Application Specific Controllers Technical Manual 636.3
                                                                                                        Accessories Section
                                                                                                           Technical Bulletin
                                                                                                                 Issue Date 0295

                                  Universal Packaging Module

    Introduction                                                                                                  Page         3
    ●    Application Overview                                                                                                  3

    Engineering                                                                                                                5
    ●    Design Considerations                                                                                                 5
    ●    Planning                                                                                                             *6

    Installation                                                                                                               9
    ●    Tools Needed                                                                                                          9
    ●    General Mounting                                                                                                     *9
    ●    Power Box and Transformer Location                                                                                 *12
    ●    Wiring                                                                                                             *13
    ●    Adding Sections to Existing Units                                                                                   16
    ●    Modifying the Lock                                                                                                  19

    Mounting Control Equipment                                                                                               21
    ●    Network Terminal Installation                                                                                       21
    ●    Mounting Companion (with a Modem)                                                                                  *23
    ●    Metasys Integrator Mounting                                                                                        *24
    ●    Zone Terminal Mounting with UPM                                                                                    *25
    ●    Mounting the ZT Behind a Window Enclosure                                                                          *26
    ●    NCM300                                                                                                              27
    ●    AHU Controller                                                                                                     *28
    ●    VAV and UNT Controllers                                                                                            *29
    ●    DX-9100                                                                                                             30
    ●    Function Module Kit                                                                                                *31
                                                                                      ●     RLY002
                                * Indicates those sections where changes have occurred since the last printing.

© 1995 Johnson Controls, Inc.                                                                                                  1
  Code No. LIT-6363070
   Commissioning Procedures                                                                            Page   35
   ●   Commissioning Considerations                                                                            35

   Specifications/Ordering Information                                                                        *37
   ●   Vendor Code Numbers                                                                                    *38

                           * Indicates those sections where changes have occurred since the last printing.

2 UPM—Universal Packaging Module
              Introduction

Application   The Universal Packaging Modules (UPMs) make up an expandable
Overview      enclosure system, which house a wide range of controllers and accessories.
              Typical uses include:
              ●   Applications Specific Controllers: Air Handling Unit Controllers,
                  Unitary Controllers, Lab and Central Plant Controllers, and System
                  9100 Controllers.
              ●   Auxiliary Gear: Relay kits, transformer kits, off-the-shelf timers,
                  gauges, pressure regulator valves, etc.

              Four completely assembled sizes of the units are available. Refer to
              Figure 1. However, due to its modular design, you can modify each unit
              to customize the enclosure to its site. (Johnson Controls Panel Unit wires
              and configures a unit, complete with gear, to your specifications.) If
              system requirements change for units that are already mounted, the
              enclosure’s modular construction lets you increase the unit’s capacity
              without having to unwire and rewire the existing controls.
              Built-in features include separate line- and low-voltage wiring troughs,
              pre-formed holes to eliminate drilling, wall thickness to accommodate
              standard conduit fasteners, easily accessible grounding, and a removable
              door.
              A full window option such as EN-WIN101-0 allows you to view the
              internal equipment while keeping it secure. Powered versions include a 24
              volt transformer to simplify installation.

                                                      UPM—Universal Packaging Module 3
                                     M ET A SY S                    M ET A SY S

                                   EWC10

                                                                  EWC20

                                     M ET A SY S                    M E T A S YS

                                   EWC30

                                                                                   UPMPB1
                                                                  EWC40

                                   Figure 1: Universal Packaging Modules

4 UPM—Universal Packaging Module
                 Engineering

Design           There are several pre-assembled sizes of enclosures available. These
Considerations   include the EN-EWC10-0, EWC20, EWC30, or the EWC40. You can
                 order any of these sizes to include a 24 VAC transformer and power box
                 (EN-EWC15-0, EWC25, EWC35, EWC45). Table 1 describes
                 configuration options for typical applications.

                 Table 1: UPM Configuration Options
                  Application                                                UPM Configuration*

                  NCM300                                         EN-EWC22-0
                  UNT                                            EN-EWC15-0
                  DX-9100                                        EN-EWC25-0
                  Network Terminal (no window)                   EN-EWC10-0
                  Network Terminal (window)                      EN-EWC10-0 and EN-WIN101-0
                  Zone Terminal (either internal or              EN-EWC10-0
                  mounted on the front)
                  Relay Kit                                      All Types
                  *   UPM configuration options indicate the smallest enclosure for each application.
                      You may select a larger unit if desired.

