SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

T-5800-3 and T-5800-4 Dual Input Receiver-Controllers Installation and Calibration Technical Bulletin

Вид документаТехнічний бюлетень
ВиробникJCI
Код документаt-5800-3-and-t-5800-4-dual-input-receiver-controllers-installation-and
Група обладнанняT-5800 Receiver-Controller
Сторінок12
Мова документаанглійська
Розмір файлу0.3 МБ

Текст документа

24- 7029- 0, Rev. A

                                                                                Technical Bulletin T-5800-3/-4
                                                                                     Issue Date 0316

                                         T-5800-3 and T-5800-4
                                    Dual Input Receiver-Controllers
                                      Installation and Calibration

The T-5800 Series Receiver-
Controllers are designed for use
with remote temperature, humidity,
or pressure transmitters
(connected to the controlled
variable “CV” input) to provide
precise control of pneumatic
devices. The T-5800-3 is a dual
input proportional-only receiver-
controller with field selectable local
or remote set point. The
T-5800-4 is also a dual input
receiver-controller with field
                                             Fig. 1: T-5800-3 Dual Input     Fig. 2: T-5800-4 Dual Input
selectable local or remote set
                                          Proportional Receiver-Controller         PI Receiver-Controller
point; however, this model
provides proportional plus integral
(PI) control. In addition, an
automatic/manual integral control
cutout feature is incorporated into
the T-5800-4 design. Utilizing the
fan “F” connection, this feature
allows the system to start up using
proportional-only control thus
keeping the system from going out
of control on startup, as is inherent
to PI (automatic reset) controllers,
when the system has been off for
some time. Refer to Product Data
T-5800 for instrument
specifications and additional
details.

Installation
The T-5800 Series Receiver-
Controllers are designed for
surface mounting; refer to Fig. 3
for space requirements and
mounting details. All air line
connections are made to the units
through two snap-on input/output
connectors which have barbed
fittings for 1/4 in. O.D. polytubing.
Both dual input models are
furnished with a clear cover, snap-
on air connectors, a double                  Fig. 3: T-5800 Series Dimensions in./mm and Mounting Details
.007 in. orifice jumper, an
additional set point dial sticker
marked with 50 graduations, and a
yellow remote indication set point
dial sticker.
© 2016 Johnson Controls, Inc.                                                                                1
  Part No. 24-7029-0, Rev. A
  Code No. LIT-7171320X
Cover Removal
The cover can be removed by
applying an inward pressure to
one of the black tabs of the
receiver-controller main body to
unlatch it. The cover can also be
removed by simply taking hold of
the top and bottom sides of the
cover and pulling outward.

Oil Indicating Supply Air Filter
Check the oil indicating supply
air filter and replace as
necessary (A-4000-137 ordered
separately). When the filter is
dirty, a pressure drop will occur.
When filtering oil-contaminated
air, the filter will change from
white to red in color. If frequent
changes are necessary, check
the air supply system to
determine the cause of dirty or
oil-contaminated air.

Positioning the Action and
Orifice Jumpers
The T-5800 must be
programmed according to the
system requirements. Both dual
input receiver-controllers are
factory set in the direct acting
mode with reverse readjustment.          Precalibration Setup                 to illustrate the pressure
The action and readjustment can                                               relationship of master “M” input
                                         Using the graph on Form 561,         vs. controlled variable “CV”
be changed by interchanging the          prepare a readjustment schedule
placement of the tube ends from                                               input. Locate the two end points
                                         (similar to the example in Fig. 6)   of the control schedule and
one lower spigot to the other            with respect to job requirements,
lower spigot (see Figs. 4, 11,                                                connect with a straight line.
                                         action, range of readjustment,
and 15).                                 transmitter spans, and               The receiver-controller ratio is
Each dual input T-5800 is                pressures. Use the graph and         determined by the following
furnished with a double .007 in.         transmitter span vs. output          formula:
orifice jumper and three yellow          comparison chart
spigot caps (see Fig. 5). The
orifice jumper provides a
restricted source of supply to low
volume non-relay type
transmitters. For best results, it
is recommended that this jumper
be used when the low volume
transmitter is located within 50 ft.
(15m) of the receiver-controller.
For all other applications, it is
recommended that the spigots
be capped and a source of
supply be furnished at the
transmitter.

