24- 9890- 161, Rev. C

                                                                           Installation Instructions
                                                                                         Issue Date March 2016

             TEC2103-2 Networked Multi-Stage Thermostat

Application
The TEC2103-2 thermostat is an N2 networked                  To install the thermostat:
thermostat that provides control of multi-stage HVAC
                                                             1.   Remove the security screw on the bottom of the
equipment. The TEC2103-2 thermostat provides
                                                                  thermostat cover using a Phillips-head
exceptional accuracy through the use of a unique
                                                                  screwdriver. Open the thermostat by pulling on
Proportional-Integral (PI) time proportioning algorithm.
                                                                  the bottom side of the thermostat cover
The algorithm virtually eliminates temperature offset
                                                                  (Figure 1).
associated with traditional, differential-based on/off
thermostats. The TEC2103-2 thermostat also uses an           2.   Unlock the Printed Circuit Board (PCB) by
adaptive control logic algorithm to control the space             carefully pressing the locking tabs to the right
temperature during recovery to minimize overshoot                 (Figure 2). Open the thermostat’s PCB to the left.
while providing maximum comfort.
                                                             3.   Pull out approximately 6 in. (152 mm) of wires
The TEC2103-2 thermostat has Metasys® N2                          from the wall and insert the cable through the
communication capability. This communication allows               hole in the base.
the user to view and adjust parameters from a remote
                                                             4.   Align the base on the wall, and using the base as
workstation. Additionally, the menu driven backlit
                                                                  a template, mark the location of the two mounting
display, plain text menus, and five keys on the
TEC2103-2 thermostat make operating the thermostat                holes on the wall. Confirm the thermostat base is
easy and intuitive.                                               installed with the proper side up.
                                                             5.   Use the supplied anchors and screws for
Note: In this document, Building Automation System
                                                                  mounting on drywall or plaster. Drill two 3/16 in.
(BAS) is a generic term that refers to the Metasys
                                                                  (4.7 mm) holes at the marked locations and tap
Network (Network Control Module [NCM] or N30
                                                                  nylon anchors flush to wall surface (Figure 3).
Series), and Companion (CPN) supervisory systems.
The specific system names are used when referring to         6.   Position base on the wall, insert screws through
system specific applications.                                     mounting base, and fasten into wall anchors. Do
                                                                  not overtighten screws.
Installation                                                 7.   Swing the thermostat PCB back to the right to
Location Considerations                                           close. Gently press on the PCB to secure each of
                                                                  the locking tabs.
Locate the TEC2103-2 thermostat:
                                                             8.   Pull out the screw terminal blocks using the
•   on a partitioning interior wall, and approximately            pull-tabs on each connector (Figure 4).
    5 ft. (1.5 m) above the floor in a location of
    average temperature                                      Note: The number of terminals on the terminal
                                                             blocks varies depending on the TEC model.
•   away from direct sunlight, radiant heat, outside
    walls, behind doors, air discharge grills, stairwells,
    or outside doors
•   away from steam or water pipes, warm air stacks,
    unheated/uncooled areas, or sources of electrical
    interference

© 2016 Johnson Controls, Inc.
  Part No. 24-9890-161, Rev. C                                                                  www.johnsoncontrols.com
IMPORTANT:            Use this TEC2103-2 networked
multi-stage thermostat only as an operating control.
Where failure or malfunction of the thermostat could
lead to personal injury or property damage to the
controlled equipment or other property, additional
precautions must be designed into the control
system. Incorporate and maintain other devices,
such as supervisory or alarm systems or safety or
limit controls, intended to warn of or protect against                                                                 PCB
                                                                                                                   Locking Tabs
failure or malfunction of the thermostat.

                                                                                                                              T600_TEC_Openm_Stat
IMPORTANT :           Utiliser ce TEC2103-2
networked multi-stage thermostat uniquement en
tant que dispositif de contrôle de fonctionnement.
Lorsqu'une défaillance ou un dysfonctionnement du
thermostat risque de provoquer des blessures ou
d'endommager l'équipement contrôlé ou un autre
équipement, la conception du système de contrôle                   Figure 2: Opening the Thermostat PCB
doit intégrer des dispositifs de protection
supplémentaires. Veiller dans ce cas à intégrer de
façon permanente d'autres dispositifs, tels que des
systèmes de supervision ou d'alarme, ou des
dispositifs de sécurité ou de limitation, ayant une
fonction d'avertissement ou de protection en cas de
défaillance ou de dysfonctionnement du thermostat.

