TEC3000 Series Single- or Two-Stage Economizer
Thermostat Controllers
Installation Instructions Part No. 24-10789-5, Rev. F
Issued July 2018
TEC3330-xx-xxx, TEC3331-xx-xxx,
TEC3630-xx-xxx, TEC3631-xx-xxx
Refer to the QuickLIT website for the most up-to-date version of this document.
Applications
The TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers are stand-alone and
field-selectable BACnet® MS/TP or N2 networked devices that provide control of the following:
• unitary rooftop units (RTUs)
• unitary RTUs with economizers
• unitary RTUs with heat pumps
• unitary RTUs with economizers and heat pumps
The networked models feature a field-selectable Building Automation System (BAS) BACnet MS/TP or N2
communication capability that enables remote monitoring and programming for efficient space temperature control.
All models include a USB port configuration that reduces installation time by allowing simple backup and restore
features from a USB drive, which enables rapid cloning of configuration between like units.
Some models have occupancy sensing capability built into the device. These thermostat controllers maximize up to
30% energy savings in high-energy usage commercial buildings, such as schools and hotels, during occupied
times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen UI with backlit display that makes setup and operation quick
and easy. Only the single-speed fan configuration is supported for fan coil equipment types.
IMPORTANT: The TEC3000 Series Thermostat Controller is intended to provide an input to equipment under
normal operating conditions. Where failure or malfunction of the thermostat controller could lead to personal
injury or property damage to the controlled equipment or other property, additional precautions must be
designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat
controller.
IMPORTANT: Le TEC3000 Series Thermostat Controller est destiné à transmettre des données entrantes à un
équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement
du thermostat controller risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre
équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires.
Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou
d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en
cas de défaillance ou de dysfonctionnement du thermostat controller.
TEC3000 Series Single- or Two-Stage Economizer Thermostat
Controllers Installation Instructions
1
North American Emissions Compliance
United States
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in
a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning the equipment
off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
Canada
This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (B) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
Installation
Parts Included
• one TEC3000 Series Thermostat Controller with integral mounting base
• one installation instructions sheet
Location Considerations
Figure 1: Thermostat Controller
Locate the TEC3000 Series Thermostat Controller:
Shown without Occupancy Sensor,
• on a partitioning wall, approximately 5 ft (1.5 m) Dimensions, in. (mm)
above the floor in a location of average
1-13/32
temperature, allowing for vertical air circulation to (36)
Security Screw
the TEC
• away from direct sunlight, radiant heat, outside
walls, outside doors, air discharge grills,
Display
stairwells, and from behind doors
4-23/32
• away from steam or water pipes, warm air stacks, (120)
unconditioned areas (not heated or cooled), or USB Port
sources of electrical interference
For integrated passive infrared (PIR) models, be sure
FIG:thermostat features
that the thermostat controller is located centrally,
where occupant movement is frequent.
5-5/8
Use insulating foam pads for installations where wiring (143)
passes through the wall to the thermostat.
Note: Allow for sufficient clearance to insert a USB drive into the USB port.
IMPORTANT: Only connect memory devices to the USB port. Do not use it for charging external devices.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
2
Installing the Thermostat Controller
1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls® T-4000-119 Allen-Head Adjustment Tool (order
separately) to remove the security screw if it is installed on the top of the thermostat controller cover. See
Figure 2.
2. Pull the top edge of the cover and open the thermostat controller as illustrated in Figure 2.
IMPORTANT: The cover is not secured on the bottom. Be careful not to drop the cover.
IMPORTANT: If you are installing more than one thermostat controller, keep track of which cover attaches to
which base.
IMPORTANT: Use proper Electrostatic Discharge (ESD) precautions during installation and servicing to avoid
damage to the electronic circuits of the thermostat controller.
Figure 2: Removing the Security Screw from the Thermostat Controller Cover
(Shown without Occupancy Sensor) (Left) and Removing the Thermostat Controller Cover (Right)
FIG:thermostat cover
FIG:security screw
3. Align the thermostat controller mounting base on the wall with the security screw on the top and use the base
as a template to mark the two mounting hole locations. See Figure 3.
Notes:
• If you need to install the thermostat controller on an electrical junction box, use
2-1/2 x 4 in. (63 x 101 mm) square boxes with mud ring covers and avoid smaller 1-1/2 x 4 in.
(38 x 101 mm) square or 3 x 2 in. (76 x 51 mm) boxes. This procedure ensures that you have enough
space for cabling, if needed.
• For surface-mounted applications, use durable mounting hardware, such as wall anchors, that cannot be
easily pulled out of the mounting surface.