                                                                    UPM—Universal Packaging Module 5
Planning
Dimensions
                    The following figures detail the footprint and interior dimensions of the
                    standard enclosures. Use these dimensions to select the appropriately
                    sized enclosure to fit the controller and auxiliary gear that you wish to
                    house. Remember, in addition to these enclosures you can also use other
                    UL Listed EN-EWC100, 200, and 500 series of enclosures to house base
                    frame controllers, or larger configurations of gauges, relays, function
                    modules, and application specific controllers.
                    To assist you in laying out and wiring any configuration in these
                    enclosures, contact the Johnson Controls Panel Unit with your design
                    requirements.

                                                         16 in.

                          7.5 in.

                                                                                           9 in.

                                                                                  UPMPB6

                                        Figure 2: Exterior Dimensions

                    Footprint dimensions (H x W x D) of the standard enclosures:
                    EN-EWC10-0                9 in. x 16 in. x 7.5 in.    (23 x 41 x 19 cm)
                    EN-EWC20-0                16 in. x 16 in. x 7.5 in.   (41 x 41 x 19 cm)
                    EN-EWC30-0                23 in. x 16 in. x 7.5 in.   (59 x 41 x 19 cm)
                    EN-EWC40-0                30 in. x 16 in. x 7.5 in.   (76 x 41 x 19 cm)

6 UPM—Universal Packaging Module
                                  13 in. (Interior)

        6 in.
     (Interior)

                                                                      7 in.
                                                                   (Interior)

                                                                   upmpb7

                    Figure 3: Interior Dimensions

Note: When selecting a powered enclosure size, be sure to account for
      the transformer and power box.

Interior dimensions (H x W x D) of the standard enclosures:
EN-EWC10-0               7 in. x 13 in. x 6 in.        (18 x 33 x 15 cm)
EN-EWC20-0               14 in. x 13 in. x 6 in.       (36 x 33 x 15 cm)
EN-EWC30-0               21 in. x 13 in. x 6 in.       (53 x 33 x 15 cm)
EN-EWC40-0               28 in. x 13 in. x 6 in.       (71 x 33 x 15 cm)

(Transformer and power box dimensions):
50 VA Transformer        3.875 x 3.25 in.              (9.8 x 8.3 cm)
100 VA Transformer       3.75 x 3.625 in.              (9.5 x 9.2 cm)
Power Box                4 x 3.75 in.                  (10.2 x 9.5 cm)

The window in the optional covered window section measures
7.25 in. x 6 in. (18 x 15 cm).

                                            UPM—Universal Packaging Module 7
Load Bearing        Select a wall space or area with sufficient room to mount the enclosure
                    and install conduit. The load-bearing capacity of the wall must be able to
                    support the full configuration weight. Wood surfaces generally only
                    require bolting the enclosure to the wall; dry wall surfaces require anchors
                    for the bolts.
                    Due to the rigidity and strength of the molded plastic enclosure, the weight
                    supported by an individual enclosure is probably higher than any
                    application requirement. The pull-out value of the screw holes on the
                    backbone is 200 pounds (90.7 kg). However, in securing a very heavy
                    object, the best practice is to distribute the weight over a number of screws.
                    The weight resting on the bottom endcap must not exceed 50 pounds
                    (22.6 kg).

Environment         The enclosure is for indoor use. Avoid areas where water leakage may
                    occur.

Power               The power option provides an integrated 50 VA (EN-EWC15,
                    EN-EWC25) or 100 VA (EN-EWC35, EN-EWC45) transformer. A
                    switch activates the transformer. Two utility outlets inside a metal power
                    entrance box are also included.
                    Power to the power box must be 120 VAC at 60 Hz.

Wiring              One side of the enclosure should be used to route low-voltage wiring
Separation          and the other side for line-voltage wiring. Off-the-shelf inserts from
                    RICHCO Plastics plug into the mounting holes of the backbone to help
                    route wires. The hole size is 0.31 inch (7.87 mm). Refer to the
                    Specifications/Ordering Information section of this document for specific
                    details regarding wire routing guides. Follow UL/NEC standards when
                    using inserts to separate low- and line-voltage wiring by a minimum of
                    two inches.

