Installation Instructions
                                                                                       Issue Date December 9, 2003

                      T600MSP-1 Programmable Thermostat

Application
The T600MSP-1 is a multi-stage programmable                  To install the thermostat:
thermostat that provides exceptional accuracy through
                                                             1. Remove the security screw on the bottom of the
the use of a unique Proportional-Integral (PI) time
                                                                thermostat cover using a Phillips-head
proportioning algorithm. The algorithm virtually
                                                                screwdriver. Open the thermostat by pulling on the
eliminates temperature offset associated with
                                                                bottom side of the thermostat cover (Figure 1).
traditional, differential-based on/off thermostats. The
T600MSP-1 also uses an adaptive control logic                2. Unlock the Printed Circuit Board (PCB) by
algorithm to control the space temperature during               carefully pressing the locking tab to the right
recovery to minimize overshoot while providing                  (Figure 2). Open the thermostat’s PCB to the left.
maximum comfort. Additionally, the menu driven
backlit display, plain text menus, and five keys on the      3. Pull out approximately 6 in. (152 mm) of wires
T600MSP-1 make operating the thermostat easy and                from the wall and insert the cable through the hole
                                                                in the base.
intuitive.
                                                             4. Align the base on the wall, and using the base as
Installation                                                    a template, mark the location of the two mounting
                                                                holes on the wall. Confirm the thermostat base is
Location Considerations                                         installed with the proper side up.
Locate the T600MSP-1 thermostat:                             5. Use the supplied anchors and screws for mounting
•   on a partitioning interior wall, and approximately          on drywall or plaster. Drill two 3/16 in. (4.7 mm)
    5 ft. (1.5 m) above the floor in a location of              holes at the marked locations and tap nylon
    average temperature                                         anchors flush to wall surface (Figure 3).

•   away from direct sunlight, radiant heat, outside         6. Position base on the wall, insert screws through
    walls, behind doors, air discharge grills, stairwells,      mounting base, and fasten into wall anchors. Do
    or outside doors                                            not overtighten screws.

•   away from steam or water pipes, warm air stacks,         7. Swing the thermostat PCB back to the right to
    unheated/uncooled areas, or sources of electrical           close. Gently press on the PCB to secure each of
    interference                                                the locking tabs.
                                                             8. Pull out the screw terminal blocks using the
                                                                pull-tabs on each connector (Figure 4).
                                                             Note: The number of terminals on the terminal
                                                             blocks varies depending on the T600 model.

                                                              IMPORTANT:            Use this T600MSP-1
                                                              programmable thermostat only as an operating
                                                              control. Where failure or malfunction of the
                                                              T600MSP-1 could lead to personal injury or property
                                                              damage to the controlled equipment or other
                                                              property, additional precautions must be designed
                                                              into the system. Incorporate and maintain other
                                                              devices such as supervisory or alarm systems or
                                                              safety or limit controls intended to warn of, or protect
                                                              against, failure or malfunction of the T600MSP-1.

© 2003 Johnson Controls, Inc.                                                                                            1
  Part No. 24-9889-29, Rev. A                                                                    www.johnsoncontrols.com
     Figure 1: Removing the Thermostat Cover

                                                              Figure 4: Removing the Terminal Blocks

                                                       Wiring

                                                          !    CAUTION: Risk of Electrical Shock.
                                                        Disconnect power supply before making electrical
                                                        connections to avoid electrical shock.
                                            PCB
                                        Locking Tabs

                                                       Note: When replacing an existing thermostat,
                                                       remove and label wires to identify terminal
                                                       designations. When replacing a T600MSP-1
                                                       thermostat, simply remove the terminal blocks and
                                                       reinsert on to the new thermostat.
      Figure 2: Opening the Thermostat PCB             To wire the thermostat:
                                                       1. Strip each wire 1/4 in. (6.35 mm) and connect to
                                                          the appropriate terminal according to the wiring
                                                          diagram (Figure 5).
                                                       2. Gently push excess wire back into wall, plug the
                                                          wall hole with fireproof material to prevent drafts
                                                          from affecting ambient temperature readings, and
                                                          install screw terminal blocks back onto the PCB.
                                                       3. Reattach the thermostat cover to the installed
                                                          base (top side first) and install the security screw
                                                          on the bottom.

                                                          !      CAUTION: Risk of Property Damage.
                                                        Do not apply power to the system before checking
     Figure 3: Mounting the Thermostat Base             all wiring connections. Short circuited or improperly
                                                        connected wires may result in permanent damage to
                                                        the equipment.