                                                                                                                              T600_TEC_Mounting_Base

                                                                   Figure 3: Mounting the Thermostat Base

                                           T600_TEC_Remove_Cover

     Figure 1: Removing the Thermostat Cover

                                                                                                   T600_TEC_Terminal_Blocks

                                                                   Figure 4: Removing the Terminal Blocks

2   TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions
Wiring                                                   2. Gently push excess wire back into the wall, plug
                                                            the wall hole with fireproof material to prevent
                                                            drafts from affecting ambient temperature
   !     CAUTION: Risk of Electric Shock.                   readings, and install screw terminal blocks back
Disconnect the power supply before making                   onto the PCB.
electrical connections to avoid electric shock.          3. Reattach the thermostat cover to the installed
                                                            base (top side first) and install the security screw
MISE EN GARDE : Risque de décharge                          on the bottom.
électrique.
Débrancher l'alimentation avant de réaliser tout
raccordement électrique afin d'éviter tout risque de         !     CAUTION: Risk of Property Damage.
décharge électrique.
                                                          Do not apply power to the system before checking
Note: When replacing an existing thermostat,              all wiring connections. Short circuited or improperly
remove and label wires to identify terminal               connected wires may result in permanent damage to
designations. When replacing a TEC2103 thermostat,        the equipment.
simply remove the terminal blocks and reinsert onto       MISE EN GARDE : Risque de dégâts matériels.
the new thermostat.                                       Ne pas mettre le système sous tension avant d'avoir
To wire the thermostat:                                   vérifié tous les raccords de câblage. Des fils formant
                                                          un court-circuit ou connectés de façon incorrecte
1. Strip each wire 1/4 in. (6.35 mm) and connect to       risquent d'endommager irrémédiablement
   the appropriate terminal according to the              l'équipement.
   TEC2103-2 thermostat wiring diagram (Figure 5).

                                       TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions        3
          Terminal                          Function
          Y1           Energizes on a call for first stage cooling
          Y2           Energizes on a call for second stage cooling
           G           Energizes fan in accordance with the selected fan mode
          RC           24 VAC from equipment transformer                                                                  3-pole right top
                                                                                             5-pole left top connector
           C           24 VAC (common) from equipment transformer                                                         connector
          RH           24 VAC for heating stages                                              Y2    Y1    G     RC    C
                                                                                                                           RH   W1 W2
          W1           Energizes on a call for first stage heating
          W2           Energizes on a call for second stage heating               N2+
          D1           Configurable digital input
          D2           Configurable digital input                                 N2-
          RS           Remote room sensor
                                                                                  REF    5-pole bottom connector
         Scom          Sensor common
          OS           Auxiliary/Outdoor air sensor                                                       D1    D2    RS Scom OS
     N2+, N2-, REF     N2 Bus

     Y2        Y1       G      RC      C     RH        W1   W2                   D1     D2         RS    Scom    OS       N2+     N2-        REF

                                                   Heat 1 Heat 2
                                                                                                                            Metasys, CPN,
                                                                                                                                NCM
    Cool 2    Cool 1   Fan

                                                                                                                                                   TEC2103-2_Wiring
                                                                                              Remote       Auxiliary/Outdoor
                                           If using the same power source                      Room             Sensor
                 24 VAC                                                                       Sensor
             Thermostat Power              for the thermostat and heating
                                           loads, install a jumper
                                           across RC and RH.
                                      Figure 5: TEC2103-2 Thermostat Wiring Schematic

Connecting the N2 Bus                                                       N2 Device Mapping
To connect the N2 Bus:                                                      When adding the TEC2103-2 thermostat to the
                                                                            Metasys system (Person-Machine Interface [PMI] and
1. Observe the polarity when connecting the N2 Bus
                                                                            Companion system), you must define the TEC2103-2
   wires to the TEC2103-2 thermostat.
                                                                            thermostat as a Vendor Device (VND). For the NCM,
     Note: An End-of-Line (EOL) is not needed on the                        except as noted in Table 1, Footnote c, do not direct
     N2 Bus at the TEC2103-2 thermostat. However,                           map any points. Run control of these points through
     one EOL is needed at the BAS (N30, Companion,                          the Control System (CS) object. See the Setting the
     Network Control Module).                                               N2 Address (N2 addr) section to set the address for
                                                                            the thermostat.
2. Continue this process for each TEC2103-2
   thermostat using the daisy chain wiring method.

4    TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions
Table 1: N2 Bus Objects
 Point Name                           TEC Point        N30/NAE          BAS Model        Override Range
                                      Type/            Object           Point Type
                                      Address          Type
 Room Tempa                           ADI-1            N2 AI            CSAD             32 to 122°F (0 to 50°C)
 Aux Temp / Outdoor Tempa             ADI-2            N2 AI            CSAD             -40 to 122°F (-40 to 50°C)
 Heating SPa, g                       ADI-3            N2 AO            CSAD             40 to 90°F (4.5 to 32°C)
 (Occupied Heating SP)
 Cooling SPa, g                       ADI-4            N2 AO            CSAD             54 to 100°F (12 to 37.5°C)
 (Occupied Cooling SP)
 Setback Heating SPa, g               ADI-5            N2 AO            CSAD             40 to 90°F (4.5 to 32°C)
 (Unoccupied Heating SP)
 Setback Cooling SPa, g               ADI-6            N2 AO            CSAD             54 to 100°F (12 to 37.5°C)
 (Unoccupied Cooling SP)
 Minimum Heat SP                      ADI-7            N2 AI            CSAD             40°F (4.5°C)
 Maximum Heat SPa                     ADI-8            N2 AO            CSAD             40 to 90°F (4.5 to 32°C)
 Minimum Cool SPa                     ADI-9            N2 AO            CSAD             54 to 100°F (12 to 37.5°C)
 Maximum Cool SP                      ADI-10           N2 AI            CSAD             100°F (37.5°C)
 Fana                                 BD-1             N2 BO            CSBD             0 = Auto, 1 = On
 Modea                                BD-2             N2 MSOd, e       CSMS             0 = Off, 1 = Cool, 2 = Heat, 3 = Auto
 Occupancya                           BD-3             N2 BO            CSBD             0 = Unoccupied, 1 = Occupied
 W1 State                             BD-4             N2 BI            CSBD             0 = Off, 1 = On
 W2 State                             BD-5             N2 BI            CSBD             0 = Off, 1 = On
 Y1 State                             BD-6             N2 BI            CSBD             0 = Off, 1 = On
 Y2 State                             BD-7             N2 BI            CSBD             0 = Off, 1 = On
 G State – Fan                        BD-8             N2 BI            CSBD             0 = Off, 1 = On
 Temp Unitsa, c                       BD-9             N2 BO            See              0 = °C, 1 = °F
 (Local Display Only)                                                   Footnote c.
 Occupancy Override                   BD-10            N2 BI            CSBD             0 = No Override, 1 = Override
 DI1b, f                              BI-1             N2 BI            CSBI             0 = Off, 1 = On
 Temp Alarmb                          BI-2             N2 BI            CSBI             0 = Normal, 1 = Alarm
 DI2b, f                              BI-3             N2 BI            CSBI             0 = Off, 1 = On
 Notes:
 a.   Commandable.
 b.   Can be a Change-of-State (COS) alarm to the BAS or N2 Dialer Module (NDM) to initiate a dial-out.
 c.   On the Metasys NCM system, map BD9 Temp Units Mode as a Binary Output (BO) object with Auto Restore and
      Local Control set.
 d.   The Multiple Command Output (MCO) object is used to schedule multiple Multi-State Objects (MSOs).
 e.   When defining the N2 MSO object, select TEC Mode from the States Text Menu. Type 4 for the TEC2103-2
      thermostat.
 f.   The state of DI1 and DI2 is communicated over the N2 network even if the digital inputs are configured as None
      through the local interface at the thermostat.
 g.   The Heating and Cooling SP cannot be overridden simultaneously (this also applies to the Unocc Heating SP and
      Unocc Cooling SP). The overridden setpoint must be released prior to overriding the other setpoint. Additionally, if one
      setpoint is overridden, the other setpoint may be automatically adjusted by the TEC2103-2 thermostat to maintain the
      minimum deadband between the two setpoints.

