TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS®
Network Staged Thermostat Controllers
Code No. LIT-12011606
Product Bulletin Issued February 8, 2010
TEC2261-4(+PIR), TEC2262-4(+PIR), TEC2263-4(+PIR), TEC2264-4(+PIR)
TEC2201-4(+PIR), TEC2202-4(+PIR), TEC2203-4(+PIR), TEC2204-4(+PIR)
The TEC226x-4(+PIR) Series Programmable and
TEC220x-4(+PIR) Series Non-Programmable
LONWORKS® Network Configurable Staged Thermostat
Controllers provide control of rooftop units (with and
without economizers), heat pumps, and single- and
multi-stage heating/cooling equipment. The
TEC226x-4+PIR and TEC220x-4+PIR Series
Thermostat Controllers have occupancy sensing
capability built into the device. These devices provide
energy savings in high-energy usage light commercial
buildings such as schools and hotels. The devices
maximize these energy savings by using additional
setpoint strategies during occupied times. Figure 1: TEC220x-4+PIR Series LONWORKS
Network Staged Thermostat Controller
The technologically advanced TEC226x-4(+PIR) and
TEC220x-4(+PIR) Series Thermostat Controllers The TEC220x-4+PIR and TEC226x-4+PIR Series
feature a Building Automation System (BAS) includes four models, each include the option of a PIR
LONWORKS Network communication capability that occupancy sensing cover:
enables remote monitoring and programming for • Single-stage (TEC22x1-4 and TEC22x1-4+PIR)
efficient space temperature control.
• Heat Pump (TEC22x2-4 and TEC22x2-4+PIR)
The TEC226x-4(+PIR) and TEC220x-4(+PIR) Series
Thermostat Controllers use an intuitive, plain text, • Multi-stage (TEC22x3-4 and TEC22x3-4+PIR)
menu-driven, backlit display that makes setup and • Economizer (TEC22x4-4 and TEC22x4-4+PIR)
operation quick and easy.
All thermostat controllers use a unique,
Proportional-Integral (PI) time-proportioning control
algorithm that virtually eliminates temperature offset
associated with traditional differential-based thermostat
controllers.
Table 1: Features and Benefits (Part 1 of 2)
Features Benefits
LONWORKS Network Provides compatibility with a proven communication network; LONWORKS Network is
Communication widely accepted by Heating, Ventilating, and Air Conditioning (HVAC) control suppliers.
Onboard Occupancy Sensor Provides energy savings without additional installation time and cost.
(Passive Infrared [PIR] Models)
Password Protection Option Protects against unwanted thermostat controller tampering.
Backlit Liquid Crystal Display Offers real-time control status of the environment in easy-to-read, English text messages
(LCD) with constant backlight that brightens during user interaction.
Simplified Setpoint Enables the user to change the setpoint by simply pressing the UP/DOWN arrow keys.
Adjustment
Five Easy-to-Use Interface Allow for easy commissioning of the thermostat, and eliminate the need for DIP switches.
Keys
Two Configurable Digital Provide additional inputs for advanced functions such as remote night setback, occupancy
Inputs override, and service or filter alarms.
TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat 1
Controllers Product Bulletin
Table 1: Features and Benefits (Part 2 of 2)
Features Benefits
Over 20 Configurable Enable the thermostat to adapt to any application, allowing installer parameter access
Parameters without opening the thermostat cover.
Optional Discharge Air Sensor Monitors unit efficiency.
Economizer Output Provides control of economizer operation for single- and multi-stage unitary rooftop
(TEC22x4-4 and equipment.
TEC22x4-4+PIR Models)
Configurable Auxiliary Output Provides 24 VAC control for lighting, exhaust fans, and other auxiliary functions.
Product Overview • Three Levels of Keypad Lockout
Provide three levels of keypad lockout that can be
The TEC226x-4(+PIR) Series Programmable and
set up through the Installer Configuration Menu.
