TE-6300 Series Temperature Sensors
Product Bulletin
Code No. LIT-216320
Issued February 2017
Introduction Figure 1: TE-6300 Series Temperature Sensors
The TE-6300 Temperature Sensor line provides
economical solutions for a wide variety of temperature
sensing needs, including wall-mount, outdoor-air, duct,
strap-mount, well-insertion, duct-averaging, and VAV
Modular Assembly (VMA) flange-mount duct-probe
applications. The TE-6300 line offers both a metal and
a plastic enclosure for the most popular models.
Sensors are available in the following types:
• 1k ohm thin-film nickel
• 1k ohm nickel averaging
• 1k ohm thin-film platinum
• 100 ohm platinum equivalent averaging
• Models with a Stainless Steel Sensor Probe—
• 1k ohm platinum equivalent averaging Protect the sensor while increasing corrosion
• 2.2k (2,252) ohm thermistor resistance.
• 10k ohm thermistor, Johnson Controls® Type II • Metal Enclosure (TE-63xxE, TE-63xxM, and
TE-63xxV Models)—Meets plenum requirements.
Features and Benefits
• Models Featuring a Retainer for the Sensor
Each sensor is packaged with the necessary mounting Holder—Allow you to lock the sensor holder into
accessories to maximize ordering and installation ease the conduit box.
and to reduce both commissioning time and cost.
• Brushed Stainless Steel Mounting Plate—Offers
• Full Line of Versatile Sensors—Supports all your a durable, aesthetically pleasing design.
temperature sensing needs from a single supplier:
wall-mount, outdoor-air, duct, duct-averaging, • Low Profile Flush Mount Design (TE-63xxF
strap-mount, well-insertion, and flange-mount duct- Models)—Provides a tamper-proof installation
probe. ideally suited for schools, sporting complexes,
retailers, prisons, and more.
• Single Assembly Ordering—Simplifies ordering;
provides a complete assembly in one box.
• Models Featuring an Integral National Pipe
Thread (NPT) Adaptor—Increase sensor
connection strength, which eliminates the need for
a special adaptor.
TE-6300 Series Temperature Sensors Product Bulletin
1
Product Overview All TE-6300 Series Temperature Sensors are two-wire,
passive, resistance-output devices.
IMPORTANT: The TE-6300 Series Temperature
Sensors are intended to provide an input to
TE-63xxA Models
equipment under normal operating conditions. The TE-63xxA (adjustable length) models:
Where failure or malfunction of the temperature • provide a thermoplastic mounting flange and gland
sensor could lead to personal injury or property nut to adjust the length of the probe
damage to the controlled equipment or other
property, additional precautions must be designed • include two hex-head self-drilling screws for
into the control system. Incorporate and maintain mounting
other devices, such as supervisory or alarm systems • come equipped with a 10 ft (3 m)
or safety or limit controls, intended to warn of or plenum-rated cable with 1/4 in. (6.35 mm) internal
protect against failure or malfunction of the thread insulated quick-connect terminations on
temperature sensor. leads
IMPORTANT : Le TE-6300 Series Temperature TE-63xxE Models
Sensors est destiné à transmettre des données
The TE-63xxE (economizer mount) models:
entrantes à un équipement dans des conditions
normales de fonctionnement. Lorsqu'une défaillance • provide a stainless steel mounting flange
ou un dysfonctionnement du temperature sensor
• include two hex-head self-drilling screws for
risque de provoquer des blessures ou
mounting
d'endommager l'équipement contrôlé ou un autre
équipement, la conception du système de contrôle • meet UL 1995 plenum use requirements
doit intégrer des dispositifs de protection
supplémentaires. Veiller dans ce cas à intégrer de
TE-63xxF Models
façon permanente d'autres dispositifs, tels que des The TE-63xxF (flush mount) models:
systèmes de supervision ou d'alarme, ou des • provide a low profile when installed in an electrical
dispositifs de sécurité ou de limitation, ayant une box
fonction d'avertissement ou de protection en cas de
défaillance ou de dysfonctionnement du temperature • thermally isolate sensor from the wall with a foam
sensor. pad
• offer a rugged stainless steel cover
• provide 22 AWG (0.6 mm diameter) lead wires with
low voltage installation
TE-6300 Series Temperature Sensors Product Bulletin
2
TE-63xxM Models TE-63x4P Wall Mount Models
The TE-63xxM (metal enclosure) models: The TE-63x4P (plastic enclosure) models:
• come with a corrosion-protected steel enclosure • come with a white thermoplastic ventilated cover
