TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS®
Network Staged Thermostat Controllers
                                                                                                Code No. LIT-12011606
Product Bulletin                                                                                 Issued February 8, 2010
TEC2261-4(+PIR), TEC2262-4(+PIR), TEC2263-4(+PIR), TEC2264-4(+PIR)
TEC2201-4(+PIR), TEC2202-4(+PIR), TEC2203-4(+PIR), TEC2204-4(+PIR)

The TEC226x-4(+PIR) Series Programmable and
TEC220x-4(+PIR) Series Non-Programmable
LONWORKS® Network Configurable Staged Thermostat
Controllers provide control of rooftop units (with and
without economizers), heat pumps, and single- and
multi-stage heating/cooling equipment. The
TEC226x-4+PIR and TEC220x-4+PIR Series
Thermostat Controllers have occupancy sensing
capability built into the device. These devices provide
energy savings in high-energy usage light commercial
buildings such as schools and hotels. The devices
maximize these energy savings by using additional
setpoint strategies during occupied times.                           Figure 1: TEC220x-4+PIR Series LONWORKS
                                                                       Network Staged Thermostat Controller
The technologically advanced TEC226x-4(+PIR) and
TEC220x-4(+PIR) Series Thermostat Controllers                   The TEC220x-4+PIR and TEC226x-4+PIR Series
feature a Building Automation System (BAS)                      includes four models, each include the option of a PIR
LONWORKS Network communication capability that                  occupancy sensing cover:
enables remote monitoring and programming for                   •   Single-stage (TEC22x1-4 and TEC22x1-4+PIR)
efficient space temperature control.
                                                                •   Heat Pump (TEC22x2-4 and TEC22x2-4+PIR)
The TEC226x-4(+PIR) and TEC220x-4(+PIR) Series
Thermostat Controllers use an intuitive, plain text,            •   Multi-stage (TEC22x3-4 and TEC22x3-4+PIR)
menu-driven, backlit display that makes setup and               •   Economizer (TEC22x4-4 and TEC22x4-4+PIR)
operation quick and easy.
                                                                All thermostat controllers use a unique,
                                                                Proportional-Integral (PI) time-proportioning control
                                                                algorithm that virtually eliminates temperature offset
                                                                associated with traditional differential-based thermostat
                                                                controllers.
Table 1: Features and Benefits (Part 1 of 2)
 Features                          Benefits
 LONWORKS Network                  Provides compatibility with a proven communication network; LONWORKS Network is
 Communication                     widely accepted by Heating, Ventilating, and Air Conditioning (HVAC) control suppliers.
 Onboard Occupancy Sensor          Provides energy savings without additional installation time and cost.
 (Passive Infrared [PIR] Models)
 Password Protection Option        Protects against unwanted thermostat controller tampering.
 Backlit Liquid Crystal Display    Offers real-time control status of the environment in easy-to-read, English text messages
 (LCD)                             with constant backlight that brightens during user interaction.
 Simplified Setpoint               Enables the user to change the setpoint by simply pressing the UP/DOWN arrow keys.
 Adjustment
 Five Easy-to-Use Interface        Allow for easy commissioning of the thermostat, and eliminate the need for DIP switches.
 Keys
 Two Configurable Digital          Provide additional inputs for advanced functions such as remote night setback, occupancy
 Inputs                            override, and service or filter alarms.

                 TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat                                1
                                                                      Controllers Product Bulletin
Table 1: Features and Benefits (Part 2 of 2)
    Features                         Benefits
    Over 20 Configurable             Enable the thermostat to adapt to any application, allowing installer parameter access
    Parameters                       without opening the thermostat cover.
    Optional Discharge Air Sensor    Monitors unit efficiency.
    Economizer Output                Provides control of economizer operation for single- and multi-stage unitary rooftop
    (TEC22x4-4 and                   equipment.
    TEC22x4-4+PIR Models)
    Configurable Auxiliary Output    Provides 24 VAC control for lighting, exhaust fans, and other auxiliary functions.