                             WSBH                BHKL            FTH-15           LWSBH
                                                                                       guides

                       Figure 4: Wiring Guides for the Universal Packaging Module
8 UPM—Universal Packaging Module
                   Installation

Tools Needed       ●    1/4 in. bolts
                   ●    No. 8 Plastite screws (for maximum holding power of 200 lb,
                        90.7 kg). No. 8 sheet metal screws, type A or AB are an alternative.
                        However, these screws have a maximum holding power of 100 lb
                        (45.3 kg).
                   ●    Wrench and screwdriver appropriate for the bolt and screw heads

Tools Needed for   ●    Torx screwdriver
Expanding the
Enclosure
                   ●    T-20 Recessed Torx screws (included with expansion kits.)

General            Follow the steps below when mounting an enclosure:
Mounting
                                    Remove Door

                             2
                         Lift Up

                                                                            1
                                                                    Open Door 90

                                                                                     mount1

                              Figure 5: Mounting a Universal Packaging Module

                   1.   To remove the cover, turn the key counterclockwise until the key is in
                        an upright position. Pull out on the blue latch and then pull the cover
                        out to a 90° angle from the base. Finally, pull the cover off the hinge,
                        up and away to completely remove it.
                   2.   Position the unit on the wall and mark the location of the mounting
                        slot on the upper-most section. Each section of an enclosure has a
                        center mounting slot and two mounting holes (Figure 6).
                   3.   Drill a hole to accommodate a 1/4 inch bolt. Anchor the bolt, leaving
                        a 3/8 inch to 1/2 inch protrusion on which to hang the backbone.

                                                            UPM—Universal Packaging Module 9
                    4.    Hang the backbone over the bolt. Plumb the box. Mark the
                          appropriate mounting holes along the wiring channels. (For units
                          with multiple backbone sections, it is only necessary to install bolts in
                          the four outside perimeter mounting holes, and alternate holes in the
                          remaining sections--see Figure 7.)
                    5.    Drill into the wall to accommodate the mounting holes (the units can
                          be left in place or removed from the wall). Secure the unit with
                          1/4 inch bolts. If field gear is already mounted in the box, remove the
                          box from the wall before mounting.
                    6. Mount the gear, using the No. 8 screws (seating torque should be
                       25 pound•inch minimum) and replace the door.

                                                     Mounting Slot

                             Mounting                                            Mounting
                               Hole                                                Hole

                                                     Wire Channels                MOUNT1A

                         Figure 6: Bolt Locations when Mounting a Single Enclosure

10 UPM—Universal Packaging Module
                             1/4 in. Anchor
                                    Bolt

        1/4 in. Bolt                                   1/4 in. Bolt

           No Bolt                                     No Bolt
          Necessary                                   Necessary

        1/4 in. Bolt                                   1/4 in. Bolt

                                                              mount2

 Figure 7: Bolt Locations When Mounting Multiple Enclosures

IMPORTANT: The EWC12/22 supplies power via the utility outlets
           and two switched power wires in the power box. If
           the devices being powered use only the utility outlets,
           make sure that the switched power wires remain
           wired-nutted and electrically insulated.

                                        UPM—Universal Packaging Module 11
Power Box and       The power box and transformer can be located in different areas of the
Transformer         enclosure, depending on the requirements of the other installed equipment.
Location            There are four discrete locations for the power box, designated as A, B, C,
                    or D on the outside of the endcap. The power box is generally located in
                    area C. Set the power box on the inside of the unit over two bosses
                    corresponding to one of the locations; A, B, C, or D. Position the
                    transformer to within 1/2 inch (1.2 cm) of the power box.

                    IMPORTANT: You must reconnect the ground wires if you move the
                               power box.

                      UPMewc15                         UPMewc25
                                                                                         UPMewc12

        EWC15                           EWC25/35                           EWC12/22

                        Figure 8: Power Configuration Options

12 UPM—Universal Packaging Module
Wiring
Landing Conduit
                  We recommend that you use a step bit, taper bit, or Greenlee punch
                  when drilling conduit holes.

                    !    CAUTION: Equipment Damage Hazard. Do not use a spade
                                  bit to drill conduit holes. Using a spade bit damages
                                  the ground plane.