with a 0.88 in. (22 mm) hole for a 1/2 in. (12.7 mm) with a brushed aluminum face plate and a steel
conduit fitting mounting plate for surface mounting
• include two hex-head self-drilling screws for • include faceplates for both horizontal and vertical
mounting the duct and duct-averaging models mounting
• offer either a direct-mount or 1/2-14 NPT threaded • offer an accessory mounting kit for mounting to a
well sensor holder for mounting in TE-6300W standard electrical box
Series Thermowells (well models; order the
• offer optional covers
thermowell separately)
• provide optional well sensor holders (order
TE-63xS Models
separately) to mount duct models in thermowells The TE-63xS (strap-mount) models:
• meet UL 1995 plenum use requirements • provide a 1/4 in. (6.35 mm) diameter stainless steel
probe without an enclosure
• offer an optional accessory kit (order separately) to
replace plastic hole plug and wiring bushing to • include three cable ties for mounting to pipe up to
meet International Mechanical Code (IMC) 2-5/8 in. (67 mm) in diameter
requirements • come equipped with a 10 ft (3 m) plenum-rated
TE-63xxP Models cable
The TE-63xxP (plastic enclosure) models: • meet UL 1995 plenum use requirements
• provide a thermoplastic conduit box with 1/2-14 • offer an accessory mounting kit for mounting to a
internal NPT for connecting to conduit pipe up to 11 in. (280 mm) in diameter
• provide aluminum mounting plate and 1/2-14 TE-63xxV Models
internal NPT hub mounting options for the duct and The TE-63xxV (VAV flange mount) models:
duct-averaging models
• provide a stainless steel mounting flange with two
• use the 1/2-14 internal NPT to mount the outdoor hex-head self-drilling mounting screws
air models directly to rigid conduit
• come equipped with a 10 ft (3 m) plenum-rated
• include sensor holders to mount duct models in cable with 1/4 in. (6.35 mm) internal thread
thermowells (order thermowell separately) insulated quick-connect terminations on leads
• offer an optional accessory metal cover and gasket • meet UL 1995 plenum use requirements
kit (order separately) to replace the plastic cover to
meet UL 1995 plenum use requirements
• include a replaceable sensing probe on
duct-probe, outdoor-air, and well-insertion models
TE-6300 Series Temperature Sensors Product Bulletin
3
Additional Product Information Note: Figure 2 shows 1k ohm platinum sensor
See Figure 2 for nickel and platinum sensor characteristics. For 100 ohm platinum sensor
Resistance/Temperature (R/T) response characteristics, divide the resistance value by 10.
characteristics. See Table 1 for all sensor See Figure 3 for 2.2k and 10k ohm thermistor sensor
Temperature/Resistance values. R/T response characteristics.
Figure 2: Nickel and Platinum Temperature Response
1500
1400
1300 Platinum
1200
Resistance, ohms
1100
1000
900
800
Nickel
700
FIG:temp
600
-50 -20 10 40 70 100 130 160 190 220
(-46) (-29) (-12) (4) (21) (38) (54) (71) (88) (104)
Figure 3: Thermistor Temperature Response
1M
100k 10k ohm
Resistance, ohms
10k
1k
2.2k ohm
100
FIG: therm
10
-50 -20 10 40 70 100 123 160 190 220
(-46) (-29) (-12) (4) (21) (38) (54) (71) (88) (104)
Temperature °F (°C)
TE-6300 Series Temperature Sensors Product Bulletin
4
Table 1: Nominal Values for: Nickel (Ni), Platinum Applications
(Pt)1, and Thermistor Sensors
Averaging Sensing
Temperature Resistance (ohms)
Series-parallel wiring arrangements of four (2 x 2), nine
F C 1k Ni 1k Pt1 Thermistor (3 x 3), sixteen (4 x 4), or more sensors provide an
2.2k 10k average temperature reading in an area or large duct
-50 -46 674 821 109,905 489,981 when one sensor cannot provide a representative
reading. (See Figure 4.)
-40 -40 699 843 75,487 366,185
-30 -34 725 865 52,584 233,990 A series-parallel arrangement requires the same
number of parallel-connected sensors as there are
-20 -29 751 887 37,123 165,085
series-connected sensors. For example:
-10 -23 777 908 26,544 117,978
• with four sensors, connect two parallel legs with
0 -18 803 930 19,210 85,349
two sensors in series in each leg
10 -12 830 952 14,063 62,464
• with nine sensors, connect three parallel legs with
20 -7 858 974 10,408 46,221
three sensors in series in each leg
30 -1 885 996 7,783 34,562
All sensors in a series-parallel network must be of the
40 4 914 1,017 5,879 26,103
same sensor type and value. For example, use all
50 10 942 1,039 4,482 19,903 100 ohm platinum or all 1k ohm nickel sensors.