2   T600MSP-1 Programmable Thermostat Installation Instructions
          Terminal                            Function
            Y1        Energizes on a call for first stage cooling
            Y2        Energizes on a call for second stage cooling
            G         Energizes fan in accordance with the selected fan mode
            RC        24 VAC from equipment transformer                                                                   3 pole right top
                                                                                            5 pole left top connector
             C        24 VAC (common) from equipment transformer                                                          connector
            RH        24 VAC for heating stages                                              Y2    Y1    G     RC     C
                                                                                                                           RH   W1 W2
            W1        Energizes on a call for first stage heating
            W2        Energizes on a call for second stage heating
            AU        Configurable auxiliary output
            D1        Configurable digital input
            D2        Configurable digital input
                                                                                        6 pole bottom connector
            RS        Remote room sensor
           Scom       Sensor common                                                                AU    D1 D2        RS Scom OS
            OS        Outdoor air sensor

     Y2        Y1      G      RC       C      RH      W1      W2            AU    D1   D2         RS    Scom     OS

                                                     Heat 1 Heat 2
                                                                            Aux
    Cool 2   Cool 1   Fan

                                                                                             Remote            Remote
                                           If using the same power source                     Room             Outdoor
                 24 VAC                                                                      Sensor
                                           for the thermostat and heating                                      Sensor
             Thermostat Power
                                           loads, install a jumper
                                           across RC and RH.
                                           Figure 5: T600MSP-1 Wiring Schematic

Setup and Adjustments
Thermostat Operation Overview

                                                                     Room Temp
                             Backlit, plain text, Liquid             75.0ºF
                             Crystal Display (LCD)                                      Light Emitting Diodes (LEDs)
                             is easy to read in any                                     indicate system activity.
                             condition.

                                           Five keys on the T600
                                           make operation easy
                                           and intuitive.

                                                     Figure 6: T600MSP-1 Front Cover

                                                           T600MSP-1 Programmable Thermostat Installation Instructions                       3
Thermostat Interface Keys                                   Programming Overview
The T600MSP-1 interface consists of five keys on            There are three menus used to view, program, and
the front cover and one configuration key                   configure the T600MSP-1 thermostat: Status Display,
(Figure 7) that is accessed by removing the front           Main User, and Installer Configuration Menus.
cover. Use the:
                                                            The Status Display Menu is displayed during normal
•   YES key to confirm a selection and move onto the        thermostat operation. The menu continually scrolls
    next menu item                                          through the following parameters:
•   NO key when you do not desire a parameter               •   Room Temperature
    change, and to advance to the next menu item
                                                            •   Day and Time
•   MENU key to access the Main User Menu or exit
    the menu                                                •   System Mode

•   down arrow key to scroll through menu selections        •   Schedule Status (Occupied/Unoccupied)
    or adjust values                                        •   Outdoor Temperature (providing sensor is
•   up arrow/SCROLL key to:                                     connected and functional)

    −   scroll through menu selections or adjust            •   Applicable Alarms (the backlight lights up as an
        values                                                  alarm condition is displayed)

    −   stop the Status Display Menu from scrolling         To temporarily stop the scrolling, press the up
        and to manually scroll to the next parameter        arrow/SCROLL key.
        on the menu. When left unattended for               The Main User Menu is used to access and change
        45 seconds, the display resumes scrolling           the thermostat’s basic operating parameters. Access
                                                            the menu by pressing the MENU key during normal
                                                            thermostat operation.
                                                            The Installer Configuration Menu is used to set up
                                                            the thermostat for application specific operation.
                                                            Access the menu by removing the front cover and
                                                            pressing the configuration key, labeled CONFIG
                                                            (Figure 7).

                                                            Configuring the T600MSP-1
                             Configuration
                                 Key                        The T600MSP-1 ships from the factory with default
                                                            settings for all configurable parameters. The default
        Figure 7: Configuration Key Location                settings are shown in Table 1. To reconfigure the
                                                            parameters, follow the steps in this section for the
Backlit Liquid Crystal Display (LCD)                        corresponding parameters. To set up the parameters,
The T600MSP-1 uses a two-line, eight-character              access the Installer Configuration Menu. Access the
backlit display. Low level backlighting is present during   Installer Configuration Menu by removing the front
normal operation and it brightens when any user             cover and pressing the configuration key (Figure 7).
interface key is pressed. The backlight returns to the
                                                            Exit the Installer Configuration Menu any time by
lower level when the thermostat is left unattended for
                                                            pressing the MENU key and, at the exit prompt,
45 seconds.
                                                            pressing the YES key. To pass over a parameter
                                                            without changing it, press the NO key.
Light-Emitting Diodes (LED)s
Three LEDs are used to indicate the status of the fan,      When the thermostat is in the Installer Configuration
call for heat, or call for cooling. When:                   Menu and left unattended for 45 seconds, it reverts to
                                                            the Status Display Menu.
•   the fan is on, the FAN LED lights up
•   heating is on, the HEAT LED lights up
•   cooling is on, the COOL LED lights up

4   T600MSP-1 Programmable Thermostat Installation Instructions
Table 1: Installer Configuration Menu
                                                                             Sets the Minimum Heating/Cooling
                 Remove the cover and press the
  RoomTemp                                                   Deadband        Deadband
                 CONFIG key from the Status Display
  75.0 °F                                                    set? Y/N        Default: 2.0°F (1.1°C)
                 Menu to enter the Installer
                                                                             See Setting the Heating/Cooling
                 Configuration Menu.
                                                                             Deadband (Deadband).
                                                                             Determines how the Fan Activates in
                 Configures Digital Input 1
  DI1                                                        Fan cont        Response to a call for Heat
                 Default: No Function (None)
  set? Y/N                                                   set? Y/N        Default: Thermostat Controls Fan (On)
                 See Configuring the Digital Inputs
                                                                             See Setting the Fan Control
                 (DI1 and DI2).
                                                                             (Fan cont).