                  Top Entry
                  There are four 3 inch by 3 inch areas designated A, B, C, or D on the
                  outside of the endcap for conduit entry into the power box. After noting
                  the location of the power box, drill or punch a hole in the selected area to
                  land the conduit (Figure 9).

                                                                                       COVERNU

                               Figure 9: Line Voltage Conduit Entry from
                                        the Top of the Enclosure

                                                          UPM—Universal Packaging Module 13
                    Side Entry
                    A “guide” groove has been molded onto each side of the backbone section
                    to help locate a drill point. Drill or punch a hole in the groove at the point
                    closest to the front (Figure 10) to land a conduit at the side of the
                    enclosure.

                                                  Front

                              Drill Point
                              Location

                                                                                             blwupsd

                     Figure 10: Line-Voltage Conduit Entry from the Side

Power               Use wire-nuts to connect the power source hot and neutral lines to the
Connections         corresponding lines inside the power box. Use wire-nuts to connect the
                    power source ground wire to the green power box wire. This grounds the
                    power outlets (which are internally connected to a ring terminal on the
                    grounding screw). The transformer is already connected to the second
                    ring terminal on the same grounding screw.
                    This connection completes the line-voltage wiring to the power outlets and
                    the transformer. Internal connections to power outlets, switch, and ground
                    are made at the factory. Switches control power to the transformer.

14 UPM—Universal Packaging Module
Grounding and   Installing the power box in any of the four designated positions locates
Bonding         one of the rear slots of the box over a grounding screw at the back of the
                endcap (each endcap has two grounding screws). The power box must be
                referenced (grounded) to a green-wire earth ground.
                When bringing multiple conduits into one end of the enclosure, the
                standard conduit connectors automatically connect to the ground plane,
                grounding all conduits together. Attaching other devices to the opposite
                screw on the same endcap also grounds those devices via the aluminum
                ground plane.
                If conduit is connected to the bottom endcap (opposite the powerbox),
                electrically bond the endcap to the grounded endcap, attach a ground wire
                from the open screw of the power box endcap to either of the grounding
                screws of the second endcap (Figure 11).

                Table 2: Wire Selection Guide
                 Incoming Service

                 15 amp                            14 AWG minimum (1.628 mm diameter)
                 20 amp                            12 AWG minimum (2.053 mm diameter)
                 30 amp                            10 AWG minimum (2.588 mm diameter)

                                                                   upmnt3

                     Figure 11: Power and Grounding/Bonding Terminations

                                                       UPM—Universal Packaging Module 15
Adding              You may add a backbone and cover to an existing unit without having to
Sections to         rewire the original controls. Figure 12 illustrates the enclosure expansion
Existing Units      units.

                         Window Kit                               Expansion Kit
                         Components                               Components

                                                                                          UPMTC7A

                                       Figure 12: UPM Expansion Units

Window Kit          For those who want to monitor equipment such as gauges and LEDs, an
Option              optional full-window cover provides easy viewing while still having the
                    equipment securely locked away from unauthorized users. The window
                    expansion kit (EN-WIN101-0) includes a full-window cover, a backbone,
                    and T-20 Torx screws (for fastening sections together). You can order this
                    kit to expand an existing enclosure at the job site or as part of an original
                    configuration through the Johnson Controls Panel Unit.

16 UPM—Universal Packaging Module
                                              B
                                          A       C
                                                         On
                                                         O ff

                                                                              upmtc7

                          Figure 13: Enclosure Showing Equipment Mounted
                                           Behind Window

Expansion Kit      The expansion kit option provides additional storage capacity for
Option             equipment that does not need to be viewed. The expansion kit
                   (EN-EXP101-0) includes a solid cover, a backbone, and T-20 Torx screws
                   (for fastening sections together). You can order this kit to expand an
                   existing enclosure at the job site or as part of an original configuration
                   through the Johnson Controls Panel Unit.

