Текст документа
24- 10225- 12, Rev . C
TM-21x1 Series Room Temperature Module
Installation Instructions
Part No. 24-10225-12, Rev. C
Issued March 2016
Applications The TM-21x1 Series Room Temperature Module also
features a Light-Emitting Diode (LED) that indicates the
The TM-21x1 Series of Room Temperature Modules
current operating mode.
are designed for use with the Facility Explorer Series of
field controllers. The setpoint dial enables the room
IMPORTANT: The TM-21x1 Series Room
occupant to adjust the working setpoint of the
Temperature Modules are intended to provide an
controller. On scaled models, the marked adjustment
input to equipment under normal operating
range is 55 to 85°F; the controller determines the
conditions. Where failure or malfunction of the
actual setpoint temperature. On Warmer/Cooler
TM-21x1 Temperature Module could lead to
models, the adjustment range is marked +/- from
personal injury or property damage to the controlled
midpoint of the dial; the controller determines the
equipment or other property, other precautions must
equivalent setpoint temperature.
be designed into the control system. Incorporate and
With the occupancy button, the occupant can switch maintain other devices, such as supervisory or
the controller’s operating mode between occupied and alarm systems or safety or limit controls, intended to
standby. In addition, the TM-21x1 Series offers the warn of or protect against failure or malfunction of
option of a temporary occupied mode during the TM-21x1 Temperature Module.
unoccupied mode.
Installation
Parts Included
Two #6-32 x 7/8 in. (22 mm) wallbox mounting screws
are included with the TM-21x1 Module.
Special Tools Needed
For tightening and loosening the TM-11x1 Series Room
Temperature Module security screw, order the optional
Allen-head tool (T-4000-119) from the nearest
Johnson Controls® representative.
TM-21x1 Series Room Temperature Module Installation Instructions 1
Dimensions TM-2161 Modules
TM-2141 Modules
1.38 (35)
1.26 (32)
3.15 (80)
3.15 (80)
Fan
Speed
Dial
4.72
4.72 (120)
(120) Mode
LED
Occupancy
Button
Setpoint
Adjustment
Dial
FIG:2161_dim
FIG:2141_dim
Figure 3: TM-2161-0002 and TM-2161-0007
Figure 1: TM-2141 Dimensions, in. (mm) Dimensions, in. (mm)
TM-2151 Modules
1.38 (35)
1.26 (32)
3.15 (80)
3.15 (80)
Mode
LED
4.72
4.72 (120)
(120) Mode
LED
Occupancy Occupancy
Button Button
Setpoint
Adjustment
FIG:2161_0005_dim
Dial
FIG:2151_dim
Figure 4: TM-2161-0000 and TM-2161-0005
Figure 2: TM-2151 Dimensions, in. (mm) Dimensions, in. (mm)
2 TM-21x1 Series Room Temperature Module Installation Instructions
TM-2191 Modules 7. Attach the housing to the base and tighten the
security screw with the allen-head tool.
Mounting
1.38 (35) Location Considerations
Mount the TM-21x1 Series Room Temperature Module
on a wall in the room to be controlled where the
3.15 (80) occupant can easily read and adjust the setpoint dial or
fan speed override adjustment dial. Consider these
additional guidelines in determining the best mounting
location:
• Avoid areas subject to excessive vibration,
electrical noise, direct sunlight, or the effects of
radiant heat.
• Keep electrical wiring as short as possible to
4.72
(120)
minimize temperature error.
• Install modules in areas where the temperature is
representative of the general room conditions.
Setpoint Wiring
Adjustment
Dial
To wire a controller to the TM-21x1 Series Room
FIG:2191_dim
Temperature Module, see the appropriate wiring
diagram (Figure 6 to Figure 10).
Figure 5: TM-2191 Dimensions, in. (mm) Note: Use 22 AWG (0.65 mm diameter) wire
minimum. Do not exceed 164 ft (50 m) between the
controller and the temperature module.
Installing the TM-21x1
Table 1: Nominal Values for 10k ohm Sensors
To install the TM-21x1 Series Room Temperature
Module: Temperature Resistance
1. Use the Allen-head tool to loosen the security F C ohm
screw located at the top center of the housing. 20 -7 48,525
2. Insert a screwdriver blade or coin into the slot on 30 -1 34,919
the top of the housing. 40 4 27,550
3. Press down gently, and pry the housing away from 50 10 19,898
the base. As the two parts separate, remove the 60 16 12,246
blade or coin and continue to pull the housing away 70 21 11,993
from the base until the housing is free.
80 27 9,222
4. Pull the wires through the base. Locate the green
90 32 7,510
terminal blocks in the upper right of the base and
position the module on the wallbox with the 100 38 5,874
terminal numbers right-side up. 110 43 4,871
5. Mount the base to the wallbox using the two #6-32 120 49 3,956
mounting screws (included). 130 54 3,277
6. Wire the controller to the module. See the Wiring
section for correct wiring.