                                           TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions                  5
The Controller Point Type is the fixed-point definition inside the controller. The BAS Model Point type is the definition inside
the model file. Use an NCM CS object to retrieve the data.
The most recent N2 command received by any of the N2 Bus Objects listed in Table 1 controls the thermostat.
If an AD object is overridden by the Metasys system, all local changes attempted through the thermostat keypad for that AD
object are ignored until the override is released. For example, if the Metasys system sends a write command to turn System
Mode Off, then the occupant selects System Mode On at the TEC keypad, the TEC ends up with the System Mode On;
however, if the Metasys system sends an override command to turn System Mode Off, then the occupant selects System
Mode On at the TEC keypad, the TEC keeps the System Mode Off.
Once an override is released, the AD object may once again be changed through the thermostat keypad, but the thermostat
does not retain any data entered at the TEC keypad during the override.
Only one of the setpoints (Heating Setpoint or Cooling Setpoint) can be overridden at a time.
    •    The value for Heating SP (ADI-3) and Setback Heating SP (ADI-5) must stay within the limits established in the
         controller by Minimum Heat SP (ADI-7 read-only) and Maximum Heat SP (ADI-8).
    •The value for Cooling SP (ADI-4) and Setback Cooling SP (ADI-6) must stay within the limits established in the
     controller by Minimum Cool SP (ADI-9) and Maximum Cool SP (ADI-10 read-only).
If a setpoint is overridden, the TEC, if necessary, adjusts the other setpoint to maintain the minimum 2 F° deadband
between the setpoints. The setpoints can be spread further apart but can never be adjusted closer than 2 F° apart.
Failure to stay within the limits for a command results in an N2 Negative Acknowledge (NAK) error from the TEC2103-2
thermostat.
Overrides take precedence over any local adjustment or command in the TEC2103-2.
You must not have a Relinquish Default for the setpoints if you want to change them from the thermostat display.
If there is a Relinquish Default for the setpoints, the Network Automation Engine (NAE) always has an Override for either an
Adjusted value or the Relinquish Default value. You should use Operator Override and Release Operator Override if you
want to command the setpoint and release it to local control.
Once all the NAE commands are released, the Override Status in the Hardware tab should be False. At that time, the user
should be able to change the setpoint from the local display.
All overrides are released automatically after 10 minutes of no communications (for example, network cable is removed
from the TEC causing loss of network communications).

6       TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions
Setup and Adjustments
Thermostat Operation Overview

                                                                                                           TEC_Front_Cover

                                                                Room Temp
                        Backlit, plain text, Liquid             75.0ºF
                        Crystal Display (LCD)                                     Light Emitting Diodes (LEDs)
                        is easy to read in any                                    indicate system activity.
                        condition.

                                      Five keys on the TEC210x
                                      make operation easy and intuitive.

