TEC226x-4(+PIR) and TEC220x-4(+PIR) Series
LONWORKS® Network Staged Thermostat Controllers
                                                                                                                       Code No. LIT-12011611
Technical Bulletin                                                                                                       Issued February 8, 2010

Network Variables (NVs) and Configuration Parameters (CPs) List . . . . . . . . . . . . . 3
    Network Variable Inputs (NVIs) Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    Network Variable Outputs (NVOs) Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    Configuration Properties (CPs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
    Space Comfort Controller Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    Commissioning the Thermostat Using a LONWORKS Network Configuration Tool . . . 18

    Service Pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    TEC22xx-4 Configuration Plug-in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    Installing the Plug-in. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    Registering the Plug-in. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    Using LN Browser to Display NVs, NCIs, and CPs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
    Running the Plug-in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
         Heating - Cooling Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

         Hardware Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

         General Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

         Model Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

         Scheduler Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

         Network Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

         About Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

    Adding a Thermostat to the Network Automation Engine (NAE) . . . . . . . . . . . . . . . . . 39

    LONWORKS Thermostat Controller Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
    TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS Network
    Staged Thermostat Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

                                  TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged                                                       1
                                                                 Thermostat Controllers Technical Bulletin
2   TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers
    Technical Bulletin
TEC226x-4(+PIR) and TEC220x-4(+PIR) Series
LONWORKS® Network Staged Thermostat
Controllers
Technical Bulletin

Network Variables (NVs) and Configuration Parameters
(CPs) List
   Table 1 shows the NVs and CPs for the TEC226x-4(+PIR) and TEC220x-4(+PIR)
   Series Thermostat Controllers. Each Network Variable Input (NVI), Network
   Variable Output (NVO), and Network Configuration Input (NCI) has a reference
   number as defined in the XIF Resource File, and some objects have a subcategory
   number.
   The Bit column shows the bit number for each of the entry fields. If a value is
   supplied, the true Metasys® Target reference is the value + 1. For example, if the
   Bit column has a value of 0, then the true mapping index is 1. You must know the
   true mapping index when mapping LONWORKS® Point Objects into a Metasys
   system.
   The Metasys Target Reference is equal to the value in the No. column plus the
   value in the Sub column or Bit column (if available) in the format
   NV.<No. >.<Bit/Sub>. For example, using filter alarm for nvoSccStatus as an
   example, the Metasys Target Reference is NV.22.14.
   Note: If the format has not been changed from the default SNVT_state_64, when
         viewed using a LONWORKS network configuration tool, the nvoSccStatus
         screen is a 64-bit field, one for each entry field.
   Table 1: NVs and CPs per Model (Part 1 of 5)
   No. Sub     Bit   Metasys     NV or CP Name               Model
                     Target                                 TEC2264-4(+PIR)
                     Reference                              Econ, Prog.
                                                            TEC2204-4(+PIR)
                                                            Econ, NonProg.
                                                            TEC2263-4(+PIR)
                                                            Multi-Stage, Prog.
                                                            TEC2203-4(+PIR)
                                                            Multi-Stage, NonProg.
                                                            TEC2261-4(+PIR)
                                                            Single Stage, Prog.
                                                            TEC2201-4(+PIR)
                                                            Single Stage, NonProg.
                                                            TEC2262-4(+PIR)
                                                            Heat Pump, Prog.
                                                            TEC2202-4(+PIR)
                                                            Heat Pump, NonProg.
   0                 NV.0        nviSpaceTemp                X    X     X    X     X    X     X   X
   1                 NV.1        nviOutdoorTemp              X    X     X    X     X    X     X   X
   2                 NV.2        nviOccManCmd                X    X     X    X     X    X     X   X
   3                 NV.3        nviApplicMode               X    X     X    X     X    X     X   X
   4                 NV.4        nviSetPoint                 X    X     X    X     X    X     X   X
   5                 NV.5        nviTimeSet                  X    N/A   X    N/A   X    N/A   X   N/A
   6                 NV.6        nciDaySched[0]              X    N/A   X    N/A   X    N/A   X   N/A
        1            NV.6.1      occupied_event_1            x    N/A   x    N/A   x    N/A   x   N/A
        2            NV.6.2      unoccupied_event_2          x    N/A   x    N/A   x    N/A   x   N/A

 TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers       3
                                                                         Technical Bulletin
    Table 1: NVs and CPs per Model (Part 2 of 5)
    No. Sub      Bit   Metasys     NV or CP Name             Model
                       Target                               TEC2264-4(+PIR)
                       Reference                            Econ, Prog.
                                                            TEC2204-4(+PIR)
                                                            Econ, NonProg.
                                                            TEC2263-4(+PIR)
                                                            Multi-Stage, Prog.
                                                            TEC2203-4(+PIR)
                                                            Multi-Stage, NonProg.
                                                            TEC2261-4(+PIR)
                                                            Single Stage, Prog.
                                                            TEC2201-4(+PIR)
                                                            Single Stage, NonProg.
                                                            TEC2262-4(+PIR)
                                                            Heat Pump, Prog.
                                                            TEC2202-4(+PIR)
                                                            Heat Pump, NonProg.
           3           NV.6.3      occupied_event_3          x     N/A   x     N/A   x     N/A   x     N/A
           4           NV.6.4      unoccupied_event_4        x     N/A   x     N/A   x     N/A   x     N/A
    7                  NV.7        nciDaySched[1]            X     N/A   X     N/A   X     N/A   X     N/A
           1           NV.7.1      occupied_event_1          x     N/A   x     N/A   x     N/A   x     N/A
           2           NV.7.2      unoccupied_event_2        x     N/A   x     N/A   x     N/A   x     N/A
           3           NV.7.3      occupied_event_3          x     N/A   x     N/A   x     N/A   x     N/A
           4           NV.7.4      unoccupied_event_4        x     N/A   x     N/A   x     N/A   x     N/A
    8                  NV.8        nciDaySched[2]            X     N/A   X     N/A   X     N/A   X     N/A
           1           NV.8.1      occupied_event_1          x     N/A   x     N/A   x     N/A   x     N/A
           2           NV.8.2      unoccupied_event_2        x     N/A   x     N/A   x     N/A   x     N/A
           3           NV.8.3      occupied_event_3          x     N/A   x     N/A   x     N/A   x     N/A
           4           NV.8.4      unoccupied_event_4        x     N/A   x     N/A   x     N/A   x     N/A
    9                  NV.9        nciDaySched[3]            X     N/A   X     N/A   X     N/A   X     N/A
           1           NV.9.1      occupied_event_1          x     N/A   x     N/A   x     N/A   x     N/A
           2           NV.9.2      unoccupied_event_2        x     N/A   x     N/A   x     N/A   x     N/A
           3           NV.9.3      occupied_event_3          x     N/A   x     N/A   x     N/A   x     N/A
           4           NV.9.4      unoccupied_event_4        x     N/A   x     N/A   x     N/A   x     N/A
    10                 NV.10       nciDaySched[4]            X     N/A   X     N/A   X     N/A   X     N/A
           1           NV.10.1     occupied_event_1          x     N/A   x     N/A   x     N/A   x     N/A
           2           NV.10.2     unoccupied_event_2        x     N/A   x     N/A   x     N/A   x     N/A
           3           NV.10.3     occupied_event_3          x     N/A   x     N/A   x     N/A   x     N/A
           4           NV.10.4     unoccupied_event_4        x     N/A   x     N/A   x     N/A   x     N/A
    11                 NV.11       nciDaySched[5]            X     N/A   X     N/A   X     N/A   X     N/A
           1           NV.11.1     occupied_event_1          x     N/A   x     N/A   x     N/A   x     N/A
           2           NV.11.2     unoccupied_event_2        x     N/A   x     N/A   x     N/A   x     N/A
           3           NV.11.3     occupied_event_3          x     N/A   x     N/A   x     N/A   x     N/A
           4           NV.11.4     unoccupied_event_4        x     N/A   x     N/A   x     N/A   x     N/A
    12                 NV.12       nciDaySched[6]            X     N/A   X     N/A   X     N/A   X     N/A
           1           NV.12.1     occupied_event_1          x     N/A   x     N/A   x     N/A   x     N/A
           2           NV.12.2     unoccupied_event_2        x     N/A   x     N/A   x     N/A   x     N/A
           3           NV.12.3     occupied_event_3          x     N/A   x     N/A   x     N/A   x     N/A
           4           NV.12.4     unoccupied_event_4        x     N/A   x     N/A   x     N/A   x     N/A
    13                             nciSetPts                 X     X     X     X     X     X     X     X
           1           NV.13.1     occupied_cool             x     x     x     x     x     x     x     x
           2           N/A         standby_cool              N/A   N/A   N/A   N/A   N/A   N/A   N/A   N/A
           3           NV.13.3     unoccupied_cool           x     x     x     x     x     x     x     x
           4           NV.13.4     occupied_heat             x     x     x     x     x     x     x     x
           5           N/A         standby_heat              N/A   N/A   N/A   N/A   N/A   N/A   N/A   N/A
           6           NV.13.6     unoccupied_heat           x     x     x     x     x     x     x     x