                 Configures Digital Input 2                                  Delays Fan Termination at Cycle’s End
  DI2            Default: No Function (None)                 Fan del         for 60 Seconds
  set? Y/N       See Configuring the Digital Inputs          set? Y/N        Default: No Delay (Off)
                 (DI1 and DI2).                                              See Setting the Fan Delay (Fan del).

                                                                             Sets the Duration for Temporary
                 Sets Keypad Lockout Level
  Lockout                                                    ToccTime        Occupancy Time
                 Default: No Lockout (0)
  set? Y/N                                                   set? Y/N        Default: Three Hours (3.0 hrs)
                 See Enabling Keypad Lockout
                                                                             See Establishing the Temporary
                 (Lockout).
                                                                             Occupancy Time (ToccTime).

                 Sets Power-up Delay                                         Room Air Sensor Calibration (Offset)
  Pwr del        Default: Ten Seconds (10.0 sec)             Cal RS          Default: 0.0°F (0.0°C)
  set? Y/N       See Setting the Power-up Delay              set? Y/N        See Room Air Sensor Calibration
                 (Pwr del).                                                  (Cal RS).

                 Enables/Disables Frost Protection                           Outdoor Air Sensor Calibration (Offset)
  Frost pr       Default: Disabled (Off)                     Cal OS          Default: 0.0°F (0.0°C)
  set? Y/N       See Enabling Frost Protection               set? Y/N        See Outdoor Air Sensor Calibration
                 (Frost pr).                                                 (Cal OS).

                 Sets the Maximum Heating Setpoint                           Enable/Disable Second Heating Stage
  Heat max       Default: 90.0°F (32.0°C)                    H Stage         Default: Two Stages
  set? Y/N       See Setting the Maximum Heating             set? Y/N        See Enable/Disable Second Heating
                 Setpoint (Heat max).                                        Stage (H Stage).

                 Sets the Minimum Cooling Setpoint                           Enable/Disable Second Cooling Stage
  Cool min                                                   C Stage
                 Default: 54.0°F (12.0°C)                                    Default: Two Stages
  set? Y/N                                                   set? Y/N        See Enable/Disable Second Cooling
                 See Setting the Minimum Cooling
                 Setpoint (Cool min).                                        Stage (C Stage).

                                                                             Disables Heating Operation based on
                 Sets the Anti-Short Cycle Timer
  Anticycl                                                   H lock          Outdoor Air Temperature
                 Default: Two Minutes (2.0 min)
  set? Y/N                                                   set? Y/N        Default: 120°F (49°C)
                 See Setting the Anti-Short Cycle Timer
                                                                             See Setting the Heating Lockout
                 (Anticycle).
                                                                             (H lock).
                 Sets the Maximum Heating Cycles per                         Disables Cooling Operation based on
  Heat cph       Hour                                        C lock          Outdoor Air Temperature
  set? Y/N       Default: Four (4.0)                         set? Y/N        Default: -40°F (-40°C)
                 See Setting the Maximum Heating                             See Setting the Cooling Lockout
                 Cycles per Hour (Heat cph).                                 (C lock).
                 Sets the Maximum Cooling Cycles per        Continued on the next page . . .
  Cool cph       Hour
  set? Y/N       Default: Four (4.0)
                 See Setting the Maximum Cooling
                 Cycles per Hour (Cool cph).

                                                T600MSP-1 Programmable Thermostat Installation Instructions            5
    Table1: Installer Configuration Menu (Cont.)              To configure the digital inputs while in the Installer
                                                              Configuration Menu:
                     Sets the Number of Events in 24-Hour
     2/4event        Period                                   1. Press YES to configure Digital Input 1 or NO to
     set? Y/N        Default: Two Events (2.0)                   advance to Digital Input 2.
                     See Selecting the Number of Events
                                                              2. Use the UP/DOWN arrow keys to locate the
                     (2/4event).
                                                                 desired function for the Digital Input 1. Press YES
                     Sets the Auxiliary Contact as Normally
                                                                 to select the desired function.
     Aux cont        Open or Normally Closed
     set? Y/N        Default: Normally Open (N.O.)            3. Press YES to configure Digital Input 2 or NO to
                     See Configuring the Auxiliary Contact       advance to the keypad lockout setup prompt.
                     (Aux cont).
                                                              4. Use the UP/DOWN arrow keys to locate the
                     Enable/Disable Progressive Recovery         desired function for the Digital Input 2. Press YES
     Prog rec
                     Default: Off                                to select the desired function.
     set? Y/N        See Enable/Disable Progressive
                     Recovery (Prog rec).                     The display now shows the keypad lockout setup
                                                              prompt. See the Enabling Keypad Lockout (Lockout)
                                                              section for instructions.