                                        Figure 6: TEC2103-2 Thermostat Front Cover

Thermostat Interface Keys
The TEC2103-2 thermostat interface consists of
five keys on the front cover and one configuration
key (Figure 7) that are accessed by removing the
front cover. The functions of the keys are as
follows. Use the:

                                                                                                                             T600_TEC_Config_Key
•   YES/SCROLL key to:
    −   confirm menu selections, and to advance to
        the next menu item
                                                                                                       Configuration
    −   stop the Status Display Menu from scrolling                                                        Key
        and to manually scroll to the next parameter
        on the menu. When left unattended for                                  Figure 7: Configuration Key Location
        45 seconds, the display resumes scrolling.
                                                                       Backlit Liquid Crystal Display (LCD)
•   NO key when you do not desire a parameter
    change, and to advance to the next menu item                       The TEC2103-2 thermostat uses a two-line,
                                                                       eight-character backlit display. Low-level backlighting
•   MENU key to access the Main User Menu or exit                      is present during normal operation and it brightens
    the menu                                                           when any user interface key is pressed. The backlight
•   UP/DOWN arrow keys to:                                             returns to the lower level when the thermostat is left
                                                                       unattended for 45 seconds.
    −   adjust values
                                                                       Light-Emitting Diodes (LEDs)
    −   activate a Temporary Setpoint
                                                                       Three LEDs are used to indicate the status of the fan,
                                                                       call for heat, or call for cooling. When:
                                                                       •    the fan is on, the FAN LED lights up
                                                                       •    heating is on, the HEAT LED lights up
                                                                       •    cooling is on, the COOL LED lights up

                                                 TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions                              7
Programming Overview                                       Table 2: Installer Configuration Menu
There are three menus used to view, program, and
                                                                             Remove the cover and press the
configure the TEC2103-2 thermostat: Status Display,          RoomTemp        CONFIG key from the Status Display
Main User, and Installer Configuration Menus.                75.0 °F         Menu to enter the Installer
The Status Display Menu displays during normal                               Configuration Menu.
thermostat operation. The menu continually scrolls
through the following parameters.                                            Configures Digital Input 1
                                                             DI1             Default: No Function (None)
•   Room Temperature                                         set? Y/N        See the Configuring the Digital Inputs
                                                                             (DI1 and DI2) section.
•   System Mode
•   Schedule Status (Occupied/Unoccupied/Override)                           Configures Digital Input 2
                                                              DI2            Default: No Function (None)
    Note: Override displays only when in the Override         set? Y/N       See the Configuring the Digital Inputs
    mode.                                                                    (DI1 and DI2) section.
•   Auxiliary Temperature (Displays outdoor or other
                                                                             Sets Keypad Lockout Level
    auxiliary temperatures. Requires the sensor to be         Lockout        Default: No Lockout (0)
    wired to the Auxiliary/Outdoor Air Sensor terminal        set? Y/N       See the Enabling the Keypad Lockout
    OS [Figure 5]). The maximum temperature                                  (Lockout) section.
    displayed is 122°F (50°C). The actual temperature
    may be above this point.                                                 Sets Power-up Delay
                                                              Pwr del        Default: Ten Seconds (10.0 sec)
•   Applicable Alarms (the backlight lights up as an          set? Y/N       See the Setting the Power-Up Delay
    alarm condition is displayed)                                            (Pwr del) section.
To temporarily stop the scrolling, press the
YES/SCROLL key.                                                              Enables/Disables Frost Protection
                                                              Frost pr       Default: Disabled (Off)
Use the Main User Menu to access and change the               set? Y/N       See the Enabling Frost Protection
thermostat’s basic operating parameters. Access the                          (Frost pr) section.
menu by pressing the MENU key during normal
thermostat operation.                                                        Sets the Maximum Heating Setpoint
                                                              Heat max       Default: 90.0°F (32.0°C)
Use the Installer Configuration Menu to set up the            set? Y/N       See the Setting the Maximum Heating
thermostat for application specific operation. Access                        Setpoint (Heat max) section.
the menu by removing the front cover and pressing the
configuration key, labeled CONFIG (Figure 7).                                Sets the Minimum Cooling Setpoint
                                                              Cool min       Default: 54.0°F (12.0°C)
Configuring the TEC2103-2 thermostat                          set? Y/N       See the Setting the Minimum Cooling
The TEC2103-2 thermostat ships from the factory with                         Setpoint (Cool min) section.
default settings for all configurable parameters. The
default settings are shown in Table 2. To reconfigure                        Sets the Anti-Short Cycle Timer
                                                              Anticycl       Default: Two Minutes (2.0 min)
the parameters, follow the steps in this section for the      set? Y/N       See the Setting the Anti-Short Cycle
corresponding parameters. The parameters must be
                                                                             Timer (Anticycl) section.
set up first by accessing the Installer Configuration
Menu. Access the Installer Configuration Menu by                            Sets the Heating Cycles per Hour
removing the front cover and pressing the                     Heat cph      Default: Four (4.0)
configuration key (Figure 7).                                 set? Y/N      See the Setting the Maximum Heating
                                                                            Stage Cycles per Hour (Heat cph)
Exit the Installer Configuration Menu any time by                           section.
pressing the MENU key and, at the exit prompt,                              Sets the Cooling Cycles per Hour
pressing the YES key. To pass over a parameter                              Default: Four (4.0)
                                                              Cool cph
without changing it press the NO key.                         set? Y/N      See the Setting the Maximum Cooling
                                                                            Stage Cycles per Hour (Cool cph)
When the thermostat is in the Installer Configuration                       section.
Menu and left unattended for 45 seconds, it reverts to
                                                            Continued on next page . . .
the Status Display Menu.