60 16 971 1,061 3,449 15,313
Figure 4: Nine-Sensor Series-Parallel Wiring
70 21 1,000 1,082 2,676 11,883
80 27 1,030 1,104 2,094 9,298
90 32 1,060 1,125 1,651 7,333
100 38 1,090 1,147 1,312 5,827
110 43 1,121 1,168 1,050 4,663
120 49 1,152 1,190 846 3,757
130 54 1,184 1,211 686 3,048
140 60 1,216 1,232 560 2,488
FIG: wrng
150 66 1,248 1,254 460 2,043
160 71 1,281 1,275 380 1,687
170 77 1,314 1,296 315 1,401
180 82 1,348 1,317 263 1,170
190 88 1,382 1,339 221 982
200 93 1,417 1,360 186 828
210 99 1,452 1,381 158 701
220 104 1,487 1,402 134 597
1. For 100 ohm platinum sensors, divide resistance values
by 10.
TE-6300 Series Temperature Sensors Product Bulletin
5
Figure 5 through Figure 8 illustrate installation of
sensor holders and well adaptors.
Figure 5: Installing the TE-63xAP-1 Figure 7: Installing the TE-63x2P-1
Sensor Holder Sensor Holder
Figure 6: Installing the TE-63xAM-1 Figure 8: Installing the TE-63x2M-1
Well Adaptor Well Adaptor
FIG: install
FIG: install
TE-6300 Series Temperature Sensors Product Bulletin
6
Table 2: TE-6300 Series Temperature Sensor Applications (Part 1 of 2)
Application Nominal Sensor Type Application Notes
Probe
Length,
in. (mm)
Duct Probe 2 (51) 1k ohm thin-film • Ideal in freezer lockers or for mounting outside of the sensed area.
4 (102) nickel • Available with plastic enclosure, metal enclosure, flange mount, or with
6 (152) 1k ohm thin-film mounting bracket for adjustable length.
8 (203) platinum • Use TE-63xxE, TE-63xxM, or TE-63xxV models for plenum applications.
12 (305) 2.2k ohm thermistor • Use TE-6300-613 Accessory Kit with TE-63xxM models to meet
18 (457) 10k ohm thermistor IMC requirements.
type II • Use TE-6001-13 Metal Cover and Gasket Kit with TE-63xxP models to
meet UL 1995 plenum requirements.
• Order an optional TE-63xxP model accessory: 12 in. (300 mm) probe.
Duct- 8 ft 1k ohm nickel wire • Use to sense duct temperature where stratification can occur, such as
Averaging (2.4 m) 100 ohm platinum mixed air ducts.
Element 10 ft (3 m) equivalent wire • Duct-averaging models come in three styles: plastic enclosure, metal
17 ft 1k ohm platinum enclosure, or flange mount.
(5.2 m) equivalent wire • Use about 1 ft (0.3 m) of sensor per sq ft (0.09 m2) of duct cross section.
20 ft • Use a series-parallel sensor network to cover larger ducts.
(6.1 m) • Use a TE-6001-8 Element Holder (recommended) when installing an
averaging sensor in a duct.
• Use TE-63xxM or TE-63xxV models for plenum-rated applications.
• Use TE-6300-613 kit with TE-63xxM models to meet IMC requirements.
• Use the TE-6001-13 Metal Cover and Gasket Kit with TE-63xxP models
to meet UL 1995 plenum requirements.
Outdoor Air 3 (76) 1k ohm thin-film nickel • Use to sense outside ambient temperature to determine efficient heating
1k ohm thin-film and cooling strategies.
platinum • Mount the sensor out of direct sunlight and away from exhaust vents or
2.2k ohm thermistor equipment that can cause inaccurate temperature sensing.
10k ohm thermistor,
type II
Strap- 3 (76) 1k ohm thin-film • Clamp the probe directly to a pipe or the device to be sensed.
Mount nickel • Mount the probe away from fans or radiant heat that can affect
1k ohm thin-film measurement of the sensed device.
platinum • Use for plenum applications.
10k ohm thermistor, • Order an accessory mounting kit or use readily available hardware for
type II pipe up to 11 in. (280 mm) in diameter.
Wall Mount N/A 1k ohm thin-film • Use to sense room or space temperature.
nickel • Order an accessory cover with a thermometer or to match the style of
1k ohm thin-film existing installations.
platinum • Mount the sensor on an inside wall, out of direct sunlight and away from
2.2k ohm thermistor radiant heat.
Wall Plate N/A Flush mount 1k ohm • Do not install the flush mount sensor in temperatures beyond 0 to 40°C.
Flush nickel sensor • Use copper conductors only. Refer to installation diagrams for
Mount Flush mount 1k ohm recommended wiring lengths.
platinum sensor
Flush mount 10k ohm
NTC sensor
TE-6300 Series Temperature Sensors Product Bulletin
7
Table 2: TE-6300 Series Temperature Sensor Applications (Part 2 of 2)
Application Nominal Sensor Type Application Notes
Probe
Length,
in. (mm)
Well 6 (152) TE-63xxM • Metal enclosure.