TEC220x-4(+PIR) Series Non-Programmable
Thermostat Controllers are specifically designed for • Adjustable Power Delay on Startup
networked control of the most common commercial Enables a delay before authorizing any operation
heating and cooling equipment. The TEC226x-4+PIR after powering-up the thermostat. You can also use
and TEC220x-4+PIR Series Thermostat Controllers this delay to sequence startup of multiple units in
include an additional occupancy sensing capability that one location.
provides energy savings in high-energy usage light
• Frost Protection Enable/Disable
commercial buildings. In addition to superior
Provides a minimum heating setpoint of
temperature control, occupancy sensing capabilities,
42.0°F/5.5°C to prevent freezing in the zone
and application flexibility, the TEC226x-4(+PIR) and
controlled by the thermostat, regardless of its
TEC220x-4(+PIR) Series Thermostat Controllers
mode.
feature LONWORKS Network communication capability,
allowing the user to view operation or make • Adjustable Maximum Heating/Minimum Cooling
adjustments at the thermostat or from a remote Setpoints
workstation. Plain text menus, backlit display, and five Establish the maximum heating setpoint and
interface keys make setup and operation quick and minimum cooling setpoint that can be entered
easy. through the user interface.
IMPORTANT: Use these TEC226x-4(+PIR) and • Adjustable Anti-Short Cycle Timer
TEC220x-4(+PIR) Series Thermostat Controllers Adjusts the minimum on/off times for heating and
only as an operating control. Where failure or cooling stages from 0 to 5 minutes.
malfunction of these thermostats could lead to • Adjustable Heating/Cooling Cycles per Hour
personal injury or property damage to the controlled (On/Off Control)
equipment or other property, additional precautions Provides configurable settings for 3 to 8 heating
must be designed into the system. Incorporate and cycles and 3 or 4 cooling cycles in a 1-hour period,
maintain other devices, such as supervisory or balancing temperature control and equipment
alarm systems or safety or limit controls, intended to cycling.
warn of or protect against failure or malfunction of
the thermostat controller. • Adjustable Heating/Cooling Deadband
Adjusts the minimum cooling/heating deadband
Additional Features from 2.0F°/1.0C° to 4.0F°/2.0C°.
The TEC226x-4(+PIR) and TEC220x-4(+PIR) Series • Fan Control
Thermostat Controllers also offer many other features, Provides option for equipment fan control.
including:
• Fan Delay Control
• Stationary or Scrolling Display Enables the user to select how the fan operates on
Offers the option of having the display continuously a call for heating and the delay at the end of the
scroll the parameters. heating or cooling cycle.
2 TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers
Product Bulletin
• Adjustable Temporary Occupancy Time • High and Low Balance Point Adjustments
Adjusts the temporary occupancy time from (TEC22x2-4 and TEC22x2-4+PIR Models)
0 to 12 hours. Allows more precise control of heat pump
operation based on the outdoor air temperature.
• Sensor Offset Adjustments
Sets desired room or outside air temperature • Heat Pump Compressor Stage Enable/Disable
calibration (offset). (TEC22x2-4 and TEC22x2-4+PIR Models)
Allows operation of the second-stage compressor
• System Mode Lockout
to be disabled, reverting the thermostat controller
Allows the heating and cooling modes to be locked
to single-stage compressor operation on heat
out based on the outdoor air temperature when an
pump thermostats.
outdoor air sensor is connected.
• 7-Day, 2- or 4-Event Schedule (Programmable
• Unoccupied Timer
Models)
Sets the time delay between Occupied mode to
Allows configuration for two- or four-event
Unoccupied mode after air movement is detected
schedule; allows individual programming for each
(PIR models only.)
day of the week to suit the required schedule.
• Progressive Recovery
• Three Light-Emitting Diodes (LEDs)
Ensures the correct temperature is reached at the
Provide fan, heating, and cooling status at a
programmed occupied time.
glance.
• Smart Fan
• Auxiliary Contact
Enables the fan to operate continuously during the
Provides 24 VAC control for exhaust fans, lighting,
occupied times and cycle with the equipment
and other auxiliary functions.
during unoccupied times.
• Remote Access
• Remote Indoor and Outdoor Sensing
Allows user to read/write and access parameters of
Accommodates remote indoor and outdoor
the thermostat via a supervisory controller or a
sensors; can average up to three indoor sensors.