8   TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions
                                                        Configuring the Digital Inputs (DI1 and DI2)
Table 2: Installer Configuration Menu (Cont.)
                                                        Press the configuration menu access key. The first
                Sets the Minimum Heating/Cooling        prompt is to program Digital Inputs DI1 and DI2.
  Deadband      Deadband
                Default: 2.0°F (1.1°C)                  The digital inputs display an alarm condition when the
  set? Y/N
                See the Setting the Heating/Cooling     input is closed. An alarm message is included on the
                Deadband (Deadband) section.            scrolling Status Display Menu and when the message
                Determines how the Fan Activates in     is displayed, the backlight momentarily lights up.
  Fan cont      Response to a call for Heat             Each digital input can be programmed in one of four
  set? Y/N      Default: Thermostat Controls Fan (On)   conditions.
                See the Setting the Fan Control
                (Fan cont) section.                     •   None – No function is associated with the input.
                Delays Fan Termination at Cycle’s End   •   Service – A Service alarm is displayed.
  Fan del       for 60 Seconds                          •   Filter – A Filter alarm is displayed.
  set? Y/N      Default: No Delay (Off)
                See the Setting the Fan Delay           •   RemOVR – Remote Override (OVR) contact. This
                (Fan del) section.                          disables all override menu functions of the
                                                            thermostat. The override function is now controlled
                Sets the N2 Address                         manually by a remote, momentarily closed
  N2 addr       Default: 253                                contact. When configured in this mode, the input
  set? Y/N      See the Setting the N2 Address
                                                            operates in a toggle mode. With this function
                (N2 addr) section.
                                                            enabled, it is now possible to toggle between
                Sets the Duration for Temporary             unoccupied and occupied setpoints for the amount
  TOccTime      Occupancy Time                              of time set by the temporary occupancy time
  set? Y/N      Default: Three Hours (3.0 hrs)              parameter.
                See the Establishing the Temporary
                Occupancy Time (TOccTime) section.          When override is enabled through the digital
                                                            inputs, an Override message appears in the
                Room Air Sensor Calibration (Offset)        Status Display Menu.
  Cal RS        Default: 0.0°F (0.0°C)
  set? Y/N      See the Room Air Sensor Calibration     To configure the digital inputs while in the Installer
                (Cal RS) section.                       Configuration Menu:
                Auxiliary/Outdoor Air Sensor
                                                        1. Press YES to configure Digital Input 1 or NO to
                Calibration (Offset)                         advance to Digital Input 2.
  Cal OS
  set? Y/N      Default: 0.0°F (0.0°C)                  2. Use the UP/DOWN arrow keys to locate the
                See the Auxiliary                            desired function for the Digital Input 1. Press YES
                Temperature/Outdoor Air Sensor               to select the desired function.
                Calibration (Cal OS) section.
                                                        3. Press YES to configure Digital Input 2 or NO to
                Disable/Enable Second Heating Stage          advance to the keypad lockout setup prompt.
  H Stage       Default: Two Stages
                                                        4. Use the UP/DOWN arrow keys to locate the
  set? Y/N      See the Disable/Enable Second
                Heating Stage (H Stage) section.
                                                             desired function for the Digital Input 2. Press YES
                                                             to select the desired function.
                Disable/Enable Second Cooling Stage     The display now shows the keypad lockout setup
  C Stage       Default: Two Stages                     prompt. See the Enabling the Keypad Lockout
  set? Y/N      See the Disable/Enable Second           (Lockout) section for instructions.
                Cooling Stage (C Stage) section.        Note: Regardless of the digital input configuration
                Disables Heating Operation based on     (None, Service, Filter or RemOVR) established
  H lock        Auxiliary/Outdoor Air Temperature       through the local interface at the TEC2103-2
  set? Y/N      Default: 123°F (51°C)                   thermostat, the states of DI1 and DI2 are
                See the Setting the Heating Lockout     communicated over the N2 network. This enables the
                (H lock) section.                       ability to communicate alarm conditions over the
                Disables Cooling Operation based on     network without local annunciation on the TEC2103-2
  C lock        Outdoor Air Temperature                 thermostat display.
  set? Y/N      Default: -40°F (-40°C)
                See the Setting the Cooling Lockout
                (C lock) section.

                                      TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions     9
Enabling the Keypad Lockout (Lockout)                      Enabling Frost Protection (Frost pr)
The TEC2103-2 thermostat has four levels of keypad         Frost protection establishes a minimum heating
lockout. The levels and degree of lockout are shown in     setpoint of 42°F (5.5°C) to prevent freezing in the zone
Table 3.                                                   controlled by the thermostat. If enabled, frost
To set the keypad lockout level while in the Installer     protection is activated even if the thermostat is set to
Configuration Menu:                                        the Off System Mode. If frost protection is active, it is
                                                           displayed as an alarm (Frost on with the backlight lit)
1. Answer NO to all prompts until the keypad lockout
                                                           on the Status Display Menu.
     setup prompt appears in the display. Press YES to
     enter the keypad lockout menu.                        To enable frost protection while in the Installer
2. Use the UP/DOWN arrow keys to locate the                Configuration Menu:
     desired lockout level. Press YES to select the        1. Answer NO to all prompts until the frost protection
     level.                                                   setup prompt appears in the display. Press YES to
The display now shows the power delay setup prompt.           enter the frost protection menu.
See the Setting the Power-Up Delay (Pwr del) section
for instructions.                                          2. Use the UP/DOWN arrow keys to select off or on.
                                                              Press YES to store the selection.
Table 3: Keypad Lockout Levels
                                                           The display now shows the maximum heating setpoint
 Function        Level 0       Level 1         Level 2     prompt. See the Setting the Maximum Heating
                                                           Setpoint (Heat max) section for instructions.
 Occupancy       Yes access    Yes access      No access
 Override
                                                           Setting the Maximum Heating Setpoint (Heat max)
 Temperature     Yes access    No access       No access
 Setpoints                                                 The maximum heating setpoint establishes the
 System          Yes access    Yes access      No access
                                                           maximum temperature in the heating setpoint range
 Mode Setting                                              that can be adjusted from the Main User Menu. The
                                                           parameter is adjustable from 40 to 90°F (4.5 to 32°C).
 Fan Mode        Yes access    Yes access      No access
 Setting                                                   Note: When adjusting the temperature, holding the
                                                           keys down changes the temperature by 5 F/C°
                                                           increments.
Setting the Power-Up Delay (Pwr del)
                                                           To set the maximum heating setpoint while in the
On initial power-up of the TEC2103-2 thermostat (or        Installer Configuration Menu:
each time power is removed and reapplied), there is a
delay before any operation is authorized (fan, cooling,    1. Answer NO to all prompts until the maximum
and heating). The delay time is adjustable between 10         heating setpoint prompt appears in the display.
and 120 seconds. This parameter can also be used to           Press YES to enter the maximum heating setpoint
sequence the startup of multiple units in one location.       menu.