Insertion 8 (203) 1k ohm thin-film • Mount the thermowell at an angle so condensation runs out of the well. If
Probe nickel not possible, seal the well adaptor and wiring end of the sensor probe with
1k ohm thin-film (room temperature vulcanization) RTV silicone sealant.
platinum • Use TE-63xxM models to meet UL 1995 plenum use applications.
2.2k ohm thermistor • No separate well adaptor to order when using recommended thermowell
10k ohm thermistor and sensor model combinations.
type II • Threaded sensor holder has 1/2-14 NPT threads; threadless holder
accommodates set screw-type wells.
• Order TE-63x2M-1, which includes a 1/2-14 NPT adaptor for
TE-6300W-110, or retrofit applications of WZ-1000-2 and WZ-1000-4
Thermowells.
• Order TE-63xAM-2 for use with direct-mount thermowells TE-6300W-101
and TE-6300W-102.
• Order TE-63xAM-1, which includes a threadless adaptor for retrofit
applications of TE-6300W-103 and WZ-1000-5 Thermowells.
• Order compatible thermowells using Table 4 and Table 5.
TE-63xxP • Plastic enclosure.
1k ohm thin-film • Mount the thermowell at an angle so condensation runs out of the well. If
nickel not possible, seal the sensor holder and the wiring end of the sensor
1k ohm thin-film probe with RTV silicone sealant.
platinum • Use TE-6001-13 Metal Cover and Gasket Kit with TE-63xxP models to
2.2k ohm thermistor meet UL 1995 plenum requirements.
• Use the accessory 12 in. (305 mm) probe with the TE-63xxP Sensor in
longer wells.
• No separate well adaptor to order when using recommended thermowell
and sensor model combinations.
• Threaded sensor holder has 1/2-14 NPT threads; threadless holder
accommodates set screw-type wells.
• Order TE-63x2P-1, which includes a 1/2-14 NPT adaptor for
TE-6300W-110, or retrofit applications of WZ-1000-2 and WZ-1000-4
Thermowells.
• Order TE-63xAP-1, which includes a threadless adaptor for
TE-6300W-103 or retrofit applications of WZ-1000-5 Thermowells.
• Order compatible thermowells using Table 4 and Table 6.
TE-6300 Series Temperature Sensors Product Bulletin
8
Ordering Information Note: Use the TE-63xxE, TE-63xxM, or TE-63xxV
model to meet plenum requirements where UL1995
To order a TE-6300 Series Temperature Sensor,
rating is accepted, or replace the existing plastic cover
contact the nearest Johnson Controls representative.
on the TE-63xxP models with the TE-6001-13 Metal
Specify the desired sensor product code number from
Cover and Gasket Kit.
Table 3 and accessories from Table 4, depending on
the model. Use the TE-63xxM model and a TE-6300-613
Accessory Kit to replace the plastic bushing to meet
International Mechanical Code (IMC) requirements.
Figure 9: Ordering Template
TE—63 x x x —
9
Sensor Type Probe Style Enclosure Type
Application
FIG: order_temp
Note: Not all possible combinations are available. See Table 3 for available models.
TE-6300 Series Temperature Sensors Product Bulletin
9
Table 3: Product Ordering (Part 1 of 2)
Sensor Mounting Style Probe Length, in. (mm) Product Code Number
Nickel (1k ohm) Adjustable 8 (203) TE-6311A-1
1
Averaging 8 ft (2.4 m) TE-6315M-1
TE-6315P-1
TE-6315V-2
17 ft (5.2 m) TE-6316M-1
TE-6316P-1
TE-6316V-2
Duct 4 (102) TE-631GM-1
8 (203) TE-6311M-1
TE-6311P-1
18 (457) TE-631JM-1
Flange (VAV) 4 (102) TE-631GV-2
8 (203) TE-6311V-2
Flush N/A TE-6310F-0
TE-6310F-1
Outdoor air 3 (76) TE-6313P-1
Strap-mount 3 (76) TE-631S-1
Wall2 N/A TE-6314P-1
Well 6 (152) TE-631AM-13
TE-631AM-2
TE-631AP-1
8 (203) TE-6312M-1
TE-6312P-1
Platinum (1k ohm) Adjustable 8 (203) TE-6351A-1
Duct 4 (102) TE-635GM-1
8 (203) TE-6351M-1
TE-6351P-1
18 (457) TE-635JM-1
Flange (VAV) 4 (102) TE-635GV-2
8 (203) TE-6351V-2
Flush N/A TE-6350F-0
TE-6350F-1
Outdoor air 3 (76) TE-6353P-1
Strap-mount 3 (76) TE-635S-1
2
Wall N/A TE-6324P-1
Well 6 (152) TE-635AM-13
TE-635AM-2
TE-635AP-1
8 (203) TE-6352M-1
TE-6352P-1
TE-6300 Series Temperature Sensors Product Bulletin
10
