Текст документа
Metasys Network Sales Resource Manual 635
Network Units Section
Product Bulletin
Issue Date August 11, 2008
Universal Packaging Module (UPM)
The Universal Packaging Modules (UPMs) are an
expandable enclosure system to house a wide
range of controllers and accessories. Rugged and
lockable, the enclosures also provide a wealth of
built-in features to reduce installation time.
If you need additional space, the UPM’s modular
construction lets you increase the unit’s capacity
without having to unwire and rewire the controls.
A full window option allows you to view the internal
equipment while keeping it secure. Powered
versions include a 24 volt transformer to simplify
installation.
Features and Benefits
Lockable Provides security against system tampering.
Multiple, Expandable Sizes Accommodate system requirements with
tiered, modular construction; flexibility to
expand without rewiring, while maintaining
lightweight, durable structure.
Removable Door Allows full access for wiring during
installation.
Built-in Power Integrates two utility outlets and a switched
transformer (50 VA or 100 VA) for easier, less
expensive installation.
Ground Bonding Plane Simplifies grounding of incoming conduit to
meet National Electrical Code (NEC)
guidelines.
Window Allows easy viewing of internal equipment.
© 2008 Johnson Controls, Inc. 1
Code No. LIT-635044
METASYS METASYS
EWC10
EWC20
METASYS METASYS
EWC30
UPMPB1
EWC40
Figure 1: Universal Packaging Modules
2 Network Units—Universal Packaging Module (UPM)
M odular System
Lightweight and rugged in structure, the
Universal Packaging Modules are constructed IMPORTANT: Before specifying the
from three standard pieces. Units are available Universal Packaging Module for plenum
completely assembled. Due to its modular applications, verify acceptance of exposed
design, however, it can be modified to plastic materials in plenum areas with the
individualize each enclosure to its site. local building authority. Building codes for
Built-in features include separate line- and low- plenum requirements vary by location.
voltage wiring troughs, preformed holes to Some local building authorities accept
eliminate drilling, wall thicknesses to
compliance to UL 1995, Heating and
accommodate standard conduit fasteners, easily
accessible grounding, and a removable door. Cooling Equipment, while others use
different acceptance criteria.
Note: Assemble together no more than four
units (EWC40 equivalent) to meet the 10 sq ft
exposed surface area requirement of UL 1995.
upmpb2
Figure 2: Universal Packaging Components
Network Units—Universal Packaging Module (UPM) 3
E xpandability
The four available sizes allow you to choose the There is no problem: remove two screws on the
box you need for your current requirements. But bottom, slide out the endcap, attach the endcap
what if the system requirements change and you to the new backbone, and install the section.
need more room inside a two section unit that is You have just added capacity to a mounted
already mounted? enclosure without having to rewire the original
controls.
Backbone
Add section
to endcap
and attach
to unit.
Endcap
upmpb3
Figure 3: Expanding the Package
P ower
Connecting auxiliary transformers and This feature allows you to eliminate the separate
enclosures can take up valuable space and transformer, controller, and auxiliary gear
installation time. The power option provides an enclosures, and substitute them with a single
integrated 50 VA or 100 VA transformer and two unit that is faster and easier to install (as well as
utility outlets inside a metal power entrance box. less expensive).
A switch activates the transformer.
UPMewc15
UPMewc25
UPMewc12
EWC15 EWC25/35 EWC12/22
Figure 4: Power Options
4 Network Units—Universal Packaging Module (UPM)
W indow Cover
For those who want to monitor equipment, such The window kit allows you to create a
as gauges and Light-Emitting Diodes (LEDs), an configuration to match your application; since
optional full-window cover provides easy viewing the kit includes a backbone, you can also
while still having the equipment securely locked expand an existing enclosure.
away from unauthorized users.
B
A C
On
Off
upmpb5
Figure 5: Enclosure Showing Equipment Mounted behind a Window in the Lower Section
Network Units—Universal Packaging Module (UPM) 5
D imensions and Configurations
The following figures detail the footprint and To assist you in laying out and wiring any
interior dimensions of the four Universal configuration in these enclosures, contact the
Packaging Modules. Use these dimensions to Johnson Controls® Poteau Panel Unit with your
select the appropriately sized enclosure to fit the design requirements.
controller and auxiliary gear that you wish to
house. Remember, in addition to these
enclosures you can also use the EN-EWC100,
200, and 500 Series of enclosures to house
base frame controllers, or larger configurations
of gauges, relays, and application specific
controllers.
16 in.
7.5 in.
9 in.