Tools Needed for   ●   Torx screwdriver
Expanding the
Enclosure
                   ●   T-20 recessed Torx screws (included with the expansion and window
                       units)

                                                          UPM—Universal Packaging Module 17
Expansion Unit      Refer to Figure 14 and follow the steps below when installing expansion
Installation        units.
                    1.   Remove the two screws holding the endcap to the backbone.
                    2.   Slide out the endcap.
                    3.   Attach the endcap to the new backbone using the same screws as just
                         removed.
                    4.   Position the endcap and new section assembly flush against the main
                         unit. Mark the holes and remove the new section.
                    5.   Drill holes into the wall and reposition the new section.
                    6.   Screw the sections together (using the included Torx screws) and
                         secure them to the wall using two 1/4 inch bolts.
                    7.   Install any gear. Be sure that any previously installed wiring for
                         grounding or bonding is reinstalled.
                    8.   Screw the new door piece to the new door.
                    9.   Replace the door.

                                                    Add section
                                                    to endcap
                                                    and attach
                                                    to unit.

                                                                                              upmpb3

                                    Figure 14: Expanding the Package

18 UPM—Universal Packaging Module
Modifying the   We offer two types of keys, “A” (master) and “B” (tenant), for use with
Lock            the EWC100, 200, and 500 enclosures. The UPM enclosures are built to
                operate with either of these keys. The “A” (master) key is supplied with
                the UPM and the “B” (tenant), key can be ordered (EN-KEY102-0.) If
                you wish to restrict access to only “A” key users, the UPM lock barrel can
                be changed to disable “B” key operation as follows:
                1.   Use the “A” key to open the enclosure door.
                2.   Remove the nut securing the lock and the cam inside the door. Notice
                     the orientation of the cam in respect to the blue latch pawl.
                3.   Pull out the key with the lock plug still attached. Rotate it 180° as
                     illustrated in Figure 14. Reinsert the plug.

                                                             Rotate 180°

                                       A
                                                                           KEY2

                                   Figure 15: Rotating the Lock Plug

                4.   Reassemble the lock cam and tighten the nut.
                The “B” key is disabled without affecting the operation of the “A” key.

                                                         UPM—Universal Packaging Module 19
20 UPM—Universal Packaging Module
                 Mounting Control Equipment

Network          You may want to house a Network Terminal (NT) inside an enclosure for
Terminal         security reasons. Two methods are available, depending on whether or not
Installation     you want to view the NT screen.

View NT Screen   This method requires a minimum of two sections of backbone and door,
                 one of which must be the Window Expansion Kit.
                 After the two sections of the enclosure are assembled, secure the NT
                 Cradle Kit inside with two No. 8 mounting screws. To ensure that the
                 cover closes over the NT Cradle, position the center slot eight holes from
                 the left edge of the backbone.

                                                            Count eight holes over
                                                            to place the center slot.

                                                                                        u p m n t1

                                Figure 16: Mounting the NT for Viewing

NT Screen Not    This method requires only one section of backbone and door. The NT can
Viewed           rest at an angle on the boss mounts of the bottom endcap (Figure 17).

                                                        UPM—Universal Packaging Module 21
                                                               upmnt2

                       Figure 17: Mounting the NT for Security Inside the Enclosure

22 UPM—Universal Packaging Module
Mounting            Follow the directions below to mount Companion into a dual high box
Companion          (EWC26) with modem.
(with a             1.     Mount EWC on wall.
Modem)
                    2.     Run 120 VAC line voltage wiring through conduit in area C. See
                           Figure 20.
                    3.     Mount other conduit as needed for low voltage bus/phone line.
                    4.     Mount electronics board with screws provided on upper bracket.
                    5.     Set modem in lower bracket and secure with two straps provided.

                                                             Hayes                         Modem power supply
                                                                                           plugs into power box.

         24 VAC Power
         with Molex Connector

                                                                                           Modem cable plugs
                                                                                           into port on electronics
                                                                                           board.

                                                                                           Modem is strapped
                                                                                           onto lower bracket.

                                          H ayes M odem
                                                                               com pm od

                                                                     P hone L ine

                                Figure 18: Companion Mounting with Modem

                                                            UPM—Universal Packaging Module 23
Metasys             Follow the directions below for mounting Metasys Integrator as
Integrator         recommended in a single high box (EWC13).
Mounting

                              2
                                                            In s e rt
                                                           S c rew s
                            Lift Up
                            and
                            Remove Door                                          mount0

                                                              1
                                                        Open Door 90

                                    Figure 19: Metasys Integrator Mounting

                    1.   After mounting the EWC on the wall, run line voltage conduit onto
                         top of the unit into shaded area D of the this illustration. Use only the
                         portion of area D that is not also a portion of area C.