2 T-5800-3/T-5800-4 Technical Bulletin
Set point Selection - Local or         the yellow dial sticker to indicate        Supply Air Interruptions
Remote                                 remote set point adjustment
                                       mode (see Fig 7). Connect the              Both dual input receiver-
Local: The arrow on the set            tubing from the remote set point           controllers have within their
point dial represents                  adjustment device to the set               circuitry a master balance
approximately a 9 PSIG (63 kPa)        point “SP” connection of the               regulator which requires that the
set point pressure. The dial           snap-on input/output connector.            supply air remain on at all times.
sticker is designed so that the        A low volume restricted source             In addition, T-5800-4 has an
actual set point can be written        of supply air (less than .005 in.          automatic/manual integral
directly on its surface using a        orifice) is automatically                  control cutout feature which also
common pencil.                         furnished; therefore, use 75% of           requires that the supply air
Note: When local set point             the overall line length that is            remain on at all times.
adjustment is used, the set            recommended for a .005 in.
point “SP” connection must             orifice.                                   Calibration
be open to atmosphere.
                                                                                  General Instructions
                                       FC and PRV Test Points
Remote: Rotate the set point                                                      Calibration and readjustment of
dial fully counterclockwise until it   The FC and PRV test points and             the T-5800 Receiver-Controller
hits its mechanical stop. Affix        their associated adjustments are           should only be done by a
                                       for FACTORY USE ONLY.                      qualified Johnson Controls

                                                                             T-5800-3/T-5800-4 Technical Bulletin 3
                                                                  Fig. 8: X-200-173 Calibration Kit

                                            Fig. 9: X-200-140 Test Probe with
                                         X-200-180 Series Transmission Gage and
                                                     F-500-42 Adapter

4 T-5800-3/T-5800-4 Technical Bulletin
representative equipped with the      Calibrating the T-5800-3                        installed in the 1:1 position. If
proper tools. An X-200-173                                                            the calculated ratio is greater
                                      (See Fig. 11)
Calibration Kit (see Fig. 8,                                                          than 2.5:1, the jumper should
ordered separately) is available      With the supply air ON, balance                 be installed in the 3:1
for making adjustments and            the receiver-controller by setting              position.
pressure checks on the T-5800.        the following:
This kit provides all of the                                                     •    Turn the ratio dial so that “1:1
necessary gages, regulators,          •   Adjust the local set point dial             (3:1)” imprinted on the dial
and connectors for a more                 or the remote adjuster                      lines up with the dial
convenient and quicker                    (manual or automatic) to                    reference point.
calibration procedure.                    produce 9 PSIG (63 kPa)
                                          using the appropriate method
                                          and gage as described                  Receiver-Controller Preset
An X-200-140 Hypodermic                                                          (See Example Fig. 6)
                                          above.
Needle Test probe and
appropriate gage (see Fig. 9,         •   Turn the gain dial clockwise           Utilize one of the pressure
ordered separately) is also               so that the word                       checking methods described
available for troubleshooting, test       “INCREASE” imprinted on                previously to obtain a master “M”
point readings, or final set point        the dial is centered with the          input pressure reading, a master
adjustments under actual job              dial reference point.                  balance “R” pressure reading,
conditions. Note: Figure 10                                                      and a controlled variable “CV”
illustrates an alternative            •   Install the ratio selection            input pressure reading.
method of checking pressure               jumper in the correct position
                                          (see Fig. 11). If the                  1.    Apply a master “M” input
readings on the T-5800 where                                                           pressure equal to the
use of a hypodermic needle                calculated ratio is less than
                                          or equal to 2.5:1, (as is the                midpoint of the desired
test probe is prohibited.                                                              working range (Example:
                                          case with the example where
                                          the calculated ratio is 2:1),                30°F on a 0 to 60°F working
                                          the jumper should be                         range or 7.2 PSIG as
                                                                                       highlighted in Fig. 12).

