TEC22x7-4 Series LONWORKS® Network Thermostat
Controllers with Two Outputs Configuration
                                                                                                                       Code No. LIT-12011612
Technical Bulletin                                                                                                       Issued February 8, 2010
TEC2227-4, TEC2247-4

Network Variables (NVs) and Configuration Properties (CPs) List. . . . . . . . . . . . . . 3
    Network Variable Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    Using the nviHeatCool, nviAuxHeatEnable, and SeqOpera Variables . . . . . . . . . . . . 10

    NVI RemLockout                  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    Network Variable Outputs (NVOs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    Configuration Network Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    Space Comfort Controller Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    Commissioning the Thermostat Using a LONWORKS Network Configuration Tool . . . 18
    Service Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    TEC22xx-4 Fan Coil Configuration Plug-in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    Installing the Plug-in. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
    Registering the Plug-in. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    Using LN Browser to Display NVs, NCIs, and CPs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    Running the Plug-in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
         Heating - Cooling Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

         General Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

         Hardware Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

         PIR Options Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

         Network Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

         About Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    Status Light Emitting Diode (LED) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    Adding a Thermostat Controller to the NAE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    LONWORKS Thermostat Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
    Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
    TEC22x7-4 Series LONWORKS Network Thermostat Controllers with Two Outputs. . . 38

                           TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs                                                       1
                                                                      Configuration Technical Bulletin
2   TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration
    Technical Bulletin
TEC22x7-4 Series LONWORKS® Network
Thermostat Controllers with Two Outputs
Configuration
Network Variables (NVs) and Configuration Properties
(CPs) List
     Table 1 shows the NVs and CPs for the TEC22x7-4 Series Thermostat Controllers.
     Each Network Variable Input (NVI), Network Variable Output (NVO), and
     Network Configuration Input (NCI) has a reference number as defined in the XIF
     Resource File, and some objects have a subcategory number.
     The Bit column shows the bit number for each of the entry fields. If a value is
     supplied, the true Metasys® Target reference is the value + 1. For example, if the
     Bit column has a value of 0, then the true mapping index is 1. You must know the
     true mapping index when mapping LONWORKS® Point Objects into a Metasys
     system.
     The Metasys Target Reference is equal to the value in the No. column plus the
     value in the Sub column or Bit column (if available) in the format
     NV.<No. >.<Bit/Sub>. For example, using Filter alarm for nvoSccStatus as an
     example, the Metasys Target Reference is NV.17.30.
     Note: If the format has not been changed from the default SNVT_state_64, when
           viewed using a LONWORKS network configuration tool, the nvoSccStatus
           screen is a 64-bit field, one for each entry field.
Table 1: NV and CPs By Model (Part 1 of 4)
No.     Sub   Bit    Metasys      NV or CP Name                              Model
                     Target

                                                                           TEC2227-4   TEC2247-4
                     Reference

0                    NV.0         nviSpaceTemp                               X           X
1                    NV.1         nviOutdoorTemp                             X           X
2                    NV.2         nviSetpoint                                X           X
3                    NV.3         nviSpaceRH                                 N/A         N/A
4                    NV.4         nviFanSpeedCmd                             N/A         N/A
5                    NV.5         nviAuxHeatEnable                           X           X
6                    NV.6         nviOccManCmd                               X           X
7                    NV.7         nviApplicMode                              X           X
8                    NV.8         nviHeatCool                                X           X
9                    NV.9         nviRemLockout                              X           X
10                   NV.10        nviDhumiLCK                                N/A         N/A
11                   NV.11        nviAuxOut                                  X           X
12                   NV.12        nvoSpaceTemp                               X           X

       TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration    3
Table 1: NV and CPs By Model (Part 2 of 4)
No.    Sub    Bit    Metasys         NV or CP Name                         Model
                     Target