                                                                                          COVER

                                  Figure 20: Line Voltage Conduit Entry from
                                           the Top of the Enclosure

                    2.   Land low voltage conduit as needed.
                    3.   Mount electronics board onto bracket with screws provided as shown
                         in the Metasys Integrator Technical Bulletin in the Metasys
                         Connectivity Technical Manual (FAN 629.5).

24 UPM—Universal Packaging Module
Zone Terminal   Using the wall mounting base, follow the instructions below to mount the
Mounting with   Zone Terminal in a UPM.
UPM

                                                                      M ET A SY S

                                                               N2
                                                             Z o ne
                                                   AHU 103    B us

                                     Zone
                                   T erm in al
                                 M ou n ted on
                                 th e Ou ts id e
                                                                            A LA R M

                                                                                       ztc o n tr

                      Figure 21: Wall Mounting the Zone Terminal with a UPM

                1.   Position the Zone Terminal Wall Mounting Base flush on the cover at
                     eye level (approximately 65 inches).
                2.   Mark mounting holes.
                3.   Mark cable hole.
                4.   Drill three size 3/32 inch pilot holes for mounting the base.
                5.   Drill 5/8 to 1 inch hole for cable.
                6.   Mount the base to the UPM cover using three No. 6 thread forming or
                     sheet metal screws. Use a No. 6 x 3/4 inch screw for the top hole and
                     two No. 6 x 1/2 inch screws for the bottom screws.

                                                              UPM—Universal Packaging Module 25
Mounting the ZT     The Panel Unit in Poteau, Oklahoma has a bracket available for mounting
Behind a            the ZT behind a window that allows control equipment to be mounted
Window              behind the ZT, thereby maximizing the use of the UPM. Contact the Panel
Enclosure           Unit for more information.

                                                B ottom V iew o f U P M

                                                         ZT

                                                         UNT

                                                               A LA RM

                                                                          z tin2

                                    Figure 22: ZTU Wall Mount Bracket

26 UPM—Universal Packaging Module
NCM300

                                                 n c 3 up m _ x

                           Figure 23: NCM300 in a UPM

         The NCM300 fits into an EWC22 enclosure. For complete mounting and
         wiring details, refer to the Network Control Module 300 Technical
         Bulletin in the Metasys Network Technical Manual (FAN 636).

                                            UPM—Universal Packaging Module 27
AHU Controller      The AHU103 Controller fits into the UPM enclosure.
                    Note: Previous versions of the AHU Controller will not be supported in
                          the UPM.

                                                                  A HU TW Rw o

                               Figure 24: AHU Controller in UPM Enclosure

                    For wiring details, please refer to the Air Handling Unit Controller (AHU)
                    Technical Bulletin located in the Application Specific Controllers
                    Technical Manual, FAN 636.3.

28 UPM—Universal Packaging Module
VAV and UNT
Controllers                                                                                                                               1 2 3 4
                                                                                                                                                                                                                1 2 3 4 5 6
                                                                                                                                          5 6

                                                                                   A N A L O G IN P U TS
                                                                                                                                                                                                                                                                              A N A L O G IN P U TS

                                                                                                                                                                                       A N A L O G I N P U TS
                                                                                                                                                           C OM M ON

                                                                                                                                                                                                                                                                             1 2 3 4 5 6

                                                                                                                                         + 1 5V D C                                                                                                                              +1 5V D C

                                                                                 B IN A R Y IN

                                                                                                                                                                                                                                                                                            B IN A R Y IN P U T
                                                                                                                                                                                                                                                                             1

                                                                                                                                                                                      24 VA C
                                                                                                                                                                                                                                                                             2
                                                                                                                                                                                                                                                                             3
                                                                                                                                                                                                                                                                             4

                                                  DSI
                                                                                                                                              24 V A C
                                                                                                                                                               CO M                                                                     Z BUS
                                                                                                                                                              ZBU S

                                                                                                                                                                              REF
                                                                                                                                                                                      N2-
                                                                                                                                                                                                                                           S TA T                   ZON E              TO
                                                                                                                                                                                N2+