                                                                            T-5800-3/T-5800-4 Technical Bulletin 5
2.   Rotate the master balance           3.   Vary the master input from    equal to 5 PSIG and the
     screw (see Fig. 10) located              minimum to maximum over       maximum master balance
     in the center of the receiver-           its working range (Example:   “R” pressure is less than
     controller (clockwise to                 0 to 60°F or 5.4 to 9 PSIG    19 PSIG (with a 20 PSIG
     increase or counterclockwise             per Fig. 6). Note: The        supply), no further
     to decrease) to produce a                master “M” INPUT is           adjustments are required. If
     9 PSIG (63 kPa) gage                     limited to not less than      the minimum master
     reading at the master                    2 PSIG nor greater than       balance “R” pressure is less
     balance “R” reference.                   17 PSIG. Note the             than 5 PSIG, rotate the
     Doing so will shift the                  pressure readings at the      master balance screw
     working range (internally) to            master balance “R”            (clockwise to increase) so
     a more linear portion of the             reference corresponding       that the minimum pressure
     ratio circuit.                           to these minimum and          is greater than 5 PSIG and
                                              maximum points.               the maximum does not
                                                                            exceed 19 PSIG.
                                              If the minimum master
                                              balance “R” pressure noted
                                              above is greater than or

6 T-5800-3/T-5800-4 Technical Bulletin
4.   After removing the pressure            will occur because the                however, the output pressure
     checking method from the               internal ratio circuitry is in        may change when the gain dial
     master balance “R”                     a balanced condition, and             is adjusted. Increasing the gain
     reference, it is suggested             any previous ratio dial               will narrow the throttling range
     that the master balance                setting (if not marked) will          (decrease offset), allowing the
     screw be sealed (using a               be lost.                              control point to be closer to the
     small dab of fingernail                                                      set point. Decreasing the gain
     polish).                               Adjust the ratio dial to cause        will widen the throttling range,
                                            the receiver-controller               forcing the control point away
5.   Return the master “M” input            output to be at a pressure            from the set point.
     pressure to the midpoint of            value which would produce
     the desired working range              the required controlled
     (Example: 30°F or 7.2 PSIG             variable “CV” input
     on a 0 to 60°F working                 (Example: Direct acting T-
     range per Fig. 6).                     5800-3, N.O. heating valve
                                            with a 3 to 7 PSIG spring
6.   Apply a controlled variable
                                            range; output should be
     “CV” input pressure to the
                                            below the midpoint of the
     value corresponding to the
                                            spring range of the valve
     value 7.2 PSIG master “M”
                                            which would produce the
     input setting (Example:
                                            required 200°F).
     140°F or 9 PSIG per Fig. 6).
                                       4.   Apply the maximum master
7.   Rotate the ratio dial (see
                                            “M” input pressure value
     Fig. 13) to a position which
                                            (Example: 60°F or 9 PSIG
     most closely represents the
                                            per Fig. 6).                          Normally, having the gain arrow
     required ratio setting
     (Example: 2:1, outer scale        5.   Apply the corresponding               set at the pointer represents a
     on dial and jumper in 1:1              controlled variable “CV”              reasonable gain adjustment
     position).                             input pressure value                  which would provide stability.
                                            (Example: 80°F or                     Increase the gain setting by
8.   Adjust the local set point dial                                              small increments until the
     or the remote adjuster                 5.4 PSIG per Fig. 6).
                                                                                  system becomes unstable and
     (manual or automatic) to          6.   Set Point dial Adjustment:            begins to cycle. Decrease the
     produce an output pressure                                                   gain setting slightly to remove
     on the controller gage equal           Adjust the set point dial to
                                            cause the output pressure to          the cycling effect. Doing so will
     to the midpoint of the spring                                                provide maximum controllability
     range of the controlled                be at the opposite end of the
                                            spring range of the                   with a minimum of offset.
     device.
                                            controlled device (Example:
Ratio and Set Point Checkout
                                            Direct Acting T-5800-3, N.O.          Calibrating the T-5800-4
                                            heating valve with a                  (see Fig. 15)
1.   Apply the minimum master               3 to 7 PSIG spring range;
     “M” input pressure value               output should be above the            When connecting the T-5800-4
     (Example: 0°F or 5.4 PSIG              midpoint of the spring range          Receiver-Controller to an
     per Fig. 6).                           of the valve which would              operating system, the fan “F”
                                            produce the required 80°F).           connection should either have
2.   Apply the corresponding                                                      the “system in operation”
     controlled variable “CV”          7.   Rotate the gain dial so that          function signal (minimum of
     input pressure value                   “10:1” imprinted on the dial          12 PSIG) attached (example:
     (Example: 200°F or                     lines up with the dial                fan on-off or water circulation
     12.6 PSIG per Fig 6).                  reference point.                      pump on-off), or the connection
3.   Ratio Dial Adjustment:            8.   The T-5800-3 is calibrated            must be capped.
                                            and ready for system                  Pulling the P/PI jumper (see
     Note: Never adjust the                 operation.                            Fig. 16) off of its spigot causes
     ratio dial when the master
                                                                                  the receiver-controller to operate
     “M” Input pressure is at
                                       Gain Adjustment (See Fig. 14)              as proportional-only controller
     the midpoint of its
                                                                                  (no integral function). The
     working range (Example:           Adjusting the gain dial will not
                                                                                  jumper must be connected
     30°F on a 0 to 60°F range         affect the controller set point;
     or 7.2 PSIG per Fig. 12).
     No output signal change

