spring return VA9204-actuated VG1241, VG1245, VG1841, and VG1845 Series ball valve with the optional
M9000-561 Thermal Barrier installed dimensions, in. (mm)

                                                                         3 1/2 (89)

                                                                         Clearance required

      3 1/4 (82)                                    2 7/8 (73)

                             A                                                                             F

                                                                                                                            Port marking
                                                                                                                            locations

                                                                                                      C

                                                                 D                                                                         G
                                                                                                                      E
                                                                                                                                                              B
Table 3: VA9204-actuated VG1241, VG1245, VG1841, and VG1845 Series NPT ball valve with the optional thermal
barrier installed dimensions, in. (mm)
Valve size,                  A                  B                    C                        D                   E               F                    G
in. (DN)
1/2 (DN15)                                                                            6 31/32 (177)       2 33/64 (64)                         1 1/4 (32)
                   6 (152)           21/32 (17)             1 7/32 (31)
3/4 (DN20)                                                                            7 1/8 (181)         2 51/64 (71)    11/32 (9)            1 13/32 (36)
1 (DN25)           6 1/16 (154)      3/4 (19)               1 19/64 (33)              7 31/64 (190)       3 13/32 (87)                         1 45/64 (43)

Note: Port A must always be connected to the coil.
Repair information
A number of replacement parts are available; see Table 4 for more details. If a VA9204 Series electric actuator fails to
operate within its specifications, replace the unit. For a replacement electric actuator, contact the nearest Johnson Controls
representative.
Accessories
Table 4: Accessories (order separately)
Code number           Description
M9000-560             Ball valve linkage kit for applying M9203, M9204 and M9208 Series actuators to VG1000 Series valves (quantity: 1)
M9000-561             Thermal barrier extends M(VA)9104, M(VA)9203, M(VA)9204, and M(VA)9208 Series electric spring return actuator applications to
                      include low pressure steam (quantity: 1)
M9000-342             Weathershield kit for VG1000 Series ball valve application of VA9104, VA9203, VA9204, and VA9208 Series electric actuators
                      (quantity: 1)
M9000-607             Position indicator for VG1000 Series ball valve applications (quantity: 5)
M9000-700             Universal ball valve linkage kit (quantity: 1)

                                                                                      3                                                LIT-12014316 Rev. —
VA9204-AGA-2Z, VA9204-AGB-2Z
Mounting                                                        4. Insert the drive shaft into Side B (Figure 6). The drive shaft
Mounting the actuator to spring return Port A (coil) open          is keyed for one-way assembly. With gentle pressure
To mount the actuator to spring return Port A (coil) open:         applied, rotate the drive shaft until the key aligns and the
                                                                   drive shaft falls into place.
1. Turn the valve stem to the position outlined in Figure 4.    Figure 6: Inserting the drive shaft
Figure 4: Positioning the valve stem

             2-way                            3-way
2. Mount the optional M9000-561 Thermal Barrier to the valve
   if fluid temperature exceeds 212°F (100°C). See the
   Mounting the thermal barrier section for more information.

Note: Proceed to Step 7 if the ball valve linkage is on actuator 5. Install the linkage base on Side B using the two
Side B.                                                             #8‑32 x 0.625 in. long screws (Figure 7). Tighten the
                                                                    linkage screws to a torque of 29 lb·in. to 33 lb·in.
3. Remove the linkage from Side A (Figure 5).                       (3.3 N•m to 3.7 N•m).
Figure 5: Removing the linkage                                   Figure 7: Installing the linkage

                                                                4                                         LIT-12014316 Rev. —
VA9204-AGA-2Z, VA9204-AGB-2Z
6. Insert the fixed pointer and M4x0.7x83 mm long screw into        Mounting the actuator to spring return Port A (coil)
   the Side A actuator hub (Figure 8). Direct the arrow on the      closed
   pointer to 100%.                                                 To mount the actuator to spring return Port A (coil) closed:
Figure 8: Installing the fixed pointer
                                                                    1. Turn the valve stem to the position outlined in Figure 10.
                                                                    Figure 10: Positioning the valve stem

                                                                                 2-way                            3-way
                                                                    2. Mount the optional M9000-561 Thermal Barrier to the valve
                                                                       if fluid temperature exceeds 212°F (100°C). See the
                                                                       Mounting the thermal barrier section for more information.