                                                                                                                                                24V A C                                                                                                                      1

                                                                                   B IN A R Y O U T P U TS
                                                                                                                                                24V A C

                                                                                                                                                                                                                                                                              B IN A R Y O U TP U T
                                                                                                                                            TR A C S

                                                                                                                                 C O M M ON

                                                                                                                                                                                                                                                                             2 3 4 5 6              7
                                                                                                                                 C O M M ON

                                                                                                                                                                                                                                                                                                                                      1 2 3 4 5 6 7 8
                                                                                                                                 C O M M ON

                                                                                                                                 C O M M ON

                                                                                                                                 C O M M ON
                                                                                                                                                                                                                                                                             8

                                                                                                                                                                                                                                                                                                                                                          withunt

                                    Figure 25: UNT in a UPM

              You can mount a VAV or UNT controller into an EWC10 or larger
              enclosure. Refer to the Commissioning Considerations section of this
              document for specific drilling and mounting instructions.

                                                                                                                                                                            1 2

                                                                                                               1 2 3 4 5 6
                                                                                                                                                                            3 4 5 6

                                                    A N A L O G INP U T S
                                                                                                                                                                                                                                         A N A L OG IN P U TS

                                                                                                                                                    A N A L O G IN P U TS
                                                                                                                             C OM M ON

                                                                                                                                                                                                                                        1 2 3 4 5 6

                                                                                                              + 1 5V D C                                                                                                                      +1 5V D C

                                                       B IN A R Y IN

                                                                                                                                                                                                                                                       B IN A R Y IN P U T
                                                                                                                                                                                                                                        1

                                                                                                                                              24 V A C
                                                                                                                                                                                                                                        2
                                                                                                                                                                                                                                        3
                                                                                                                                                                                                                                        4

                                            DSI

                                                                                                                                                                                                                          Z BUS
                                                                                                                   24 V A C
                                                                                                                                 CO M
                                                                                                                             ZBU S
                                                                                                                                         REF
                                                                                                                                                                                                                              STAT   ZO N E
                                                                                                                                          N2-                                                                                                        TO
                                                                                                                                         N2+

                                                                                                                      24V A C                                                                                                           1

                                                       B IN A R Y O U TP U T S
                                                                                                                      24V A C

                                                                                                                                                                                                                                         B IN A R Y OU TP U T
                                                                                                                TR A C S

                                                                                                             C O M M ON
                                                                                                             C O M M ON

                                                                                                                                                                                                                                        2 3 4 5 6             7 8

                                                                                                                                                                                                                                                                                                                    1 2 3 4 5 6 7 8
                                                                                                             C O M M ON

                                                                                                             C O M M ON
                                                                                                             C O M M ON

                                                                                                                                                                                                                                                                                                                                                        untpwer

                          Figure 26: UNT Pre-mounted in Enclosure

              If you purchase the UNT pre-mounted into an enclosure UNTxxx-101, it
              comes with a 50 VA transformer and no power entry box.

                                                                                                                                                                                                                                                                                                                  UPM—Universal Packaging Module 29
DX-9100

                                                   XT     XP      XP

                                                                         2-xpxtdx

                                        Figure 27: DX-9100 in a UPM

DIN Rail            You can mount units inside the enclosure on a DIN Rail for close to door
Mounting            viewing. Refer to Figure 28.

                                                    W in d o w

                                           XT              XP           XT

                                                        D in R a il

                                                    B o tt o m V ie w                   D IN RA IL

                                        Figure 28: DIN Rail Mounting

30 UPM—Universal Packaging Module
Function               The FMK102 fits into the UPM enclosure.
Module Kit             Note: Previous versions of the Function Module Kit are not supported in
                             the UPM.