                                                                             T-5800-3/T-5800-4 Technical Bulletin 7
8 T-5800-3/T-5800-4 Technical Bulletin
in order for the system to have        previously to obtain a master “M”               screw be sealed (using) a
normal proportional plus integral      input pressure reading, a master                small dab of fingernail
control.                               balance “R” pressure reading,                   polish).
                                       and a controlled variable “CV”
The T-5800-4 has an                                                               5.   Return the master “M” input
                                       input pressure reading.
automatic/manual integral                                                              pressure to the midpoint of
control cutout feature when the        1.   Apply a master “M” input                   the desired working range
fan “F” connection is used. This            pressure equal to the                      (Example: 30°F or 7.2 PSIG
feature keeps the system from               midpoint of the desired                    on a 0 to 60°F working
going out of control on startup             working range (Example:                    range per Fig. 6).
(after it’s been off for some time)         30°F on a 0 to 60°F working
by allowing the system to start             range or 7.2 PSIG as                  6.   Apply a controlled variable
up using proportional-only                  highlighted in Fig. 12).                   “CV” input pressure to the
control. If it is determined that                                                      value corresponding to the
there is not a need for the cutout     2.   Rotate the master balance                  7.2 PSIG master “M” input
feature, cap the unused fan “F”             screw (see Fig. 10) located                setting (Example: 140°F or 9
connection. Doing so will allow             in the center of the receiver-             PSIG per Fig. 6).
normal proportional plus integral           controller (clockwise to
                                            increase or counterclockwise          7.   Rotate the ratio dial (see
control of the system at all times,                                                    Fig. 13) to a position which
provided that the P/PI jumper is            to decrease) to produce a
                                            9 PSIG (63 kPa) gage                       most closely represents the
connected.                                                                             required ratio setting
                                            reading at the master
With the supply air ON, balance             balance “R” reference.                     (Example: 2:1, outer scale
the receiver-controller by setting          Doing so will shift the                    on dial and jumper in
the following:                              working range (internally) to              1:1 position).
                                            a more linear portion of the          8.   Adjust the local set point dial or
•   Pull the P/PI jumper off of its         ratio circuit.
    spigot so that the receiver-                                                       the remote adjuster (manual or
    controller will operate as a       3.   Vary the master input from                 automatic) to produce an
    proportional-only controller            minimum to maximum over                    output pressure on the
    (no integral function).                 its working range (Example:                controller gage equal to the
                                            0 to 60°F or 5.4 to 9 PSIG                 midpoint of the spring range of
•   Adjust the local set point dial                                                    the controlled device.
                                            per Fig. 6). Note: The
    or the remote adjuster
                                            master “M” INPUT is
    (manual or automatic) to
                                            limited to not less than              Ratio and Set Point Checkout
    produce 9 PSIG (63 kPa)
                                            2 PSIG nor greater than
    using the appropriate method                                                  1.   Apply the minimum master
    and gage as described                   17 PSIG. Note the pressure
                                            readings at the master                     “M” input pressure value
    previously.
                                            balance “R” reference                      (Example: 0°F or 5.4 PSIG
•   Install the ratio selection             corresponding to these                     per Fig. 6).
    jumper in the correct position          minimum and maximum                   2.   Apply the corresponding
    (see Fig. 15). If the                   points.                                    controlled variable “CV”
    calculated ratio is less than                                                      input pressure value
                                            If the minimum master
    or equal to 2.5:1 (as is the
                                            balance “R” pressure noted                 (Example: 200°F or
    case with the example where
                                            above is greater than or equal             12.6 PSIG per Fig 6).
    the calculated ratio is 2:1),
                                            to 5 PSIG and the maximum
    the jumper should be                                                          3.   Ratio Dial Adjustment:
                                            master balance “R” pressure
    installed in the 1:1 position.
                                            is less than 19 PSIG (with a               Note: Never adjust the ratio
    If the calculated ratio is
                                            20 PSIG supply), no further                dial when the master “M”
    greater than 2.5:1, the
                                            adjustments are required. If               Input pressure is at the
    jumper should be installed in
                                            the minimum master balance                 midpoint of its working
    the 3:1 position.
                                            “R” pressure is less than                  range (Example: 30°F on a
•   Turn the ratio dial so that “1:1        5 PSIG, rotate the master                  0 to 60°F range or 7.2 PSIG
    (3:1)” imprinted on the dial            balance screw (clockwise to                per Fig. 12). No output
    lines up with the dial                  increase) so that the minimum              signal change will occur
    reference point.                        pressure is greater than                   because the internal ratio
                                            5 PSIG and the maximum
                                                                                       circuitry is in a balanced
                                            does not exceed 19 PSIG.
Receiver-Controller Preset                                                             condition, and any previous
(See Example Fig. 6)                   4.   After removing the pressure                ratio dial setting (if not
                                            checking method from the                   marked) will be lost.
Utilize one of the pressure                 master balance “R”
checking methods described                                                             Adjust the ratio dial to cause
                                            reference, it is suggested
                                                                                       the receiver-controller
                                            that the master balance
                                                                                       output to be at the midpoint