Table 3: Product Ordering (Part 2 of 2)
Sensor Mounting Style Probe Length, in. (mm) Product Code Number
Platinum Equivalent 1k ohm 10 ft (3 m) TE-6327P-1
averaging1
20 ft (6.1 m) TE-6328P-1
100 ohm 10 ft (3 m) TE-6337P-1
averaging1
20 ft (6.1 m) TE-6338P-1
Thermistor Adjustable 8 (203) TE-6341A-1
(2.2k ohm)
Duct 8 (203) TE-6341P-1
Flange (VAV) 4 (102) TE-634GV-2
8 (203) TE-6341V-2
Outdoor air 3 (76) TE-6343P-1
Wall2 N/A TE-6344P-1
Well 6 (152) TE-634AM-2
8 (203) TE-6342M-1
Thermistor Adjustable 8 (203) TE-6361A-1
(10k ohm)
Duct 4 (102) TE-636GM-1
Type II
8 (203) TE-6361M-1
TE-6361P-1
18 (457) TE-636JM-1
Flange (VAV) 4 (102) TE-636GV-2
8 (203) TE-6361V-2
Flange (economizer) 2 (51) TE-6369E-2
6 (152) TE-636ME-2
8 (203) TE-6361E-2
12 (305) TE-636NE-2
Flush N/A TE-6360F-0
TE-6360F-1
Outdoor air 3 (76) TE-6363P-1
Strap-mount 3 (76) TE-636S-1
Well 6 (152) TE-636AM-13
TE-636AM-2
8 (203) TE-6362M-1
1. Two TE-6001-8 Element Holders come with the platinum equivalent averaging sensors. Order separately to use with a nickel
averaging sensor.
2. Order the TE-1800-9600 Mounting Hardware separately to mount the wall unit to a wallbox.
3. TE-631AM-1, TE-635AM-1, and TE-636AM-1 include TE-6300-612 Threadless Brass Sensor Holder/Well Adaptor for retrofit
to TE-6300W-103 or WZ-1000-5 Thermowells.
TE-6300 Series Temperature Sensors Product Bulletin
11
Table 4: Optional Accessories and Replacement Parts1
Product Code Number Description
F-1000-182 Thermal conductive grease for element wells (8 oz. [0.23 kg])
T-4000-119 Allen head tool for wall mount cover screws (order in multiples of 30)
TE-1800-9600 Mounting hardware for mounting the wall-mount unit to a wall box
TE-6001-8 Averaging sensor mounting bracket (order in multiples of ten)
TE-6001-13 Metal cover and gasket kit (order in multiples of five)
TE-6300-101 12 in. (305 mm) 1k ohm nickel probe (cut to an appropriate length)2
TE-6300-103 1/2-14 NPT plastic sensor holder without retainer (order in multiples of ten)
TE-6300-105 12 in. (305 mm) 1k ohm platinum Class A probe (cut to an appropriate length)2
TE-6300-601 8 in. (203 mm) 1k ohm nickel probe
TE-6300-603 3 in. (76 mm) 1k ohm nickel probe
TE-6300-605 1/2-14 NPT threaded plastic sensor holder/well adaptor with retainer
(order in multiples of ten)
TE-6300-606 8 in. (203 mm) 2.2k ohm thermistor probe
TE-6300-607 3 in. (76 mm) 2.2k ohm thermistor probe
TE-6300-611 1/2-14 NPT threaded brass sensor holder/well adaptor (order in multiples of ten)
TE-6300-612 Threadless brass sensor holder/well adaptor (order in multiples of ten)
TE-6300-613 IMC kit with metal plugs and clamp connector (order in multiples of ten)
TE-6300-614 Cable tie mounting kit, 0.50 to 2.625 in. (12.7 to 66.7 mm) bundle diameter
(order in multiples of ten)
TE-6300-615 Cable tie mounting kit, 11 in. (280 mm) maximum bundle diameter
TE-6300-616 8 in. (203 mm) 1k ohm platinum Class A probe
TE-6300-617 3 in. (76 mm) 1k ohm platinum Class A probe
TQ-6000-1 4 to 20 mA output transmitter for use with the 100 ohm platinum sensor
TE-6300W-1013 Thermowell, brass with copper bulb, 2.38 in. (60.5 mm) immersion depth, with thermal
grease, direct mount, no adaptor required, for use with 6 in. (150 mm) probe model
TE-63xAM-2
TE-6300W-1023 Thermowell, stainless steel, 2.38 in. (60.5 mm) immersion depth, without thermal
grease, direct mount, no adaptor required, for use with 6 in. (150 mm) probe model
TE-63xAM-2
TE-6300W-103 Thermowell, brass with copper bulb, 2.38 in. (60.5 mm) immersion depth, with thermal
grease, threadless adaptor required, for use with 6 in. (150 mm) probe models
TE-63xAM-1 (adaptor included) and TE-63xAP-1 (adaptor included)
TE-6300W-110 Thermowell, stainless steel, 4.50 in. (114.3 mm) immersion depth, without thermal
grease, 1/2-14 NPT adaptor required, for use with 8 in. (200 mm) probe models
TE-63x2M-1 (adaptor included) and TE-63x2P-1 (adaptor included)