Configuring the Digital Inputs (DI1 and DI2)                  Enabling Keypad Lockout (Lockout)
Press the configuration menu access key. The first            The T600MSP-1 has three levels of keypad lockout.
prompt is to program Digital Inputs DI1 and DI2.              The levels and degree of lockout are shown in Table 2.
The digital inputs display an alarm condition when the        To set the keypad lockout level while in the Installer
input is closed. An alarm message is included on the          Configuration Menu:
scrolling Status Display Menu and when the message            1. Answer NO to all prompts until the keypad lockout
displays, the backlight momentarily lights up.                     setup prompt appears in the display. Press YES to
Each digital input can be programmed in one of five                enter the keypad lockout menu.
conditions.                                                   2. Use the UP/DOWN arrow keys to locate the
                                                                   desired lockout level. Press YES to select the
•     None – No function is associated with the input.
                                                                   level.
•     Service – A Service alarm is displayed.                 The display now shows the power delay setup prompt.
•     Filter – A Filter alarm is displayed.                   See the Setting the Power-up Delay (Pwr del) section
                                                              for instructions.
•     RemNSB – Remote Night Setback (NSB) timer
      clock input. The scheduling is set per the digital      Table 2: Keypad Lockout Levels
      input when this option is selected. The time                                Level 0       Level 1       Level 2
      continues to be displayed, but the menu related to        Resume to
                                                                                 Yes access    Yes access    No access
      scheduling is disabled and no longer accessible.          Scheduling
      −   Open Contact = Occupied setpoints                     Temperature
                                                                                 Yes access    No access     No access
                                                                 Setpoints
      −   Closed Contacts = Unoccupied setpoints               System Mode
                                                                                 Yes access    Yes access    No access
•     RemOVR – Remote override contact. This                      Setting
      disables all override menu functions of the                Fan Mode
                                                                                 Yes access    Yes access    No access
      thermostat. The override function is controlled             Setting
      manually by a remote, momentarily closed                   Schedules
                                                                                 Yes access    No access     No access
      contact. When configured in this mode, the input            Setting
      operates in a toggle mode. With this function            Clock Setting                                    Yes
                                                                                 Yes access    Yes access
      enabled, it is now possible to toggle between                                                            access
      unoccupied and occupied setpoints for the amount           Permanent
      of time set by the temporary occupancy time                                Yes access    Yes access    No access
                                                                    Hold
      parameter.
      When override is enabled through the digital
      inputs, an Override message appears in the
      Status Display Menu.

6     T600MSP-1 Programmable Thermostat Installation Instructions
Setting the Power-up Delay (Pwr del)
On initial power-up of the T600MSP-1 (or each time             To set the maximum heating setpoint while in the
power is removed and reapplied), there is a delay              Installer Configuration Menu:
before any operation is authorized (fan, cooling, and
                                                               1. Answer NO to all prompts until the maximum
heating). The delay time is adjustable between 10 and
                                                                  heating setpoint prompt appears in the display.
120 seconds. This parameter also can be used to
                                                                  Press YES to enter the maximum heating setpoint
sequence the start-up of multiple units in one location.
                                                                  menu.
Note: When adjusting the time with the UP/DOWN
                                                               2. Use the UP/DOWN arrow keys to adjust the
arrow keys, holding the keys down changes the time
                                                                  maximum heating setpoint temperature. Press
by 10-second intervals.
                                                                  YES to store the value.
To set the delay time while in the Installer
                                                               The display now shows the minimum cooling setpoint
Configuration Menu:
                                                               prompt. See the Setting the Minimum Cooling Setpoint
1. Answer NO to all prompts until the power delay              (Cool min) section for instructions.
   setup prompt appears in the display. Press YES to
   enter the power delay setup menu.                           Setting the Minimum Cooling Setpoint (Cool min)
2. Use the UP/DOWN arrow keys to adjust the                    The minimum cooling setpoint establishes the
   power-up delay setting. Press YES to store the              minimum temperature in the cooling setpoint range
   setting.                                                    that can be adjusted from the Main User Menu. The
                                                               parameter is adjustable from 54 to 100°F
The display now shows the frost protection setup               (12 to 37.5°C).
prompt. See the Enabling Frost Protection (Frost pr)
section for setup instructions.                                Note: When adjusting the temperature, holding the
                                                               keys down changes the temperature by 5 F/C°
Enabling Frost Protection (Frost pr)                           increments.
Frost protection establishes a minimum heating                 To set the minimum cooling setpoint while in the
setpoint of 42°F (5.5°C) to prevent freezing in the zone       Installer Configuration Menu:
controlled by the thermostat. If enabled, frost
protection is activated even if the thermostat is set to       1. Answer NO to all prompts until the minimum
the Off System Mode. If frost protection is active, it            cooling setpoint prompt appears in the display.
displays as an alarm (Frost on with the backlight lit)            Press YES to enter the minimum cooling setpoint
on the Status Display Menu.                                       menu.
To enable frost protection while in the Installer              2. Use the UP/DOWN arrow keys to adjust the
Configuration Menu:                                               minimum cooling setpoint temperature. Press YES
                                                                  to store the value.
1. Answer NO to all prompts until the frost protection
   setup prompt appears in the display. Press YES to           The display now shows the anti-short cycle timer
   enter the frost protection menu.                            prompt. See the Setting the Anti-Short Cycle Timer
2. Use the UP/DOWN arrow keys to select off or on.             (Anticycl) section for instructions.
   Press YES to store the selection.
                                                               Setting the Anti-Short Cycle Timer (Anticycl)
The display now shows the maximum heating setpoint
prompt. See the Setting the Maximum Heating                    The anti-short cycle timer establishes the minimum
Setpoint (Heat max) section for instructions.                  on/off times for the cooling and heating stages. The
                                                               timer is adjustable from 0 to 5 minutes in 1-minute
                                                               increments. Set the anti-short cycle to 0 for equipment
Setting the Maximum Heating Setpoint (Heat max)
                                                               that possesses its own anti-short cycle timer.
The maximum heating setpoint establishes the
maximum temperature in the heating setpoint range
that can be adjusted from the Main User Menu. The
parameter is adjustable from 40 to 90°F (4.5 to 32°C).
                                                                  !     CAUTION: Risk of Property Damage.
                                                                Do not set the T600MSP-1 anti-short cycling timer to
Note: When adjusting the temperature, holding the               0 minutes if the controlled equipment is not
keys down changes the temperature by 5 F/C°                     protected by its own internal anti-short cycling timer.
increments.                                                     Doing so may result in damage to the controlled
                                                                equipment.

