VA9104-xGA-3S Series Electric Non-Spring Return Valve
Actuators
Installation Guide
VA9104-AGA-3S, VA9104-GGA-3S, VA9104-IGA-3S
                                                                                                      Issued March 2019

   Applications                                                Installation
   The VA9104 Series Actuators are direct-mount,               Install the ball valve with the actuator at or above the
   non-spring return electric valve actuators that operate     centerline of the horizontal piping (Figure 1).
   on AC 24 V power. These synchronous, motor-driven
   actuators are used to provide accurate positioning on        IMPORTANT: Do not install or use this VA9104
   Johnson Controls® VG1000 Series ball valves in               Series Electric Non-Spring Return Valve Actuator in
   Heating, Ventilating, and Air Conditioning (HVAC)            or near environments where corrosive substances or
   applications.                                                vapors could be present. Exposure of the electric
                                                                actuator to corrosive environments may damage the
   The VA9104 Series Electric Non-Spring Return                 internal components of the device, and will void the
   Actuators provide a running torque of 35 lbin (4 Nm).      warranty.
   The nominal travel time is 60 seconds at 60 Hz
   (72 seconds at 50 Hz) for 90° of rotation.                  Special tools
                                                               To install the actuator, use a digital voltmeter.
    IMPORTANT: Use this VA9104 Series Electric
    Non-Spring Return Valve Actuator only to control
    equipment under normal operating conditions.
    Where failure or malfunction of the electric actuator
    could lead to personal injury or property damage to
    the controlled equipment or other property,
    additional precautions must be designed into the
    control system. Incorporate and maintain other
    devices, such as supervisory or alarm systems or
    safety or limit controls, intended to warn of or protect
    against failure or malfunction of the electric actuator.
    IMPORTANT : Utiliser ce VA9104 Series Electric
    Non-Spring Return Valve Actuator uniquement pour
    commander des équipements dans des conditions
    normales de fonctionnement. Lorsqu'une défaillance

                                                                                                        FIG:mntpos_H2O_app
    ou un dysfonctionnement du electric actuator risque
    de provoquer des blessures ou d'endommager
    l'équipement contrôlé ou un autre équipement, la
    conception du système de contrôle doit intégrer des
    dispositifs de protection supplémentaires. Veiller          Figure 1: Mounting positions for chilled water
    dans ce cas à intégrer de façon permanente                     and condensing atmosphere applications
    d'autres dispositifs, tels que des systèmes de
    supervision ou d'alarme, ou des dispositifs de
    sécurité ou de limitation, ayant une fonction
    d'avertissement ou de protection en cas de
    défaillance ou de dysfonctionnement du electric
    actuator.

                                                                                   P/N 14-1336-23, Rev. L

                                                                                  *14133623L*
Accessories
Table 1: Accessories (order separately)
 Code number       Description
 M9000-561         Thermal Barrier extends M(VA)9104, M(VA)9203, M(VA)9208, and M(VA)9310 Series Electric Actuator
                   applications to Include low pressure steam (quantity 1)
 M9000-342         Weathershield Kit for VG1000 Series Ball Valve application of VA9104, VA9203, VA9208, and VA9310
                   Series Electric Spring Return Actuators (quantity 1)
 M9000-700         Universal Ball Valve Linkage Kit

Mounting the actuator                                                      4. Check that the actuator coupler and handle are in
1. Turn valve stem to position below.                                         the full counterclockwise position as viewed from
                                                                              the top of the actuator. If not, press the actuator
                                                                              gear release and rotate the handle until the
                                                                              actuator coupler is fully counterclockwise.
                                                                           5. Install the valve actuator over the ball valve
                                                                              mounting flange. Depending on the installation,
                                                                              position the assembly in any one of four 90°
                                                                              increments on the valve.

                                                              FIG:VG1000
                                                                               Note: For proper operation, the actuator must
           2 Way                          3 Way                                drive the valve counterclockwise to open Port A
                                                                               when viewed from above the valve
      Figure 2:    Positioning the valve stem

2. Mount optional M9000-561 Thermal Barrier to the
   valve if fluid temperature exceeds 212°F (100°C).
   See the Mounting the thermal barrier section for
   more information.
3. Place the handle the top of the drive shaft
   (Figure 3). The handle is keyed on and can only be
   mounted in one orientation.

                                                                                                                     FIG: CUPLACT

                                                                              Figure 4:   Coupling the actuator to the valve

                                                  FIG: hndl                6. To secure the actuator to the valve, use a 1/4 in.
                                                                              (6 mm) flat blade screwdriver. Recommended
          Figure 3:   Installing the handle                                   torque is 8 to 12 lbin (0.9 to 1.4 Nm).