4. Pull approximately 6 in. (152 mm) of wire from the wall and insert the wire through the center hole in the
thermostat controller mounting base. See Figure 3.
5. Secure the mounting base to the wall surface using two mounting screws (user supplied) as illustrated in
Figure 3.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
3
Note: Be careful not to overtighten the mounting screws.
Figure 3: Mounting Hole Locations, Dimensions, in. (mm) (Left) and Securing the Thermostat Controller
Mounting Base to the Wall (Right)
4-1/16
(103)
3-1/4
(83)
FIG:TEC Backplane2
FIG:TEC Backplane1
Wiring
When an existing thermostat controller is replaced, remove and label the wires to identify the terminal functions.
Risk of Electric Shock.
Disconnect the power supply before making electrical connections to avoid electric shock.
Risque de décharge électrique.
Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge
électrique.
Risk of Property Damage.
Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected
wires may result in permanent damage to the equipment.
Risque de dégâts matériels.
Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un
court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
4
IMPORTANT: Make all wiring connections in accordance with local, national, and regional regulations. Do not
exceed the electrical ratings of the TEC3000 Series Thermostat Controller.
IMPORTANT: Use proper ESD precautions during installation and servicing to avoid damage to the electronic
circuits of the thermostat controller.
To wire the thermostat controller:
1. Strip the ends of each wire 1/4 in. (6 mm) and connect them to the appropriate screw terminals as indicated in
Table 2 and Figure 7.
Note: For more details on wiring the MS/TP Communications Bus, refer to the MS/TP Communications Bus
Technical Bulletin (LIT-12011034).
2. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature
readings.
3. Reattach the communication wires to the terminal block.
Note: If multiple wires are inserted into the terminals, be sure to properly twist the wires together before
inserting them into the terminal connectors.
4. Set the bus end-of-line (EOL) termination switch to the desired location on the TEC3630-00-000 and
TEC3631-00-000 models only.
The bus EOL termination switch allows you to designate the thermostat controller as the end of the Field
Controller (FC) Bus and N2 Bus. The default position is OFF. If the thermostat controller is at the end of a daisy
chain of devices on the FC Bus and N2 Bus, set the EOL switch to the ON position. See Figure 4.
Figure 4: EOL Switch Positions (Left) and Installing the Thermostat Controller Cover (Right)
O O
N N
EOL Switch EOL Switch FIG:EOL_Swtch
ON Position OFF Position
O
N
FIG:close thermostat cover
FIG:TEC Backplane2_EOL Switch
5. Reattach the thermostat controller cover to the mounting base (bottom side first).
IMPORTANT: Make sure you reattach the cover that corresponds to its correct base. The CPU board number
needs to match the base board number. Otherwise, an operation error occurs after you reattach a cover and
base that do not belong together (as shown in Figure 5). See Table 1 for TEC3000 model names and code
numbers.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
5
Figure 5: Error Code Indicating
Mismatched Boards Table 1: TEC3000 Model Names and Code Numbers
Name Code Number1 Name Code Number1
TEC3310 00 TEC3610 0A
TEC3311 01 TEC3611 0B
TEC3312 02 TEC3612 0C
TEC3313 03 TEC3613 0D
TEC3320 04 TEC3620 0E
TEC3321 05 TEC3621 0F
TEC3322 06 TEC3622 10
TEC3323 07 TEC3623 11
CPU Board Base Board
TEC3330 08 TEC3630 12
TEC3331 09 TEC3631 13
1. The two-character code number is listed within the error code to
indicate that the CPU board and base board do not belong together.
However, if the same code number appears as both the CPU board
and base board, there is no error. For example, if 0B is listed as the
CPU board and the base board, the model is the TEC3611.
6. Use a 1/16 in. (1.5 mm) Allen wrench or Figure 6: Installing the Security Screw from the
Johnson Controls T-4000-119 Allen-Head Adjustment Thermostat Controller Cover
Tool (order separately) to reinstall the security screw (Shown without Occupancy Sensor)
on the top of the thermostat controller cover.
7. Remove the protective plastic cover sheet from the
display.
IMPORTANT: If the display is dirty, gently wipe it
clean with isopropyl alcohol or ethyl alcohol. Do not
scrub hard as to avoid damaging the surface. Do not
use other cleaners such as water, ketones, and
aromatic solvents, since they may damage the
polarizer.