Note: When adjusting the time with the UP/DOWN             2. Use the UP/DOWN arrow keys to adjust the
arrow keys, holding the keys down changes the time            maximum heating setpoint temperature. Press
by 10-second intervals.                                       YES to store the value.

To set the delay time while in the Installer               The display now shows the minimum cooling setpoint
Configuration Menu:                                        prompt. See the Setting the Minimum Cooling Setpoint
                                                           (Cool min) section for instructions.
1. Answer NO to all prompts until the power delay
   setup prompt appears in the display. Press YES to       Setting the Minimum Cooling Setpoint (Cool min)
   enter the power delay setup menu.
                                                           The minimum cooling setpoint establishes the
2. Use the UP/DOWN arrow keys to adjust the                minimum temperature in the cooling setpoint range
   power-up delay setting. Press YES to store the          that can be adjusted from the Main User Menu. The
   setting.                                                parameter is adjustable from 54 to 100°F
The display now shows the frost protection setup           (12 to 37.5°C).
prompt. See the Enabling Frost Protection (Frost pr)       Note: When adjusting the temperature, holding the
section for instructions.                                  keys down changes the temperature by 5 F/C°
                                                           increments.

10   TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions
To set the minimum cooling setpoint while in the            Setting the Maximum Heating Stage Cycles per
Installer Configuration Menu:                               Hour (Heat cph)
1. Answer NO to all prompts until the minimum               The heating cycles per hour establishes the maximum
   cooling setpoint prompt appears in the display.          number of times the equipment or stages are turned
   Press YES to enter the minimum cooling setpoint          on and off in one hour. The selection ranges from
   menu.                                                    three to eight cycles per hour.

2. Use the UP/DOWN arrow keys to adjust the                 Note: A higher number of heating cycles per hour
   minimum cooling setpoint temperature. Press YES          results in more accurate temperature control but could
   to store the value.                                      accelerate the wear of mechanical components in the
                                                            equipment.
The display now shows the anti-short cycle timer
prompt. See the Setting the Anti-Short Cycle Timer          To set the maximum number of heating cycles per
(Anticycl) section for instructions.                        hour while in the Installer Configuration Menu:
                                                            1. Answer NO to all prompts until the heating cycles
Setting the Anti-Short Cycle Timer (Anticycl)                  per hour prompt appears in the display. Press
The anti-short cycle timer establishes the minimum             YES to enter the heating cycles per hour menu.
on/off times for the cooling and heating stages. The
                                                            2. Use the UP/DOWN arrow keys to adjust the
timer is adjustable from 0 to 5 minutes in 1-minute
                                                               maximum number of heating cycles per hour.
increments. Set the anti-short cycling to 0 minutes for
                                                               Press YES to store the value.
equipment that possesses its own anti-short cycling
timer.                                                      The display now shows the cooling cycles per hour
                                                            setup prompt. See the Setting the Maximum Cooling
                                                            Stage Cycles per Hour (Cool cph) section for
   !      CAUTION: Risk of Property Damage.
                                                            instructions.
 Do not set the TEC2103-2 thermostat’s anti-short
 cycling timer to 0 minutes if the controlled equipment     Setting the Maximum Cooling Stage Cycles per
 is not protected by its own internal anti-short cycling    Hour (Cool cph)
 timer. Setting the anti-short cycling timer to 0           The cooling cycles per hour establishes the maximum
 minutes may result in damage to the controller.            number of times the equipment or stages are turned
                                                            on and off in one hour. The selection ranges from
 MISE EN GARDE : Risque de dégâts matériels.                three to four cycles per hour.
 Ne pas régler le temporisateur anti court-cycle de l'      Note: A higher number of cooling cycles per hour
 TEC2103-2 thermostat sur 0 minute si l'équipement          results in more accurate temperature control but could
 contrôlé n'est pas protégé par son propre                  accelerate the wear of mechanical components in the
 temporisateur anti court-cycle interne. Le réglage du      equipment.
 temporisateur anti court-cycle sur 0 minute risque
 d'endommager le régulateur.                                To set the maximum number of cooling cycles per
                                                            hour while in the Installer Configuration Menu:
To set the anti-short cycle time while in the Installer     1. Answer NO to all prompts until the cooling cycles
Configuration Menu:                                              per hour prompt appears in the display. Press
1. Answer NO to all prompts until the anti-short cycle           YES to enter the cooling cycles per hour menu.
   timer prompt appears in the display. Press YES to        2. Use the UP/DOWN arrow keys to adjust the
   enter the anti-short cycling timer menu.                      maximum number of cooling cycles per hour.
                                                                 Press YES to store the value.
2. Use the UP/DOWN arrow keys to adjust the
   minimum on/off times for the heating and cooling         The display now shows the minimum heating/cooling
   stages. Press YES to store the value.                    deadband prompt. See the Setting the
                                                            Heating/Cooling Deadband (Deadband) section for
The display now shows the heating cycles per hour           instructions.
setup prompt. See the Setting the Maximum Heating
Stage Cycles per Hour (Heat cph) section for                Setting the Heating/Cooling Deadband (Deadband)
instructions.
                                                            The heating/cooling deadband setting establishes the
                                                            minimum difference between the heating and cooling
                                                            setpoints. The range is adjustable from 2 to 4 F°
                                                            (1 to 2 C°).