                                                                            IMPORTANT: Do not overtighten the manual
                                                                            handle mounting screw. Overtightening may strip
                                                                            the threads resulting in damage to the valve stem
                                                                            threads.

                                                                                                       P/N 14-1336-23, Rev. L
Mounting the thermal barrier                                2. Rotate the drive shaft to align marks on the top of
Figure 5 shows the optional M9000-561 Thermal                  the thermal drive shaft with matching marks on the
Barrier.                                                       valve stem.
                     Machine Screws                         3. Mount the thermal barrier onto the valve using the
                                                               four included M5x16 mm machine screws and four
                                                               M5 flange nuts. Tighten the screws to a
                                                               recommended torque of 21 to 25 lb·in.
                                                               (2.4 to 2.8 N·m) (Figure 7).

                                    Flange
                                     Nuts
   Barrier

                                       Drive
                                       Shaft

 Figure 5:     Optional M9000-561 Thermal Barrier

To mount the optional thermal barrier:
1. Install the thermal barrier drive shaft into the
   thermal barrier by aligning the tab on the drive
                                                                                                     FIG:in_act
   shaft with the slot on the thermal barrier (Figure 6).

                                                                      Figure 7:   Installing the barrier

                                                            4. Proceed to Mounting the actuator. Follow the same
                                                               steps as mounting directly to the valve when
                                                               mounting the actuator to the thermal barrier.

             Figure 6: Installing the drive
              shaft into the thermal barrier

                                                                                       P/N 14-1336-23, Rev. L
Wiring

                                                         Risk of Property Damage.
Risk of Electric Shock.                                  Do not apply power to the system before checking all
Disconnect or isolate all power supplies before making   wiring connections. Short circuited or improperly
electrical connections. More than one disconnection or   connected wires may result in permanent damage to
isolation may be required to completely de-energize      the equipment.
equipment. Contact with components carrying
hazardous voltage can cause electric shock and may
result in severe personal injury or death.
                                                         Risque de dégâts matériels.
                                                         Ne pas mettre le système sous tension avant d'avoir
                                                         vérifié tous les raccords de câblage. Des fils formant
Risque de décharge électrique.                           un court-circuit ou connectés de façon incorrecte
Débrancher ou isoler toute alimentation avant de         risquent d'endommager irrémédiablement
réaliser un branchement électrique. Plusieurs            l'équipement.
isolations et débranchements sont peut-être
nécessaires pour -couper entièrement l'alimentation
de l'équipement. Tout contact avec des composants
conducteurs de tensions dangereuses risque
d'entraîner une décharge électrique et de provoquer
                                                         Risk of Property Damage.
des blessures graves, voire mortelles.
                                                         Insulate and secure each unused wire lead before
                                                         applying power to the [device]. Failure to insulate and
                                                         secure each unused wire lead may result in property
                                                         damage.

Risk of Electric Shock.
Disconnect the power supply before making electrical
connections to avoid electric shock.
                                                         Risque de dégâts matériels.
                                                         Isoler et protéger chaque fil non utilisé avant de mettre
                                                         l'[appareil] sous tension. Le non-respect de cette
                                                         obligation d'isolation et de protection de chaque fil non
Risque de décharge électrique.                           utilisé risque d'entraîner des dégâts matériels.
Débrancher l'alimentation avant de réaliser tout
raccordement électrique afin d'éviter tout risque de
décharge électrique.                                     IMPORTANT: Make all wiring connections in
                                                         accordance with the National Electrical Code and
                                                         local regulations. Use proper Electrostatic Discharge
                                                         (ESD) precautions during installation and servicing
                                                         to avoid damaging the electronic circuits of the
                                                         actuator.

                                                                                     P/N 14-1336-23, Rev. L
VA9104-AGA-3S and VA9104-IGA-3S                            Note: For all VA9104-AGA Series Actuators, use a
The VA9104-AGA and VA9104-IGA Series Electric              controller and/or software that provides a timeout
Non-Spring Return Valve Actuators require an AC 24 V       function at the end of rotation (stall) to avoid excessive
input signal and work with a variety of controllers.       wear or drive time on the actuator motor. The -GGA
These electric actuators include M3 Screw terminals;       and -IGA models have an auto shutoff feature to
see Figure 8 and Figure 9 to wire the applicable           prevent excessive wear or drive time on the motor.
VA9104 Series model.                                       VA9104-GGA-3S
                   ~           ~                           The VA9104-GGA Series Electric Non-Spring Return
                   3       1   2                           valve actuators require AC 24 V power and a
                                                           DC 0(2) to 10 V or 0(4) to 20 mA controller input signal.
                                                           These electric actuators include M3 screw terminals;
                                                           see Figure 10 for proper wiring.