LONWORKS configuration tool.
• Nonvolatile Electrically Erasable
• Accessible Configuration Parameters
Programmable Read-Only Memory (EEPROM)
Allow local access to all configurable parameters
Prevents loss of adjusted parameters during a
while limiting unwanted parameter tampering once
power failure.
the thermostat is set up.
• Heating and Cooling Stage Enable/Disable
(TEC22x3-4, TEC22x3-4+PIR, TEC22x4-4, and
TEC22x4-4+PIR Models)
Reverts the operation of two-stage thermostats to a
single-stage thermostat when the second heating
or cooling stage is not needed.
TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers 3
Product Bulletin
PIR motion detector
saves energy using
standby setpoints.
Status LED beneath cover
indicates network status.
Room Temp
Backlit, plain text 70.0ºF
Liquid Crystal Display (LCD)
is easy to read in any condition. Light-Emitting Diodes (LEDs)
indicate system activity.
FIG:frnt_vw
Five keys on the thermostat controller
make operation easy and intuitive.
Figure 3: Front Cover of Thermostat Controller (TEC22xx-4+PIR Model Shown)
4-15/16 4-15/16
(125) (125)
Room Temp Room Temp
70.0ºF 70.0ºF
3-3/8 3-3/8
(86) (86)
FIG:dmnsns_tec22xx
1-1/8 1-3/8
(29) (36)
Figure 2: Thermostat Controller Dimensions, in. (mm) (TEC22xx-4 and TEC22xx-4+PIR Models Shown)
Thermostat Controller User Interface Keys Note: When the thermostat is left unattended for
45 seconds, the thermostat display resumes
The TEC226x-4(+PIR) and TEC220x-4(+PIR) Series
scrolling.
Thermostat Controllers UI consists of five keys on the
front cover (Figure 3). The function of each key is as • Use the NO key to decline a parameter change and
follows: to advance to the next menu item.
• Use the YES key to: • Use the MENU key to:
- confirm menu selections and to advance to the - access the Main User Menu or to exit the menu
next menu item (See the Main User Menu section.)
- stop the Status Display Menu from scrolling - access the Installer Configuration Menu or to
and to manually scroll to the next parameter on exit the menu (See the Installer Configuration
the menu Menu section.)
4 TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers
Product Bulletin
• Use the UP/DOWN arrow keys to change the • Applicable Alarms – The backlight lights up as an
configuration parameters and to activate a setpoint alarm condition is displayed.
adjustment.
Note: Press the YES key to temporarily stop this
Backlit LCD menu from scrolling.
The TEC226x-4(+PIR) and TEC220x-4(+PIR) Series Note: An option is available within the Installer
Thermostat Controllers include a 2-line, 8-character Configuration Menu to lock out the scrolling display and
backlit display. Low-level backlighting is present during show only the Room Temperature parameter.
normal operation, and it brightens when any user
Status LED
interface key is pressed. The backlight returns to low
level when the thermostat is left unattended for 45 The status LED shows the operational status of the
seconds. thermostat controller. See Table 2. The Status LED is a
small green light under the thermostat controller cover
LEDs (under the LONWORKS daughter board on the left edge
Three LEDs are included to indicate the fan status, call when facing the thermostat controller).
for heat, or call for cooling: Table 2: Status LED Explanation
Status LED Explanation
• The fan LED is on when the fan is on.
Condition
• The heat LED is on when heating is on. Continuously The thermostat controller does not have
On an application loaded in its memory.
Flashing at a The thermostat controller has an
• The cool LED is on when cooling is on. 0.5 Hz Rate application loaded in its memory but is
not configured. Use a LONWORKS
Integrated PIR Sensor – network management tool to bind the
TEC226x-4+PIR and TEC220x-4+PIR thermostat controller to a LONWORKS
network.
Series Thermostat Controllers
Continuously The thermostat controller has an
The integrated PIR sensor allows for automatic Off application loaded in its memory and is
switching between fully adjustable Occupied and bound to a LONWORKS network.