                                                                         TEC2227-4   TEC2247-4
                     Reference

13                    NV.13          nvoDischAirTemp                       X           X
14                    NV.14          nvoSpaceRH                            N/A         N/A
15                    NV.15          nvoEffectOccup                        X           X
16                                   nvoUnitStatus                         X           X
       1              NV.16.1        mode                                  X           X
       2              NV.16.2        heat_output_primary                   X           X
       3              N/A            heat_output_secondary                 N/A         N/A
       4              NV.16.4        cool_output                           X           X
       5              N/A            econ_output                           N/A         N/A
       6              NV.16.6        fan_output                            N/A         N/A
       7              NV.16.7        in_alarm                              X           X
17                                   nvoSccStatus                          X           X
Associate with UNVT_thermo_state_fc format file.
       1      2       NV.17.3        bi1_status                            X           X
       1      1       NV.17.2        bi2_status                            X           X
       2      0       NV.17.1        ui3_status                            X           X
       3      7       NV.17.8        dehumidification_active               N/A         N/A
       4      13      NV.17.14       state_terminal_bo1                    X           N/A
       5      12      NV.17.13       state_terminal_bo2                    X           N/A
       6      15      NV.17.16       state_terminal_bo3                    X           N/A
       7      14      NV.17.15       state_terminal_bo4                    X           N/A
       8      20      NV.17.21       state_terminal_bo5                    X           X
       9      21      NV.17.22       fan_low                               N/A         N/A
       10     22      NV.17.23       fan_med                               N/A         N/A
       11     23      NV.17.24       fan_high                              N/A         N/A
       12     24      NV.17.25       window_opened                         X           X
       13     28      NV.17.29       service_alarm                         X           X
       14     29      NV.17.30       filter_alarm                          X           X
       15     39      NV.17.40       local_pir_motion                      X           X
18                    NV.18          nvoTerminalLoad                       X           X
19                                   nciSetPts                             X           X
       1              NV.19.1        occupied_cool                         X           X
       2              NV.19.2        standby_cool                          X           X
       3              NV.19.3        unoccupied_cool                       X           X
       4              NV.19.4        occupied_heat                         X           X
       5              NV.19.5        standby_heat                          X           X
       6              NV.19.6        unoccupied_heat                       X           X

4     TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration
Table 1: NV and CPs By Model (Part 3 of 4)
No.    Sub    Bit    Metasys         NV or CP Name                        Model
                     Target

                                                                        TEC2227-4   TEC2247-4
                     Reference

20                                   nciCfg2FcuZn                         X           X
Associate with UNVT_cfg_2_fcu_zn format file.
       1             NV.20.1         bi1_config                           X           X
       2             NV.20.2         bi2_config                           X           X
       3             NV.20.3         ui3_config                           X           X
       4             NV.20.4         room_humidity_display                N/A         N/A
       5             NV.20.5         dehumidification_setpoint            N/A         N/A
       6             NV.20.6         dehumidification_hysterisis          N/A         N/A
       7             NV.20.7         dehumidification_max_cooling         N/A         N/A
       8             NV.20.8         calib_room_humidity_sensor           N/A         N/A
21                                   nciCfg1FcuZn                         X           X
Associate with UNVT_cfg_1_fcu_zn format file.
       1             NV.21.1         password                             X           X
       2             NV.21.2         control_type                         X           N/A
       3             NV.21.3         floating_actuator_time               X           N/A
       4             NV.21.4         cycles_per_hour                      X           N/A
       5             NV.21.5         reverse_or_direct_acting_output      N/A         X
       6             NV.21.6         menu_scroll                          X           X
       7             NV.21.7         auto_mode                            N/A         N/A
       8             NV.21.8         temperature_scale                    X           X
       9             NV.21.9         pipe_number_main_out_config          X           X
       10            NV.21.10        sequence_of_operation                X           X
       11            NV.21.11        fan_menu_sequence                    N/A         N/A
       12            NV.21.12        heat_maximum_setpoint                X           X
       13            NV.21.13        cool_minimum_setpoint                X           X
       14            NV.21.14        calib_room_sensor                    X           X
       15            NV.21.15        deadband                             X           X
       16            NV.21.16        setpoint_type                        X           X
       17            NV.21.17        setpoint_function                    N/A         N/A
       18            NV.21.18        temporary_occ_time                   X           X
       19            NV.21.19        proportional_band                    X           X
       20            NV.21.20        aux_contact_config                   X           X
       21            NV.21.21        reheat_time_base                     X           X
       22            NV.21.22        fan_mode                             N/A         N/A
       23            NV.21.23        auto_fan                             N/A         N/A
       24            NV.21.24        pir_standby_time                     X           X
       25            NV.21.25        pir_unoccupied_time                  X           X

      TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration   5
Table 1: NV and CPs By Model (Part 4 of 4)
No.    Sub    Bit    Metasys         NV or CP Name                         Model
                     Target

                                                                         TEC2227-4   TEC2247-4
                     Reference

22                                   nciSccModel                           X           X
Associate with UNVT_model_info_2 format file.
       1             NV.22.1         Thermostat Model Number               X           X
       2             NV.22.2         Software Version                      X           X
23                   NV.23           nciHvacType                           X           X
24                   NV.24           nciSndHrtBt                           X           X
25                   NV.25           nciMinOutTm                           X           X
26                   NV.26           nciRcvHrtBt                           X           X
27                   NV.27           nciMajVer                             X           X
28                   NV.28           nciMinVer                             X           X