                                                                                DC 0(2)...10 V Control
                                                                                              ~   0(2)...10 V
                                   ~AC 24 V 50/60 Hz                               1          2         3
            Figure 8: VA9104-AGA-3S
            and VA9104-IGA-3S Floating
              Control Wiring Diagram

                                                                                       AC               +
                                                                                       24 V   ~
                                                                                       DC 0(2)...10 V   Y
                       ~       ~
               1       2       3

                                                                               0(4)...20 mA Control with
                                                                                   External Resistor
                                                                                              ~   0(2)...10 V
                                                                                   1          2         3

                          ~ AC 24 V 50/60 Hz
             Figure 9: VA104-IGA-3S
                                                                                                        +
             Control Wiring Diagram,                                                   AC
                                                                                       24 V   ~
                      On/Off                                                           0(4)...20 mA
                                                                                                        Y

Note: When using the VA9104-AGA-1S or
VA9104-IGA-1S Series actuator with a controller                         Figure 10: VA9104-GGA-3S
featuring triac output, add a 4.7k ohm resistor one half                  Control Wiring Diagram
watt between the Common (COM) and
Counterclockwise (CCW) terminals.

                                                                                          P/N 14-1336-23, Rev. L
                                                                                                          For Reverse Acting (RA) operation, a minimum control
 Override to MIN position                 Override to MAX position                                        signal drives the actuator to the full CW position and a
    BLK RED GRY                             BLK RED GRY                                                   maximum signal drives the actuator to the full CCW
     1   2   3                               1   2   3                                                    position. To change the factory settings, remove the
                                                                                                          actuator cover and adjust the switches on the circuit
                                                                                                          board as shown in Figure 12.
                              +                                       +
           AC
          24 V   ~                                                                                        Setup and adjustments
                                                              B
                     A
                                                 AC                   C
                                                24 V    ~
         DC 0(2)...10 V   Y
                                               DC 0(2)...10 V         Y

   COM
                                           COM
 A Open = MIN Position
                                          B Closed = MAX Position
 A Closed = Normal Operation
                                          C Closed = Normal Operation

          Override to
  MIN, MID, MAX positions                         Override to                                                 Figure 12: VA9104-GGA Factory Switch Setting
  0(4)...20 mA Control with                 MIN, MID, MAX positions
      External Resistor                        0(2)...10 V Control
   BLK RED GRY                               BLK RED GRY
     1           2        3                   1   2   3

                                                                                                              Risk of Electric Shock.
                              +                                       +                                       Disconnect the power supply before making electrical
                     A                                        A
                                                                                                              connections to avoid electric shock.
                     B                                            B

           AC                                     AC
          24 V   ~                               24 V   ~

      0(4)...20 mA
                     C                             DC
                                                                  C                                           Risque de décharge électrique.
                          Y                                           Y
                                                0(2)...10 V
         500 Ω / 0.25 W                                                                                       Débrancher l'alimentation avant de réaliser tout
   COM                                     NCOM                                                               raccordement électrique afin d'éviter tout risque de
                                                                          B   C
  N
                                      C                           A
                                           O
                      A           B
  O                                        I
                                           T
                                                                                                              décharge électrique.
  I
  T
  C
  N
  U                                        C
                                           N
                                           U
                                           F
  F

 0% ( MIN︶                                0% ( MIN )

                                                                                  FIG:VA9104GGx2(Z)_wir
                                          50% ( MID )
 50% ( MID )
                                                                                                          Commissioning
 100% ( MAX )                             100% ( MAX )
                                          NORMAL
                                                                                                          After wiring is complete, apply power and provide input
 NORMAL
                                                                                                          signals to the actuator to drive it at least one complete
 Figure 11: VA9104-GGA Control Wiring Diagram                                                             cycle open and closed.
                  (Overrides)
                                                                                                          Troubleshooting
VA9104-GGA actuators are factory set for Direct                                                           If the VA9104 Series Electric Non-Spring Return Valve
Acting (DA) mode and for a DC 0 to 10 V input control                                                     Actuator is not responding or working properly:
signal. In DA mode, a minimum control signal drives                                                       •      Verify that the actuator assembly is properly
the actuator to the full CCW position, and a maximum                                                             secured to the valve.
control signal drives the actuator to the full Clockwise
(CW) position.                                                                                            •      Check that all electrical connections are complete
                                                                                                                 and that power is applied.
                                                                                                          •      Verify that the valve fully opens and closes, using
                                                                                                                 the gear release button on the actuator and the
                                                                                                                 manual override handle.

