*24403434E*
24-4034-34, Rev. E
Product/Technical Bulletin TE-6001
Issue Date September 2017
TE-6001 Hardware Assemblies
for TE-6000 Temperature Elements
TE-6001-2
TE-6001 Hardware Assemblies are used with
TE-6000 Temperature Elements in a wide variety of
TE-6001-3
applications. Hardware and elements are ordered
separately and field assembled, depending on the TE-6001-1
application. Refer to TE-6000 Temperature Sensing TE-6001-11
Elements Product Bulletin for a description of available
temperature sensors and TE-6100 Series Temperature
Sensors and Completed Sensor/Hardware Assemblies
Product/Technical Bulletin for available factory
assembled units.
TE-6001-6
TE-6001-4 TE-6001-7
Figure 1: TE-6001 Hardware Assemblies
Features and Benefits
Ease of Mounting Some assemblies include plastic clips that
TE-6000 temperature elements snap easily into
Standard All Metal Meets code requirements for metal
Construction electrical boxes
Identical Replacements for Permits maintenance of consistent installation
Many Existing Installations appearance
TE-6001 Hardware Assemblies for TE-6000 Temperature Elements
Product/Technical Bulletin
Code No. LIT-216300
1
A pplications
TE-6001-1 TE-6001-2
The TE-6001-1 Duct Temperature Element Holder is The TE-6001-2 is a metal housing used with a
used with TE-6000 elements in duct insertion TE-6000 Temperature Element in applications
applications. The TE-6001-1 is designed to hold requiring outside air temperature sensing. A factory
one or two temperature sensors. A handi-box is mounted plastic clip is provided to hold the TE-6000
supplied with the element holder. sensor in place.
1-5/16
33
9-3/16
233
4-3/16 7/8
106 22
1-5/16
2-3/16 1-1/4 33
55 32
Figure 2: TE-6001-1 Duct Insertion Element Holder 4-1/2
with Handi-box Dimensions (in./mm) 114
Figure 4: TE-6001-2 Dimensions (in./mm)
Knockout for
1/2 in. Conduit
(Top and Bottom)
TE-6001-3
13/16
20.5 The TE-6001-3 Handi-box (includes packing nut and
fittings) is used with WZ-1000-2, -4, and -5
1-3/32 Immersion Wells to house TE-6000 elements in well
27.5 Knockouts for
2-3/16 insertion applications.
1/2 in. Conduit 2-1/8
55 (Both Sides)
1-1/16 54 1
13/16
27 25.4
17/32 20.5
13.5 1-3/8 1/2 14 NPT
17/32 35 13
13.5
13/16 13/16
20.5 20.5 6-1/2
1/2
1-1/16 165
13
27
13/16 13/16 5-1/8
20.5 20.5 130
4-3/16
106
1/4 Holes (4)
6
5/8
Figure 3: TE-6001-1 and -3 Dimensions (in./mm) 16
Figure 5: WZ-1000-2 and -4
Dimensions (in./mm)
2 TE-6001 Hardware Assemblies for TE-6000 Temperature Elements Product/Technical Bulletin
7/8
22
Table 1: T-4000 Plastic Covers for
TE-6001-4 Assemblies
2-5/16
59 Product
Code Description
4-11/16
119 1/2 in.
Number
14 NPT Horizontal
T-4000-2139 without Setpoint Window or
19/64 Thermometer, with Johnson Controls
2-3/8
7.5 Logo, Silver Faceplate
60
T-4000-2140 without Setpoint Window, with F/C
Thermometer and Johnson Controls
3/8
9.5
Logo, Silver Faceplate
T-4000-2639 Concealed Setpoint, without
Figure 6: WZ-1000-5 Dimensions (in./mm) Thermometer, with Johnson Controls
Logo, Gold Faceplate
TE-6001-4 T-4000-2640 Concealed Setpoint, with
Thermometer and Johnson Controls
The TE-6001-4 Temperature Element Holder is used Logo, Gold Faceplate
with TE-6000 sensors in room temperature sensing
Horizontal or Vertical
applications. The TE-6001-4 can hold up to
two temperature sensors. A mounting bracket and T-4000-2138 without Setpoint Window,
wallplate adaptor are supplied. Thermometer, or Johnson Controls
Logo, Silver Faceplate
Note: A T-4000 cover is required and must be Vertical
ordered separately. (See Table 1 for
T-4000-2144 without Setpoint Window or
ordering information.) Thermometer, with Johnson Controls
1/16 in. Logo, Silver Faceplate
Allen-head Screw
(Each Side)
TE-6001-5
The TE-6001-5 Dew Point Sensor Kit is used to seal
a TE-6000 1000 ohm sensor inside a Foxboro 2761
2-3/32 2-3/4
53
Dewcel. The kit consists of a packing nut adaptor,
70
packing gland, washer, and packing nut.