FIG:security screw
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
6
Table 2: Terminal Identification (See Figure 7 for Wiring Diagram)
Terminal Label Function
TEC3330, TEC3331 TEC3630, TEC3631
24 V 24 VAC hot from the sensor
Y1 Cooling stage 1
Y2 Cooling stage 2
OAD Economizer
AUX Auxiliary binary output
AUX Auxiliary
W1 OB Heating 1 (RTU mode)/Reversing valve (O/B) (Heat Pump mode)
RH 1 Power for W1 and W2
W2 SUP Heating 2 (RTU mode)/Supplemental heat (Heat Pump mode)
OAT Outside air temperature
COM 2 Common
G Fan
BI2 Configurable binary input 2
BI1 Configurable binary input 1
SAT Supply temperature sensor
R SEN Zone temperature sensor
NET+ Not connected Field bus+/N2+
NET- Not connected Field bus-/N2-
NET COM Not connected Isolated common for field bus
1. RH needs to be connected for W1 and W2 to energize. For heating systems with an isolated power
supply, connect RH to the R terminal of the heating system. For systems that switch the hot supply
to the heating commands, jumper to 24 V. For systems that switch the neutral supply to the heating
commands, jumper to COM.
2. The common terminals, which do not include NET COM, are internally connected and can be used
for all inputs and outputs.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
7
Note: Only one transformer is required for each TEC.
Figure 7: Staged Wiring Diagram - Rooftop Unit (See Table 2 for Terminal Identification)
Outdoor Air Temp Heat 1
TB1
W2 SUP
RH
W1 OB
Y1
Y2
G
AUX
AUX
FIG:Model 3 Wiring_input
Cool 2 Cool 1
24 V
Common
NET COM
R SEN
SAT
OAD
24V
COM
Supply/Aux
Thermistor
Thermistor
24 V
FIG:Model 3 Wiring_output
Economizer Vin
Common
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
8
Note: Only one transformer is required for each TEC.
Figure 8: Staged Wiring Diagram - Heat Pump (See Table 2 for Terminal Identification)
Outdoor Air Temp O/B
TB1
W2 SUP
RH
W1 OB
Y1
Y2
G
AUX
AUX
FIG:Model 3 Wiring_input_heatpump
Compressor Compressor
2 1
24 V
Common
NET COM
R SEN
SAT
OAD
24V
COM
Supply/Aux
Thermistor
Thermistor
24 V
FIG:Model 3 Wiring_output
Economizer Vin
Common
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
9
Figure 9: AUX Contact Wiring
Hot
19 to 30 VAC
FIG:Aux Contact Wiring
AUX Contact
Load
Figure 10: Binary Input Wiring
Dry Contact
FIG:Binary Input Wiring
BI1
Dry Contact Bi2
Setup and Adjustments
IMPORTANT: Table 10 provides a full list of TEC3000 menu settings. In the upcoming sections, step-by-step
instructions are included on how to access and adjust the more commonly used menus.
Overview
Figure 11 shows the thermostat controller home screen. You can customize it to show or hide various elements
from the occupant. See Table 3 for a listing of the touchscreen icons and Table 10 to identify the home screen
settings under the Display Settings. When screen customization is used in conjunction with a passcode, the
building owner can control which options the occupant can access and adjust.
IMPORTANT: If lockout levels are used, some icons are hidden. Table 4 provides details of these levels.
Figure 11: Thermostat Controller
Home Screen
This model cannot be purchased with a built-in sensor. The only way for the unit to display humidity is if the network
override for humidity is active. If this override is active, the humidity level is displayed on the home screen.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
10
Customizing the Home Screen
Customizing the Home screen settings include:
• Brightness • Units • Time Zone • Date
• Enable Backlight • Time • Time Format • Date Format
You can also show or hide these items on the Home screen:
• Fan Button • Off Button • Alarm Indication • Date/Time
• Space Temperature • Hold Button • Occupancy Status
• Humidity • Setpoint • Unit Status
To customize the Home screen:
1. Press the Menu icon.
2. Press Display Settings.
3. Enable or disable elements of the home screen as appropriate for the building owner and occupants.
4. Set the passcode on the thermostat controller to prevent the occupants from changing settings that they should
not have access to change.
Touchscreen Icons
Table 3 describes the home screen touchable icons. Press and release a touchscreen icon to activate the TEC.
Additional touchable icons appear based on the menu, and those icons are also described in Table 3.
Table 3: Touchscreen Icons (Part 1 of 2)
Icon Icon Name Description
Displays the configuration screens where various settings may be adjusted.
Menu
Indicates that the thermostat controller has triggered an alarm.
Alarm
Unit Power Powers the thermostat controller on or off.
On Note: This icon disables all equipment control, but does not physically
power down the unit.
Off
Indicates that the thermostat controller detected a supervisory controller and
Network Communication both are online.
Increases or decreases a value depending on the configuration screen.
Arrow
Displays the current setpoint. Hold mode is enabled by pressing the button.
Run/Hold
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
11
Table 3: Touchscreen Icons (Part 2 of 2)
Icon Icon Name Description
Displays the current setpoint. Hold mode is not enabled.