                                        TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions    11
To change the minimum deadband between the                Setting the N2 Address (N2 addr)
heating and cooling setpoints while in the Installer      To adjust the N2 address (adjustable from 1 to 253)
Configuration Menu:                                       while in the Installer Configuration Menu:
1. Answer NO to all prompts until the deadband            1. Answer NO to all prompts until the setting the
     setpoint prompt appears in the display. Press YES       N2 address prompt appears in the display. Press
     to enter the deadband setpoint menu.                    YES to set the address.
2. Use the UP/DOWN arrow keys to adjust the
                                                          2. Use the UP/DOWN arrow keys to display the
     minimum deadband between the heating and
                                                             desired address. Press YES to store the address.
     cooling setpoints. Press YES to store the value.
                                                          The display now shows the temporary occupancy time
The display now shows the fan control prompt. See
                                                          prompt. See the Establishing the Temporary
the Setting the Fan Control (Fan cont) section for
                                                          Occupancy Time (TOccTime) section for instructions.
instructions.
                                                          Note: Pressing the YES and NO keys
Setting the Fan Control (Fan cont)                        simultaneously for 5 seconds on the user interface of
This parameter controls how the fan activates in          the TEC2103-2 thermostat temporarily displays the N2
response to a call for auxiliary heating.                 address of the thermostat.
When the fan is in Auto Mode (as selected on the Main     Establishing the Temporary Occupancy Time
User Menu):                                               (TOccTime)
                                                          The temporary occupancy is the length of time the
•    Selecting on enables the thermostat to control the
                                                          occupied mode setpoints are used when the override
     fan on a call for heating or cooling.
                                                          function is enabled (the override function can be
•    Selecting off enables the thermostat to energize     enabled from the Main User Menu when the
     the fan on a call for cooling only. On a call for    thermostat is in unoccupied mode or from one of
     auxiliary heating, the fan is controlled by the      the digital inputs) or a temporary setpoint is entered.
     equipment fan limit control.                         The range is adjustable from 0 to 12 hours.
To set the fan control while in the Installer             To change the temporary occupancy time while in the
Configuration Menu:                                       Installer Configuration Menu:
1. Answer NO to all prompts until the fan control         1. Answer NO to all prompts until the temporary
     prompt appears in the display. Press YES to enter        occupancy time prompt appears in the display.
     the fan control menu.                                    Press YES to enter the temporary occupancy time
                                                              menu.
2. Using the UP/DOWN arrow keys, select on or off.
     Press YES to store the selection.                    2. Use the UP/DOWN arrow keys to adjust the length
                                                              of time the temporary occupancy setpoint should
The display now shows the fan delay prompt. See the           be in effect. Press YES to store the time.
Setting the Fan Delay (Fan del) section for
instructions.                                             The display now shows the room sensor calibration
                                                          prompt. See the Room Air Sensor Calibration (Cal RS)
Setting the Fan Delay (Fan del)                           section for instructions.
The fan delay extends the fan operation by                Room Air Sensor Calibration (Cal RS)
60 seconds after the call for heating or cooling has
ended. This feature is only active when the fan is in     An offset can be added or subtracted to the actual
the Auto mode.                                            displayed room temperature as needed. The range is
                                                          ±5.0 F° (±2.5 C°), adjustable in increments of 1 F°
To enable the fan delay while in the Installer            (0.5 C°).
Configuration Menu:
                                                          To change the room sensor calibration/offset while in
1. Answer NO to all prompts until the fan delay           the Installer Configuration Menu:
   prompt appears in the display. Press YES to enter      1. Answer NO to all prompts until the room sensor
   the fan delay menu.                                         calibration prompt appears in the display. Press
2. Using the UP/DOWN arrow keys, select on or off.             YES to enter the room sensor calibration menu.
   Press YES to store the selection.                      2. Use the UP/DOWN arrow keys to adjust the
                                                               correction that should be applied to the sensor
The display now shows the N2 address prompt. See
                                                               reading. Press YES to store the offset.
the Setting the N2 Address (N2 addr) section for
instructions.                                             The display now shows the auxiliary
                                                          temperature/outdoor air sensor calibration prompt.