Product Overview                                                  •    Three Levels of Keypad Lockout
                                                                       Provide three levels of keypad lockout that can be
The TEC226x-4(+PIR) Series Programmable and
                                                                       set up through the Installer Configuration Menu.
TEC220x-4(+PIR) Series Non-Programmable
Thermostat Controllers are specifically designed for              •    Adjustable Power Delay on Startup
networked control of the most common commercial                        Enables a delay before authorizing any operation
heating and cooling equipment. The TEC226x-4+PIR                       after powering-up the thermostat. You can also use
and TEC220x-4+PIR Series Thermostat Controllers                        this delay to sequence startup of multiple units in
include an additional occupancy sensing capability that                one location.
provides energy savings in high-energy usage light
                                                                  •    Frost Protection Enable/Disable
commercial buildings. In addition to superior
                                                                       Provides a minimum heating setpoint of
temperature control, occupancy sensing capabilities,
                                                                       42.0°F/5.5°C to prevent freezing in the zone
and application flexibility, the TEC226x-4(+PIR) and
                                                                       controlled by the thermostat, regardless of its
TEC220x-4(+PIR) Series Thermostat Controllers
                                                                       mode.
feature LONWORKS Network communication capability,
allowing the user to view operation or make                       •    Adjustable Maximum Heating/Minimum Cooling
adjustments at the thermostat or from a remote                         Setpoints
workstation. Plain text menus, backlit display, and five               Establish the maximum heating setpoint and
interface keys make setup and operation quick and                      minimum cooling setpoint that can be entered
easy.                                                                  through the user interface.

    IMPORTANT: Use these TEC226x-4(+PIR) and                      •    Adjustable Anti-Short Cycle Timer
    TEC220x-4(+PIR) Series Thermostat Controllers                      Adjusts the minimum on/off times for heating and
    only as an operating control. Where failure or                     cooling stages from 0 to 5 minutes.
    malfunction of these thermostats could lead to                •    Adjustable Heating/Cooling Cycles per Hour
    personal injury or property damage to the controlled               (On/Off Control)
    equipment or other property, additional precautions                Provides configurable settings for 3 to 8 heating
    must be designed into the system. Incorporate and                  cycles and 3 or 4 cooling cycles in a 1-hour period,
    maintain other devices, such as supervisory or                     balancing temperature control and equipment
    alarm systems or safety or limit controls, intended to             cycling.
    warn of or protect against failure or malfunction of
    the thermostat controller.                                    •    Adjustable Heating/Cooling Deadband
                                                                       Adjusts the minimum cooling/heating deadband
Additional Features                                                    from 2.0F°/1.0C° to 4.0F°/2.0C°.
The TEC226x-4(+PIR) and TEC220x-4(+PIR) Series                    •    Fan Control
Thermostat Controllers also offer many other features,                 Provides option for equipment fan control.
including:
                                                                  •    Fan Delay Control
•     Stationary or Scrolling Display                                  Enables the user to select how the fan operates on
      Offers the option of having the display continuously             a call for heating and the delay at the end of the
      scroll the parameters.                                           heating or cooling cycle.