No Hold/Hold
Displays the active setpoint. Hold mode is not enabled.
Hold/Hold
Proceeds to the next screen.
Right Arrow
Fan Overrides for Adjusts the fan override between On, Auto, and Quiet for single-speed fans.
Single-speed Fans
On
Auto
Quiet
Returns the display to the main home screen.
Home
Returns to the previous screen.
Back
Saves the current configuration and parameter settings.
Save
Deletes the scheduled event.
Delete
Clears the password entry on the keypad screen.
Clear
Indicates that the value is editable.
Wrench
Indicates that an event or schedule is programmed for a specific day of the
Checkmark week.
Indicates that an error has occurred.
Exclamation Point
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
12
User Lockout
You can select from three different levels of access at the local display to manage functionality through the
supervisory controller. This lockout is independent of any display or passcode settings. The existing temporary
occupancy capability is unaffected by this feature. User lockout hides the icons that are not operable. The lockout
levels are described in Table 4.
Table 4: User Lockout Levels
Lockout Level Capability
State 0 Allows full access to Home Screen Display Adjustments and icons (default).
State 1 Hides the Menu icon.
State 2 Only allows the screen to trigger temporary occupancy. Menu, Unit Power, the Up
and Down arrows, and Run/Hold are hidden.
Using the USB Port
The USB port allows you to quickly and easily load firmware upgrades, backup settings, and restore settings to the
TEC3000 by using a USB drive. The TEC3000 can recognize eight configuration files or firmware package files.
The USB drive format must be FAT or FAT32. The drive cannot be NTFS or USB 3.0. If you are upgrading firmware
or copying configuration files, you need the TEC3000 passcode, if it has been set up. Do not remove the USB drive
until the firmware upgrade is complete. The TEC3000 may restart and go offline to the NAE after a firmware
upgrade. The upgrade takes approximately three minutes.
Configurations are copied, except for the Communication mode. See Choosing the Communication Mode
(TEC3630-00-000 and TEC3631-00-000 Models) to configure each device.
Loading the Firmware
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Scroll down the menu and press Update.
5. Press Load Firmware.
6. Select the correct firmware version. The correct file name has the .pkg extension.
7. Press Confirm if you have the correct firmware version.
The firmware is loaded from the USB drive into the TEC3000 operating system. The TEC3000 locates the new
firmware only if the new firmware is on the root drive of the USB drive. See Troubleshooting if the firmware is
not loaded correctly.
8. Remove the USB drive from the TEC3000 controller when the update is complete.
The TEC3000 firmware update is complete when the TEC3000 restarts and returns to the home screen.
Backing Up the Settings
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Scroll down the menu and press Update.
5. Press Backup.
A message appears stating that the file is saved locally and on a USB drive.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
13
6. Press Confirm to save locally and on USB.
The setting files are named based on the TEC3000 model name, date, and time stamp
(for example, TEC3311-00_2015-10-08T1). The files are saved locally and on the USB drive’s root directory.
See Troubleshooting if the settings are not backed up correctly.
7. After the settings are saved onto the USB drive, remove the USB drive from the TEC3000.
Restoring the Settings
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Press Update.
5. Press Restore.
6. Select Local Storage or the correct configuration file created from a previous backup operation.
The setting files are named based on the TEC3000 model name, date, and time stamp
(for example, TEC3311-00_2015-10-08T1). The files are saved locally and on the USB drive’s root directory.
7. Press Confirm if you have the correct file name.
The settings are loaded from the USB drive.
8. After the settings are loaded from the USB drive, remove the USB drive from the TEC3000.
Choosing the Communication Mode (TEC3630-00-000 and TEC3631-00-000 Models)
1. Ensure that the TEC screen is on.
2. Press the Menu icon.
3. Press Network Setup.
4. Press FC Comm Mode.
5. Select BACnet or N2 by pressing .
6. Proceed to Step 7 to perform BACnet communication and Step 15 to perform N2 communication.
7. Press to return to the previous screen.
8. Press BACnet Instance ID.
9. Enter the unique BACnet instance ID through the keypad.
10. Press Save.
11. Press to return to the previous screen.
12. Press BACnet Address.
13. Enter the BACnet MS/TP address through the keypad.
14. Press Save.
15. After selecting N2 in Step 5, press Save.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
14
16. Press to return to the previous screen.
17. Press N2 Address.
18. Enter the N2 address through the keypad.
19. Press Save.
Configuring the Thermostat Controller
Use the Menu icon on the home screen to access and change the basic operating parameters of the thermostat
controller. During normal operation, press the Menu icon once to access the following parameters:
• Faults Status • Display Settings • Equipment Setup • Controller Information
• Setpoints • Control Setup • System Status • Commissioning
• Schedule • Network Setup • Control Status • Update
Installer Configuration Menu
The thermostat controller comes from the factory with default settings for all configuration parameters. The UI
menu navigation and default settings are shown in Table 10. Before any outputs turn on, the controller must be
configured for the equipment connected. You need to start from the home screen to perform any of the following
tasks.