1. For accessory usage, see Table 5, Table 6, and Table 7.
2. Cut 12 in. (305 mm) probes to a minimum of 3 in. (76 mm).
3. Direct-mount thermowells TE-6300W-101 and TE-6300W-102 can be used only with the TE-6300M Sensors.
TE-6300 Series Temperature Sensors Product Bulletin
12
Table 5: Typical Accessory and Replacement Part Usage for TE-6300M Models
Product Description TE-6311M-1
TE-6312M-1
TE-6315M-1
TE-6316M-1
Code TE-631AM-1
TE-631AM-2
TE-631GM-1
Number
TE-631JM-1
TE-6351M-1
TE-6352M-1
TE-635AM-2
TE-635GM-1
TE-635JM-1
TE-6361M-1
TE-6362M-1
TE-636AM-2
TE-636GM-1
TE-636JM-1
TE-634AM-2
TE-6001-8 Averaging sensor mounting bracket X X
TE-6300-611 1/2-14 NPT threaded brass sensor X X X
holder/well adaptor, for use with
TE-6300W-110 (replacement part,
included with TE-63x2M-1)
TE-6300-612 Threadless brass sensor holder/well X X X X X
adaptor, for use with TE-6300W-103
(included with TE-631AM-1)
TE-6300-613 IMC kit with metal plugs and clamp X X X X X X X X X X X X X X X X X X X
connector
TE-6300W-101 Thermowell, brass with copper bulb, X X X X
2.38 in. (60.5 mm) immersion depth,
with thermal grease, direct mount, no
adaptor required, for use with 6 in. (150
mm) probe
TE-6300W-102 Thermowell, stainless steel, 2.38 in. X X X X
(60.5 mm) immersion depth, without
thermal grease, direct mount, no
adaptor required, for use with 6 in. (150
mm) probe
TE-6300W-103 Thermowell, brass with copper bulb, X
2.38 in. (60.5 mm) immersion depth,
with thermal grease, threadless adaptor
required, for use with 6 in. (150 mm)
probe (TE-631AM-1 includes adaptor)
TE-6300W-110 Thermowell, stainless steel, 4.50 in. X X X
(114.3 mm) immersion depth, without
thermal grease, 1/2-14 NPT adaptor
required, for use with 8 in. (200 mm)
probe (TE-63x2M-1 includes adaptor)
TE-6300 Series Temperature Sensors Product Bulletin
13
Table 6: Typical Accessory and Replacement Part Usage for TE-6300P Models
Product Code Description TE-6311P-1
TE-6312P-1
TE-6313P-1
TE-6314P-1
Number TE-6315P-1
TE-6316P-1
TE-631AP-1
TE-6324P-1
TE-6327P-1
TE-6328P-1
TE-6337P-1
TE-6338P-1
TE-6341P-1
TE-6343P-1
TE-6344P-1
TE-6351P-1
TE-6352P-1
TE-6353P-1
TE-635AP-1
TE-6361P-1
TE-6363P-1
T-4000-119 Allen head tool X X X
TE-1800-9600 Mounting hardware X X X
TE-6001-8 Averaging sensor mounting bracket X X X X X X
TE-6001-13 Metal cover and gasket kit X X X X X X X X X X X X X X X X X X
TE-6300-101 12 in. (305 mm) 1k ohm nickel probe X
TE-6300-105 12 in. (305 mm) 1k ohm platinum Class A X
probe
TE-6300-601 8 in. (203 mm) 1k ohm nickel probe X
TE-6300-603 3 in. (76 mm) 1k ohm nickel probe X
TE-6300-605 1/2-14 NPT threaded plastic sensor holder/ X X X X X X X X X X X X
well adaptor with retainer, for use with
TE-6300W-110 (replacement part, included
with TE-63xxP-1)
TE-6300-606 8 in. (203 mm) 2.2k ohm thermistor probe X
TE-6300-607 3 in. (76 mm) 2.2k ohm thermistor probe X
TE-6300-616 8 in. (203 mm) 1k ohm platinum Class A X
probe
TE-6300-617 3 in. (76 mm) 1k ohm platinum Class A probe X
TQ-6000-1 4 to 20 mA output transmitter X X
Thermowells
F-1000-182 Thermal conductive grease (8 oz. [0.23 kg]) X X X X
TE-6300W-103 Thermowell, brass with copper bulb, 2.38 in. X X
(60.5 mm) immersion depth, with thermal
grease, threadless adaptor required, for use
with 6 in. (150 mm) probe (TE-63xAP-1
includes adaptor)
TE-6300W-110 Thermowell, stainless steel, 4.50 in. (114.3 X X
mm) immersion depth, without thermal
grease, 1/2-14 NPT adaptor required, for use
with 8 in. (200 mm) probe (TE-63x2P-1