                                                    T600MSP-1 Programmable Thermostat Installation Instructions           7
To set the anti-short cycle time while in the Installer   To set the maximum number of cooling cycles per
Configuration Menu:                                       hour while in the Installer Configuration Menu:
1. Answer NO to all prompts until the anti-short cycle    1. Answer NO to all prompts until the cooling cycles
   timer prompt appears in the display. Press YES to         per hour prompt appears in the display. Press
   enter the anti-short cycle timer menu.                    YES to enter the cooling cycles per hour menu.
2. Use the UP/DOWN arrow keys to adjust the               2. Use the UP/DOWN arrow keys to adjust the
   minimum on/off times for the heating and cooling          maximum number of cooling cycles per hour.
   stages. Press YES to store the value.                     Press YES to store the value.
The display now shows the heating cycles per hour         The display now shows the minimum heating/cooling
setup prompt. See the Setting the Maximum Heating         deadband prompt. See the Setting the Heating/Cooling
Cycles per Hour (Heat cph) section for instructions.      Deadband (Deadband) section for instructions.

Setting the Maximum Heating Cycles per Hour               Setting the Heating/Cooling Deadband (Deadband)
(Heat cph)                                                The heating/cooling deadband setting establishes the
The heating cycles per hour establishes the maximum       minimum difference between the heating and cooling
number of times the equipment is turned on and off in     setpoints. The range is adjustable from 2 to 4 F°
one hour. The selection ranges from three to eight        (1 to 2 C°).
cycles per hour.
                                                          To change the minimum deadband between the
Note: A higher number of heating cycles per hour          heating and cooling setpoints while in the Installer
results in more accurate temperature control, but could   Configuration Menu:
accelerate the wear of mechanical components in the       1. Answer NO to all prompts until the deadband
equipment.                                                     setpoint prompt appears in the display. Press YES
To set the maximum number of heating cycles per                to enter the deadband setpoint menu.
hour while in the Installer Configuration Menu:           2. Use the UP/DOWN arrow keys to adjust the
1. Answer NO to all prompts until the heating cycles           minimum deadband between the heating and
   per hour prompt appears in the display. Press               cooling setpoints. Press YES to store the value.
   YES to enter the heating cycles per hour menu.         The display now shows the fan control prompt. See
                                                          the Setting the Fan Control (Fan cont) section for
2. Use the UP/DOWN arrow keys to adjust the               instructions.
   maximum number of heating cycles per hour.
   Press YES to store the value.                          Setting the Fan Control (Fan cont)
The display now shows the cooling cycles per hour         This parameter controls how the fan activates in
setup prompt. See the Setting the Maximum Cooling         response to a call for heating.
Cycles per Hour (Cool cph) section for instructions.      When the fan is in Auto Mode (as selected on the Main
                                                          User Menu):
Setting the Maximum Cooling Cycles per Hour
(Cool cph)                                                •   Selecting on enables the thermostat to control the
                                                              fan on a call for heating or cooling.
The cooling cycles per hour establishes the maximum
number of times the equipment turns on and off in one     •    When selecting off, the thermostat on a call for
hour. The selection ranges from three to four cycles           cooling only energizes the fan. On a call for
per hour.                                                      heating, the fan is controlled by the equipment fan
                                                               limit control.
Note: A higher number of cooling cycles per hour
                                                          To set the fan control while in the Installer
results in more accurate temperature control, but could
                                                          Configuration Menu:
accelerate the wear of mechanical components in the
equipment.                                                1. Answer NO to all prompts until the fan control
                                                               prompt appears in the display. Press YES to enter
                                                               the fan control menu.
                                                          2. Using the UP/DOWN arrow keys, select on or off.
                                                               Press YES to store the selection.
                                                          The display now shows the fan delay prompt. See the
                                                          Setting the Setting the Fan Delay (Fan del) section for
                                                          instructions.