6     TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration
Network Variable Inputs
Table 2: NVIs (Part 1 of 3)
Parameter           NVI Name and       Range and Enumeration Definition
                    SNVT Type
Room Temperature    nviSpaceTemp       Valid Range: -40°F/-40.0°C to 122°F/50.0°C
                    SNVT_temp_p        Default Null (release) Value: 621.8°F/327.67.0°C or (0x7FFF)
                                       represents invalid data.
                                       The heartbeat receive time is used by this network variable
                                       (nciRcvHrtBt).
                                       Note: This NVI allows the temperature setpoint for the occupied mode
                                              to be changed via the network. When bound or written to, the
                                              internal temperature reading (internal sensor) is no longer used.
Outdoor Air         nviOutdoorTemp     Valid Range: -40°F/-40.0°C to 122°F/50.0°C
Temperature         SNVT_temp_p        Default Null (release) Value: 621.8°F/327.67.0°C or (0x7FFF)
                                       represents invalid data.
                                       Note: This NVI provides outdoor air temperature information to the
                                              thermostat from a bound network outside air temperature value.
                                              Once bound, the thermostat automatically displays the value.
Occupied Cooling    nviSetpoint        Valid Range: Occupied Cooling 54°F/12°C to 100°F/37.5°C
and Heating         SNVT_temp_p        Valid Range: Occupied Heating 40°F/4.5°C to 90°F/32.0°C
Setpoint1                              Standby Cool Setpoint (Not used)
                                       Standby Heat Setpoint (Not used)
                                       Default Null (release) Value: 621.8°F/327.67°C or (0x7FFF) represents
                                       invalid data.
                                       Note: This NVI allows the temperature setpoints for the occupied mode
                                               to be changed via the network. The unoccupied setpoints are not
                                               changed.
Room Humidity       nviSpaceRH         Not used.
                    SNVT_lev_percent
Fan Mode            nviFanSpeedCmd     Not used.
                    SNVT_switch
Sequence of         nviAuxHeatEnable   State       Value      Equivalent         Auxiliary Heat Operation
Operation           SNVT_switch                               Percentage
                                       0           N/A        N/A                Disabled (Not used)
                                       0           0          0%                 Disabled
                                       1           1 to 199   0.5 to 99.5%       Partially Enabled (Not used)
                                       1           200 to     100%               Enabled
                                                   255
                                       0xFF        N/A        N/A                Enabled (Invalid)
                                       Note: This NVI enables or disables the auxiliary heat stage. It is also
                                             used in conjunction with nviHeatCool and SeqOper.
Occupancy           nviOccManCmd       0 = OC_OCCUPIED
                    SNVT_occupancy     1 = OC_UNOCCUPIED
                                       2 = OC_BYPASS (Not used)
                                       3 = OC_STANDBY (Not used)
                                       0XFF = OC_NUL (Release to internal schedule)
                                       Note: This NVI commands the Space Comfort Controller into different
                                             occupancy modes. It is typically sent by a supervisory node to
                                             manually control occupancy modes, or to override the scheduled
                                             occupancy. See Figure 1 for additional information on the Space
                                             Comfort Controller.

      TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration                    7
Table 2: NVIs (Part 2 of 3)
Parameter           NVI Name and      Range and Enumeration Definition
                    SNVT Type
System Mode         nviApplicMode     0 = HVAC_AUTO (Default)
                    SNVT_hvac_mode    1 = HVAC_HEAT
                                      2 = HVAC_MRNG_WRMUP (Not used)
                                      3 = HVAC_COOL
                                      4 = HVAC_NIGHT_PURGE (Not used)
                                      5 = HVAC_PRE_COOL (Not used)
                                      6 = HVAC_OFF
                                      7 = HVAC_TEST (Not used)
                                      8 = HVAC_EMERG_HEAT (Not used)
                                      9 = HVAC_FAN_ONLY (Not used)
                                      10 = HVAC_FREE_COOL (Not used)
                                      11 = HVAC_ICE (Not used)
                                      12 = HVAC_MAX_HEAT (Not used)
                                      13 = HVAC_ECONOMY (Not used)
                                      14 = HVAC_DEHUMID (Not used)
                                      15 = HVAC_CALIBRATE (Not used)
                                      16 = HVAC_EMERG_COOL (Not used)
                                      17 = HVAC_EMERG_STEAM (Not used)
                                      18 = 0XFF = HVAC_NUL (Not used)
                                      The heartbeat receive time is used by this network variable
                                      (nciRcvHrtBt).
                                      Note: This NVI coordinates the Space Comfort Controller with any
                                             supervisory controller providing the supply energy; for example,
                                             hot or cold water. It is used as heat/cool changeover. It is also
                                             used in conjunction with nviHeatCool and SeqOper. See Figure 1
                                             for additional information on the Space Comfort Controller.
Sequence of         nviHeatCool       0 = HVAC_AUTO (Default)
Operation           SNVT_hvac_mode    1 = HVAC_HEAT
                                      2 = HVAC_MRNG_WRMUP (Not used)
                                      3 = HVAC_COOL
                                      4 = HVAC_NIGHT_PURGE (Not used)
                                      5 = HVAC_PRE_COOL (Not used)
                                      6 = HVAC_OFF
                                      7 = HVAC_TEST (Not used)
                                      8 = HVAC_EMERG_HEAT (Not used)
                                      9 = HVAC_FAN_ONLY (Not used)
                                      10 = HVAC_FREE_COOL (Not used)
                                      11 = HVAC_ICE (Not used)
                                      12 = HVAC_MAX_HEAT (Not used)
                                      13 = HVAC_ECONOMY (Not used)
                                      14 = HVAC_DEHUMID (Not used)
                                      15 = HVAC_CALIBRATE (Not used)
                                      16 = HVAC_EMERG_COOL (Not used)
                                      17 = HVAC_EMERG_STEAM (Not used)
                                      18 = 0XFF = HVAC_NUL (Not used)
                                      The heartbeat receive time is used by this network variable
                                      (nciRcvHrtBt).
                                      Note: This NVI coordinates the Space Comfort Controller with any node
                                             that needs to control the heat/cool changeover of the unit. It is
                                             overridden by nviApplicMode, unless nviApplicMode is
                                             HVAC_AUTO. If nviApplicMode is HVAC_AUTO, then
                                             nviHeatCool determines the effective mode of the unit. See
                                             Figure 1 for additional information on the Space Comfort
                                             Controller.
                                      See Table 3 for information on using the nviHeatCool,
                                      nviAuxHeatEnable, and SeqOpera variables.