UPMPB6
Figure 6: Outside Dimensions
Footprint dimensions (H x W x D) of the four Universal Packaging Modules:
EN-EWC10/15-0 9 x 16 x 7.5 in. (23 x 41 x 19 cm)
EN-EWC20/25-0 16 x 16 x 7.5 in. (41 x 41 x 19 cm)
EN-EWC30/35-0 23 x 16 x 7.5 in. (59 x 41 x 19 cm)
EN-EWC40/45-0 30 x 16 x 7.5 in. (77 x 41 x 19 cm)
6 Network Units—Universal Packaging Module (UPM)
13 in. (Interior)
6 in.
(Interior)
7 in.
(Interior)
upmpb7
Note: In the powered versions, make sure
to account for the transformer and
power box dimensions.
Figure 7: Interior Dimensions
Interior dimensions (H x W x D) of the four Universal Packaging Modules:
EN-EWC10-0 7 x 13 x 6 in. (18 x 33 x 15 cm)
EN-EWC20-0 14 x 13 x 6 in. (36 x 33 x 15 cm)
EN-EWC30-0 21 x 13 x 6 in. (53 x 33 x 15 cm)
EN-EWC40-0 28 x 13 x 6 in. (71 x 33 x 15 cm)
Split Bobbin Transformer and power box dimensions (H x W):
50 VA Transformer 3.875 x 3.25 in. (9.6 x 8.3 cm)
100 VA Transformer 3.75 x 3.625 in. (9.5 x 9.2 cm)
Power Box 4 x 3.75 in. (10.2 x 9.5 cm)
The window in the optional covered window section measures 7.25 x 6 in. (18 x 15 cm).
Network Units—Universal Packaging Module (UPM) 7
S pecifications
Code Number Description Shipping Weight Typical Uses
Universal Packaging Modules without Power Components
EN-EWC10-0 UPM (Single unit) 5.0 lb (2.3 kg) Auxiliary Gear
Mounting
EN-EWC20-0 UPM (Dual unit) 8.0 lb (3.6 kg) Auxiliary Gear
Mounting
EN-EWC30-0 UPM (Triple unit) 11.0 lb (5.0 kg) Auxiliary Gear
Mounting
EN-EWC40-0 UPM (Quad unit) 14.0 lb (6.4 kg) Auxiliary Gear
Mounting
Universal Packaging Modules with Power Entry Box Only
EN-EWC12-0 UPM (Single unit) 5.5 lb (2.5 kg) N2 Dialer
EN-EWC22-0 UPM (Dual unit) 8.5 lb (3.9 kg) NCM300
Universal Packaging Modules with Power Entry Box and Transformer
EN-EWC15-0 UPM (Single unit with 50 VA) 7.3 lb (3.3 kg) UNT/VAV
EN-EWC25-0 UPM (Dual unit with 50 VA) 10.3 lb (4.7 kg) DX-9100
EN-EWC35-0 UPM (Triple unit with 100 VA) 15.8 lb (7.2 kg) AHU
EN-EWC45-0 UPM (Quad unit with 100 VA) 18.8 lb (8.5 kg) Multiple Controllers
Universal Packaging Modules with Brackets
EN-EWC13-0 UPM with 1 bracket and 50 VA 7.3 lb (3.3 kg) Companion/Ingegrator
EN-EWC 26-0 UPM with 2 brackets and 50 10.4 lb (4.7 kg) Companion with
VA and power box Modem
Expansion Units
EN-EXP101-0 Expansion cover and 3.2 lb (1.5 kg) Expand existing
backbone kit; endcaps not enclosure
included
EN-WIN101-0 Window cover and backbone 3.0 lb (1.4 kg) Showing internal
kit; endcaps not included equipment
Accessories
EN-UTLBRK-0 Utility Bracket 0.5 lb (0.2 kg) Mounting Modems
EN-KIT103-0 NT Cradle Kit 3.0 lb (1.4 kg) Mount in NTU
AS-ZTUWMB-0 ZTU Wall Mount Bracket 0.5 lb (0.2 kg) Mounting ZTU
Power Requirements 120 VAC at 60 Hz (1 amp)
Standards Compliance UL 916 Listed and CSA Certified as part of the Metasys® system
Module Housing is Plenum Rated per UL 1995, Heating and Cooling
Equipment.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond
these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from
misapplication or misuse of its products.
Controls Group FAN 635
507 E. Michigan Street Metasys Network Sales Resource Manual
P.O. Box 423 Printed in U.S.A.
Milwaukee, WI 53201
8 Network Units—Universal Packaging Module (UPM)Позиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.