TM-21x1 Series Room Temperature Module Installation Instructions 3
TM-2141-0000 TM-2161-0002 and TM-2161-0007
Room Temperature Room Temperature
Module Module
51 Three-Speed Fan
Override
14 Occupancy Button
20 NTC Sensor
15 Mode LED
FIG:2141_WIR
20 NTC Sensor
21 Common
23 Temperature Setpoint
FIG:2161_0207_WIR
Figure 6: Wiring to an NTC Room Sensor
21 Common
22 DC +5 V
TM-2151-0000
Figure 9: Wiring to a Room Temperature Module
Room Temperature
Module
Featuring an NTC Sensor with Temperature
Setpoint Adjustment, Occupancy Override, and
14 Occupancy Button
Three Speed Fan Override
15 Mode LED
TM-2191-0000 and TM-2191-0005
20 NTC Sensor
Room Temperature
FIG:2151_WIR
Module
21 Common
Figure 7: Wiring to a Room Temperature Module
Featuring an NTC Sensor with Occupancy
20 NTC Sensor
Override
23 Temperature Setpoint
21 Common
FIG:2191_WIR
TM-2161-0000 and TM-2161-0005
22 DC +5 V
Room Temperature
Module
Figure 10: Wiring to a Room Temperature Module
14 Occupancy Button
Featuring an NTC Sensor without Occupancy
15 Mode LED Override
20 NTC Sensor
23 Temperature Setpoint
FIG:2161_0005_WIR
21 Common
22 DC +5 V
Figure 8: Wiring to a Room Temperature Module
Featuring an NTC Sensor with Temperature
Setpoint Adjustment, and Occupancy Override
4 TM-21x1 Series Room Temperature Module Installation Instructions
The following messages apply to wiring this product. IMPORTANT: Use copper conductors only. Make
all wiring connections in accordance with local,
CAUTION: Risk of Electric Shock.
national, and regional regulations. Do not exceed
Disconnect power supply before making
! electrical connections to avoid electric
the Temperature Module electrical ratings.
shock. Setup and Adjustments
Mise En Garde: Risque de décharge
électrique. Débrancher l'alimentation Make temperature or fan speed adjustments using the
avant de réaliser tout raccordement rotating dial, shown in Figure 3 and Figure 5.
électrique afin d'éviter tout risque de Repair Information
décharge électrique.
Do not field repair the TM-21x1 Series Room
Temperature Module. As with any electrical device,
CAUTION: Risk of Property Damage. keep the air vents clean and free from dust and
Do not run low voltage cable in the same
! conduit or wiring troughs with high
obstruction. To order replacement parts, contact the
nearest Johnson Controls representative.
voltage wires. Running low and high
voltage wires in the same conduit or
wiring troughs may damage the
equipment or cause system malfunction.
MISE EN GARDE : Risque de dégâts
matériels.
Ne pas faire courir un câble basse
tension dans les mêmes gaines ou
goulottes électriques que des câbles
haute tension. L'installation de fils basse
tension et haute tension dans les mêmes
gaines ou goulottes électriques risque
d'endommager l'équipement ou de
provoquer des dysfonctionnements du
système.
CAUTION: Risk of Property Damage.
Do not apply power to the system before
! checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
Mise En Garde: Risque de dégâts
matériels. Ne pas mettre le système
sous tension avant d'avoir vérifié tous les
raccords de câblage. Des fils formant un
court-circuit ou connectés de façon
incorrecte risquent d'endommager
irrémédiablement l'équipement.
TM-21x1 Series Room Temperature Module Installation Instructions 5
Technical Specifications
TM-21x1 Series Room Temperature Module (Part 1 of 2)
Models TM-2141-0000 Temperature Output Only
TM-2151-0000 Temperature Output with Occupancy Override
TM-2161-000x Temperature Output with Setpoint Adjustment and Occupancy
Override and Optional Fan Speed Adjustment
TM-2191-000x Temperature Output with Setpoint Adjustment
Power Requirements 5 VDC
Power Consumption N/A: Refer to individual component specification.
Inputs None
Adjustments Temperature Setpoint, Fan Speed (Optional by Model)
Mode Indicator Green LED (5 V, 4 mA)
Occupancy Button Momentary Contact Switch, 5 V at 1 mA
Output Temperature Sensing Resistance Temperature Device (RTD) Thermistor Negative
Element Temperature Coefficient (NTC) 10k ohm at 77°F (25°C)
Fan Speed 10k ohm potentiometer, with mechanically guided positions at
0, 25, 50, 75, 100% for Auto, Off, I (low speed),
II (medium speed), and III (high speed)
6 TM-21x1 Series Room Temperature Module Installation Instructions
TM-21x1 Series Room Temperature Module (Part 2 of 2)
Setpoint Range TM-2141-0000 No setpoint range
TM-2151-0000
TM-2161-0000 10k ohm potentiometer marked for 55 to 85°F
TM-2191-0000
TM-21x1-0002 10k ohm potentiometer marked for 55 to 85°F
Fan Speed Adjustment: Auto, Off, I, II, and III
TM-21x1-0005 10k ohm potentiometer marked for +/- (5F°)
TM-21x1-0007 10k ohm potentiometer marked for +/- (5F°)
Fan Speed Adjustment: Auto, Off, I, II, and III
Accuracy ±0.9°F (±0.5°C)
Field Connection 18 to 22 AWG (1.00 to 0.65 mm diameter) recommended
Mounting Wallbox Mount
Housing Material ABS + PC, Self-Extinguishing HB UL94
Protection IP30 (EN 60529)
Ambient Operating Conditions 32 to 122°F (0 to 50°C)
10 to 90% RH, noncondensing
Ambient Storage Conditions -40 to 158°F (-40 to 70°C)
5 to 95% RH, noncondensing
Dimensions TM-2141 4.72 x 3.15 x 1.26 in.
(H x W x D) TM-2151 (120 x 80 x 32 mm)
TM-2161 4.72 x 3.15 x 1.38 in.
TM-2191 (120 x 80 x 35 mm)
Shipping Weight 0.44 lb (0.2 kg)
Compliance Europe CE Mark: EMC Directive, EN-61000-6-2
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS
WESTENDHOF 3 507 E MICHIGAN ST C/O CONTROLS PRODUCT
45143 ESSEN MILWAUKEE WI 53202 MANAGEMENT
GERMANY USA NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
TM-21x1 Series Room Temperature Module Installation Instructions 7