8    TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration
Table 2: NVIs (Part 3 of 3)
 Parameter                NVI Name and            Range and Enumeration Definition
                          SNVT Type
 Lockout                  nviRemLockout           See Table 4 for Lockout information.
                          SNVT_count              Note: This NVI enables or disables user access to the thermostat
                                                        controller.
 DehumiLCk                nviDhumiLCK             Not used.
 Aux Contact              nviAuxOut               0 = Auxiliary contact Off
                          SNVT_switch             1 = Auxiliary contact On
                                                  5 = Follow secondary network command
                                                  Note: If this NVI is used to remotely command the Auxiliary Output
                                                          (BO5), then the Auxiliary Output must be configured to a value of
                                                          5 for this function to operate.
 Room Humidity            nvoSpaceRH              Not used.
                          SNVT_lev_percent
 Fan Mode                 nviFanSpeedCmd          Not used.
                          SNVT_switch

1.   If one setpoint of a pair of heating and cooling setpoints (for example, Occupied Heat Setpoint and Occupied Cool
     Setpoint) is overridden, the other setpoint of the pair may be automatically adjusted by the thermostat controller to
     maintain the minimum deadband between the two setpoints.

        TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration                              9
Using the nviHeatCool, nviAuxHeatEnable, and SeqOpera Variables
Table 3: nviHeatCool, nviAuxHeatEnable, and SeqOpera Variables
Current           nviAuxHeatEnable       SeqOpera            If nviHeatCool         SeqOpera
nviHeatCool                                                  Changed To:
                        Same Outputs and Different Outputs
3 = HVAC_COOL     Disabled               0 = Cooling only    0 = HVAC_AUTO          4 = Cool/Heat
                                                                                    Different
                                                                                    Outputs
                                                             1 = HVAC_HEAT          1 = Heating
                                                                                    only
3 = HVAC_COOL     Enabled                2 = Cooling and     0 = HVAC_AUTO          5 = Cool/Heat
                                         Reheat                                     and Reheat,
                                                                                    Different
                                                                                    Outputs
                                                             1 = HVAC_HEAT          3 = Heating
                                                                                    and Reheat
1 = HVAC_HEAT     Disabled               1 = Heating only    0 = HVAC_AUTO          4 = Cool/Heat
                                                                                    Different
                                                                                    Outputs
                                                             3 = HVAC_COOL          0 = Cooling
                                                                                    only
1 = HVAC_HEAT     Enabled                3 = Heating and     0 = HVAC_AUTO          5 = Cool/Heat
                                         Reheat                                     and Reheat,
                                                                                    Different
                                                                                    Outputs
                                                             3 = HVAC_COOL          2 = Cooling
                                                                                    and Reheat
                                 Different Outputs
0 = HVAC_AUTO     Disabled               4 = Cooling only    0 = HVAC_HEAT          1 = Heating
                                                                                    only
                                                             3 = HVAC_COOL          0 = Cooling
                                                                                    only
0 = HVAC_AUTO     Enabled                5 = Cooling and     0 = HVAC_HEAT          3 = Heating
                                         Reheat                                     and Reheat
                                                             3 = HVAC_COOL          2 = Cooling
                                                                                    and Reheat

NVI RemLockout
Table 4: NVI RemLockout
Parameter      NV and SNVT        Lockout         Unoccupied                Occupied
               Types              Level           Override                  Temperature
                                                                            Setpoints
Lockout        nviRemLockout      (0)             Access                    Access
               SNVT_count         (1)             No Access                 Access
                                  (2*)            This lockout level is not used.
                                  (3*)            This lockout level is not used.
                                  (4)             Access                    No Access
                                  (5)             No Access                 No Access
                                  *If lockout level (2) or (3) is selected, the lockout functions
                                  like lockout level (0) or (1), respectively.
                                  Note: This NVI enables or disables user access to the
                                        thermostat controller.