2        TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers
         Product Bulletin
•   Adjustable Temporary Occupancy Time                   •   High and Low Balance Point Adjustments
    Adjusts the temporary occupancy time from                 (TEC22x2-4 and TEC22x2-4+PIR Models)
    0 to 12 hours.                                            Allows more precise control of heat pump
                                                              operation based on the outdoor air temperature.
•   Sensor Offset Adjustments
    Sets desired room or outside air temperature          •   Heat Pump Compressor Stage Enable/Disable
    calibration (offset).                                     (TEC22x2-4 and TEC22x2-4+PIR Models)
                                                              Allows operation of the second-stage compressor
•   System Mode Lockout
                                                              to be disabled, reverting the thermostat controller
    Allows the heating and cooling modes to be locked
                                                              to single-stage compressor operation on heat
    out based on the outdoor air temperature when an
                                                              pump thermostats.
    outdoor air sensor is connected.
                                                          •   7-Day, 2- or 4-Event Schedule (Programmable
•   Unoccupied Timer
                                                              Models)
    Sets the time delay between Occupied mode to
                                                              Allows configuration for two- or four-event
    Unoccupied mode after air movement is detected
                                                              schedule; allows individual programming for each
    (PIR models only.)
                                                              day of the week to suit the required schedule.
•   Progressive Recovery
                                                          •   Three Light-Emitting Diodes (LEDs)
    Ensures the correct temperature is reached at the
                                                              Provide fan, heating, and cooling status at a
    programmed occupied time.
                                                              glance.
•   Smart Fan
                                                          •   Auxiliary Contact
    Enables the fan to operate continuously during the
                                                              Provides 24 VAC control for exhaust fans, lighting,
    occupied times and cycle with the equipment
                                                              and other auxiliary functions.
    during unoccupied times.
                                                          •   Remote Access
•   Remote Indoor and Outdoor Sensing
                                                              Allows user to read/write and access parameters of
    Accommodates remote indoor and outdoor
                                                              the thermostat via a supervisory controller or a
    sensors; can average up to three indoor sensors.
                                                              LONWORKS configuration tool.
•   Nonvolatile Electrically Erasable
                                                          •   Accessible Configuration Parameters
    Programmable Read-Only Memory (EEPROM)
                                                              Allow local access to all configurable parameters
    Prevents loss of adjusted parameters during a
                                                              while limiting unwanted parameter tampering once
    power failure.
                                                              the thermostat is set up.
•   Heating and Cooling Stage Enable/Disable
    (TEC22x3-4, TEC22x3-4+PIR, TEC22x4-4, and
    TEC22x4-4+PIR Models)
    Reverts the operation of two-stage thermostats to a
    single-stage thermostat when the second heating
    or cooling stage is not needed.

     TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers                     3
                                                                              Product Bulletin
                                PIR motion detector
                                saves energy using
                                 standby setpoints.

                         Status LED beneath cover
                          indicates network status.

                                                                   Room Temp
                                 Backlit, plain text               70.0ºF
                      Liquid Crystal Display (LCD)
                  is easy to read in any condition.                                      Light-Emitting Diodes (LEDs)
                                                                                         indicate system activity.

                                                                                                                                     FIG:frnt_vw
                                   Five keys on the thermostat controller
                                   make operation easy and intuitive.

                Figure 3: Front Cover of Thermostat Controller (TEC22xx-4+PIR Model Shown)

                                                       4-15/16                                     4-15/16
                                                        (125)                                       (125)

                                 Room Temp                                      Room Temp
                                 70.0ºF                                         70.0ºF

                                 3-3/8                                           3-3/8
                                 (86)                                            (86)

                                                                                                                FIG:dmnsns_tec22xx
                                                           1-1/8                                       1-3/8
                                                           (29)                                        (36)

    Figure 2: Thermostat Controller Dimensions, in. (mm) (TEC22xx-4 and TEC22xx-4+PIR Models Shown)

Thermostat Controller User Interface Keys                                   Note: When the thermostat is left unattended for
                                                                            45 seconds, the thermostat display resumes
The TEC226x-4(+PIR) and TEC220x-4(+PIR) Series
                                                                            scrolling.
Thermostat Controllers UI consists of five keys on the
front cover (Figure 3). The function of each key is as                 •    Use the NO key to decline a parameter change and
follows:                                                                    to advance to the next menu item.
•    Use the YES key to:                                               •    Use the MENU key to:
     -    confirm menu selections and to advance to the                     -   access the Main User Menu or to exit the menu
          next menu item                                                        (See the Main User Menu section.)
     -    stop the Status Display Menu from scrolling                       -   access the Installer Configuration Menu or to
          and to manually scroll to the next parameter on                       exit the menu (See the Installer Configuration
          the menu                                                              Menu section.)