Unoccupied temperature setpoints without user
interaction. This feature generates incremental energy
Main User Menu
savings during scheduled occupied periods while the
space is unoccupied. The Main User Menu is used to access and change the
basic operating parameters of the thermostat. During
Programming Overview normal thermostat operation, press the MENU key
Three menus are available to view, program, and once to access the Main User Menu.
configure the TEC226x-4(+PIR) and TEC220x-4(+PIR) This menu is most commonly used by the zone
Series Thermostat Controllers: occupant, and includes the following parameters:
Status Display Menu • Schedule Override/Resume
The Status Display Menu is displayed during normal
• Temperature Setpoints
thermostat operation. This menu continuously scrolls
through the following parameters: • System Mode
• Room Temperature • Fan Mode
• Clock (Programmable models only) • Schedule Set (Programmable models)
• System Mode • Clock Set (Programmable models)
• Occupancy Status The Main User Menu uses Auto Help. Auto Help is
(Occupied/Unoccupied/Override) displayed automatically in the Main User Menu when
there is a pause in programming activity.
• Outdoor Temperature – An outdoor air temperature
sensor must be connected.
TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers 5
Product Bulletin
Installer Configuration Menu • Number of Cooling Stages (TEC22x3-4,
The Installer Configuration Menu is used to set up the TEC22x3-4+PIR, TEC22x4-4, and
thermostat for an application-specific operation. To TEC22x4-4+PIR Models)
access the menu, press and hold the MENU key for • Number of Heat Pump Compressor Stages
approximately 8 seconds. (TEC22x2-4 and TEC22x2-4+PIR Models)
The Installer Configuration Menu includes the following • Outdoor Air Temperature Heating Lockout
parameters that are accessed by pressing the same
MENU key: • Outdoor Air Temperature Cooling Lockout
• Password Setting • Unoccupied Timer Value (when occupancy sensor
is used)
• DI1 and DI2 Input Configuration
• Two or Four Events per Day Configuration
• Menu Scroll (Programmable Models)
• Three Keypad Lockout Levels • Auxiliary Configuration
• Power Delay on Power Up • Enable/Disable Progressive Recovery
• Frost Protection (programmable models)
• Maximum Heating Setpoint/Minimum Cooling The following parameters are for the TEC22x2-4 and
Setpoint TEC22x2-4+PIR models only:
• Proportional Band • High Balance Point
• Anti-Short Cycle Times • Low Balance Point
• Heating Stage Cycles per Hour • Comfort/Economy Auxiliary Heat
• Cooling Stage Cycles per Hour • Reversing Valve Operation
• Heating/Cooling Minimum Deadband • Heat Pump Compressor/Auxiliary Heat Interlock
• Heating/Cooling Fan Control The following parameters are for the TEC22x4-4 and
TEC22x4-4+PIR models only:
• End-of-Cycle Fan Delay
• Outdoor Air Temperature Changeover Setpoint
• Temporary Occupancy Time
• Outdoor Air Damper Minimum Position
• Room Air Sensor Calibration
• Mechanical Cooling On/Off during Economizer
• Outdoor Air Sensor Calibration Operation
• Number of Heating Stages (TEC22x3-4, • Mixed Air Temperature Setpoint
TEC22x3-4+PIR, TEC22x4-4, and
TEC22x4-4+PIR Models) • Mixed Air Temperature Display
Table 3: LONWORKS Network Configurable Staged Thermostat Controller Models (Part 1 of 2)
Code Number Description Programmable Applications
TEC2261-4 Single-Stage Yes Unit Heaters and Single-Stage Packaged
Heating/Cooling Equipment
TEC2201-4 No
TEC2261-4+PIR Single-Stage with Onboard Yes
Occupancy Sensor
TEC2201-4+PIR No
TEC2262-4 Heat Pump Yes Heat Pumps with up to 3 Heating/2 Cooling
Stages
TEC2202-4 No
TEC2262-4+PIR Heat Pump with Onboard Yes
Occupancy Sensor
TEC2202-4+PIR No
6 TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers
Product Bulletin
Table 3: LONWORKS Network Configurable Staged Thermostat Controller Models (Part 2 of 2)
Code Number Description Programmable Applications
