| Вид документа | Інструкція з монтажу |
|---|---|
| Виробник | JCI |
| Код документа | v-9502-75-positioner-kit-for-v-3000-8001-pneumatic-actuators-mounted-to-vg7000 |
| Група обладнання | V-3000-8001 Pneumatic Actuator |
| Сторінок | 4 |
| Мова документа | англійська |
| Розмір файлу | 0.0 МБ |
Текст документа
V-9502-75 Positioner Kit for
V-3000-8001 Pneumatic Actuators Mounted to
VG7000 Series Bronze Valves
Note: The positioner spring must be ordered separately. Refer to Table 1
for appropriate code number.
Kit Includes (See Figure 1)
• one positioner with cover and mounting bracket
• one feedback connector
• one No. 8 x 32 x 1/2 in. flat head mounting screw
• one elbow barbed fitting
• two spacers
• two No. 10-24 x 15 mm (5/8 in.) mounting screws
Tools Required
• standard screwdriver
• 7/16 in. open end or adjustable wrench
• 3/16 in. Allen wrench
Table 1: Accessories
Description Code Number
Pilot Positioner Springs:
5/16 in. Stroke (8 mm Lift) - 3 psi Span V-9502-6801
1/2 in. Stroke (13 mm Lift) - 5 psi Span V-9502-6801
3/4 in. Stroke (19 mm Lift) - 10 psi Span V-9502-6801
5/16 in. Stroke (8 mm Lift) - 8 psi Span V-9502-6802
1/2 in. Stroke (13 mm Lift) - 12 psi Span V-9502-6802
3/4 in. Stroke (19 mm Lift) - 4 psi Span V-9502-6803
Part No. 14-384-17, Rev. — 1
© 1995 Johnson Controls, Inc. Printed in U.S.A.
Upper Spring
Seat
Flat head
Screw
Feedback
Connector
Figure 1: Upper Spring Seat Assembly
Plastic Elbow
Tubing Fitting
Spacers
Figure 2: V-3000-8001 Positioner Mounting
Back Plate Positioner Lever Arm
Feedback
Spring
Feedback Connector
Spacers
Mounting Screw
Figure 3: Actuator Fittings
2
Actuator Removal
1. Disconnect the air line attached to the actuator and cap it to prevent control
system operation problems.
2. Make sure that the pressure in the actuator has been relieved.
3. Using a screwdriver, remove the V-3000-8001 Actuator from the valve by
loosening the mounting set screw. See Figure 3.
! CAUTION: The spring under the actuator is attached to the valve
stem and is precompressed. Unknown damage to the
valve stem may create a hazardous condition.
Mounting Procedure
1. Attach the feedback connector to the upper spring seat with flat head screw
(refer to Figure 1) and using an Allen wrench, tighten the screw.
2. Remove the straight barbed fitting on the actuator and replace it with the
elbow fitting. See Figure 2.
3. Using the two No. 10-24 screws and the two spacers, mount the positioner
to the actuator through the two lower mounting slots of the positioner back
plate (refer to Figure 3). Do not tighten the screws at this time.
4. Place the actuator over the valve spring assembly and feedback connector.
Using a screwdriver, tighten the mounting screw against the valve bonnet.
5. Rotate the feedback connector until the hole is directly under the positioner
lever arm.
6. Attach one end of the feedback spring to the first hole in the positioner
lever arm and attach the other end to the feedback connector.
See Figure 3.
7. Slide the positioner until the spring is just snug and tighten the screws from
Step 3 with a screwdriver.
8. Using plastic tubing, connect the actuator to the Output “O” port on the
positioner. See Figure 2.
9. Adjust the positioner starting point to suit your application. The operating
span is determined by the spring used (refer to Table 1). Refer to the
V-9502 Product Data in the Valve and Actuator Manual (FAN 977) for the
procedure.
3
4Позиції каталогу з цим документом