4        TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers
         Product Bulletin
•   Use the UP/DOWN arrow keys to change the                •      Applicable Alarms – The backlight lights up as an
    configuration parameters and to activate a setpoint            alarm condition is displayed.
    adjustment.
                                                            Note: Press the YES key to temporarily stop this
Backlit LCD                                                 menu from scrolling.
The TEC226x-4(+PIR) and TEC220x-4(+PIR) Series              Note: An option is available within the Installer
Thermostat Controllers include a 2-line, 8-character        Configuration Menu to lock out the scrolling display and
backlit display. Low-level backlighting is present during   show only the Room Temperature parameter.
normal operation, and it brightens when any user
                                                            Status LED
interface key is pressed. The backlight returns to low
level when the thermostat is left unattended for 45         The status LED shows the operational status of the
seconds.                                                    thermostat controller. See Table 2. The Status LED is a
                                                            small green light under the thermostat controller cover
LEDs                                                        (under the LONWORKS daughter board on the left edge
Three LEDs are included to indicate the fan status, call    when facing the thermostat controller).
for heat, or call for cooling:                              Table 2: Status LED Explanation
                                                                Status LED      Explanation
•   The fan LED        is on when the fan is on.
                                                                Condition
•   The heat LED        is on when heating is on.               Continuously    The thermostat controller does not have
                                                                On              an application loaded in its memory.
                                                                Flashing at a   The thermostat controller has an
•   The cool LED        is on when cooling is on.               0.5 Hz Rate     application loaded in its memory but is
                                                                                not configured. Use a LONWORKS
Integrated PIR Sensor –                                                         network management tool to bind the
TEC226x-4+PIR and TEC220x-4+PIR                                                 thermostat controller to a LONWORKS
                                                                                network.
Series Thermostat Controllers
                                                                Continuously    The thermostat controller has an
The integrated PIR sensor allows for automatic                  Off             application loaded in its memory and is
switching between fully adjustable Occupied and                                 bound to a LONWORKS network.
Unoccupied temperature setpoints without user
interaction. This feature generates incremental energy
                                                            Main User Menu
savings during scheduled occupied periods while the
space is unoccupied.                                        The Main User Menu is used to access and change the
                                                            basic operating parameters of the thermostat. During
Programming Overview                                        normal thermostat operation, press the MENU key
Three menus are available to view, program, and             once to access the Main User Menu.
configure the TEC226x-4(+PIR) and TEC220x-4(+PIR)           This menu is most commonly used by the zone
Series Thermostat Controllers:                              occupant, and includes the following parameters:
Status Display Menu                                         •      Schedule Override/Resume
The Status Display Menu is displayed during normal
                                                            •      Temperature Setpoints
thermostat operation. This menu continuously scrolls
through the following parameters:                           •      System Mode
•   Room Temperature                                        •      Fan Mode
•   Clock (Programmable models only)                        •      Schedule Set (Programmable models)
•   System Mode                                             •      Clock Set (Programmable models)
•   Occupancy Status                                        The Main User Menu uses Auto Help. Auto Help is
    (Occupied/Unoccupied/Override)                          displayed automatically in the Main User Menu when
                                                            there is a pause in programming activity.
•   Outdoor Temperature – An outdoor air temperature
    sensor must be connected.

      TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers                          5
                                                                               Product Bulletin
Installer Configuration Menu                               •   Number of Cooling Stages (TEC22x3-4,
The Installer Configuration Menu is used to set up the         TEC22x3-4+PIR, TEC22x4-4, and
thermostat for an application-specific operation. To           TEC22x4-4+PIR Models)
access the menu, press and hold the MENU key for           •   Number of Heat Pump Compressor Stages
approximately 8 seconds.                                       (TEC22x2-4 and TEC22x2-4+PIR Models)
The Installer Configuration Menu includes the following    •   Outdoor Air Temperature Heating Lockout
parameters that are accessed by pressing the same
MENU key:                                                  •   Outdoor Air Temperature Cooling Lockout

