Текст документа
24- 4034- 204, Rev. C
Installation Instructions TE-6300P Wall Mount
Issue Date March 2016
TE-6300P Series Wall Mount Temperature Sensors
Applications
North American Emissions Compliance Dimensions
IMPORTANT: The TE-6300P Series Wall
Mount Temperature Sensor is intended to provide an
input to equipment under normal operating
conditions. Where failure or malfunction of the
TE-6300P ii01.cdr
sensor could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or Figure 1: Sensor Dimensions, in. (mm)
protect against failure or malfunction of the sensor.
Accessories
IMPORTANT: Le TE-6300P Series Wall Mount To mount the TE-6300P Series Wall Mount Sensor to
Temperature Sensor est destiné à transmettre des an electrical box, order the TE-1800-9600 Mounting
données entrantes à un équipement dans des Hardware. To order a different cover for the wall mount
conditions normales de fonctionnement. Lorsqu'une sensor, refer to the TE-6300 Series Temperature
défaillance ou un dysfonctionnement du sensor Sensors Product Bulletin (LIT-216320).
risque de provoquer des blessures ou
d'endommager l'équipement contrôlé ou un autre Mounting
équipement, la conception du système de contrôle
doit intégrer des dispositifs de protection Location Considerations
supplémentaires. Veiller dans ce cas à intégrer de Consider the following mounting location guidelines:
façon permanente d'autres dispositifs, tels que des • Avoid areas subject to excessive vibration,
systèmes de supervision ou d'alarme, ou des electrical noise, direct sunlight, or the effects of
dispositifs de sécurité ou de limitation, ayant une radiant heat.
fonction d'avertissement ou de protection en cas de
défaillance ou de dysfonctionnement du sensor. • Keep electrical wiring as short as possible to
minimize temperature error.
Mounting the Temperature Sensor
See Figure 2 and mount the temperature sensor as
Installation follows:
IMPORTANT: Do not install the TE-6300P 1. Loosen the socket-head screws on each side of
Series Wall Mount Temperature Sensor in ambient the unit with a 0.62 in. hex key and remove the
temperatures beyond the specified -50 to 122°F cover.
(-46 to 50°C) temperature range. Installing the 2. Drill the optional 5/16 in. (8 mm) hole only if using
temperature sensor in ambient temperatures beyond the drywall anchors provided; then insert the
this range may damage the unit and void the anchors into the holes.
warranty.
3. Mount the base plate to the wall using the screws
provided.
4. Wire the sensor to the controller wire with the wire
nuts provided.
© 2016 Johnson Controls, Inc. 1
Part No. 24-4034-204, Rev. C www.johnsoncontrols.com
5. Reposition the cover and tighten the retention screws.
6. Install the optional faceplate (vertical mount only). Table 1: Lead Wiring (22 AWG, 6 in.) Color Code
Sensor Type Lead Color
1k ohm Nickel White
1k ohm Platinum White with blue stripe
2.2k ohm Thermistor Red
!
TE-6300P ii02.cdr
CAUTION: Risk of Property Damage.
Do not apply power to the system before checking
all wiring connections. Short circuited or improperly
connected wires may result in permanent damage to
Figure 2: Installing the Wall Mount Sensor the equipment.
Wiring MISE EN GARDE: Risque de dégâts matériels.
For 1k ohm nickel temperature sensors, wire Ne pas mettre le système sous tension avant d'avoir
resistance can cause approximately 1F° (0.56C°) of vérifié tous les raccords de câblage. Des fils formant
error for every 250 ft (76 m) run of 18 AWG wire, or un court-circuit ou connectés de façon incorrecte
every 100 ft (31 m) run of 22 AWG wire. For 1k ohm risquent d'endommager irrémédiablement
platinum temperature sensors, can cause l'équipement.
approximately 1F° (0.56C°) of error for every 150 ft
(46 m) run of 18 AWG wire, or every 50 ft (15 m) run of
22 AWG wire. To minimize error due to field wiring,
limit the total resistance of all nickel temperature IMPORTANT: Make all wiring connections in
sensor wiring to 3 ohms, and all platinum temperature accordance with local, national, and regional
sensor wiring to 2 ohms. regulations.
The 2k ohm thermistor applications permit wiring to be
quite long before wire resistance adds significantly to Repair Information
total resistance measured at the controller. As a For a replacement device, refer to the TE-6300 Series
general rule, a 150 ft (46 m) two-wire 18 AWG run Temperature Sensors Product Bulletin (LIT-216320) and
contributes 2 ohms of error, or less than 1F° (0.56C°) contact the nearest Johnson Controls® representative.
error over the sensor operating temperature range.
See the appropriate controller documentation for
recommended sensor wiring. See Table 1 for an
explanation of the lead wiring color convention.
2 TE-6300P Series Wall Mount Temperature Sensors Installation Instructions
Technical Specifications
Product TE-6300P Series Wall Mount Temperature Sensors
Models TE-6314P-1: Thin-Film Nickel Temperature Sensor
TE-6324P-1: Thin-Film Platinum Temperature Sensor
TE-6344P-1: NTC Thermistor Temperature Sensor
Sensor Reference Nickel: 1k ohms at 70°F (21°C)
Resistance Platinum: 1k ohms at 32°F (0°C)
Thermistor: 2,252 ohms at 77°F (25°C)
Sensor Accuracy Nickel: ±0.34F° at 70°F (±0.19C° at 21°C)
Platinum: ±0.73F° at 70°F (±0.41C° at 21°C), DIN Class B
Thermistor: ±0.36F° (±0.2C°) in the range: 32 to 158°F (0 to 70°C)
Sensor Temperature Nickel: Approximately 3 ohms/F° (5.4 ohms/C°)
Coefficient Platinum: Approximately 2 ohms/F° (3.9 ohms/ C°)
Thermistor: Nonlinear, Negative Temperature Coefficient (NTC)
Materials Base Plate: Galvanized Steel
Cover: Rigid Thermoplastic, White
Face Plate: Brushed Aluminum
Operating Conditions Temperature -50 to 122°F (-46 to 50°C)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS
WESTENDHOF 3 507 E MICHIGAN ST C/O CONTROLS PRODUCT
45143 ESSEN MILWAUKEE WI 53202 MANAGEMENT
GERMANY USA NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
TE-6300P Series Wall Mount Temperature Sensors Installation Instructions 3Позиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.