includes adaptor)
TE-6300 Series Temperature Sensors Product Bulletin
14
Table 7: Typical Accessory and Replacement Part Usage for TE-63xS Models
Product Code Number Description
F-1000-182 Thermal conductive grease for element wells (8 oz. [0.23 kg])
TE-6300-614 Cable tie mounting kit, 0.50 to 2.625 in. (12.7 to 66.7 mm) bundle diameter (order in multiples
of ten)
TE-6300-615 Cable tie mounting kit, 11 in. (280 mm) maximum bundle diameter
Table 8: T-4000 Covers Available for the Wall-Mount TE-63x4P Series
Product Code Horizontal Vertical Thermometer, Faceplate/Cover Color
Number Johnson Controls Johnson Controls with °F/°C Scale
Logo Logo
T-4000-21381 Brushed aluminum/beige
T-4000-2139 X
T-4000-2140 X X
T-4000-2144 X
T-4000-2639 X Brown and gold/beige
T-4000-2640 X X
T-4000-2644 X
T-4000-3139 X Brushed aluminum/white
T-4000-3140 X X
T-4000-3144 X
1. Without Johnson Controls logo
. Repair Information
If the TE-6300 Series Temperature Sensor fails to
operate within its specifications, replace the unit. For a
replacement temperature sensor, see Table 3 and
contact the nearest Johnson Controls representative.
For a replacement sensor probe for TE-63xxP duct,
well, and outdoor-air models, see Table 4.
TE-6300 Series Temperature Sensors Product Bulletin
15
Technical Specifications
TE-6300 Series Temperature Sensors (Part 1 of 3)
Sensor 1k ohm nickel 1k ohms at 70F (21C)
Reference
1k ohm nickel averaging
Resistance
1k ohm platinum 1k ohms at 32°F (0°C)
100 ohm platinum averaging 100 ohms at 32°F (0°C)
1k ohm platinum averaging 1k ohms at 32F (0C)
2.2k ohm thermistor 2,252 ohms at 77F (25C)
10k ohm thermistor 10.0k ohms at 77°F (25°C)
Sensor 1k ohm nickel ±0.34F° at 70°F (±0.19C° at 21°C)
Accuracy
1k ohm nickel averaging ±3.4F° at 70°F (±1.9C° at 21°C)
1k ohm platinum Class A EN 60751 Class A, ± [0.15 + 0.002 * | T °C |], ±0.19C° at 21°C (±0.35F° at
(TE-635xx) 70°F)
100 ohm platinum Class A
1k ohm platinum Class B EN 60751 Class B, ± [0.30 + 0.005 * | T °C |], ±0.41C° at 21°C (±0.73F° at
(TE-632xx) 70°F)
100 ohm platinum averaging ±1.0F°at 70°F (±0.58C° at 21°C)
1k ohm platinum averaging
2.2k ohm thermistor ±0.36F° (±0.2C°) in the range: 32 to 158°F (0 to 70°C)
10k ohm thermistor ±0.9F° (±0.5C°) in the range: 32 to 158°F (0 to 70°C)
Sensor 1k ohm nickel Approximately 3 ohms/F° (5.4 ohms/C°)
Temperature
1k ohm nickel averaging
Coefficient
(see Table 1) 1k ohm platinum Approximately 2 ohms/F° (3.9 ohms/C°), 3,850 ppm/K
100 ohm platinum averaging Approximately 0.2 ohms/F (0.39 ohms/C)
1k ohm platinum averaging Approximately 2 ohms/F (3.9 ohms/C)
2.2k ohm thermistor Nonlinear, negative temperature coefficient (NTC)
10k ohm thermistor Nonlinear NTC, Johnson Controls Type II
Electrical TE-63xxE 22 AWG (0.6 mm diameter) x 6 in. (152 mm) long
Connection
TE-63xxM
TE-63xxP
TE-63xxF 22 AWG (0.6 mm diameter) x 12 ft (3 m) braided copper wires, low voltage
insulation, half-stripped ends
TE-63xxP nickel averaging 18 AWG (1.0 mm diameter) x 6 in. (152 mm) long
TE-63xS 22 AWG (0.6 mm diameter) x 10 ft (3 m) long plenum-rated cable
TE-63xxA 22 AWG (0.6 mm diameter) x 10 ft (3 m) long plenum-rated cable, with
2-position plug terminal block for 1/4 in. (6.35 mm) external tab terminals
TE-63xxV
on 0.197 in. (5 mm) centers
TE-6300 Series Temperature Sensors Product Bulletin
16
TE-6300 Series Temperature Sensors (Part 2 of 3)
Materials Probes Nickel averaging: 0.094 in. (2.4 mm) outside diameter (O.D.)