                                                                    Note: Proceed to Step 7 if the ball valve linkage is on actuator
                                                                    Side A.

                                                                    3. Remove the linkage from Side B (Figure 11).
                                                                    Figure 11: Removing the linkage
7. Install the actuator on the ball valve (Figure 9). Tighten the
   actuator mounting screw to a torque of 10 lb·in. to 12 lb·in.
   (1.1 N•m to 1.4 N•m) and snap the large adjustable pointer
   into place.
Figure 9: Mounting the actuator

                                                                    5                                        LIT-12014316 Rev. —
VA9204-AGA-2Z, VA9204-AGB-2Z
4. Insert the drive shaft into Side A (Figure 12). The drive shaft 6. Insert the fixed pointer and M4x0.7x83 mm long screw into
   is keyed for one-way assembly. With gentle pressure                the Side B actuator hub (Figure 14). Direct the arrow on the
   applied, rotate the drive shaft until the key aligns and the       pointer to 0%.
   drive shaft falls into place.                                   Figure 14: Installing the fixed pointer
Figure 12: Inserting the drive shaft

5. Install the linkage base on Side A using the two
   #8-32 x 0.625 in. long screws (Figure 13). Tighten the
   linkage screws to a torque of 29 lb·in. to 33 lb·in.
   (3.3 N•m to 3.7 N•m).
Figure 13: Installing the linkage
                                                                 7. Install the actuator on the ball valve (Figure 15). Tighten the
                                                                    actuator mounting screw to a torque of 10 lb·in. to 12 lb·in.
                                                                    (1.1 N•m to 1.4 N•m) and snap the large adjustable pointer
                                                                    into place.
                                                                 Figure 15: Mounting the actuator

                                                                6                                          LIT-12014316 Rev. —
VA9204-AGA-2Z, VA9204-AGB-2Z
Mounting the thermal barrier                                          2. Rotate the drive shaft to align marks on the top of the
Figure 16 shows the optional M9000-561 Thermal Barrier.                  thermal drive shaft with matching marks on the valve stem.
Figure 16: Optional M9000-561 Thermal Barrier                         3. Mount the thermal barrier onto the valve using the four
                                                                         included M5x16 mm machine screws and four M5 flange
                         Machine screws                                  nuts. Tighten the screws to a torque of 21 lb·in. to 25 lb·in.
                                                                         (2.4 N•m to 2.8 N•m) (Figure 18).
                                                                      Figure 18: Installing the barrier

                                                        Flange
                                                        nuts

Barrier
                                                          Drive
                                                          shaft

To mount the optional thermal barrier:

1. Install the thermal barrier drive shaft into the thermal barrier
   by aligning the tab on the drive shaft with the slot on the
   thermal barrier (Figure 17).
Figure 17: Installing the drive shaft into the thermal
barrier
                                                                      4. Proceed to actuator mounting instructions. Follow the same
                                                                         steps as mounting directly to the valve when mounting the
                                                                         actuator to the thermal barrier.

                                                                  7                                             LIT-12014316 Rev. —
VA9204-AGA-2Z, VA9204-AGB-2Z
Wiring                                                                   Figure 20: Auxiliary switch wiring diagram
See Figure 19 and Figure 20 to wire the applicable                                 5.0 (2.9) A 240 V
VA9204‑AGx-2Z Series model.                                                              21
                                                                                                 S1

Figure 19: Control wiring diagrams                                           23

Floating control, four wire          Open/close, single wire control         22
                                                                                         21

                     RA RA                                  RA RA             BLK /     BLK /    BLK /
                                                                              RED       BLU      GRY
                   DA         DA                       DA         DA
                                                                                  21     22       23
   BLK RED GRY ORN                      BLK RED GRY ORN
     1       2       3        4           1       2         3      4