10   TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration
Network Variable Outputs (NVOs)
Table 5: NVOs (Part 1 of 3)
Parameter       NVO Name and       Range and Enumeration Definition
                SNVT Type
Room            nvoSpaceTemp       Valid Range: 14°F/-10.0°C to 122°F/50.0°C
Temperature     SNVT_temp_p        Default Null (release) Value: 621.8°F/327.67.0°C or (0x7FFF) represents
                                   invalid data.
                                   Note: This NVO monitors the effective space temperature sensor that the
                                           Space Comfort Controller is using for control. It echoes the internal
                                           value on the device temperature sensor or that of nviSpaceTemp if it
                                           is bound, or a value is written to it.
Supply          nvoDischAirTemp    Valid Range: -40°F/-40.0°C to 122°F/50.0°C
Temperature     SNVT_temp_p        Default Null (release) Value: 621.8°F/327.67.0°C or (0x7FFF) represents
                                   invalid data.
                                   Note: This NVO monitors the temperature of the air that leaves the Space
                                           Comfort Controller. UI3 needs to be configured to (SS) supply air
                                           sensor monitoring.
Room Humidity   nviSpaceRH         Not used.
                SNVT_lev_percent
Occupancy       nvoEffectOccup     0 = OC_OCCUPIED
                SNVT_EffectOccup   1 = OC_UNOCCUPIED
                                   2 = OC_BYPASS1
                                   3 = OC_STANDBY (Not used)
                                   4 = OC_NUL
                                   Note: This NVO indicates the actual occupancy mode of the unit. This
                                          information is typically reported to a supervisory controller or
                                          provided to another Space Comfort Controller to coordinate the
                                          operation of multiple units.
                                   1OC_BYPASS can be initiated by either nviOccManCmd or a local input.
                                   NvoEffectOccup is only in OC_BYPASS for the duration of the ToccTime
                                   (nciCfg1FcuZn), until reinitiated by either a transition of the local input or an
                                   update to nviOccManCmd.

     TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration                          11
Table 5: NVOs (Part 2 of 3)
Parameter       NVO Name and       Range and Enumeration Definition
                SNVT Type
Unit Status     nvoUnitStatus      Sub    Bit     Name               Valid Value
                SNVT_hvac_status   01             Mode               0 = HVAC_AUTO
                                                                     1 = HVAC_HEAT
                                                                     2 = HVAC_MRNG_WRMUP (Not used.)
                                                                     3 = HVAC_COOL
                                                                     4 = HVAC_NIGHT_PURGE (Not used.)
                                                                     5 = HVAC_PRE_COOL (Not used.)
                                                                     6 = HVAC_OFF
                                                                     7 = HVAC_TEST (Not used.)
                                                                     8 = HVAC_EMERG_HEAT (Not used.)
                                                                     9 = HVAC_FAN_ONLY (Not used.)
                                                                     10 = HVAC_FREE_COOL (Not used.)
                                                                     11 = HVAC_ICE (Not used.)
                                                                     12 = HVAC_MAX_HEAT (Not used.)
                                                                     13 = HVAC_ECONOMY (Not used.)
                                                                     14 = HVAC_DEHUMID (Not used.)
                                                                     15 = HVAC_CALIBRATE (Not used.)
                                                                     16 = HVAC_EMERG_COOL (Not used.)
                                                                     17 = HVAC_EMERG_STEAM (Not used.)
                                                                     0XFF = HVAC_NUL (Not used.)
                                                                     Note: This NVO reports the Space
                                                                            Comfort Controller inputs’ and
                                                                            outputs’ status. It combines the
                                                                            operating mode, the capacity of
                                                                            heating and cooling used, and an
                                                                            indication if any alarms are present
                                                                            in the object.
                                   02             heat_output_primary                       0-100%, 0xFFF
                                                                                            (invalid)
                                   03             heat_output_secondary                     Not used.
                                   04             cool_output                               0-100%, 0xFFF
                                                                                            (invalid)
                                   05             econ_output                               Not used.
                                   06             fan_output                                0-100%, 0xFFF
                                                                                            (invalid)
                                   07             in_alarm                                  0 = No alarms
                                                                                            1 = Alarm On
                                                                                            0x7FF (Alarm
                                                                                            disabled) Not used.
                                   Note: This NVO is available to report the Space Comfort Controller status. It
                                         combines the operating mode, the capacity of heating and cooling
                                         used, and an indication if any alarms are present in the object.