                                                                             T-5800-3/T-5800-4 Technical Bulletin 9
     of the actual spring range of        reasonable gain adjustment               controlled variable deviation,
     the controlled device.               which would provide stability.           then return the set point dial to
                                          Increase the gain setting by             its original position producing the
4.   Apply the maximum master                                                      noted pressure. If the system
                                          small increments until the
     “M” input pressure value                                                      response is not as desired,
                                          system becomes unstable and
     (Example: 60°F or 9 PSIG             begins to cycle. Decrease the            adjust the integral time and gain
     per Fig. 6).                         gain setting slightly to remove          dials as prescribed above to
5.   Apply the corresponding              the cycling effect and mark this         obtain the desired system
     controlled variable “CV”             position on the dial. Rotate the         response.
     input pressure value                 dial fully clockwise until it hits its
     (Example: 80°F or                    mechanical stop, then                    System Startup Response
     5.4 PSIG per Fig. 6).                counterclockwise to the midpoint
                                          between the stop and the                 The following procedure is for
6.   Set Point Dial Adjustment:           marked position. Doing so will           determining whether an
                                          provide a suitable gain to allow         additional time delay is required
     Adjust the set point dial to                                                  for proper system startup.
     cause the output pressure to         the introduction of the integral
     be at the midpoint of the            function.
     actual spring range of the           After the system stabilizes again,            ! WARNING: Before
     controlled device.                   reconnect the P/PI jumper to                    stopping a system, be sure
                                          return the integral function to the             that a change in output
7.   Start up the system to be
                                          receiver-controller. After a                    pressure will not upset the
     controlled. After a
                                          reasonable period of time, the                  system and cause
     reasonable period of time,
                                          control point should stabilize at               damage.
     the receiver-controller
     should be in control (as a           the set point value and no further
     proportional-only controller)        adjustments will be required. If         A.    Receiver-controllers
     WITHIN the throttling range          the control point does not                     Using Fan “F” Connection
     of the controlled device.            stabilize at the set point value or
                                          if excessive cycling occurs,                   When the system becomes
8.   Proceed to the Gain                  proceed to the Integral Time                   stable, stop the system and
     Adjustment section.                  Adjustment section.                            allow enough time to pass
                                                                                         until the controlled variable
                                          Integral Time Adjustment                       deviates from the set point.
Gain Adjustment (See Fig. 17)                                                            (Remember when the system
                                          (See Figs. 17 & 18)
Note: All gain adjustments                                                               is off, the receiver-controller
                                          Adjusting the integral time dial               returns to proportional-only
must be made with the P/PI
                                          will not affect the controller set             control. This feature
jumper still removed from the
                                          point. If the system response                  eliminates integral windup
spigot.                                   toward the set point is too slow,              during off periods.) Restart
Adjusting the gain dial will not          decrease the integral time                     the system and observe to
affect the controller set point;          and/or increase the gain dial                  see how well it comes into
however, the output pressure              settings by small increment                    control. When the system is
may change when the gain dial             each. If cycling occurs,                       started and the fan signal is
is adjusted. Increasing the gain          increase the integral time and/or              increased to maximum
will narrow the throttling range          decrease the gain dial settings                (20 PSIG), the proportional-
(decrease offset), allowing the           by small increments each. Using                only controller returns to
control point to be closer to the         the appropriate pressure                       proportional plus integral
set point. Decreasing the gain            checking method described                      control to cause the control
will widen the throttling range,          previously, note the exact set                 point to equal the set point. If
forcing the control point away            point pressure value. Upset the                the system response is not as
from the set point.                       system by rotating the set point               desired, determine whether
                                          dial to force the controlled device            the cause is an improper time
                                          to an open position. Wait a                    delay (see T-5800-100 Time
                                          sufficient period of time to cause             Delay section) or an incorrect
                                                                                         integral time setting (repeat
                                                                                         Integral Time Adjustment
                                                                                         procedure above).