3-1/8 TE-6001-6
79 1-13/16 1/8
Clearance: Allow 46 3 TE-6001-6 Adhesive Mounting Pads are used to attach
3-1/2 in. (89 mm) each TE-6000 sensors to T-4100 and T-4110 Pneumatic
side for cover screw Room Thermostats. This provides a means of
removal with
T-4000 Allen wrench.
electronic temperature indication. (See Figure 1.)
4-1/2
114 TE-6001-7
Figure 7: TE-6001-4 Dimensions (in./mm) TE-6001-7 Mounting Clips are used to attach
TE-6000 sensors to single setpoint T-4002 and
T-4003 thermostats, H-4100 humidistats, and
H-5100 humidity transmitters. This provides a
means of electronic temperature indication on
pneumatic room devices. (See Figure 1.)
TE-6001 Hardware Assemblies for TE-6000 Temperature Elements Product/Technical Bulletin 3
TE-6001-8
The TE-6001-8 Mounting Bracket is used with
1 3/4
TE-6100 and TE-6300 averaging sensors to 19
maintain the minimum bend radius recommended for 1/2 25
13
these sensors. It mounts to ductwork with a single
1/2
sheet metal screw. 13
1
25
1-1/2
1/2 38
13
3/4
19
1-1/2
38
Figure 10: Hole Pattern for Installation
of TE-6001 -1 and -11 (in./mm)
TE-6001-961 and -962
The TE-6001-961 Momentary Pushbutton Switch is
designed for use with the C210A-1 VAV Controller or
Figure 8: TE-6001-8 Dimensions (in./mm) the C260A-1 Heat Pump Controller.
The TE-6001-962 Maintained Toggle Switch is used
TE-6001-11 with either networked or standalone controllers to
place the zone controller in the occupied mode. The
The TE-6001-11 Duct Temperature Element Holder TE-6001-962 is wired directly to the unoccupied
is used with TE-6000 sensors. It has a rigid terminal on the controller.
aluminum support that extends in the duct to hold
one or two TE-6000 temperature sensing elements. TE-6001-961 and -962 switches are used with either
the TE-6100-960 or TE-6100-961 room temperature
sensing assemblies, which must be ordered separately.
M ounting
TE-6001-1 and -11
The TE-6001-1 and -11 assemblies should be
Figure 9: TE-6001-11 Dimensions (in./mm) attached to ducts with No. 6 sheet metal screws.
Both assemblies have factory mounted plastic clips
that TE-6000 temperature elements easily snap into.
Route element leads through the bracket opening.
TE-6001-2
The TE-6001-2 should be mounted where the effects
of sunlight and radiant heat are minimal. The
housing is threaded to fit 1/2 inch rigid conduit.
Seal-off fittings must be used to prevent
condensation on the element or in the housing.
4 TE-6001 Hardware Assemblies for TE-6000 Temperature Elements Product/Technical Bulletin
TE-6001-3
The TE-6001-3 packing nut and fittings are used with
WZ-1000-2 and -5 wells. These wells are factory
filled with thermal compound for maximum
conductivity.
IMPORTANT: To prevent condensation of
1/2 in. NPS
moisture in the well and failure of Handi-box
Star Nut
the element, apply plumber’s (Screw tight
against Adaptor
putty or some other suitable
thread relief
sealant (such as silicon rubber on adaptor.)
sealant) around the packing nut
adaptor as well as the point Grey Spacer
where the two sensor leads pass
through the adaptor.