                                                                     Angle Mounted FM Ks
                                                                     L o w V o lta g e   L in e V o lta g e

                                         8 3/4 In . (2 2 2.3 m m )
                                                E xte rio r

                                FM

             5 3/4 in . (1 4 6.0 m m )
                    E xte rio r

                                           A n g le d P o sitio n

                                                                                                      ah u1 0 3X

                                           Figure 29: Installing the Function Module Kit

                                                                     UPM—Universal Packaging Module 31
                                      Mounting
                                         Holes

                                                                   NEWFMK1

                                        Figure 30: Function Module Kit

                    Refer to Figure 30 and follow the steps below when installing an FMK102
                    into the UPM.
                    1.   Remove all Function Modules (FMs) from the FMK102. The
                         mounting holes are accessible through this area.
                    2.   Position the FMK in the desired area of the UPM. Ensure your
                         selected mounting position will not interfere with door closure. Align
                         the two mounting holes in the FMK with the grid pattern holes in the
                         UPM. Mark these holes to reference the mounting area.
                    3.   Set the FMK aside and install the two mounting screws provided in
                         the desired holes. Insert the screws so there is approximately
                         1/2 inch thread visible.
                    4.   Install the FMK mounting slots over the mounting screws. Slide the
                         FMK into place so the screws are positioned at the small end of the
                         slot.
                    5.   Tighten the screws and insert the FMs.

32 UPM—Universal Packaging Module
RLY002    To install the RLY002, use the two enclosed screws.
          Install the UPM in the desired location. Refer to the Installation section of
          this document for instructions on installing the UPM.
          Position the RLY002 so the terminal for relay contacts is adjacent to the
          line voltage wiring in the UPM. Figure 31 illustrates one of the many
          options for positioning the RLY002.

                                                                      L o w V o lta g e   Line Voltage
         IMPORTANT:   It is extremely important to separate
                      line voltage wiring and control/low
                      voltage wiring and circuitry by a
                      minimum of one inch. If this
                      condition is not met, the
                      installation may not comply with
                      local code requirements.

                                                                                                  AHU 103

              Figure 31: Mounting the RLY002 with Control Equipment

                                                              UPM—Universal Packaging Module 33
                    Use the two No. 8 sheet metal screws provided with the RLY002 to secure
                    the relay to the UPM backbone. Use two of the four standoffs on the
                    RLY002, keeping the mounting screws diagonally positioned from each
                    other as illustrated in Figure 32.

                        Install mounting screws on the
                        diagonal as illustrated:
                        either black screws to black holes,
                        or white screws to white holes.

                                                                                    upmrly

                                               Figure 32: Mounting the RLY002

                    For complete installation instructions for the RLY002, refer to
                    AS-RLY050-0 / AS-RLY100-1 / AS-RLY002 Relay Module Installation
                    Sheet.

34 UPM—Universal Packaging Module
                 Commissioning Procedures

Commissioning    ●   Take care when drilling or punching conduit holes to not introduce
Considerations       metal chips from the ground planes onto any electronic circuitry.
                 ●   Be sure to mount the unit high enough to provide room at the bottom
                     if you plan to add extra sections in the future. To further allow for
                     future expansion, bring conduit into the top or side of the unit, leaving
                     the bottom removable without rewiring.
                 ●   Equipment whose mounting holes are not on 1/2 inch center can still
                     be mounted by drilling the appropriate pilot holes directly into the
                     backbone (e.g., use a No. 27 drill 9/64 inch diameter for a No. 8
                     self-tapping screw). For maximum holding force, drill the holes
                     above or below (instead of to the left or right) of the existing
                     molded-in screw holes.

                                                         UPM—Universal Packaging Module 35
36 UPM—Universal Packaging Module
               Specifications/Ordering
               Information

Table 3: Specifications and Ordering Information
Code Number                Description                              Shipping Weight            Typical Uses

                    Universal Packaging Modules without Power Components
EN-EWC10-0                 UPM (Single unit)                        5.0 lb (2.3 kg)             Auxiliary Gear Mounting
EN-EWC20-0                 UPM (Dual unit)                          8.0 lb (3.6 kg)             Auxiliary Gear Mounting
EN-EWC30-0                 UPM (Triple unit)                        11.0 lb (5.0 kg)            Auxiliary Gear Mounting
EN-EWC40-0                 UPM (Quad unit)                          14.0 lb (6.4 kg)            Auxiliary Gear Mounting
                     Universal Packaging Modules with Power Entry Box Only
EN-EWC12-0                 UPM (Single unit)                        5.5 lb (2.5 kg)             N2 Dialer
EN-EWC22-0                 UPM (Dual unit)                          8.5 lb (3.9 kg)            NCM 300
              Universal Packaging Modules with Power Entry Box and Transformer
EN-EWC15-0                 UPM (Single unit with 50 VA)          