12   TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration
Table 5: NVOs (Part 3 of 3)
Parameter         NVO Name and         Range and Enumeration Definition
                  SNVT Type
Thermostat I/O    nvoSccStatus         Sub    Bit     Name               Valid Value            Default Value
Status            UNVT_thermo_state_   01     2       BI1 Status         0 = Activated          1 = Not Activated
                  fc                                                     1 = Not Activated
                                       02     1       BI2 Status         0 = Activated          1 = Not Activated
                                                                         1 = Not Activated
                                       03     0       UI3 Status         0 = Activated          1 = Not Activated
                                                                         1 = Not Activated
                                       04     7       Dehumidification   Not used               N/A
                                                      Active
                                       05     13      State Terminal     0 = Off                0 = Off
                                                      BO1                1 = On
                                       06     12      State Terminal     0 = Off                0 = Off
                                                      BO2                1 = On
                                       07     15      State Terminal     0 = Off                0 = Off
                                                      BO3                1 = On
                                       08     14      State Terminal     0 = Off                0 = Off
                                                      BO4                1 = On
                                       09     20      State Terminal     0 = Off                0 = Off
                                                      BO5                1 = On
                                       10     21      Fan Low            Not used               N/A
                                       11     22      Fan Med            Not used               N/A
                                       12     23      Fan High           Not used               N/A
                                       13     24      Window             0= No alarm            0 = No alarm
                                                      Opened             1 = Alarm On
                                       14     28      Service Alarm      0= No alarm            0 = No alarm
                                                                         1 = Alarm On
                                       15     29      Filter Alarm       0= No alarm            0 = No alarm
                                                                         1 = Alarm On
                                       16     39      Local PIR          0 = No motion          0 = No motion
                                                      Motion             1 = Motion
Heating/Cooling   nvoTerminalLoad      Valid Range: -100% to +100%
Demand            SNVT_lev_percent     Note: This NVO indicates the current heat/cool energy demand of the unit.
                                              Positive values indicate that cooling energy is in use by the space
                                              comfort controller, while negative values indicate that heating energy
                                              is in use by the space comfort controller.

     TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration                       13
Configuration Network Variables
Table 6: Configuration Network Variables (Part 1 of 4)
Parameter     NCI Name and         Range and Enumeration Definition
              SNVT, UNVT or
              SCPT Name
Temperature   nciSetPts            This CP defines the space temperature setpoints for various heat, cool, and
Setpoints1    SNVT_temp_setpt      occupancy modes.
                                   The stand-by setpoints can be modified, but are not used by the controller, as
                                   it does not support Stand-By occupancy mode.
                                   Sub       Mode                     Min.             Max.         Default
                                   01        occupied_cool            54°F/12°C        100°F/       75°F/
                                                                                       37.5°C       24°C
                                   02        standby_cool             54°F/12°C        100°F/       75°F/
                                                                                       37.5°C       25.5°C
                                   03        unoccupied_cool          54°F/12°C        100°F/37.    80°F/
                                                                                       5°C          26.5°C
                                   04        occupied_heat            40°F/4.5°C       90°F/        72°F/
                                                                                       32°C         22°C
                                   05        standby_heat             40°F/4.5°C       90°F/        69°F
                                                                                       32°C         20.5°C
                                   06        unoccupied_heat          40°F/4.5°C       90°F/        62°F/
                                                                                       32°C         16.5°C
RH Options    nciCfg2FcuZn         Sub       Name                     Valid Range                   Default
              UNVT_cfg_2_fcu_zn    01                                 0 = None                      0 = None
                                             BI1 Config2
                                                                      1 = Rem NSB
                                                                      2 = Motion NO
                                                                      3 = Motion NC
                                                                      4 = Window
                                   02        BI2 Config2              0 = None                      0 = None
                                                                      1 = Door Dry
                                                                      2 = Override
                                                                      3 = Filter
                                                                      4 = Service
                                   03        UI3 Config2              0 = None                      0 = None
                                                                      1 = COC/NH
                                                                      2 = COC/NC
                                                                      3 = COS
                                                                      4 = SS
                                   04        Room Humidity            Not used                      N/A
                                             Display
                                   05        Dehumidification         Not used                      N/A
                                             Setpoint
                                   06        Dehumidification         Not used                      N/A
                                             Hysteresis
                                   07        Dehumidification Max     Not used                      N/A
                                             Cooling
                                   08        Calib Room Humidity      Not used                      N/A
                                             Sensor