•     Password Setting                                     •   Unoccupied Timer Value (when occupancy sensor
                                                               is used)
•     DI1 and DI2 Input Configuration
                                                           •   Two or Four Events per Day Configuration
•     Menu Scroll                                              (Programmable Models)
•     Three Keypad Lockout Levels                          •   Auxiliary Configuration
•     Power Delay on Power Up                              •   Enable/Disable Progressive Recovery
•     Frost Protection                                         (programmable models)

•     Maximum Heating Setpoint/Minimum Cooling             The following parameters are for the TEC22x2-4 and
      Setpoint                                             TEC22x2-4+PIR models only:

•     Proportional Band                                    •   High Balance Point

•     Anti-Short Cycle Times                               •   Low Balance Point

•     Heating Stage Cycles per Hour                        •   Comfort/Economy Auxiliary Heat

•     Cooling Stage Cycles per Hour                        •   Reversing Valve Operation

•     Heating/Cooling Minimum Deadband                     •   Heat Pump Compressor/Auxiliary Heat Interlock

•     Heating/Cooling Fan Control                          The following parameters are for the TEC22x4-4 and
                                                           TEC22x4-4+PIR models only:
•     End-of-Cycle Fan Delay
                                                           •   Outdoor Air Temperature Changeover Setpoint
•     Temporary Occupancy Time
                                                           •   Outdoor Air Damper Minimum Position
•     Room Air Sensor Calibration
                                                           •   Mechanical Cooling On/Off during Economizer
•     Outdoor Air Sensor Calibration                           Operation
•     Number of Heating Stages (TEC22x3-4,                 •   Mixed Air Temperature Setpoint
      TEC22x3-4+PIR, TEC22x4-4, and
      TEC22x4-4+PIR Models)                                •   Mixed Air Temperature Display
Table 3: LONWORKS Network Configurable Staged Thermostat Controller Models (Part 1 of 2)
    Code Number          Description                 Programmable        Applications
    TEC2261-4            Single-Stage                Yes                 Unit Heaters and Single-Stage Packaged
                                                                         Heating/Cooling Equipment
    TEC2201-4                                        No
    TEC2261-4+PIR        Single-Stage with Onboard   Yes
                         Occupancy Sensor
    TEC2201-4+PIR                                    No
    TEC2262-4            Heat Pump                   Yes                 Heat Pumps with up to 3 Heating/2 Cooling
                                                                         Stages
    TEC2202-4                                        No
    TEC2262-4+PIR        Heat Pump with Onboard      Yes
                         Occupancy Sensor
    TEC2202-4+PIR                                    No

6       TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers
        Product Bulletin
Table 3: LONWORKS Network Configurable Staged Thermostat Controller Models (Part 2 of 2)
 Code Number          Description                       Programmable         Applications
 TEC2263-4            Multi-Stage                       Yes                  Multi-Staged Packaged Heating/Cooling
                                                                             Equipment
 TEC2203-4                                              No
 TEC2263-4+PIR        Multi-Stage with Onboard          Yes
                      Occupancy Sensor
 TEC2203-4+PIR                                          No
 TEC2264-4            Multi-Stage, Economizer           Yes                  Economizer Operation for Single- and
                                                                             Multi-Stage Unitary Rooftop Equipment
 TEC2204-4                                              No
 TEC2264-4+PIR        Multi-Stage, Economizer with      Yes
                      Onboard Occupancy Sensor
 TEC2204-4+PIR                                          No

Table 4: Accessories (Order Separately)
 Code Number           Description
 SEN-600-1             Remote Indoor Air Temperature Sensor
 SEN-600-4             Remote Indoor Air Temperature Sensor with Occupancy Override and LED
 TE-6361M-11           Duct Mount Air Temperature Sensor

 TE-636S-11            Strap-Mount Temperature Sensor

 TE-6363P-11           Outdoor Air Temperature Sensor

 TEC-3-PIR2            Cover with Occupancy Sensor

1.   Additional TE-636xx-x Series 10k Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature
     Sensors Product Bulletin (LIT-216320) for more details.
2.   The TEC-3-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC22xx-4 Staged Thermostat
     Controller to provide occupancy sensing capability.