TE-6000
Note: See Figures 11 and 12 for proper positioning Temperature
of the TE-6000 sensor. Sensor
Set Screws
(Tighten onto
mating groove
Packing Nut in adaptor.)
Immersion Well
Washer WZ-1000-5
Figure 12: TE-6001-3 and WZ-1000-5 Assembly
Packing Gland Packing Nut (with TE-6000 Sensor)
Adaptor
TE-6001-4
Mount the TE-6001-4 assembly on a wall where air
is free to circulate around the elements, but away
from nonrepresentative air conditions such as drafts
or heat radiation. Mount the assembly 5 to 6 feet
TE-6000
Sensor (1.5 to 1.8 m) above the floor on a standard electrical
Handi-box
wallbox. Two factory mounted plastic clips are
Spanner Nut
provided to hold the TE-6000 elements. Route
(Screw tight against element leads through the bracket opening. (See
thread relief on Figure 13.)
packing nut adaptor.) Well Assembly
WZ-1000-2 or -4
Figure 11: TE-6001-3 and WZ-1000-2, -4 Assembly
(with TE-6000 Sensor)
TE-6001 Hardware Assemblies for TE-6000 Temperature Elements Product/Technical Bulletin 5
No. 6-32 x 1/4 in.
Flat-head Screws*
TE-6001-4 Element
Holder with
TE-6000 Element Conduit Box
Mounting Bracket*
T-4000
Cover
Wallplate Adaptor*
No. 6-32 x 7/8 in.
Pan-head Screws* *Supplied with TE-6001-4
Figure 13: TE-6001-4 Assembly Mounting Detail
! ! CAUTION: Danger de Dégâts d'Equipement.
CAUTION: Equipment Danger Hazard
Ne pas insérer immédiatement le capteur TE-6000
Do not immediately insert the TE-6000 sensor
dans l'élément Dewcel. Les températures dans la
into the Dewcel element. Temperatures in the
cavité de dewcel peuvent initialement s'élever au-
dewcel cavity may initially rise above the upper
dessus de la limite de température ambiante
ambient temperature limit of the TE-6000
supérieure de la capteur TE-6000, 250 ° F (121 ° C),
sensor, 250 ° F (121 ° C),as the Dewcel
car le Dewcel tente d'atteindre la température
attempts to reach equilibrium temperature.
d'équilibre.
TE-6000-100
Temperature Sensor
TE-6001-5
To install the TE-6001-5 Dew Point Sensor Kit:
Packing Nut Adaptor*
1. Moisten the Dewcel element with lithium chloride Packing Gland*
salt upon initial installation or after washing of Washer*
Dewcel Element
the element. Packing Nut*
2. Install the Dewcel in the duct, connect to *All are part of
TE-6000 kit.
VQ-5000 power supply, and wait at least
20 minutes for the Dewcel to stabilize.
White Leads
3. Install the TE-6000 sensor as shown in of TE-6000 Power Supply
Figure 14. Leads
Figure 14: TE-6001-5 Foxboro Dewcel Assembly
6 TE-6001 Hardware Assemblies for TE-6000 Temperature Elements Product/Technical Bulletin
! CAUTION: Equipment Damage Hazard ! CAUTION: Danger de Dégâts d'Equipement.
Check all wiring connections before applying power Vérifiez toutes les connexions de câblage avant
to the system.Short circuited or improperly d'alimenter le système. Les fils à court-circuit ou
connected wires will result in permanent damage to incorrectement connectés entraîneront un
the equipment. endommagement permanent de l'équipement.
IMPORTANT IMPORTANT
Make all wiring connecgtions in accordance with the Effectuez toutes les connexions de câblage
National Electrical Code and all electrical regulations. conformément au Code national de l'électricité et à
toutes les réglementations locales.
TE-6001-6
TE-6001-961 and -962
A TE-6001-6 Adhesive Mounting Pad is used to
attach a TE-6000 sensor to a T-4100 thermostat. The TE-6001-961 and -962 are furnished with a
When mounting, make certain that the sensor does No. 6-32 x 1/8 in. pan-head screw for mounting the
not restrict the setpoint adjustment. switches to the TE-6100-960 or -961. (See
Figure 15 for proper positioning of the TE-6001-961
On T-4110 thermostats, affix the sensor on the
and -962.) Depressing the pushbutton on the
mounting plate or on the aspirator cover if an
TE-6001-961 connects blue to white/yellow.
aspirator is used.