                                                                             COM NC               NO

                                                                                       WARNING: Risk of electric shock.
                                                                                       Disconnect or isolate all power supplies before
     T       ~           24 VAC           T       ~             24 VAC                 making electrical connections. More than one
      -      +           24 VDC           -       +             24 VDC
                                                                                       disconnection or isolation may be required to
On/off control, two wire
                                                                                       completely de-energize equipment. Contact with
                     RA RA                                                             components carrying hazardous voltage can cause
                                                                                       electric shock and may result in severe personal
                   DA         DA                                                       injury or death.
   BLK RED GRY ORN
     1       2       3        4                                                        AVERTISSEMENT : Risque de décharge
                                                                                       électrique.
                                                                                       Débrancher ou isoler toute alimentation
                                                                                       avant de réaliser un raccordement électrique.
                                                                                       Plusieurs isolations et débranchements sont
                                                                                       peut-être nécessaires pour couper entièrement
                                                                                       l’alimentation de l’équipement. Tout contact avec
                                                                                       des composants porteurs de tensions dangereuses
     T               ~ 24 VAC                                                          risque d’entraîner une décharge électrique et de
      -              + 24 VDC
                                                                                       provoquer des blessures graves, voire mortelles.
Floating control, multiple actuators with one transformer

                     RA RA                                  RA RA                      CAUTION: Risk of property damage.
                   DA         DA                       DA         DA                   Do not apply power to the system before checking
                                                                                       all wiring connections. Short circuited or improperly
   BLK RED GRY ORN                      BLK RED GRY ORN                                connected wires may result in permanent damage
     1       2       3        4           1       2         3      4                   to the equipment.

                                                                                       MISE EN GARDE : Risque de dégâts matériels.
                                                                                       Ne pas mettre le système sous tension avant
                                                                                       d’avoir vérifié tous les raccords de câblage.
                                                                                       Des fils formant un court-circuit ou connectés
                                                                                       de façon incorrecte risquent d’endommager
                                                                                       irrémédiablement l’équipement.

     T       ~           24 VAC
      -      +           24 VDC

                                                                         8                                             LIT-12014316 Rev. —
VA9204-AGA-2Z, VA9204-AGB-2Z
         CAUTION: Risk of property damage.                         Setup and adjustments
         Insulate and secure each unused wire lead before          Mode selection switch
         applying power to the actuator. Failure to insulate       Actuators have an external mode selection switch to reverse
         and secure each unused wire lead may result in            control logic. The switch is accessible from both A and B sides
         property damage.                                          of the actuator as illustrated in Figure 22. You can switch the
                                                                   factory-set Direct Acting (DA) mode to Reverse Acting (RA)
         MISE EN GARDE : Risque de dégâts matériels.               mode.
         Isoler et protéger chaque fil non utilisé avant de        Figure 22: Mode selection
         mettre l’actuator sous tension. Le non-respect
         de cette obligation d’isolation et de protection de
         chaque fil non utilisé risque d’entraîner des dégâts
         matériels.
                                                                       DA                  RA RA                            DA
 IMPORTANT: Make all wiring connections in accordance
                                                                         Side A of actuator               Side B of actuator
 with the National Electrical Code and local regulations. Use
                                                                   Control response
 proper Electrostatic Discharge (ESD) precautions during
                                                                   The installation side of the actuator and the position of the
 installation and servicing to avoid damaging the electronic
                                                                   mode selection switch combine to determine control response
 circuits of the actuator.
                                                                   from the actuator. See Figure 23.
Using conduit                                                      Figure 23: Control response
All VA9204 Series actuators accept 1/2 in. threaded
electrician’s fittings (Figure 21).                                                                 Installation side
Figure 21: Adding flexible metal conduit

                                                                                                      A          B
                                                                                                 Mode selection switch
                                                                        Control inputs
                                                                        GRY       ORN
                                                                         3         4     DA             RA     RA           DA
1. Feed the actuator cables through the field-supplied
                                                                       CLOSED    OPEN
   electrician’s fitting and conduit.
2. Thread the electrician’s fitting into the actuator and secure       OPEN     CLOSED
   the conduit to the fitting in accordance with local building
   code requirements.                                                  OPEN      OPEN     STOP      STOP        STOP     STOP