Screen Reset
The current screen returns to the home screen if the current screen is not touched for 3 minutes.
Selecting Rooftop or Heat Pump Mode
By default, the thermostat controller is configured for Rooftop mode. This mode is used for up to two discrete
stages of heating (W1, W2) and up to two discrete stages of cooling (Y1, Y2). Certain heat pumps do not require an
O/B input and instead take standard W and Y commands as heat or cool commands, internally sequencing the
equipment. For these type of heat pump units, leave the controller in Rooftop mode.
When in heat pump mode, the TEC controls up to two stages of compressors (Y1, Y2) for both heating and cooling.
O/B is controlled through the W1/OB output and one stage of supplemental heat is controlled through the W2/SUP
output. To configure heat pump mode:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press Heat Pump.
4. Press Heat Pump Supported and select Yes.
5. If supplemental heating is installed, press Supp Heating Installed and select Yes.
6. Press Reversing Valve Polarity and set appropriately for the O/B input on the equipment based on if the
equipment is normally cooling until the thermostat output is activated or normally heating (typically, Normally
Heat for O and Normally Cool for B).
7. Press to save and to return to the previous screen.
Configuring Heating and Cooling Stages
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press General.
4. Press Number of Compressors and adjust the number of compressor inputs on the equipment being
controlled.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
15
5. If the thermostat controller is in rooftop mode, press Number of Heating Stages and adjust the number of
heating inputs on the equipment being controlled.
6. Press to save and to return to the previous screen.
Configuring Economizer
If the equipment has an analog (between 0 to 10 V) input for an economizer damper command, configure the
economizer as follows:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press Economizer.
4. Press Economizer Installed and select Yes.
5. Press Min Position and set to the percentage that the damper must be kept open to ensure fresh air flow in
the zone.
6. Press Closed Voltage and set to the voltage output at which the damper is fully closed.
7. Press Opened Voltage and set to the voltage output at which the damper is fully opened.
8. Press to save and to return to the previous screen.
The TEC supports three methods of determining economizer availability. These are Dry Bulb, Single Enthalpy, and
Dual Enthalpy, in increasing order of accuracy. To run an economizer, outdoor air temperature (OAT) is required to
run in Dry Bulb mode. This can be provided by connecting a sensor to the OAT input on the TEC. It also can be
provided by writing to NET-OAT from a Building Automation System (BAS), which overrides the internal sensor. If
Outdoor Air Humidity (OAH) is also provided by writing to NET-OAH, then the single enthalpy method is used to
determine if economizer cooling should be used. Finally, if Zone Humidity (ZNH) is also provided by writing to
NET-ZNH, then the dual enthalpy method is used to determine if economizer cooling should be used.
All network overrides to the TEC work on a timeout basis. If the value is written to, it remains active as long as the
BAS writes a new value within 15 minutes of the first one. If the 15-minute timeout occurs without getting any data
written, the TEC stops using the network data
When operating in Dry Bulb or Single Enthalpy mode, it is necessary to provide a Dry Bulb Setpoint or an OA
Enthalpy Setpoint, respectively. The TEC ships with default values set, but depending on climate it may be
necessary to change these. To access these values:
1. Press the Menu icon.
2. Press Equipment Setup.
3. Press Economizer.
4. Press Dry Bulb Setpoint or OA Enthalpy Setpoint and adjust according.
5. Press to save and to return to the previous screen.
Setting the Control Mode
The Control Mode tells the controller to run in Cooling only, Heating only, or Automatic mode, based on the
temperature in the zone relative to the heating and cooling setpoints. This setting does not override equipment
lockouts, such as low or high outdoor temperature lockouts. To set the Control Mode:
1. Press the Menu icon.
2. Press Control Setup.
3. Press General.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
16
4. Press Control Mode and select Cooling, Heating, or Auto as desired.
5. Press to save and to return to the previous screen.
Setting the Fan Mode
The Fan Mode informs the controller how to handle the fan. There are two options for fan configuration: a Fan
Mode available to the installer through the menu system, and a fan override available as an option to the end user
from the Fan icon on the home screen. See Customizing the Home Screen for information on enabling and
disabling end-user controls. The Fan Mode available to the installer is dependent on the fan type. The following
options are provided for single-speed fans:
• On—Fan is continuously on
• Auto—Fan cycles on demand with the stages of heating or cooling (continuous when free cooling with the
economizer is running)
• Smart—Fan cycles on demand with the stages of heating or cooling during unoccupied periods but is
continuously running during occupied/standby periods
The Fan Override icon on the home screen is dependent on the fan type. The following options are provided for
single-speed fans:
• On—Overrides the fan to be continuously on
• Auto—Follows the behavior set as Fan Mode
• Quiet—Follows the behavior set as Auto Mode. The Quiet option has no effect on the RTU/heat pump
equipment as only a single-speed fan is supported.