8   T600MSP-1 Programmable Thermostat Installation Instructions
Setting the Fan Delay (Fan del)                             Outdoor Air Sensor Calibration (Cal OS)
The fan delay extends the fan operation by                  An offset can be added or subtracted to the actual
60 seconds after the call for heating or cooling has        displayed outdoor air temperature as needed. The
ended. This feature is only active when the fan is in       range is ±5.0 F° (±2.5 C°), adjustable in increments of
the Auto mode.                                              1 F° (0.5 C°).
To enable the fan delay while in the Installer              To change the outdoor air sensor calibration/offset
Configuration Menu:                                         while in the Installer Configuration Menu:
1. Answer NO to all prompts until the fan delay
                                                            1. Answer NO to all prompts until the outdoor sensor
   prompt appears in the display. Press YES to enter
                                                               calibration prompt appears in the display. Press
   the fan delay menu.
                                                               YES to enter the outdoor sensor calibration menu.
2. Using the UP/DOWN arrow keys, select on or off.
                                                            2. Use the UP/DOWN arrow keys to adjust the
   Press YES to store the selection.
                                                               correction that should be applied to the sensor
The display now shows the occupancy override                   reading. Press YES to store the offset.
prompt. See the Establishing the Temporary
                                                            The display now shows the heating stage setting
Occupancy Time (ToccTime) section for instructions.
                                                            prompt. See the Enable/Disable Second Heating
Establishing the Temporary Occupancy Time                   Stage (H Stage) section for instructions.
(ToccTime)
The temporary occupancy time is the length of time          Enable/Disable Second Heating Stage (H Stage)
the occupied mode setpoints are used when the               This parameter reverts the operation of two-stage
override function is enabled (the override function can     thermostats to a single stage when the second heating
be enabled from the Main User Menu or from one of           stage is not needed.
the digital inputs) or a temporary setpoint is entered.
                                                            To disable or enable the second heating stage while in
The range is adjustable from 0 to 12 hours.
                                                            the Installer Configuration Menu:
To change the temporary occupancy time while in the
Installer Configuration Menu:                               1. Answer NO to all prompts until the setting heating
                                                               stages prompt appears in the display. Press YES
1. Answer NO to all prompts until the temporary                to enter the setting heating stages menu.
    occupancy time prompt appears in the display.
    Press YES to enter the temporary occupancy time         2. Using the UP/DOWN arrow keys; select 1.0 or 2.0
    menu.                                                      stages. Press YES to store the selection.
2. Use the UP/DOWN arrow keys to adjust the length          The display now shows the cooling stage setting
    of time the temporary occupancy setpoint should         prompt. See the Enable/Disable Second Cooling
    be in effect. Press YES to store the time.              Stage (C Stage) section for instructions.
The display now shows the room sensor calibration
prompt. See the Room Air Sensor Calibration (Cal RS)        Enable/Disable Second Cooling Stage (C Stage)
section for instructions.                                   This parameter reverts the operation of two-stage
Room Air Sensor Calibration (Cal RS)                        thermostats to a single stage when the second cooling
                                                            stage is not needed.
An offset can be added or subtracted to the actual
displayed room temperature as needed. The range is          To disable or enable the second cooling stage while in
±5.0 F° (±2.5 C°), adjustable in increments of 1 F°         the Installer Configuration Menu:
(0.5 C°).
                                                            1.   Answer NO to all prompts until the setting cooling
To change the room sensor calibration/offset while in            stages prompt appears in the display. Press YES
the Installer Configuration Menu:                                to enter the setting cooling stages menu.
•   Answer NO to all prompts until the room sensor          2.   Using the UP/DOWN arrow keys; select 1.0 or 2.0
    calibration prompt appears in the display. Press             stages. Press YES to store the selection.
    YES to enter the room sensor calibration menu.
                                                            The display now shows the heating lockout prompt.
•   Use the UP/DOWN arrow keys to adjust the                See the Setting the Heating Lockout (H lock) section
    correction that should be applied to the sensor         for instructions.
    reading. Press YES to store the offset.
The display now shows the outdoor air sensor
calibration prompt. See the Outdoor Air Sensor
Calibration (Cal OS) section for instructions.
                                                 T600MSP-1 Programmable Thermostat Installation Instructions       9
Setting the Heating Lockout (H lock)                     Selecting the Number of Events (2/4event)
This feature disables heating operation based on         This feature sets the number of events per 24-hour
outdoor air temperature (requires outdoor air            period that can be programmed into the daily
temperature sensor to be connected for the function to   schedule.
be enabled). If the outdoor air temperature is above
                                                         Two events selects one occupied and one unoccupied
the heating lockout temperature, heating operation is
                                                         period per 24 hours and four events selects two
disabled.
                                                         occupied and two unoccupied periods per 24 hours.
The heating lockout temperature parameter is
                                                         To change the number of events in a 24-hour period
adjustable from -15 to 120°F (-26 to 49°C) in
                                                         while in the Installer Configuration Menu:
increments of 5 F/C°.
                                                         1. Answer NO to all prompts until the number of
To change the outdoor air temperature heating lockout       events prompt appears in the display. Press YES
while in the Installer Configuration Menu:                  to enter the number of events menu.
1. Answer NO to all prompts until the heating lockout    2. Use the UP/DOWN arrow keys to select 2 or 4
   prompt appears in the display. Press YES to enter        events. Press YES to store the value.
   the heating lockout menu.
                                                         The display now shows the auxiliary contact
2. Use the UP/DOWN arrow keys to adjust the              configuration prompt. See the Configuring the Auxiliary
   lockout temperature. Press YES to store the value.    Contact (Aux cont) section for instructions.
The display now shows the cooling lockout prompt.
See the Setting the Cooling Lockout (C lock) section     Configuring the Auxiliary Contact (Aux cont)
for instructions.                                        The auxiliary contact is an output that can be used to
                                                         energize peripheral devices (for example, lighting
Setting the Cooling Lockout (C lock)                     equipment, exhaust fans, and economizers). The
This feature disables cooling operation based on         contact can be configured as normally open or
outdoor air temperature (requires outdoor air            normally closed and toggles with the internal
temperature sensor to be connected for the function to   occupied/unoccupied schedule (or the remote NSB
be enabled). If the outdoor air temperature is below     contact on one of the digital inputs, if used).
the cooling lockout temperature, cooling operation is
disabled.                                                Table 3: Operation of Auxiliary Contact
                                                                                    Contact         Contact
The cooling lockout temperature parameter is                Configuration
                                                                                   Occupied        Unoccupied
adjustable from -40 to 95°F (-40 to 35°C) in                   Setup
                                                                                    Status           Status
increments of 5 F/C°.
                                                           Normally Opened           Closed           Opened
To change the outdoor air temperature cooling lockout
while in the Installer Configuration Menu:
                                                           Normally Closed          Opened             Closed
1. Answer NO to all prompts until the cooling lockout
   prompt appears in the display. Press YES to enter
   the cooling lockout menu.                             To configure the auxiliary contact while in the Installer
2. Use the UP/DOWN arrow keys to adjust the              Configuration Menu:
   lockout temperature. Press YES to store the value.    1. Answer NO to all prompts until the auxiliary
The display now shows the number of events prompt.          contact prompt appears in the display. Press YES
See the Selecting the Number of Events (2/4event)           to enter the auxiliary contact menu.
section for instructions.                                2. Use the UP/DOWN arrow keys to select Normally
                                                            Open (N.O.) or Normally Closed (N.C.). Press
                                                            YES to store the selection.
                                                         The display now shows the progressive recovery
                                                         prompt. See the Enable/Disable Progressive Recovery
                                                         (Prog rec) section for instructions.