                                                                       CLOSED   CLOSED

                                                                   9                                         LIT-12014316 Rev. —
VA9204-AGA-2Z, VA9204-AGB-2Z
Auxiliary switch (VA9204-xxB-xx models)                             The switch point is continuously adjustable throughout the
The VA9204-xxB-xx models include one integral auxiliary             actuator’s rotation range. For the most accurate switch
switch with a switch adjuster accessible on either face             positioning, see Figure 24 and use the method in the following
of the actuator (Figure 24). The factory setting for the            example. To change the switch point of auxiliary switch:
auxiliary switch is 10% closing (relative to the 0% to 100%
rotation range as printed on the product label). See the            1. Position the actuator in the full spring return position.
Technical specifications table for the auxiliary switch ratings.
                                                                    Note: The switch is factory set to trip when the actuator
         WARNING: Risk of electric shock and property
                                                                    reaches the 10% position.
         damage.
         Insulate and secure each unused wire lead before
                                                                    2. Rotate the switch adjuster until it points to the desired
         applying power to the actuator. Failure to insulate
                                                                       switch point.
         and secure each unused wire lead may result
                                                                    3. Connect the auxiliary switch to a power source or an
         in property damage, electric shock, and severe
                                                                       ohmmeter and apply power to the actuator. The actuator
         personal injury or death.
                                                                       moves to the fully open position and holds while power is
                                                                       applied.
         AVERTISSEMENT : Risque de décharge
                                                                    4. Observe the switch point. If required, repeat Step 1 through
         électrique et dégâts matériels.
                                                                       Step 3.
         Isoler et protéger chaque fil non utilisé avant de
                                                                    Figure 24: Switch trip point settings
         mettre l’actuator sous tension. Le non-respect
         de cette obligation d’isolation et de protection
         de chaque fil non utilisé risque d’entraîner des
         dégâts matériels, des décharges électriques et des
         blessures graves, voire mortelles.

                                                                   10                                          LIT-12014316 Rev. —
VA9204-AGA-2Z, VA9204-AGB-2Z
Technical specifications
VA9204-AGx-2Z Series On/Off and Floating Point Electric Spring Return Actuators
Specification                            Description
Power requirements                       24 VAC (19.2 VAC to 28.8 VAC) at 50/60 Hz: Class 2 (North America) or Safety Extra-Low Voltage (SELV) (Europe), 5.1 VA running,
                                         2.8 VA holding position 24 VDC (21.6 VDC to 28.8 VDC): Class 2 (North America) or SELV (Europe) 1.9 W running, 1.1 W holding.
                                         Holding position minimum transformer size: 6 VA for each actuator
Input signal/adjustments                 19.2 VAC to 28.8 VAC at 50/60 Hz or 24 VDC +20%/-10%
                                         Class 2 (North America) or SELV (Europe). Minimum pulse width: 500 ms
Control input impedance                  4,700 ohm control inputs
Auxiliary switch    -xxB models          One single-pole, double-throw (SPDT), double-insulated switch with silver contacts:
rating                                   24 VAC, 50 VA pilot duty
                                         120 VAC, 5.8 A resistive, 1/4 hp, 275 VA pilot duty
                                         240 VAC, 5.0 A resistive, 1/4 hp, 275 VA pilot duty
Spring return                            Direction is selectable with mounting position of actuator:
                                         Actuator face labeled A is away from valve: CCW spring return
                                         Actuator face labeled B is away from valve: CW spring return
                    Power on             35 lb·in. (4 N•m) all operating temperatures
                    (running)
Rated torque
                    Power off            35 lb·in. (4 N•m) all operating temperatures
                    (spring returning)
Rotation range                           Maximum full stroke: 95°
                    Power on             90 s constant for 0 lb·in to 35 lb·in. (4 N•m) load, at all operating conditions
Rotation time for   (running)
90 degrees of       Power off            12 s to 17 s for 0 lb·in to 35 lb·in. (4 N•m) load, at room temperature
travel              (spring returning)   16 s nominal at full rated load
                                         22 s maximum with 35 lb·in. (4 N•m) load, at -22°F (-30°C)
Life cycles                              60,000 full stroke cycles with 35 lb·in. (4 N•m) load, 1,500,000 repositions with 35 lb·in. (4 N•m) load
                    Power on             <37 dBA at 35 lb·in. (4 N•m) load, at a distance of 39 13/32 in. (1 m)
                    (running)
Audible noise       Power on             <20 dBA at a distance of 39 13/32 in. (1 m)
rating              (holding)
                    Power off            <56 dBA at 35 lb·in. (4 N•m) load, at a distance of 39 13/32 in. (1 m)
                    (spring returning)
Electrical          AGA-2Z models        36 in. (0.9 m) UL 444 Type CMP plenum-rated cable with 19 AWG (0.75 mm2) conductors and 1/4 in. (6 mm) ferrule ends
connections         AGB-2Z models        48 in. (1.2 m) UL 758 Type AWM halogen-free cable with 18 AWG (0.85 mm2) conductors and 1/4 in. (6 mm) ferrule ends
Conduit connections                      Integral 1/2 in. (13 mm) threaded conduit connectors
                    VG12x1 and           23°F to 203°F (-5°C to 95°C), not rated for steam service
                    VG18x1 Series
                    VG12x5 and           -22°F to 212°F (-30°C to 100°C), not rated for steam service
Fluid temperature   VG18x5 Series
limits              VG12x5 and           -22°F to 284°F (-30°C to 140°C) water; 15 psig (103 kPa) at 250°F (121°C) saturated steam
                    VG18x5 Series with
                    M9000-561 Thermal
                    Barrier installed
Ambient condi-      Standard operating   -22°F to 140°F (-30°C to 60°C); 90% RH maximum, non-condensing
tions               Storage              -40°F to 185°F (-40°C to 85°C); 95% RH maximum, non-condensing
Enclosure rating                         NEMA 2 (IP54) for all mounting directions
Compliance          United States        UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, Automatic Electrical Controls for Household and Similar Use;
                                         and UL 60730-2-14: 2002-02, Ed. 1, Part 2 Particular Requirements for Electric Actuators. Plenum Rated (UL 2043). Suitable for use
                                         in other environmental air space (plenums) in accordance with Section 300.22 (C) of the National Electric Code.