To set the Fan Mode:
1. Press the Menu icon.
2. Press Control Setup.
3. Press General.
4. Press Fan Mode and select On, Auto, or Smart.
5. Press to save and to return to the previous screen.
Configuring the Zone Space or Equipment Size
With non-binary outputs, the TEC3000 is configured by default to have a slower temperature response for larger
zones with normal-sized equipment. In installations with small zones and oversized equipment, set the Equipment
Size parameter to Oversized.
To set the Equipment Size parameter:
1. Press the Menu icon.
2. Press Control Setup.
3. Press Tuning.
4. Use the up and down arrows to navigate to Equipment Size.
5. Press Equipment Setup and select Oversized.
6. Press to save and to return to the previous screen.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
17
Temperature Setpoints
The thermostat controller provides a flexible setpoint configuration to give power to the building owner while being
easy to use by the occupant. In addition to a simple up/down offset adjustment on the home screen for the
occupant, there are six temperature setpoints on the TEC. The six temperature setpoints are Cooling and Heating
setpoints for Occupied, Unoccupied, and Standby modes. To set these setpoints:
1. Press the Menu icon.
2. Press Setpoints.
3. Select the desired setpoint to adjust and change as desired.
4. Press to save and to return to the previous screen.
Note: The TEC enforces a 2-degree deadband between heating and cooling setpoints. If a setpoint violates this
standard (for example, cooling setpoint is set to 70 with a heating setpoint already set to 70), the opposing setpoint
is modified to comply with this deadband (in the previous example, the heating setpoint would automatically
change to 68).
The occupant has access to an up/down adjustment from the home screen. This adjustment applies a fixed offset
(+/-) to the currently active setpoint, and this offset holds until the occupancy state of the controller changes. If the
user taps the setpoint on the home screen, the icon inverts and displays white text on a black icon. The offset is
held throughout all occupancy periods. For example, if the TEC is cooling in Occupied mode to an occupied cooling
setpoint of 72 and you raise the setpoint 2 degrees to 74 from the home screen and then select hold, then the +2
degree offset persists through an occupancy change. If the occupancy then changes to unoccupied, with a setpoint
of 80 degrees, the effective setpoint is 82 degrees. This allows the occupant to have a small amount of control over
raising or lowering the temperature, but the building owner can still set back setpoints during standby and
unoccupied periods. When the setpoint is in Hold mode, pressing the icon again releases the hold and immediately
sets the setpoint offset back to 0.
When the TEC is in Min/Max mode (Setpoints/Occ Setpoint Select are equal to Min and Max Setpoint), the TEC
rejects any attempts to change the present value outside of the valid range. If the present value is outside of the
valid range (for example, if the Occ Setpoint Select is switched from Setpoint Offset to Min and Max Setpoint), the
present value is reset to be in the center of the valid range.
The four modes of setpoint operation are described in Table 5.
Table 5: Setpoint Operation
Mode of Setpoint Details
Operation
Occ Setpoint Select = This is the default mode and the original mode of operation that the TEC was released with
Setpoint Offset and (the next three modes are new). In this mode, the TEC has a heating setpoint and a cooling
Heat Cool Setpoint Mode = setpoint. There is a common Setpoint Offset (warmer/cooler adjust) that is applied to each
Individual Setpoints setpoint simultaneously. The range of setpoint adjustment is two-fold:
• There are large constant ranges bounding the individual heating and cooling setpoints.
• There is also a smaller configurable range limit set to the Setpoint Offset point (Control
Setup > General > Max Setpoint Offset).