4       TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers
        Technical Bulletin
  Table 1: NVs and CPs per Model (Part 3 of 5)
  No. Sub     Bit   Metasys     NV or CP Name                    Model
                    Target                                       TEC2264-4(+PIR)
                    Reference                                    Econ, Prog.
                                                                 TEC2204-4(+PIR)
                                                                 Econ, NonProg.
                                                                 TEC2263-4(+PIR)
                                                                 Multi-Stage, Prog.
                                                                 TEC2203-4(+PIR)
                                                                 Multi-Stage, NonProg.
                                                                 TEC2261-4(+PIR)
                                                                 Single Stage, Prog.
                                                                 TEC2201-4(+PIR)
                                                                 Single Stage, NonProg.
                                                                 TEC2262-4(+PIR)
                                                                 Heat Pump, Prog.
                                                                 TEC2202-4(+PIR)
                                                                 Heat Pump, NonProg.
  14                              nciCfg1RtuHp                   X     X     X     X     X     X     X     X
  Associate with UNVT_cfg_1_rtu_hp format file
        1           NV.14.1       password                       x     x     x     x     x     x     x     x
        2           NV.14.2       unoccupied_timer               x     x     x     x     x     x     x     x
        3           NV.14.3       anticycle                      x     x     x     x     x     x     x     x
        4           NV.14.4       power_up_delay                 x     x     x     x     x     x     x     x
        5           NV.14.5       temporary_occ_time             x     x     x     x     x     x     x     x
        6           NV.14.6       heating_stages_CPH             x     x     x     x     x     x     x     x
        7           NV.14.7       cooling_stages_CPH             x     x     x     x     x     x     x     x
        8           NV.14.8       heat_max_setpoint              x     x     x     x     x     x     x     x
        9           NV.14.9       cool_min_setpoint              x     x     x     x     x     x     x     x
        10          NV.14.10      OA_temp_heat_lockout           x     x     x     x     x     x     x     x
        11          NV.14.11      OA_temp_cool_lockout           x     x     x     x     x     x     x     x
        12          NV.14.12      calib_room_sensor              x     x     x     x     x     x     x     x
        13          NV.14.13      calib_outside_air_sensor       x     x     x     x     x     x     x     x
        14          NV.14.14      deadband                       x     x     x     x     x     x     x     x
        15          NV.14.15      fan_mode                       x     x     x     x     x     x     x     x
        16          NV.14.16      fan_control                    x     x     x     x     x     x     x     x
        17          NV.14.17      fan_delay                      x     x     x     x     x     x     x     x
        18          NV.14.18      keypad_lockout                 x     x     x     x     x     x     x     x
        19          NV.14.19      proportional_band              x     x     x     x     x     x     x     x
        20          NV.14.20      temperature_units              x     x     x     x     x     x     x     x
        21          NV.14.21      frost_protection               x     x     x     x     x     x     x     x
        22          NV.14.22      menu_scroll                    x     x     x     x     x     x     x     x
  15                              nciCfg2RtuHp                   X     X     X     X     N/A   N/A   X     X
  Associate with UNVT_cfg_2_rtu_hp format file
        1           NV.15.1       di1_config                     x     x     x     x     x     x     x     x
        2           NV.15.2       di2_config                     x     x     x     x     x     x     x     x
        3           NV.15.3       aux_contact_config             x     x     x     x     x     x     x     x
        4           NV.15.4       number_of_events               x     N/A   x     N/A   x     N/A   x     N/A
        5           NV.15.5       progressive_recovery           x     N/A   x     N/A   x     N/A   x     N/A
        7           NV.15.7*      a.hp_rev_valve_config          N/A   N/A   N/A   N/A   N/A   N/A   x     x
        8           NV.15.8**     a.number_of_heating_stages     x     x     x     x     N/A   N/A   N/A   N/A
        9           NV.15.9       number_of_cool_or_hp_stages    x     x     x     x     N/A   N/A   x     x
        10          NV.15.10      econo_min_position             x     x     N/A   N/A   N/A   N/A   N/A   N/A
        12          NV.15.12*     b.hp_high_balance_point        N/A   N/A   N/A   N/A   N/A   N/A   x     x
        13          NV.15.13**    b.econo_changeover_setpoint    x     x     N/A   N/A   N/A   N/A   N/A   N/A
        15          NV.15.15*     c.hp_low_balance_point         N/A   N/A   N/A   N/A   N/A   N/A   x     x
        16          NV.15.16**    c.econo_mixed_air_setpoint     x     x     N/A   N/A   N/A   N/A   N/A   N/A
        18          NV.15.18*     d.hp_comfort_or_economy_mode   N/A   N/A   N/A   N/A   N/A   N/A   x     x

TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers                 5
                                                                        Technical Bulletin
    Table 1: NVs and CPs per Model (Part 4 of 5)
    No. Sub      Bit   Metasys       NV or CP Name                       Model
                       Target                                            TEC2264-4(+PIR)
                       Reference                                         Econ, Prog.
                                                                         TEC2204-4(+PIR)
                                                                         Econ, NonProg.
                                                                         TEC2263-4(+PIR)
                                                                         Multi-Stage, Prog.
                                                                         TEC2203-4(+PIR)
                                                                         Multi-Stage, NonProg.
                                                                         TEC2261-4(+PIR)
                                                                         Single Stage, Prog.
                                                                         TEC2201-4(+PIR)
                                                                         Single Stage, NonProg.
                                                                         TEC2262-4(+PIR)
                                                                         Heat Pump, Prog.
                                                                         TEC2202-4(+PIR)
                                                                         Heat Pump, NonProg.
           19           NV.15.19**     d.econo mechanical_cool_enable    x     x     N/A   N/A   N/A   N/A   N/A   N/A
           20           NV.15.20       hp compressor_auxheat_interlock   N/A   N/A   N/A   N/A   N/A   N/A   x     x
    *Used for heat pump models, do not map for rooftop models.
    **Used for rooftop models, do not map for heat pump models.
    16                  NV.16          nciHvacType                       X     X     X     X     X     X     X     X
    17                                 nciSccModel                       X     X     X     X     X     X     X     X
           1            NV.17.1        Thermostat Model                  x     x     x     x     x     x     x     x
           2            NV.17.2        Software Version                  x     x     x     x     x     x     x     x
    18                  NV.18          nvoSpaceTemp                      X     X     X     X     X     X     X     X
    19                                 nvoUnitStatus                     X     X     X     X     X     X     X     X
           1            NV.19.1        mode                              x     x     x     x     x     x     x     x
           2            NV.19.2        heat_output_primary               x     x     x     x     x     x     x     x
           3            NV.19.3        heat_output_secondary             N/A   N/A   N/A   N/A   N/A   N/A   x     x
           4            NV.19.4        cool_output                       x     x     x     x     x     x     x     x
           5            NV.19.5        econo_output                      x     x     N/A   N/A   N/A   N/A   N/A   N/A
           6            NV.19.6        Fan_output                        x     x     x     x     x     x     x     x
           7            NV.19.7        in_alarm                          x     x     x     x     x     x     x     x
    20                  NV.20          nvoDischAirTemp                   X     X     X     X     X     X     X     X
    21                  NV.21          nvoEffectOccup                    X     X     X     X     X     X     X     X
    22                                 nvoSccStatus                      X     X     X     X     X     X     X     X
    For all non heat pump models, associate with UNVT_thermo_state_rtu
           1       2    NV.22.3        fan_output                        x     x     x     x     x     x     N/A   N/A
           2       3    NV.22.4        cooling_stage_1                   x     x     x     x     x     x     N/A   N/A
           3       4    NV.22.5        cooling_stage_2                   x     x     x     x     N/A   N/A   N/A   N/A
           4       5    NV.22.6        auxiliary_contact                 x     x     x     x     x     x     N/A   N/A
           5       6    NV.22.7        heating_stage_1                   x     x     x     x     x     x     N/A   N/A
           6       7    NV.22.8        heating_stage_2                   x     x     x     x     x     x     N/A   N/A
           7       12   NV.22.13       service_alarm                     x     x     x     x     x     x     N/A   N/A
           8       13   NV.22.14       filter_alarm                      x     x     x     x     x     x     N/A   N/A
           9       17   NV.22.18       di2_direct_status                 x     x     x     x     x     x     N/A   N/A
           10      18   NV.22.19       di1_direct_status                 x     x     x     x     x     x     N/A   N/A
           11      22   NV.22.23       set_clock_alarm                   x     N/A   x     N/A   x     N/A   N/A   N/A
           12      23   NV.22.24       frost_protection_alarm            x     x     x     x     x     x     N/A   N/A
           13      24   NV.22.25       local_pir_motion                  x     x     x     x     x     x     N/A   N/A
           14      25   NV.22.26       fan_lock_alarm                    x     x     x     x     x     x     N/A   N/A
    For all heat pump models, associate with UNVT_thermo_state_hp
           1       2    NV.22.3        fan_output                        N/A   N/A   N/A   N/A   N/A   N/A   x     x
           2       3    NV.22.4        compressor_stage_1                N/A   N/A   N/A   N/A   N/A   N/A   x     x
           3       4    NV.22.5        compressor_stage_2                N/A   N/A   N/A   N/A   N/A   N/A   x     x
           4       5    NV.22.6        auxiliary_contact                 N/A   N/A   N/A   N/A   N/A   N/A   x     x

6    TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers
     Technical Bulletin
  Table 1: NVs and CPs per Model (Part 5 of 5)
  No. Sub    Bit   Metasys     NV or CP Name             Model
                   Target                                TEC2264-4(+PIR)
                   Reference                             Econ, Prog.
                                                         TEC2204-4(+PIR)
                                                         Econ, NonProg.
                                                         TEC2263-4(+PIR)
                                                         Multi-Stage, Prog.
                                                         TEC2203-4(+PIR)
                                                         Multi-Stage, NonProg.
                                                         TEC2261-4(+PIR)
                                                         Single Stage, Prog.
                                                         TEC2201-4(+PIR)
                                                         Single Stage, NonProg.
                                                         TEC2262-4(+PIR)
                                                         Heat Pump, Prog.
                                                         TEC2202-4(+PIR)
                                                         Heat Pump, NonProg.
       5     6     NV.22.7     heating_stage_1           N/A   N/A   N/A   N/A   N/A   N/A   x   x
       6     7     NV.22.8     reversing valve           N/A   N/A   N/A   N/A   N/A   N/A   x   x
       7     12    NV.22.13    service_alarm             N/A   N/A   N/A   N/A   N/A   N/A   x   x
       8     13    NV.22.14    filter_alarm              N/A   N/A   N/A   N/A   N/A   N/A   x   x
       9     17    NV.22.18    di2_direct_status         N/A   N/A   N/A   N/A   N/A   N/A   x   x
       10    18    NV.22.19    di1_direct_status         N/A   N/A   N/A   N/A   N/A   N/A   x   x
       11    22    NV.22.23    set_clock_alarm           N/A   N/A   N/A   N/A   N/A   N/A   x   N/A
       12    23    NV.22.24    frost_protection_alarm    N/A   N/A   N/A   N/A   N/A   N/A   x   x
       13    24    NV.22.25    local_pir_motion          N/A   N/A   N/A   N/A   N/A   N/A   x   x
       14    25    NV.22.26    fan_lock_alarm            N/A   N/A   N/A   N/A   N/A   N/A   x   x
  23               NV.23       nvoEffectSetpt            X     X     X     X     X     X     X   X
  24               NV.24       nvoSetpoint               X     X     X     X     X     X     X   X
  25               NV.25       nciSndHrtBt               X     X     X     X     X     X     X   X
  26               NV.26       nciMinOutTm               X     X     X     X     X     X     X   X
  27               NV.27       nciRcvHrtBt               X     X     X     X     X     X     X   X
  28               NV.28       nciMajVer                 X     X     X     X     X     X     X   X
  29               NV.29       nciMinVer                 X     X     X     X     X     X     X   X
  30               N/A         nciLocation               x     x     x     x     x     x     x   x

TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers       7
                                                                        Technical Bulletin
Network Variable Inputs (NVIs) Table
    Table 2: NVIs (Part 1 of 2)
     Parameter       NVI Name and     Range and Enumeration Definition
                     SNVT Type
     Room            nviSpaceTemp     Valid Range: -40 to 122°F (-40 to 50.0°C)
     Temperature     SNVT_temp_p      Default Null (release) Value: 621.8°F (327.67°C)
                                      0x7FFF represents invalid data.
                                      Note: This NVI allows the temperature setpoint for the occupied mode to be
                                             changed via the network. When bound or written to, the internal
                                             temperature reading (internal sensor) is no longer used. To change the
                                             thermostat back to using its internal sensor, break the bind for bound
                                             stats, or for commanded stats, issue a reset to the thermostat.
                                      This NVI is subject to the Receive Heartbeat Time, nciRcvHrtBt.
     Outdoor Air     nviOutdoorTemp   Valid Range: -40 to 122°F (-40 to 50.0°C)
     Temperature     SNVT_temp_p      Default Null (release) Value: 621.8°F (327.67°C)
                                      0x7FFF represents invalid data
                                      Note: This NVI provides outdoor air temperature information to the thermostat
                                             from a bound network temperature value or when an outside air sensor
                                             is connected to the OS and Scom terminals. Once bound, or when the
                                             outside air sensor is connected, the thermostat automatically displays
                                             the value.
     Occupancy       nviOccManCmd     0 = OC_OCCUPIED*
                     SNVT_occupancy   1 = OC_UNOCCUPIED*
                                      2 = OC_BYPASS
                                      3 = OC_STANDBY (Not used)
                                      0XFF = OC_NUL (Release to internal schedule)**
                                      *OC_OCCUPIED and OC_UNOCCUPIED commands always have authority
                                      over the local occupancy routines of the thermostat whether they are through a
                                      local input or a PIR cover.
                                      **OC_NUL command releases the thermostat controller to use its own internal
                                      occupancy routine driven by the local schedule (by a digital input or onboard
                                      PIR cover).
                                      Note: This NVI commands the Space Comfort Controller into different
                                              occupancy modes. It is typically sent by a supervisory node to manually
                                              control occupancy modes, or to override the scheduled occupancy.
                                              Default Null Value: OC_NUL = 0xFF
     System Mode     nviApplicMode    0 = HVAC_AUTO (Default)
                     SNVT_hvac_mode   1 = HVAC_HEAT
                                      2 = HVAC_MRNG_WRMUP (Not used)
                                      3 = HVAC_COOL
                                      4 = HVAC_NIGHT_PURGE (Not used)
                                      5 = HVAC_PRE_COOL (Not used)
                                      6 = HVAC_OFF
                                      7 = HVAC_TEST (Not used)
                                      8 = HVAC_EMERG_HEAT (Not used)
                                      9 = HVAC_FAN_ONLY (Not used)
                                      10 = HVAC_FREE_COOL (Not used)
                                      11 = HVAC_ICE (Not used)
                                      12 = HVAC_MAX_HEAT (Not used)
                                      13 = HVAC_ECONOMY (Not used)
                                      14 = HVAC_DEHUMID (Not used)
                                      15 = HVAC_CALIBRATE (Not used)
                                      16 = HVAC_EMERG_COOL (Not used)
                                      17 = HVAC_EMERG_STEAM (Not used)
                                      0XFF = HVAC_NUL (Not used)
                                      Note: This NVI coordinates the Space Comfort Controller with any node that
                                             may need to control the heat/cool changeover of the unit.
                                      This NVI is subject to the Receive Heartbeat Time, nciRcvHrtBt.

8     TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers
      Technical Bulletin
  Table 2: NVIs (Part 2 of 2)
   Parameter       NVI Name and      Range and Enumeration Definition
                   SNVT Type
   Occupied        nviSetpoint       Occupied Cooling - Valid Range: 54 to 100°F (12 to 37.5°C)
   Cooling and     SNVT_temp_p       Occupied Heating - Valid Range: 40 to 90°F (4.5 to 32°C)
   Heating                           Standby Cool Setpoint (Not used)
   Setpoints                         Standby Heat Setpoint (Not used)
                                     Default Null (release) Value: 621.8°F (327.67°C)
                                     0x7FFF represents invalid data
                                     Note: This NVI allows the temperature setpoints for the occupied mode to be
                                            changed via the network. The unoccupied setpoints are not changed.
                                     Note: If one setpoint of a pair of heating and cooling setpoints (for example,
                                            Occupied Heat Setpoint and Occupied Cool Setpoint) is overridden, the
                                            other setpoint of the pair may be automatically adjusted by the
                                            thermostat to maintain the minimum deadband between the two
                                            setpoints.
   Date and Time   nviTimeSet        Sub          Name               Valid Range      Default Value
                   SNVT_time_stamp   1            year               0 to 3000        0
                                     2            month              0 to 12          0
                                     3            day                0 to 31          0
                                     4            hour               0 to 23          0
                                     5            minute             0 to 59          0
                                     6            second             0 to 59          0
                                     Note: This NVI is used to set the time and date of the Space Comfort
                                           Controller. TEC226x-4(+PIR) models only.

TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers                   9
                                                                        Technical Bulletin
Network Variable Outputs (NVOs) Table
     All NVOs are updated no faster than the Minimum Send Time (nciMinOutTm)
     configuration value, if used. An NVO transmits immediately when its value
     changes significantly. Additionally, this variable is also transmitted as a heartbeat
     output on a regular basis as dictated by the Maximum Send Time (nciSndHrtBt)
     configuration value.
     Table 3: NVOs (Part 1 of 3)
      Parameter      NVO Name and            Range and Enumeration Definition
                     SNVT Type
      Room           nvoSpaceTemp            Valid Range: -40 to 122°F (-40 to 50°C)
      Temperature    SNVT_temp_p             Default Null (release) Value: 621.07°F (327.67°C)
                                             0x7FFF represents invalid data.
                                             Note: This NVO monitors the effective space temperature sensor that
                                                    the Space Comfort Controller is using for control. This output
                                                    echos the value of the input. In the event of a sensor failure, the
                                                    value 621.07°F (327.67°C or 0x7FFF) is sent as an invalid value.
      Unit Status    nvoUnitStatus           Sub    Name                       Valid Value
                     SNVT_hvac_status        01     mode                       HVAC_HEAT
                                                                               HVAC_MRNG_WRMUP (Not used)
                                                                               HVAC_COOL
                                                                               HVAC_NIGHT_PURGE (Not used)
                                                                               HVAC_PRE_COOL (Not used)
                                                                               HVAC_HVAC_OFF
                                                                               HVAC_HVAC_TEST (Not used)
                                                                               HVAC_HVAC_EMERG_HEAT
                                                                                    (Not used)
                                                                               HVAC_FAN_ONLY (Not used)
                                                                               HVAC_MAX_HEAT (Not used)
                                             02     heat_output_primary        0 to 100%
                                             03     heat_output_secondary      0 to 100%
                                             04     cool_output                0 to 100%
                                             05     econ_output                0 to 100%
                                             06     fan_output                 0 to 100%
                                             07     In_alarm                   0 = No alarms
                                                                               1 = Alarm On
                                                                               0xFFF = Alarm disabled (Not used)
                                             Note: This NVO reports the Space Comfort Controller status. It
                                                   combines the Operating mode, the capacity of heating and
                                                   cooling used, and an indicates if any alarms are present in the
                                                   object.
      Outdoor        nvoOutdoorTemp          Valid Range: -40 to 122°F (-40 to 50°C)
      Temperature    SNVT_temp_p             Default Null (release) Value: 621.8°F (327.67°C)
                                             0x7FFF represents invalid data
                                             Note: This NVO is used to monitor the outdoor air temperature. In the
                                                    event of a sensor failure, the value 621.07°F (327.67°C or
                                                    0x7FFF) is sent as an invalid value.
                                             Note: For this to function, an outside air sensor must be connected to
                                                    the OS and Scom terminals.

10     TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers
       Technical Bulletin
  Table 3: NVOs (Part 2 of 3)
   Parameter     NVO Name and         Range and Enumeration Definition
                 SNVT Type
   Supply        nvoDischAirTemp      Valid Range: -40 to 122°F (-40 to 50°C)
   Temperature   SNVT_temp_p          Default Null (release) Value: 621.8°F (327.67°C)
                                      0x7FFF represents invalid data
                                      Note: This NVO is used to monitor the temperature of the air that
                                             leaves the Space Comfort Controller. In the event of a sensor
                                             failure, the value 621.07°F (327.67°C or 0x7FFF) is sent as an
                                             invalid value.
                                      Note: For this to function, a supply air sensor must be connected to the
                                             MS and Scom terminals.
   Occupancy     nvoEffectOccup       0 = OC_OCCUPIED
                 SNVT_occupancy       1 = OC_UNOCCUPIED
                                      2 = OC_BYPASS
                                      3 = OC_STANDBY (Not used)
                                      0XFF = OC_NUL (Release to internal schedule)
                                      Note: OC_BYPASS can be initiated by either OccManCmd or a local
                                            input. NvoEffectOccup is only in OC_BYPASS for the duration of
                                            the ToccTime (nciCfg1RtuHp), until reinitiated by either a
                                            transition of the local input or an update to nviOccManCmd. This
                                            NVO indicates the actual occupancy mode of the unit. The
                                            information is typically reported to a supervisory controller or
                                            provided to another Space Comfort Controller to coordinate
                                            operation of multiple units. Default Null Value: OC_NUL = 0xFF

TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers                 11
                                                                        Technical Bulletin
     Table 3: NVOs (Part 3 of 3)
     Parameter      NVO Name and            Range and Enumeration Definition
                    SNVT Type
     Thermostat’s   nvoSccStatus            Bit   Name                       Valid Value     Default Value
     I/O Status     UNVT_thermo_state_rtu   2     fan output                 0 = Off         N/A
                    UNVT_thermo_state_hp                                     1 = On
                                            3     cooling stage 1            0 = Off         N/A
                                                  compressor stage 1         1 = On
                                            4     cooling stage 2            0 = Off         N/A
                                                  compressor stage 2         1 = On
                                            5     auxiliary contact          0 = Off         N/A
                                                                             1 = On
                                            6     heating stage 1            0 = Off         N/A
                                                                             1 = On
                                            7     heating stage 2            0 = Off         N/A
                                                  reversing valve            1 = On
                                            12    service alarm              0 = Off         N/A
                                                                             1 = On
                                            13    filter alarm               0 = Off         N/A
                                                                             1 = On
                                            17    di2 direct status          0 = Activated   N/A
                                                                             1 = Not
                                                                                 Activated
                                            18    di1 direct status          0 = Activated   N/A
                                                                             1 = Not
                                                                                 Activated
                                            22    set clock alarm            0 = Off         N/A
                                                                             1 = On
                                            23    frost protection alarm     0 = Off         N/A
                                                                             1 = On
                                            24    local pir motion           0 = Off         N/A
                                                                             1 = On
                                            25    fan lock alarm             0 = Off         N/A
                                                                             1 = On
                                            Note: This NVO reports the status of the Space Comfort Controller’s
                                                  inputs and outputs.
     Setpoint       nvoEffectSetpt          Valid Range: 40 to 100°F (4.5 to 37.5°C)
                    SNVT_temp_p             Default Null (release) Value: 621.8°F (327.67°C)
                                            0x7FFF represents invalid data
                                            Note: This NVO is used to monitor the effective temperature setpoint,
                                                   which may depend on nciSetpoints, nvoEffectOccup, nviSetpoint,
                                                   and any local setpoint adjustment. For example, if the occupancy
                                                   state is unoccupied and the heat/cool state is heat, the effective
                                                   setpoint would be equal to the unoccupied heating setpoint
                                                   defined in nciSetpoints.
     Local          nvoSetPoint             Valid Range: 40 to 100°F (4.5 to 37.5°C)
     Setpoint       SNVT_temp_p             Default Null (release) Value: 621.8°F (327.67°C)
     Output                                 0x7FFF represents invalid data
                                            Note: This NVO monitors the space temperature setpoint.

12     TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers
       Technical Bulletin
Configuration Properties (CPs)
   Table 4: CP and NCIs (Part 1 of 5)
    Parameter      CP Name and          Function
                   NCI Type
    Schedule       nciDay_Sched[x]      Sub     Name                    Default Value
                   x = 0 to 6           1       occupied_event_1        0
                   UNVT_day_sched
                                        2       unoccupied_event_2      1439
                                        3       occupied_event_3        0
                                        4       unoccupied_event_4      1439
                                        Valid Range: 0 to 1,439 minutes
                                        2 or 4 events can be entered, depending on the nb_of_events variable.
                                        Starting and ending times are entered in minutes. For example,
                                        11:59 P.M. is equal to 1439 minutes (23 hours * 60 minutes +
                                        59 minutes)
                                        Note: This CP defines the schedule for every day of the week (from
                                                Monday (Day 0) to Sunday (Day 6). This NCI is linked with the
                                                nvoEffectOccup variable.
    Temperature    nciSetPts            Sub     Name                    Valid Range       Default Value
    Setpoints      SNVT_temp_setpt      1       occupied_cool           54 to 100°F       75°F (24°C)
                                                                        (12 to 37.5°C)
                                        2       standby_cool            Not Used          N/A
                                        3       unoccupied_cool         54 to 100°F       80°F (26.5°C)
                                                                        (12 to 37.5°C)
                                        4       occupied_heat           40 to 90°F        72°F (22°C)
                                                                        (4.5 to 32°C)
                                        5       standby_heat            Not Used          N/A
                                        6       unoccupied_heat         40 to 90°F        62°F (16.5°C)
                                                                        (4.5 to 32°C)
                                        Note: This CP defines the space temperature setpoints for various
                                                heat, cool, and occupancy modes.
                                        The stand-by setpoints can be modified, but are not used by the
                                        controller, as it does not support Stand-By occupancy mode.

 TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers                     13
                                                                         Technical Bulletin
     Table 4: CP and NCIs (Part 2 of 5)
     Parameter       CP Name and          Function
                     NCI Type
     Thermostat’s    nciCfg1RtuHpt        Sub   Name                   Valid Range      Default Value
     Common CPs      UNVT_cfg_1_rtu_hp    1     password               0 to 1000        0
                                          2     unoccupied timer       0.5 to 24.0      0.5 hours
                                                                       hours
                                          3     anticycle              0 to 5 minutes   2 minutes
                                                                       (in 1 min.
                                                                       increments)
                                          4     powerup delay          10 to 120 sec.   10 sec.
                                          5     temporary occ time     0 to 12 hours    3 hours
                                          6     heating stages cph     3 to 8 CPH       4 CPH
                                          7     cooling stages cph     3 or 4 CPH       4 CPH
                                          8     heat maximum           40 to 90°F       90°F
                                                setpoint               (4.5 to 32°C)    (32°C)
                                          9     cool minimum           54 to 100°F      54°F
                                                setpoint               (12 to 37.5°C)   (12°C)
                                          10    oa temp heat lockout   -15 to 120°F     120°F
                                                                       (-26 to 49°C)    (49°C)
                                          11    oa temp cool lockout   -40 to 95°F      -40°F
                                                                       (-40 to 35°C)    (-40°C)
                                          12    calib room sensor      ±5°F             0°F
                                                                       (±2.5°C)
                                          13    calib outdoor air      ±5°F             0°F
                                                sensor                 (±2.5°C)
                                          14    deadband               2 to 4F° (1F°    2F°
                                                                       increments)      (1C°)
                                                                       (1 to 2C°)
                                          15    fan mode               0 = On           0 = On
                                                                       1 = Auto
                                                                       2 = Smart
                                          16    fan control            0 = Off          1 = On
                                                                       1 = On
                                          17    fan delay              0 = Off          0 = Off
                                                                       1 = On
                                          18    keypad lockout         0 = No_Lockout   No_Lockout
                                                                       1 = Level_1
                                                                       2 = Level_2
                                          19    proportional band      2.0 to 8.0F°     2F°
                                                                       (1.1 to 4.4C°)   (1.1C°)
                                          20    temperature units      0 = °C           °F
                                                                       1 = °F
                                          21    frost protection       0 = Off          0 = Off
                                                                       1 = On
                                          22    temperature scale      0 = °C           °F
                                                                       1 = °F

14     TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers
       Technical Bulletin
  Table 4: CP and NCIs (Part 3 of 5)
   Parameter      CP Name and          Function
                  NCI Type
   Thermostat’s   nciCfg2RtuHpt        Sub   Name                    Valid Range         Default Value
   Common CPs     UNVT_cfg_2_rtu_hp
                                       01    di1 config              0 = None            0 = None
   (continued)
                                                                     1 = RemNSB
                                                                     2 = RemOVR
                                                                     3 = Filter
                                                                     4 = Service
                                       02    di2 config              0 = None            0 = None
                                                                     1 = RemNSB
                                                                     2 = RemOVR
                                                                     3 = Filter
                                                                     4 = Service
                                       03    aux contact config      0 = NORMALLY_       0
                                                                         OPEN
                                                                     2 = NORMALLY_
                                                                         CLOSED
                                       04    number of events        2 or 4              2
                                       05    progressive recovery    0 = Off             0 = Off
                                                                     1 = Active
                                       06    a.hp rev valve config   1 = Normally        2
                                                                         Heat
                                                                     2 = Normally
                                                                         Cool
                                       07    a.number of heating     1 = 1 Stage         2
                                             stages                  2 = 2 Stages
                                       08    number of cool or hp    1 = 1 Stage         2
                                             stages                  2 = 2 Stages
                                       09    econo min position      0 to 100%           0%
                                       10    b.hp high balance       34.0 to 90.0°F      90.0°F
                                             point                   (1.1 to 32.2°C)     (32.2°C)
                                       11    b.econo changeover      14 to 70°F          55.0°F
                                             setpoint                (-10.0 to 21.1°C)   (12.8°C)
                                       12    c.hp low balance        -40.0 to 30.0°F     -12.0°F
                                             point                   (-40.0 to -1.1°C)   (-24.4°C)
                                       13    c.econo mixed air       50.0 to 90.0°F      50.0°F
                                             setpoint                (10.0 to 32.2°C)    (10.0°C)
                                       14    d.hp comfort or         0 = Comfort         0 = Comfort
                                             economy mode            1 = Economy
                                       15    d.econo mechanical      0 = Off             0 = Off
                                             cool enable             1 = On
                                       16    hp compressor           0 = Off             0 = Off
                                             auxheat interlock       1 = On

TEC226x-4(+PIR) and TEC220x-4(+PIR) Series LONWORKS® Network Staged Thermostat Controllers               15
                                                                        Technical Bulletin
     Table 4: CP and NCIs (Part 4 of 5)
     Parameter        CP Name and         Function
                      NCI Type
     HVAC Unit Type   nciHvac_type        Value   Identifier              Name
     Identifier       SNVT_hvac_type      0       HVT_GENERIC             Not Used
                                          1       HVT_FAN_COIL            Fan Coil Unit
                                          2       HVT_VAV                 Not Used
                                          3       HVT_HEAT_PUMP           Heat Pump
                                          4       HVT_ROOFTOP             Rooftop Unit
                                          5       HVT_UNIT_VENT           Not Used
                                          6       HVT_CHIL_CEIL           Not Used
                                          7       HVT_RADIATOR            Not Used
                                          8       HVT_AHU                 Not Used
                                          9       HVT_SLF_CONT            Not Used
                                          Note: This CP helps the user identify the type of equipment being
                                                monitored.
     Thermostat’s     nciSccModel         Sub     Name                    Valid Range       Default Value
     Model Number     UNVT_model_info_2
                                          01      Thermostat Model        01 = TEC2264-4    Depends on the
                                                                          02 = TEC2261-4    model used
                          