                    Canada               UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002, 3rd Ed., Automatic Electrical Controls for Household
                                         and Similar Use; and CSA C22.2 No. 24-93 Temperature Indicating and Regulating Equipment.

                    Europe               Johnson Controls declares that this products is in compliance with the essential requirements and other relevant provisions of the
                                         EMC Directive and Low Voltage Directive, and equivalent UK regulations.

                    Australia and        RCM Mark, Australia/NZ Emissions Compliant
                    New Zealand

                    -AGA models          2.0 lb (0.9 kg)
Shipping weight
                    -AGB models          2.4 lb (1.1 kg)

                                                                                       11                                                           LIT-12014316 Rev. —
VA9204-AGA-2Z, VA9204-AGB-2Z

Product warranty
This product is covered by a limited warranty, details of which can be found at www.johnsoncontrols.com/buildingswarranty.
Patents
Patents: https://jcipat.com
Single point of contact
 APAC                                               EU                           UK                               NA/SA
 JOHNSON CONTROLS                                   JOHNSON CONTROLS             JOHNSON CONTROLS                 JOHNSON CONTROLS
 C/O CONTROLS PRODUCT MANAGEMENT                    VOLTAWEG 20                  TYCO PARK                        5757 N GREEN BAY AVE.
 NO. 32 CHANGJIANG RD. NEW DISTRICT                 6101 XK ECHT                 GRIMSHAW LANE                    GLENDALE WI 53209
 WUXI JIANGSU PROVINCE 214028                       THE NETHERLANDS              MANCHESTER                       USA
 CHINA                                                                           M40 2WL
                                                                                 UNITED KINGDOM
For more contact information, refer to www.johnsoncontrols.com/locations.

Building Technologies & Solutions
Headquarters: Milwaukee, Wisconsin, USA
Branch offices: Principal cities worldwide
Johnson Controls® is a registered trademark of Johnson Controls.
All other marks herein are the marks of their respective owners.
© Copyright 2023 Johnson Controls. All rights reserved. Any unauthorized use or copying is strictly prohibited.
www.johnsoncontrols.com