Occ Setpoint Select = Min In this mode, the TEC has a heating setpoint and a cooling setpoint. Each setpoint has a
and Max Setpoints and configurable range (Setpoints > Min Cooling Setpoint, Max Cooling Setpoint, Min
Heat Cool Setpoint Mode = Heating Setpoint, and Max Heating Setpoint). The configurable range values are bounded
Individual Setpoints by the larger constant bounds used in Setpoint Offset mode and are constrained in the
following manner: Min must be below Max and Heating must be below Cooling, so in order
from least to greatest, the values are: Min Heating Setpoint, Max Heating Setpoint, Min
Cooling Setpoint, and Max Cooling Setpoint.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
18
Table 5: Setpoint Operation
Mode of Setpoint Details
Operation
Occ Setpoint Select = In this mode, the TEC has one setpoint, Common Setpoint, for heating and cooling. There is
Setpoint Offset and also a common Setpoint Offset (warmer/cooler adjust) that is only applied to Common
Heat Cool Setpoint Mode = Setpoint. Otherwise, this setting works the same as when Occ Setpoint Select = Setpoint
Common Setpoint Offset and Heat Cool Setpoint Mode = Individual Setpoints.
Occ Setpoint Select = Min In this mode, the TEC has one setpoint, Common Setpoint, for heating and cooling. There is
and Max Setpoints and a configurable range for Common Setpoint, Min Setpoint, and Max Setpoint.
Heat Cool Setpoint Mode =
Common Setpoint
Configuring Occupancy
The TEC3000 controller supports a wide variety of occupancy sources to adapt to nearly any application.
• Local stand-alone weekly scheduler
• Remote schedule from BAS
• Occupancy sensor (internal or remote)
• Occupancy binary input (configurable)
• Manual occupancy override
• Temporary occupancy (by interacting with screen while unoccupied)
• Temporary occupancy binary input
Occupancy is determined using a top-down decision matrix as shown in Table 6.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
19
Enumerations may not match the TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat
Controllers with Dehumidification Capability Installation Instructions (Part No. 24-10787-6), TEC3000 Series
Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification Capability Installation
Instructions
(Part No. 24-10788-0), TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation
Instructions (Part No. 24-10789-5), and TEC3000 Series Field-Selectable BACnet MS/TP or N2 Networked
Thermostat Controllers Technical Bulletin (LIT-12011956) for NAE releases prior to 7.x.
Table 6: Occupancy Determination
Sequence of Operation (Highest to Lowest Priority) Status Indicated
Manual Occupancy Temporary Occupancy Motion Effective Occupancy
Occupancy BI (BI1-S, Occupancy2, Schedule Sensor4 Occupancy Source
Mode BI2-S)1 3 (External or (EFF-OCC) (OCCSOURCE-S)
(OCCOVRD Schedule)
-MODE) (OCC-
CONFIG,
NET-OCC)
Occupied – – – – Occupied- Occ Override
Override
Unoccupied Unoccupied-
Override
No Override Closed1 Occupied Occupancy BI
Open1 Unoccupied
Not True2 NOT Temp Temp Occ
Configured1 Occupied Occupancy
True3 NOT Temp Temp Occ BI
Occupied Occupancy
False Occupied True Occupied Occupancy Sensor
False Standby
Disabled Occupied Occupancy
Schedule
Unoccupied – Unoccupied
Standby Standby
Not Set5 True Occupied Occupancy Sensor
False Unoccupied
Disabled Occupied Occupancy
Schedule
1. Not Configured means that neither BI1 Config nor BI2 Config is set to Occupancy BI. Open and Closed refer to the current
state of the BI when configured as Occupancy.
2. True is triggered by interacting with the screen during a scheduled unoccupied period. A value of True can only occur when
the schedule is not Occupied.
3. When triggered by a BI configured for Temp Occ, the input is ignored when the schedule is Occupied, the Manual
Occupancy Mode is not No Override, or an Occupancy BI is configured.
4. Built-in occupancy sensing (PIR) or EI configured for Motion NO or Motion NC.
5. Not Set occurs when no events are scheduled through the local scheduler, or the schedule source is set to Schedule and
the Schedule is writing Not Set as the schedule.
Selecting Schedule Source
Scheduling
The TEC3000 thermostat controller can operate as a stand-alone unit with an internal schedule or scheduled with
an external schedule. The OCC-CONFIG object sets the method used for scheduling.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
20
If the OCC-CONFIG is set to External, the NET-OCC object is used to control the unit externally.
If the OCC-CONFIG is set to Schedule, the internal schedule commands the LOCAL-OCC object, which sets the
Occupancy Schedule command.
Note: If you do not have a schedule in the Schedule object and you have the OCC-CONFIG set to Schedule, you
can control the unit with the LOCAL-OCC object externally; however, we do not recommend this method.
See Table 7 for scheduling information.
Once the Occupancy Schedule command is set, the effective occupancy is determined by settings shown in the
Occupancy Determination table. See Table 6.