                                                                                                                                         P/N 14-1336-23, Rev. L
Repairs and replacement
If the VA9104 Series Electric Non-Spring Return Actuator fails to operate within its specifications, replace the unit.
For a replacement electric actuator, contact the nearest Johnson Controls representative.
Technical specifications
VA9104-xGA-3S Series Electric Non-Spring Return Valve Actuators
 Power requirements                                          AC 24 V +25%/-20% at 50/60 Hz, 2.3 VA (AGA), 2.9 VA (GGA), and
                                                             3.0 VA (IGA) Supply, Class 2 or Safety Extra-Low Voltage (SELV)
 Control type                         VA9104-AGA-3S          Floating or on/off control without timeout
                                      VA9104-GGA-3S          Proportional control
                                      VA9104-IGA-3S          Floating or on/off control with timeout
 Input signal                         VA9104-AGA-3S          AC 24 V +25%/-20% at 50/60 Hz, Class 2 or SELV without timeout
                                      VA9104-GGA-3S          DC 0 (2) to 10 V or 0 (4) to 20 mA with field-furnished 500 ohm resistor
                                      VA9104-IGA-3S          AC 24 V +25%/-20% at 50/60 Hz, Class 2 or SELV with timeout
 Motor input impedance                VA9104-AGA-3S          200 ohms nominal
 Control input impedance              VA9104-GGA-3S          Voltage input: 200,000 ohm
                                                             Current input: 500 ohms with field-furnished 500 ohm resistor
 Running torque                                              35 lbin. (4 Nm)
 Travel time                                                 60 seconds at 60 Hz (72 seconds at 50 Hz) for 90° of rotation
 Rotation range                                              93° ±3°, CW or CCW
 Cycles                                                      100,000 full stroke cycles;
                                                             2,500,000 repositions at rated running torque
 Audible noise rating                                        35 dBA nominal at 39-13/32 in. (1 m)
 Electrical connections               VA9104-xGA-3S          M3 screw terminals
 Enclosure                            VA9104-xGA-3S          NEMA 1, IP40
 Ambient conditions                   Operating              -4 to 140°F (-20 to 60°C); 90% RH maximum, noncondensing
                                      Storage                -20 to 150°F (-29 to 66°C); 90% RH maximum, noncondensing
 Fluid temperature limits             VG12x1 and             23 to 203°F (-5 to 95°C)
 (Actuator and valve                  VG18x1 Series
 assembly)
                                      VG1245 and             -22 to 212°F (-30 to 100°C)
                                      VG1845 Series
                                      VG12x5 and             -22 to 284°F (-30 to 140°C) Water; 15 psig (103 kPa) at 250°F (121°C)
                                      VG18x5 Series          saturated steam
                                      with M9000-561
                                      Thermal Barrier
 Compliance                           United States          UL Listed, CCN XAPX, File 27734
                                                             Plenum rated, UL2043, suitable for use in other environmental spaces
                                                             (plenums) in accordance with section 300.22.(c) of the National
                                                             Electrical Code
                                      Canada                 cUL Listed, CCN XAPX7, File 27734
                                                             Plenum Rated Per CSA 22.2 No. 236/UL 1995, Heating and Cooling
                                                             Equipment
                                      Europe                 Johnson Controls declares that this product is in compliance with the
                                                             essential requirements and other relevant provisions of the EMC
                                                             Directive and the Low Voltage Directive.
                                      Australia and          RCM Mark, Australia/NZ Emissions Compliant
                                      New Zealand
 Shipping weight                                             1.25 lb (0.55 kg)

The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or
misuse of its products.

                                                                                                            P/N 14-1336-23, Rev. L
European Single Point of Contact:       NA/SA Single Point of Contact:             APAC Single Point of Contact:
JOHNSON CONTROLS                        JOHNSON CONTROLS                           JOHNSON CONTROLS
WESTENDHOF 3                            507 E MICHIGAN ST                          C/O CONTROLS PRODUCT
45143 ESSEN                             MILWAUKEE WI 53202                         MANAGEMENT
GERMANY                                 USA                                        NO. 22 BLOCK D NEW DISTRICT
                                                                                   WUXI JIANGSU PROVINCE 214142
                                                                                   CHINA

                                                                                              Building Technologies & Solutions
                                                                                  507 E. Michigan Street, Milwaukee, WI 53202
                                                            Johnson Controls® is a registered trademark of Johnson Controls.
                                    All other marks herein are the marks of their respective owners. © 2019 Johnson Controls.

                                                                                               P/N 14-1336-23, Rev. L