10   T600MSP-1 Programmable Thermostat Installation Instructions
Enable/Disable Progressive Recovery (Prog rec)             Table 4: Programming the T600MSP-1
When the progressive recovery is enabled, the desired
occupied temperature is attained by the time the             RoomTemp      Press the MENU key while in the
occupied schedule starts                                     75.0 °F       Status Display Menu to enter the Main
                                                                           User Menu.
When the progressive recovery is disabled, the system
restarts at the programmed occupied time.
                                                                           Overrides Unoccupied Setpoints
Note: Programming one of the digital inputs to               Override      Only Appears if Thermostat is in
remote NSB disables the progressive recovery                 schd Y/N      Unoccupied State
function.                                                                  See Enabling Override Schedule.
To enable/disable the progressive recovery feature                         Resumes Regular Programmed
while in the Installer Configuration Menu:                   Resume        Schedule and Setpoints
                                                             schd Y/N      Only Appears if Thermostat is in
1. Answer NO to all prompts until the progressive                          Override Mode
   recovery prompt appears in the display. Press                           See Resuming the Programmed
   YES to enter the Progressive Recovery menu.                             Schedule.
2. Use the UP/DOWN arrow keys to select on or off.
   Press YES to store the selection.                         Temperat      Sets the Temperature Setpoints
                                                             set? Y/N      See Entering Temperature Setpoints.
3. The exit menu is displayed. Press YES to exit the
   Installer Configuration Menu or press NO to return
   to the beginning of the menu (digital input
   configuration).                                           Sys mode      Selects the System Mode
                                                             set? Y/N      Default: Automatic Mode (auto)
                                                                           See Selecting the System Mode.
Operation
Programming/Operating the T600MSP-1
                                                                           Selects the Fan Mode
Once the T600MSP-1 is configured through the                 Fan mode
                                                                           Default: Automatic (auto)
Installer Configuration Menu, the thermostat’s               set? Y/N
                                                                           See Selecting the Fan Mode.
operating parameters can be programmed through the
Main User Menu (access the Main User Menu by                               Sets the Occupied and Unoccupied
pressing the MENU key during normal thermostat               Schedule      Time Periods
operation). The Main User Menu contains the basic            set? Y/N      See Programming the Daily Schedule
operating features of the T600MSP-1.                                       – Two-Event and Programming the
The Main User Menu uses Auto Help. Auto Help is                            Daily Schedule – Four-Event.
displayed automatically in the Main User Menu when
there is a pause in programming activity. To exit Auto       Clock         Sets the Day and Time
Help, continue with the programming selection.               set? Y/N      See Setting the Day and Time.
When the thermostat is in the Main User Menu and is
left unattended for 45 seconds, it reverts to the Status
Display Menu.                                                              Sets a Permanent Hold on the
                                                             Schedule
Follow the steps in Table 4 to program the                   hold? Y/N     Schedule or Resumes the Schedule
T600MSP-1.                                                                 See Setting Permanent Hold.