Repair Information
If a TEC226x-4(+PIR) Series Programmable or
TEC220x-4(+PIR) Series Non-Programmable
LONWORKS Network Configurable Staged Thermostat
Controller fails to operate within its specifications,
replace the unit. For a replacement thermostat, contact
the nearest Johnson Controls® representative.
Technical Specifications
TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS Network Staged Thermostat
Controllers (Part 1 of 2)
 Power Requirements                     19 to 30 VAC, 50/60 Hz, 2 VA (Terminals RC and C) at 24 VAC nominal, Class 2 or
                                        Safety Extra-Low Voltage (SELV)
 Relay Contact Rating                   19 to 30 VAC, 1.0 A Maximum, 15 mA Minimum, 3.0 A In-Rush, Class 2 or SELV
 Analog Inputs                          Resistive Inputs (RS and UI3) for 10k ohm Johnson Controls Type II Negative
                                        Temperature Coefficient (NTC) Thermistor Sensors
 Digital Inputs                         Voltage-Free Contacts across Terminal C to Terminals DI1 and DI2
 Economizer         Rating              0 to 10 VDC into 2k ohm resistance minimum
 Output
                    Accuracy            ±3%
 (TEC22x4-4 and
 TEC22x4-4+PIR
 Models)

      TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers                          7
                                                                               Product Bulletin
TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS Network Staged Thermostat
Controllers (Part 2 of 2)
 Wire Size                                       Unshielded Twisted Pair - 22 AWG (0.6 mm Diameter) Minimum, 18 AWG (1.0 mm
                                                 Diameter) Recommended
 Temperature Sensor Type                         Local 10k ohm Type II NTC Thermistor
 LONWORKS Network Standard                       64 Devices Maximum without repeater, 128 Devices Maximum with repeater; 6,250
                                                 ft (1,905 m) Maximum Length (Bus Topology)
 Temperature            Backlit Display          -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° Increments
 Range
                        Heating Control          40.0°F/4.5°C to 90.0°F/32.0°C
                        Cooling Control          54.0°F/12.0°C to 100.0°F/38.0°C
 Accuracy               Temperature              ±0.9F°/±0.5C° at 70.0°F/21.0°C Typical Calibrated
 Minimum Deadband                                2F°/1C° between Heating and Cooling
 Ambient                Operating                32 to 122°F (0 to 50°C); 95% RH Maximum, Noncondensing
 Conditions
                        Storage                  -22 to 122°F (-30 to 50°C); 95% RH Maximum, Noncondensing
 Compliance             United States            UL Listed, File E27734, CCN XAPX,
                                                 Under UL 873, Temperature Indicating and Regulating Equipment
                                                 FCC Compliant to CFR 47, Part 15, Subpart B, Class A
                                                 LONMARK® Certification 3.4
                        Canada                   UL Listed, File E27734, CCN XAPX7,
                                                 Under CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
                                                 Industry Canada, ICES-003
                        Europe                   CE Mark, EMC Directive 2004/108/EC
                                                 EN 61000-6-1 and EN 61000-6-3
                        Australia and            C-Tick Mark, Australia/NZ Emissions Compliant
                        New Zealand
 Shipping Weight                                 TEC226x-4 and TEC220x-4 Models: 0.75 lb (0.34 kg)
                                                 TEC226x-4+PIR and TEC220x-4+PIR Models: 0.77 lb (0.35 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
United States Emissions Compliance:
This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be required to correct the interference at his/her own expense.
Canadian Emissions Compliance:
This Class (A) digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel broullier du Canada.

                                                                                                                     Building Efficiency
                                                                                            507 E. Michigan Street, Milwaukee, WI 53202
                                             Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                    All other marks herein are the marks of their respective owners. © 2010 Johnson Controls, Inc.