12   TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions
See the Auxiliary Temperature/Outdoor Air Sensor         Setting the Heating Lockout (H lock)
Calibration (Cal OS) section for instructions.           This feature disables heating operation based on
Auxiliary Temperature/Outdoor Air Sensor                 auxiliary or outdoor air temperature (requires
Calibration (Cal OS)                                     temperature sensor to be connected to the
                                                         Auxiliary/Outdoor Air Sensor terminal OS for the
An offset can be added or subtracted to the actual
                                                         function to be enabled). If the outdoor air temperature
displayed auxiliary/outdoor air temperature as needed.
                                                         is above the heating lockout temperature, heating
The range is ±5.0 F° (±2.5 C°), adjustable in            operation is disabled.
increments of 1 F° (0.5 C°).
To change the sensor calibration/offset while in the     The heating lockout temperature parameter is
Installer Configuration Menu:                            adjustable from -15 to 123°F (-26 to 51°C) in
                                                         increments of 5 F/C°.
1. Answer NO to all prompts until the
    auxiliary/outdoor sensor calibration prompt
    appears in the display. Press YES to enter the        IMPORTANT:          Setting the heating lockout to
    auxiliary/outdoor sensor calibration menu.            123°F (51°C) disables the heating lockout feature.
2. Use the UP/DOWN arrow keys to adjust the
                                                         If this parameter is being set at 123°F (51°C) to
    correction that should be applied to the sensor
                                                         monitor discharge air temperature or temperatures
    reading. Press YES to store the offset.
                                                         above 122°F (50°C), note that the maximum
The display now shows the heating stage setting          temperature displayed for auxiliary temperature during
prompt. See the Disable/Enable Second Heating            operation is 122°F (50°C). The actual temperature
Stage (H Stage) section for instructions.                may be above this point.

Disable/Enable Second Heating Stage (H Stage)            To change the auxiliary/outdoor air temperature
                                                         heating lockout while in the Installer Configuration
This parameter reverts the operation of two stage
                                                         Menu:
thermostats to a single stage when the second heating
stage is not needed.                                     1. Answer NO to all prompts until the heating lockout
To enable or disable the second heating stage while in      prompt appears in the display. Press YES to enter
the Installer Configuration Menu:                           the heating lockout menu.
1. Answer NO to all prompts until the setting heating    2. Use the UP/DOWN arrow keys to adjust the
     stages prompt appears in the display. Press YES        lockout temperature. Press YES to store the value.
     to enter the setting heating stages menu.
                                                         The display now shows the cooling lockout prompt.
2. Using the UP/DOWN arrow keys; select 1.0 or 2.0       See the Setting the Cooling Lockout (C lock) section
   stages. Press YES to store the selection.             for instructions.
The display now shows the cooling stage setting
                                                         Setting the Cooling Lockout (C lock)
prompt. See the Disable/Enable Second Cooling
Stage (C Stage) section for instructions.                This feature disables cooling operation based on
                                                         outdoor air temperature (requires outdoor air
Disable/Enable Second Cooling Stage (C Stage)            temperature sensor to be connected for the function to
                                                         be enabled). If the outdoor air temperature is below
This parameter reverts the operation of two-stage
                                                         the cooling lockout temperature, cooling operation is
thermostats to a single stage when the second cooling
                                                         disabled.
stage is not needed.
To enable or disable the second cooling stage while in   The cooling lockout temperature parameter is
the Installer Configuration Menu:                        adjustable from -40 to 95°F (-40 to 35°C) in
1. Answer NO to all prompts until the setting cooling    increments of 5 F/C°.
     stages prompt appears in the display. Press YES     To change the outdoor air temperature cooling lockout
     to enter the setting cooling stages menu.           while in the Installer Configuration Menu:
2. Using the UP/DOWN arrow keys; select 1.0 or 2.0       1. Answer NO to all prompts until the cooling lockout
   stages. Press YES to store the selection.                prompt appears in the display. Press YES to enter
The display now shows the heating lockout prompt.           the cooling lockout menu.
See the Setting the Heating Lockout (H lock) section     2. Use the UP/DOWN arrow keys to adjust the
for instructions.                                           lockout temperature. Press YES to store the value.

                                     TEC2103-2 Networked Multi-Stage Thermostat Installation Instructions       13
3. The exit menu appears. Press YES to exit the             Resuming the Programmed Schedule (only
   Installer Configuration Menu or press NO to return       appears when in the Override Mode)
   to the beginning of the menu (digital input              To resume the schedule while in the Main User Menu:
   configuration).
                                                            1.   Answer NO to all prompts until the Resume
Operation                                                        Schedule prompt appears. If the thermostat is in
                                                                 the override state, this is the first prompt.
Programming/Operating the TEC2103-2                         2.   Press YES to resume the programmed schedule.
Thermostat
                                                            The TEC2103-2 thermostat returns to the Status
Once the TEC2103-2 thermostat is configured through
                                                            Display Menu.
the Installer Configuration Menu, the thermostat’s
operating parameters can be programmed through the
Main User Menu (access the Main User Menu by                Entering Permanent Temperature Setpoints
pressing the MENU key during normal thermostat              The first prompt appearing in the Main User Menu of
operation). The Main User Menu contains the basic           the TEC2103-2 thermostat is to set the permanent
operating features of the TEC2103-2 thermostat. The         temperature setpoints. Permanent setpoints are
Main User Menu uses Auto Help. When there is a              permanently stored in the programmed schedule.
pause in programming activity, Auto Help                    To enter the permanent heating and cooling setpoints
automatically appears in the Main User Menu. To exit        for the occupied and unoccupied modes, follow the
Auto Help, continue with the Programming selection.         steps in Table 4. When changing the temperat