                                              T600MSP-1 Programmable Thermostat Installation Instructions        11
Enabling Override Schedule                                   Entering Temperature Setpoints
Note: Enabling Override Schedule only appears                When the T600MSP-1 is in the occupied state, the first
when in the Unoccupied Mode.                                 prompt appearing in the Main User Menu is to set the
                                                             temperature setpoints. This is where the heating and
The override schedule prompt only appears when the
                                                             cooling setpoints for the occupied and unoccupied
thermostat is in the unoccupied state. This menu
                                                             states are entered. It is also where any temporary
selection gives the user the option of overriding the
                                                             setpoints are entered.
unoccupied setpoints with the occupied setpoints for
the amount of time specified under the Establishing          To enter the heating and cooling setpoints for the
the Temporary Occupancy Time (ToccTime)                      occupied and unoccupied modes (permanent or
parameter (see Configuring the T600MSP-1 section).           temporary), follow the steps in Table 5. When
If one of the digital inputs is configured to operate as a   changing the temperatures, pressing the keys once
remote override contact, this menu is disabled.              changes the temperature 0.5 F/C° and holding down
To override the unoccupied state while in the Main           the keys changes the temperature by 5 F/C°
User Menu:                                                   increments.

1. Answer NO to all prompts until the Override               Setpoint Type
   Schedule prompt appears. If the thermostat is in          Permanent Setpoints are permanently stored in the
   the unoccupied state, this is the first prompt.           programmed schedule. This is the default setpoint
2. Press YES to enable the temporary override. The           type.
   T600MSP-1 returns to the Status Display Menu.             Temporary Setpoints are changed, but are in effect
When scrolling through the Status Display Menu,              only for the time specified in the Establishing the
Override now appears for the schedule status                 Temporary Occupancy Time (ToccTime) parameter
parameter.                                                   (see the Configuring the T600MSP-1 section).
                                                             There is no indication that a temporary setpoint is
Resuming the Programmed Schedule                             enabled or active.
Note: Resuming the Programmed Schedule only
appears when in the Temporary Occupancy Mode.                After the specified time, the temporary setpoint reverts
                                                             to the permanent setpoint.
This menu only appears when the T600MSP-1 is in
the:                                                         The temporary setpoint can be cancelled at any time
                                                             by using the Permanent Setpoint option in this menu.
•    unoccupied override mode                                When permanent modifications of the setpoints are
                                                             required, this parameter needs to be set to permanent.
•    permanent occupied hold mode
•    permanent unoccupied hold mode                          Table 5: Entering Temperature Setpoints
Note: If the T600MSP-1 is not in one of these
modes, this prompt does not appear. Answering YES               RoomTemp         Press MENU from the Status Display
to this prompt enables the T600MSP-1 to resume the              75.0°F           Menu to enter the Main User Menu.
regular scheduled program and setpoints.
To resume the schedule while in the Main User Menu:                              Answer NO to all prompts until the
                                                                Temperat         temperature set prompt appears in
1. Answer NO to all prompts until the Resume                                     the display (it may be the first
                                                                set? Y/N
   Schedule prompt appears. If the thermostat is in                              prompt). Press YES to enter
   the temporary occupancy state, this is the first                              temperature setting menu.
   prompt.
                                                                                 Press YES to change occupied
2. Press YES to resume the programmed schedule.                 Cooling          cooling setpoint. Press NO to
                                                                set? Y/N         advance to occupied heating setpoint
The T600MSP-1 returns to the Status Display Menu.                                menu.

                                                                Cooling          Use the UP/DOWN arrow keys to set
                                                                75.0°F           temperature. Press YES to store
                                                                                 value and advance to next menu.

                                                              Continued on the next page . . .

12   T600MSP-1 Programmable Thermostat Installation Instructions
                                                         Selecting the System Mode
Table 5: Entering Temperature Setpoints (Cont.)
                                                         The T600MSP-1 has four system modes.
                Press YES to change the occupied         •   Automatic Mode (auto)
 Heating        heating setpoint. Press NO to
 set? Y/N                                                    Automatic changeover between heating and
                advance to unoccupied cooling
                setpoint menu.
                                                             cooling. This is the default setting.
                                                         •   Cooling Mode (cool)
                                                 