SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Universal Packaging Module (UPM) Product Bulletin

Вид документаБюлетень виробу
ВиробникJCI
Код документаuniversal-packaging-module-upm-product-bulletin
Група обладнанняUniversal Packaging Module
Сторінок8
Мова документаанглійська
Розмір файлу0.8 МБ

Текст документа

Metasys Network Sales Resource Manual     635
                                                                      Network Units Section
                                                                            Product Bulletin
                                                                                Issue Date     August 11, 2008

                      Universal Packaging Module (UPM)

The Universal Packaging Modules (UPMs) are an
expandable enclosure system to house a wide
range of controllers and accessories. Rugged and
lockable, the enclosures also provide a wealth of
built-in features to reduce installation time.
If you need additional space, the UPM’s modular
construction lets you increase the unit’s capacity
without having to unwire and rewire the controls.
A full window option allows you to view the internal
equipment while keeping it secure. Powered
versions include a 24 volt transformer to simplify
installation.

                                       Features and Benefits
            ‰ Lockable                          Provides security against system tampering.

            ‰ Multiple, Expandable Sizes        Accommodate system requirements with
                                                tiered, modular construction; flexibility to
                                                expand without rewiring, while maintaining
                                                lightweight, durable structure.

            ‰ Removable Door                    Allows full access for wiring during
                                                installation.

            ‰ Built-in Power                    Integrates two utility outlets and a switched
                                                transformer (50 VA or 100 VA) for easier, less
                                                expensive installation.

            ‰ Ground Bonding Plane              Simplifies grounding of incoming conduit to
                                                meet National Electrical Code (NEC)
                                                guidelines.

            ‰ Window                            Allows easy viewing of internal equipment.

© 2008 Johnson Controls, Inc.                                                                                    1
  Code No. LIT-635044
                             METASYS                                  METASYS

                         EWC10

                                                               EWC20

                             METASYS                                  METASYS

                         EWC30

                                                                                UPMPB1
                                                               EWC40

                              Figure 1: Universal Packaging Modules

2   Network Units—Universal Packaging Module (UPM)
M odular System
Lightweight and rugged in structure, the
Universal Packaging Modules are constructed               IMPORTANT:         Before specifying the
from three standard pieces. Units are available           Universal Packaging Module for plenum
completely assembled. Due to its modular                  applications, verify acceptance of exposed
design, however, it can be modified to                    plastic materials in plenum areas with the
individualize each enclosure to its site.                 local building authority. Building codes for
Built-in features include separate line- and low-         plenum requirements vary by location.
voltage wiring troughs, preformed holes to                Some local building authorities accept
eliminate drilling, wall thicknesses to
                                                          compliance to UL 1995, Heating and
accommodate standard conduit fasteners, easily
accessible grounding, and a removable door.               Cooling Equipment, while others use
                                                          different acceptance criteria.

                                                          Note: Assemble together no more than four
                                                          units (EWC40 equivalent) to meet the 10 sq ft
                                                          exposed surface area requirement of UL 1995.

                                                                                                  upmpb2

                              Figure 2: Universal Packaging Components

                                                    Network Units—Universal Packaging Module (UPM)         3
E xpandability
The four available sizes allow you to choose the             There is no problem: remove two screws on the
box you need for your current requirements. But              bottom, slide out the endcap, attach the endcap
what if the system requirements change and you               to the new backbone, and install the section.
need more room inside a two section unit that is             You have just added capacity to a mounted
already mounted?                                             enclosure without having to rewire the original
                                                             controls.

                              Backbone
                                                     Add section
                                                     to endcap
                                                     and attach
                                                     to unit.

                          Endcap

                                                                               upmpb3

                                       Figure 3: Expanding the Package

P ower
Connecting auxiliary transformers and                        This feature allows you to eliminate the separate
enclosures can take up valuable space and                    transformer, controller, and auxiliary gear
installation time. The power option provides an              enclosures, and substitute them with a single
integrated 50 VA or 100 VA transformer and two               unit that is faster and easier to install (as well as
utility outlets inside a metal power entrance box.           less expensive).
A switch activates the transformer.

                            UPMewc15
                                                                    UPMewc25
                                                                                                          UPMewc12

           EWC15                                  EWC25/35                                  EWC12/22

                                           Figure 4: Power Options

4   Network Units—Universal Packaging Module (UPM)
W indow Cover
For those who want to monitor equipment, such             The window kit allows you to create a
as gauges and Light-Emitting Diodes (LEDs), an            configuration to match your application; since
optional full-window cover provides easy viewing          the kit includes a backbone, you can also
while still having the equipment securely locked          expand an existing enclosure.
away from unauthorized users.

                                          B
                                      A       C
                                                        On
                                                        Off

                                                                            upmpb5

    Figure 5: Enclosure Showing Equipment Mounted behind a Window in the Lower Section

                                                   Network Units—Universal Packaging Module (UPM)          5
D imensions and Configurations
The following figures detail the footprint and                To assist you in laying out and wiring any
interior dimensions of the four Universal                     configuration in these enclosures, contact the
Packaging Modules. Use these dimensions to                    Johnson Controls® Poteau Panel Unit with your
select the appropriately sized enclosure to fit the           design requirements.
controller and auxiliary gear that you wish to
house. Remember, in addition to these
enclosures you can also use the EN-EWC100,
200, and 500 Series of enclosures to house
base frame controllers, or larger configurations
of gauges, relays, and application specific
controllers.