14   TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration
Table 6: Configuration Network Variables (Part 2 of 4)
Parameter      NCI Name and        Range and Enumeration Definition
               SNVT, UNVT or
               SCPT Name
Thermostat’s   nciCfg1FcuZn        Note: This NV defines the thermostat controller’s common configuration
Common CPs     UNVT_cfg_1_fcu_zn         parameters and their settings.
                                   Sub       Name                   Valid Range                  Default
                                   01        Password               0 to 1000                    0
                                   02        Control Type           0 = On/Off Control           0 = On/Off
                                                                    1 = Floating Control         Control
                                   03        Floating Actuator      0.5 to 9.0 minutes,          1.5 minutes
                                             Time                      (in 0.5-minute
                                                                        increments)
                                   04        Cycles Per Hour        3, 4, 5, 6, 7, and 8 CPH     4 CPH
                                   05        Reverse or Direct      0 = Direct Acting (DA)       0 = Direct
                                             Acting Output          1 = Reverse Acting               Acting
                                                                        (RA)
                                   06        Menu Scroll            0 = No scroll                1
                                                                    1 = Scroll active
                                   07        Auto Mode              0 = Not Active               1 = Active
                                                                    1 = Active
                                   08        Temperature Scale      0 = °C                       1 = °F
                                                                    1 = °F
                                   09        Pipes # Main Out       2.0 = 2-Pipe                 4-Pipe
                                             Configuration              (Heat/Cool same
                                                                         output)
                                                                    4.0 = 4-Pipe
                                                                         (Heat/Cool
                                                                          different outputs)
                                   10        Sequence of            0 = Cooling Only             1 = Heating
                                             Operation              1 = Heating Only                 Only
                                                                    2 = Cooling & Reheat
                                                                    3 = Heating & Reheat
                                                                    4 = Cooling/Heating
                                                                        4-Pipes
                                                                    5 = Cooling/Heating
                                                                        4-Pipes and
                                                                        Reheat
                                   11        Fan Menu               Not used                     N/A
                                   12        Heat Maximum           40 to 90°F                   90°F
                                             Setpoint               (4.5 to 32°C)                (32°C)
                                   13        Cool Minimum           54 to 100°F                  54°F
                                             Setpoint               (12 to 37.5°C)               (12°C)
                                   14        Calibration Room       -5 to 5°F                    0°C
                                             Sensor                 (-2.5 to 2.5°C)
                                   15        Deadband               2, 3, 4, or 5F°              2.0F°
                                                                    (1.0 to 2.5C°)               (1.0C°)
                                   16        Setpoint Type          0 = Permanent                0=
                                                                    1 = Temporary                Permanent
                                   17        Setpoint Function      0 = Dual Setpoints           0 = Dual
                                                                    1 = Attached
                                                                        Setpoints                Setpoints
                                   18        Temporary Occ Time     0, 1, 2, 3, up to 24 Hours   2 Hours

     TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration                 15
Table 6: Configuration Network Variables (Part 3 of 4)
Parameter      NCI Name and        Range and Enumeration Definition
               SNVT, UNVT or
               SCPT Name
Thermostat’s   nciCfg1FcuZn        19        Proportional Band       3 to 10F°                       3F°
Common CPs     UNVT_cfg_1_fcu_zn                                     (1.7 to 5.6C°)                  (1.7C°)
(continued)
                                   20        Aux Contact Config      0 = Aux Contact used            0
                                                                         for reheat
                                                                     1 = Aux NO with
                                                                         Occupancy
                                                                     2 = Aux NC with
                                                                         Occupancy
                                                                     3 = Aux NO with
                                                                         Occupancy and
                                                                         Fan On
                                                                     4 = Aux NC with
                                                                         Occupancy and
                                                                         Fan On
                                                                     5 = Remote Control
                                                                         nviAuxOut
                                   21        Reheat Time Base        0 = 15 minutes                  0
                                                                     1 = 10 seconds
                                   22        Fan Mode                N/A                             N/A
                                   23        Auto Fan                N/A                             N/A
                                   24        PIR Stand-By Timer      0.5 to 24.0 Hours               0.5 Hours
                                   25        PIR Unoccupied          0.0 to 24.0 Hours               0.0 Hours
                                             Timer
Thermostat’s   nciSccNumber        Sub       Name                    Valid Range                     Default
Model          UNVT_model_info_2   01        Thermostat Model        60 = TEC2227-4                  Depends on
Number
                                                                     61 = TEC2247-4                  model in
                                                                                                     use
                                   02        Software Version        Unsigned short                  Thermostat
                                                                                                     dependent.
                                   Note: This NV defines the model number and software version of the
                                         thermostat controller.
HVAC Unit      nciHvacType         Value     Identifier                               Name
Type           SNVT_hvac_type      0         HVT_GENERIC - Not used                   Generic
Identifier
                                   1         HVT_FAN_COIL                             Fan Coil
                                   2         HVT_VAV                                  VAV Terminal
                                   3         HVT_HEAT_PUMP                            Heat Pump
                                   4         HVT_ROOFTOP                              Rooftop Unit
                                   5         HVT_UNIT_VENT - Not used                 Unit Ventilator
                                   6         HVT_CHIL_CEIL - Not used                 Chilled Ceiling
                                   7         HVT_RADIATOR                             Radiator
                                   8         HVT_AHU - Not used                       Air Handling Unit
                                   9         HVT_SLF_CONT - Not used                  Self-Contained Unit
                                   Note: This NV identifies the type of equipment being monitored.
Maximum        nciSendHrtBt        Valid Range: 0 to 6,553.4 seconds
Send Time      SNVT_time_sec       Default Null Value = 0.0 seconds (no automatic update)
                                   Note: Setting nciSendHrtBt to 0 disables the Send Heartbeat mechanism.
                                   Note: This NV defines the maximum period of time that expires before the
                                          specified network variable outputs are automatically updated.