TEC2263-4 Multi-Stage Yes Multi-Staged Packaged Heating/Cooling
Equipment
TEC2203-4 No
TEC2263-4+PIR Multi-Stage with Onboard Yes
Occupancy Sensor
TEC2203-4+PIR No
TEC2264-4 Multi-Stage, Economizer Yes Economizer Operation for Single- and
Multi-Stage Unitary Rooftop Equipment
TEC2204-4 No
TEC2264-4+PIR Multi-Stage, Economizer with Yes
Onboard Occupancy Sensor
TEC2204-4+PIR No
Table 4: Accessories (Order Separately)
Code Number Description
SEN-600-1 Remote Indoor Air Temperature Sensor
SEN-600-4 Remote Indoor Air Temperature Sensor with Occupancy Override and LED
TE-6361M-11 Duct Mount Air Temperature Sensor
TE-636S-11 Strap-Mount Temperature Sensor
TE-6363P-11 Outdoor Air Temperature Sensor
TEC-3-PIR2 Cover with Occupancy Sensor
1. Additional TE-636xx-x Series 10k Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature
Sensors Product Bulletin (LIT-216320) for more details.
2. The TEC-3-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC22xx-4 Staged Thermostat
Controller to provide occupancy sensing capability.
Repair Information
If a TEC226x-4(+PIR) Series Programmable or
TEC220x-4(+PIR) Series Non-Programmable
LONWORKS Network Configurable Staged Thermostat
Controller fails to operate within its specifications,
replace the unit. For a replacement thermostat, contact
the nearest Johnson Controls® representative.
Technical Specifications
TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS Network Staged Thermostat
Controllers (Part 1 of 2)
Power Requirements 19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC nominal, Class 2 or
Safety Extra-Low Voltage (SELV)
Relay Contact Rating 19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV
Analog Inputs Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
Temperature Coefficient (NTC) Thermistor Sensors
Digital Inputs Voltage-Free Contacts across Terminal C to Terminals DI1 and DI2
Economizer Rating 0 to 10 VDC into 2k ohm resistance minimum
Output
Accuracy ±3%
(TEC22x4-4 and
TEC22x4-4+PIR
Models)
TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers 7
Product Bulletin
TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS Network Staged Thermostat
Controllers (Part 2 of 2)
Wire Size Unshielded Twisted Pair - 22 AWG (0.6 mm Diameter) Minimum, 18 AWG (1.0 mm
Diameter) Recommended
Temperature Sensor Type Local 10k ohm Type II NTC Thermistor
LONWORKS Network Standard 64 Devices Maximum without repeater, 128 Devices Maximum with repeater; 6,250
ft (1,905 m) Maximum Length (Bus Topology)
Temperature Backlit Display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments
Range
Heating Control 40.0°F/4.5°C to 90.0°F/32.0°C
Cooling Control 54.0°F/12.0°C to 100.0°F/38.0°C
Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
Minimum Deadband 2F°/1C° between Heating and Cooling
Ambient Operating 32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
Conditions
Storage -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
Compliance United States UL Listed, File E27734, CCN XAPX,
Under UL 873, Temperature Indicating and Regulating Equipment
FCC Compliant to CFR 47, Part 15, Subpart B, Class A
LONMARK® Certification 3.4
Canada UL Listed, File E27734, CCN XAPX7,
Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
Industry Canada, ICES-003
Europe CE Mark, EMC Directive 2004/108/EC
EN 61000-6-1 and EN 61000-6-3
Australia and C-Tick Mark, Australia/NZ Emissions Compliant
New Zealand
Shipping Weight TEC226x-4 and TEC220x-4 Models: 0.75 lb (0.34 kg)
TEC226x-4+PIR and TEC220x-4+PIR Models: 0.77 lb (0.35 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
United States Emissions Compliance:
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Canadian Emissions Compliance:
This Class (A) digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel broullier du Canada.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2010 Johnson Controls, Inc.
8 TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers
Product Bulletin