Pushing the TE-6001-962 toggle switch to the right
TE-6001-7 (front view) connects white/yellow to blue, and
pushing the switch to the left connects blue to
The TE-6001-7 Mounting Clips snap onto a white/orange.
pneumatic controller on the side opposite the dial (on
side opposite test point for H-5100). (See Figure 1.)
Pull the TE-6000 element leads around the side of
the instrument and through the mounting bracket The TE-6001-961 (shown)
opening. If a terminal connector is used on the or TE-6001-962 Switch Kit for use No. 6-32 x 1/4 in.
Flat-head Screws
with TE-6100-960 and -961
mounting bracket, route the leads through the slot at has to be ordered separately.
the bottom of the connector or through the unused
hole of the connector if a 3-pipe controller is not
used. If a wallbox is used, the leads may also be run
through a spare hole in the bracket itself. Room
Conduit Box
Sensing Element
Assembly
Mounting Bracket
TE-6001-8 T-4000
Cover
Wallplate Adaptor
Attach the TE-6001-8 Mounting Bracket to ducts with
a No. 6 sheet metal screw. (See Figure 8.)
No. 6-32 x 7/8 in.
Pan-head Screws
Figure 15: TE-6100-960 and -961 Mounting Detail
TE-6001 Hardware Assemblies for TE-6000 Temperature Elements Product/Technical Bulletin 7
Table 2: Dewcel to Dew Point Table 3: Models
Temperatures TE-6001- Description
Dewcel Resistance Dew Point
1 Duct Temperature Element Holder
Temperature (ohms) Temperature
with Handi-box
°F °C °F °C 2 Housing for Outside Air Temperature
Sensing Element
93 34 1069 30 -1
3 Handi-box, Packing Nut, and Fittings
99 37 1087 35 2
for Use with WZ-1000 Wells
106 41 1108 40 4
4 Single/Dual Element Holder for TE-6000
112 44 1127 45 7 Elements in Room Temperature Sensing
119 48 1149 50 10 Applications
127 53 1174 55 13 5 Dew Point Sensor Kit
134 57 1196 60 16 6 Ten Adhesive Mounting Pads for Use with
T-4100, T-4110
141 61 1219 65 18
149 65 1245 70 21
7 Ten Clips for Use with T-4002/4003 and
H-4100/5100
156 69 1268 75 24
8 Mounting Bracket for Use with TE-6100 and
163 73 1291 80 27 TE-6300 Averaging Sensors
171 77 1318 85 29 11 Duct Temperature Element Holder
179 82 1345 90 32 (Less Handi-box)
188 87 1375 95 35 961 Momentary Pushbutton Switch
196 91 1403 100 38 962 Maintained Toggle Switch
Specifications
Product TE-6001 Hardware Assemblies for TE-6000 Temperature Elements
Shipping Weight TE-6001-1: 1.3 lb (0.590 kg); TE-6001-2: 0.5 lb (0.227 kg)
TE-6001-3: 1.0 lb (0.454 kg); TE-6001-4: 0.5 lb (0.227 kg)
TE-6001-5: 0.3 lb (0.136 kg); TE-6001-6: 0.2 lb (0.091 kg)
TE-6001-7: 0.2 lb (0.091 kg); TE-6001-8: 0.8 lb (0.363 kg)
TE-6001-11: 0.7 lb (0.318 kg); TE-6001-961: 0.5 lb (0.227 kg)
TE-6001-962: 0.2 lb (0.091 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications,
consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS
WESTENDHOF 3 507 E MICHIGAN ST C/O CONTROLS PRODUCT
45143 ESSEN MILWAUKEE WI 53202 MANAGEMENT
GERMANY USA NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
Building Technologies & Solutions
507 E. Michigan Street
Milwaukee, WI 53202 Published in U.S.A.
8 TE-6001 Hardware Assemblies for TE-6000 Temperature Elements Product/Technical BulletinПозиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.