16   TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration
Table 6: Configuration Network Variables (Part 4 of 4)
 Parameter         NCI Name and              Range and Enumeration Definition
                   SNVT, UNVT or
                   SCPT Name
 Minimum           nciMinOutTm               Valid Range: 0 to 6,553.4 seconds
 Send Time         SNVT_time_sec             Default Null Value : 0.0 seconds (no minimum send time)
                                             Note: Setting nciRcvHrtBt to 0 disables the Minimum Send Time mechanism.
                                             Note: This NV defines the minimum period of time between automatic
                                                    network variable outputs transmissions.
 Minimum           nciRcvHrtBt               Valid Range: 0 to 6,553.4 seconds
 Receive Time      SNVT_time_sec             Default Null Value : 0.0 seconds (no failure detected)
                                             Note: Setting nciRcvHrtBt to 0 disables the Receive Heartbeat mechanism.
                                             Note: This NV is used to control the maximum time that elapses after the last
                                                    update to a specified network variable input before the Space Comfort
                                                    Controller starts to use its default values.
 Major             nciMajVer                 Valid Range: 0 to 255
 Hardware or       SCPT_maj_ver              Note: This NV defines the major module hardware and software revisions.
 Software
 Revisions
 Minor             nciMinVer                 Valid Range: 0 to 255
 Hardware or       SCPT_min_ver              Note: This NV defines the minor module hardware and software revisions.
 Software
 Revisions

1.   If one setpoint of a pair of heating and cooling setpoints (for example, Occupied Heat Setpoint and Occupied Cool
     Setpoint) is overridden, the other setpoint of the pair may be automatically adjusted by the thermostat controller to
     maintain the minimum deadband between the two setpoints.
2.   The Binary Input (BI) object type status is available even if the configuration is set to None.

        TEC22x7-4 Series LONWORKS® Network Thermostat Controllers with Two Outputs Configuration                             17
Space Comfort Controller Object
     Figure 1 provides an overview of thermostat controller object details.
                                              TEC22x7-4 Series
                                           Space Comfort Controller
                                             Object Type #8500

                                              Mandatory Network               nvoSpaceTemp
                      nviSpaceTemp                Variables                   SNVT_temp_p
                      SNVT_temp_p
                                                                              nvoUnitStatus
                                                                              SNVT_hvac_status

                      nviOutdoorTemp          Optional Network                nvoDischAirTemp
                      SNVT_temp_p                 Variables                   SNVT_temp_p

                      nviSetpoint                                             nvoEffectOccup
                      SNVT_temp_p                                             SNVT_occupancy

                      nviFanSpeedCmd                                          nvoTerminalLoad
                      SNVT_switch                                             SNVT_lev_percent

                      nviOccManCmd
                      SNVT_occupancy

                      nviApplicMode
                      SNVT_hvac_mode

                      nviHeatCool
                      SNVT_hvac_mode

                                           Configuration Properties

                                          Send Heartbeat (Mandatory)
                                       Temperature Setpoints (Mandatory)
                                         Minimum Send Time (Optional)
                                          Receive Heartbeat (Optional)

                      nviRemLockout           Manufacturer Network            nvoSCCstate
                      SNVT_count                   Variables                  SNVT_state_64

                      nviAuxOut
                      SNVT_switch

                                       Manufacturer Configuration Properties

                                         Please see the manual for details.

                                                                                                FIG:spc_comf_cont

               Figure 1: TEC22x7-4 Space Comfort Controller Object

Commissioning the Thermostat Using a LONWORKS Network
Configuration Tool
     A thermostat controller must first be commissioned using a LONWORKS network
     configuration tool before it can be added to the LONWORKS Integration of the
     Network Automation Engine (NAE). This process i