                                                         16 in.

                   7.5 in.

                                                                                           9 in.

                                                                                  UPMPB6

                                         Figure 6: Outside Dimensions

Footprint dimensions (H x W x D) of the four Universal Packaging Modules:
    EN-EWC10/15-0            9 x 16 x 7.5 in. (23 x 41 x 19 cm)
    EN-EWC20/25-0            16 x 16 x 7.5 in. (41 x 41 x 19 cm)
    EN-EWC30/35-0            23 x 16 x 7.5 in. (59 x 41 x 19 cm)
    EN-EWC40/45-0            30 x 16 x 7.5 in. (77 x 41 x 19 cm)

6   Network Units—Universal Packaging Module (UPM)
                                                       13 in. (Interior)

                    6 in.
                 (Interior)

                                                                                           7 in.
                                                                                        (Interior)

                                                                               upmpb7

                                 Note:    In the powered versions, make sure
                                          to account for the transformer and
                                          power box dimensions.

                                         Figure 7: Interior Dimensions

Interior dimensions (H x W x D) of the four Universal Packaging Modules:
   EN-EWC10-0            7 x 13 x 6 in.      (18 x 33 x 15 cm)
   EN-EWC20-0            14 x 13 x 6 in. (36 x 33 x 15 cm)
   EN-EWC30-0            21 x 13 x 6 in. (53 x 33 x 15 cm)
   EN-EWC40-0            28 x 13 x 6 in. (71 x 33 x 15 cm)

Split Bobbin Transformer and power box dimensions (H x W):
   50 VA Transformer          3.875 x 3.25 in.        (9.6 x 8.3 cm)
   100 VA Transformer         3.75 x 3.625 in.        (9.5 x 9.2 cm)
   Power Box                  4 x 3.75 in.            (10.2 x 9.5 cm)
The window in the optional covered window section measures 7.25 x 6 in. (18 x 15 cm).

                                                       Network Units—Universal Packaging Module (UPM)   7
S pecifications
 Code Number                   Description                           Shipping Weight           Typical Uses
                      Universal Packaging Modules without Power Components
 EN-EWC10-0                    UPM (Single unit)                     5.0 lb (2.3 kg)           Auxiliary Gear
                                                                                               Mounting
 EN-EWC20-0                    UPM (Dual unit)                       8.0 lb (3.6 kg)           Auxiliary Gear
                                                                                               Mounting
 EN-EWC30-0                    UPM (Triple unit)                     11.0 lb (5.0 kg)          Auxiliary Gear
                                                                                               Mounting
 EN-EWC40-0                    UPM (Quad unit)                       14.0 lb (6.4 kg)          Auxiliary Gear
                                                                                               Mounting
                      Universal Packaging Modules with Power Entry Box Only
 EN-EWC12-0                    UPM (Single unit)                     5.5 lb (2.5 kg)           N2 Dialer
 EN-EWC22-0                    UPM (Dual unit)                       8.5 lb (3.9 kg)           NCM300
              Universal Packaging Modules with Power Entry Box and Transformer
 EN-EWC15-0                    UPM (Single unit with 50 VA)          7.3 lb (3.3 kg)           UNT/VAV
 EN-EWC25-0                    UPM (Dual unit with 50 VA)            10.3 lb (4.7 kg)          DX-9100
 EN-EWC35-0                    UPM (Triple unit with 100 VA)         15.8 lb (7.2 kg)          AHU
 EN-EWC45-0                    UPM (Quad unit with 100 VA)           18.8 lb (8.5 kg)          Multiple Controllers
                               Universal Packaging Modules with Brackets
 EN-EWC13-0                    UPM with 1 bracket and 50 VA          7.3 lb (3.3 kg)           Companion/Ingegrator
 EN-EWC 26-0                   UPM with 2 brackets and 50            10.4 lb (4.7 kg)          Companion with
                               VA and power box                                                Modem
                                                  Expansion Units
 EN-EXP101-0                   Expansion cover and                   3.2 lb (1.5 kg)           Expand existing
                               backbone kit; endcaps not                                       enclosure
                               included
 EN-WIN101-0                   Window cover and backbone             3.0 lb (1.4 kg)           Showing internal
                               kit; endcaps not included                                       equipment
                                                     Accessories
 EN-UTLBRK-0                   Utility Bracket                       0.5 lb (0.2 kg)           Mounting Modems
 EN-KIT103-0                   NT Cradle Kit                         3.0 lb (1.4 kg)           Mount in NTU
 AS-ZTUWMB-0                   ZTU Wall Mount Bracket                0.5 lb (0.2 kg)           Mounting ZTU
 Power Requirements            120 VAC at 60 Hz (1 amp)
 Standards Compliance          UL 916 Listed and CSA Certified as part of the Metasys® system
                               Module Housing is Plenum Rated per UL 1995, Heating and Cooling
                               Equipment.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond
these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from
misapplication or misuse of its products.

Controls Group                                                                                                            FAN 635
507 E. Michigan Street                                                                     Metasys Network Sales Resource Manual
P.O. Box 423                                                                                                      Printed in U.S.A.
Milwaukee, WI 53201
8   Network Units—Universal Packaging Module (UPM)

Позиції каталогу з цим документом

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.