Table 7: BAS Objects for Scheduling
BAS Objects for Scheduling
OCC-CONFIG LOCAL-OCC NET-OCC Occupancy Schedule
(Commanded by Command1
Internal Schedule)
External Any State Occupied Occupied
(Internal Schedule in
Unoccupied Unoccupied
Control)
Standby Standby
Not Set Not Set
Schedule Occupied Not Applicable Occupied
Unoccupied Unoccupied
Standby Standby
Not Set Not Set
1. The effective occupancy can be affected by other factors listed in Table 6.
The occupancy schedule can come from either the weekly scheduler built into the TEC or as an input from the
BAS. The Schedule Source must be selected to tell the controller where to read the occupancy source from. To
select the schedule source:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Schedule Source and select Schedule (Local) or External (BAS).
5. Press to save and to return to the previous screen.
This option is also exposed to the BAS through the point OCC-CONFIG. If BAS is configured as the occupancy
source, map the point NET-OCC in and write to that point to control the schedule remotely. If the supervisor goes
offline (as identified by the network icon going away on the home screen of the TEC), the control logic
automatically falls back to the local schedule as the occupancy source. If that schedule is not set, the default
occupancy is continuously occupied.
Setting the Local Schedule
A weekly occupancy schedule with up to four occupancy events for each day can be set locally on the TEC and
operate independently of a supervisor. To set the schedule:
1. See Selecting Schedule Source to ensure the schedule source is set to Local.
2. Press the Menu icon.
3. Press Schedule.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
21
4. Press Set Schedule.
5. Select the days to which the schedule should apply. Note that if events are already set for the selected days,
they appear in the corresponding event box. If any events conflict between selected days, an asterisk appears
in the event box.
6. Select the event to be set.
7. Set the Occupancy to Not Set, Occupied, Unoccupied, or Standby and press Save.
IMPORTANT: Internally, the TEC 3000 uses a BACnet schedule where daily schedules are independent of the
previous and next days. The default occupancy of the TEC3000 from the factory is set to Occupied. As a result,
a daily event at 12:00 AM must be scheduled if you do not want the controller to transition to Occupied Mode at
midnight.
Figure 12: Selecting the Days (Left) and Selecting the Event (Right)
Figure 13: Setting the Room Occupancy (Left) and Setting the Occupancy Mode (Right)
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
22
8. Set the time to the time at which the event should occur and press Save.
Figure 14: Setting the Event Time (Left) and Viewing the Event Time (Right)
9. Press Save to save the event and press the Return icon to return to the main scheduler screen.
Figure 15: Returning to the Main Menu
10. Press to save and to return to the previous screen.
Overriding the Occupancy Mode
The TEC supports a manual override of all other schedule sources (for example, Schedule, Occupancy BI, and
temporary occupancy). To override the Occupancy Mode:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Manual Occupancy Mode and select Occupied, Unoccupied, or No Override.
5. Press to save and to return to the previous screen.
This option is also exposed to the BAS through the point OCCOVRD-MODE.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
23
Enabling Optimal Start
The TEC supports an advanced optimal start algorithm. The algorithm works in conjunction with a local schedule to
pre-heat or pre-cool the zone before scheduled occupancy periods begin, in order to bring the zone to the desired
occupied setpoint when the scheduled occupancy period begins. Occupant comfort is ensured while automatically
minimizing energy usage. This algorithm creates a model of the zone being controlled and automatically
determines when to start the equipment before the scheduled transition to Occupied. The start time automatically
adjusts daily to minimize the time between reaching setpoint and entering Occupied state.
Note: Optimal Start does not work when the schedule source is set to External.
To enable this feature:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Optimal Start Enable and select Yes.
5. Press to save and to return to the previous screen.
Enabling the Motion Sensor (TEC3x31-00-000 Models)
By default on models with integral motion sensing capability, the motion sensor is enabled with a default timeout of
15 minutes from the last detection of motion in the zone. On models without an integrated sensor, the default
timeout is still 15 minutes, but it only is applied when one of the two configurable binary inputs is set to be a motion
sensor (see Configurable Binary Inputs for information on configuring the binary inputs). To disable motion sensing
capabilities, set the Motion Sensor Timeout to 0 minutes. See Table 6 to view the available setpoints. See Table 10
to view the setpoint values. To adjust the motion sensor timeout:
1. Press the Menu icon.
2. Press Schedule.
3. Press Schedule Options.
4. Press Motion Sensor Timeout and adjust accordingly.
5. Press to save and to return to the previous screen.
PID/PRAC+ Automatic Control Tuning
The TEC3000 features advanced proportional-integral-derivative (PID) control algorithms to maximize control
performance while minimizing excessive cycling and wear on the equipment. PID is used in conjunction with a
Multi-Stage Controller (MSC) for all occupied and standby control.
Additionally, the PID features Johnson CПоказано початок документа. Повний текст — у PDF за посиланням вище.