copper tubing
Nickel averaging adaptor: 0.25 in. (6.35 mm) O.D. brass
Platinum averaging probe: 0.19 in. (4.8 mm) aluminum tubing
All others: 0.25 in. (6.35 mm) O.D. stainless steel
TE-63xxA Mounting adaptor plate
and gland: thermoplastic
TE-63xxF Flush mount: stainless steel
TE-63xxM Enclosure: corrosion-protected steel
Well sensor holder: 0.875 in. (22.2 mm) hex brass
TE-63xxP Conduit box and shield: rigid thermoplastic
Mounting plate: aluminum
Sensor holder: rigid thermoplastic
Wall mount base plate: corrosion-protected steel
Wall mount cover: rigid thermoplastic (white)
Wall mount face plate: brushed aluminum
TE-63xxE Mounting flange: stainless steel
TE-63xxV
Operating TE-63xxA -50 to 140°F (-46 to 60°C)
Conditions
TE-63xxF 32 to 104°F (0 to 40°C)
TE-63xxE -50 to 220°F (-46 to 104°C)
TE-63xxM
TE-63xxP Enclosure: -50 to 122°F (-46 to 50°C)
Sensor probe: -50 to 220°F (-46 to 104°C)
TE-63xS Sensor probe: -50 to 220°F (-46 to 104°C)
TE-63xxV Wire harness: -50 to 122°F (-46 to 50°C)
Shipping TE-63xxA 0.2 lb (0.09 kg)
Weight
TE-63xxE
TE-63xxF 0.25 lb (113.4 kg)
TE-63xxM Duct averaging: 0.9 lb (0.41 kg)
Duct mount: 0.4 lb (0.18 kg)
Well insertion: 0.5 lb (0.23 kg)
TE-63xxP Duct averaging: 0.5 lb (0.23 kg)
Duct mount: 0.4 lb (0.18 kg)
Outdoor air: 0.5 lb (0.23 kg)
Wall mount: 0.2 lb (0.09 kg)
Well insertion: 0.35 lb (0.16 kg)
TE-63xS Strap mount: 0.2 lb (0.09 kg)
TE-63xxV Duct averaging: 0.7 lb (0.32 kg)
Duct mount: 0.2 lb (0.09 kg)
TE-6300 Series Temperature Sensors Product Bulletin
17
TE-6300 Series Temperature Sensors (Part 3 of 3)
Dimensions TE-63xxA 2.17 in. (55 mm) diameter plus 4 or 8 in.
(H x W x D) (102 or 203 mm) element
TE-63xxE Duct mount: 2.5 x 1.50 in. (57 x 38 mm) plus 2, 6,
8, or 12 in. (51, 152, 203, or 305 mm)
element
TE-63xxF Flush mount: 4-1/2 x 2-3/4 in. (114 x 70 mm)
TE-63xxM Duct averaging: 1.87 x 1.87 x 1.80 in.
(47.5 x 47.5 x 45.8 mm) plus 8 or 17 ft
(2.4 or 5.2 m) element
Duct mount: 1.87 x 1.87 x 1.80 in.
(47.5 x 47.5 x 45.8 mm) plus 4, 8, or 18 in.
(102, 203, or 457 mm) element
Well insertion: 1.87 x 1.87 x 1.80 in.
(47.5 x 47.5 x 45.8 mm) plus 6 or 8 in.
(152 or 203 mm) element
TE-63xxP Duct averaging: 5.97 x 1.38 x 2.75 in. (152 x 35 x 70 mm)
plus 8, 10, 17, or 20 ft (2.4, 3.0, 5.2, or 6.1 m)
element
Duct mount: 5.97 x 1.38 x 2.75 in. (152 x 35 x 70 mm)
plus 6 or 8 in. (152 or 203 mm) probe
Outdoor air: 5.97 x 3.47 x 4.46 in. (152 x 88 x 113 mm)
Wall mount: 2.09 x 3.12 x 1.80 in. (53 x 79 x 46 mm)
Well insertion: 5.97 x 1.38 x 2.75 in. (152 x 35 x 70 mm)
plus 6 or 8 in. (152 or 203 mm) probe