Normally, having the gain arrow
set at the pointer represents a

10 T-5800-3/T-5800-4 Technical Bulletin
B.   Receiver-Controllers                Note: If the system is                 proportional control function
     Having Fan “F”                      shut down (power failure,              settles out. To eliminate this
     Connection Capped                   cleaning, repair, etc.), the           problem, a T-5800-100 Time
     (System ON 100% of the              P/PI jumper must be                    Delay (ordered separately) must
     Time)                               disconnected and left                  be added to the fan “F”
                                         vented for a period of time            connection (see Fig 19). This
     When the system becomes                                                    device will delay the pressure
                                         equal to the integral time
     stable, stop the system and                                                increase to the fan “F”
                                         dial setting. Start up the
     disconnect the P/PI jumper.                                                connection of the receiver-
                                         system and reconnect the
     Allow enough time to pass                                                  controller, allowing more time for
     until the controlled variable       P/PI jumper when the
                                         system becomes stable.                 the system to achieve stable
     deviates from the set point.                                               proportional control before the
     Restart the system,                                                        integral control function is
     reconnect the P/PI jumper,                                                 initiated.
     and observe to see how well     T-5800-100 Time Delay (When
     the system comes into           Fan “F” Connection is Used)
     control. If the system          After system startup, if the
     response is not as desired,     system response is too slow, the
     repeat the Integral Time        integral control function will act
     Adjustment procedure            on the signal before the
     above.

 European Single Point of Contact:   NA/SA Single Point of Contact:         APAC Single Point of Contact:
 JOHNSON CONTROLS                    JOHNSON CONTROLS                       JOHNSON CONTROLS
 WESTENDHOF 3                        507 E MICHIGAN ST                      C/O CONTROLS PRODUCT
 45143 ESSEN                         MILWAUKEE WI 53202                     MANAGEMENT
 GERMANY                             USA                                    NO. 22 BLOCK D NEW DISTRICT
                                                                            WUXI JIANGSU PROVINCE
                                                                            214142
                                                                            CHINA

                                                                          T-5800-3/T-5800-4 Technical Bulletin 11
Controls Group
507 E. Michigan Street
P.O. Box 423                              Printed in U.S.A.
Milwaukee, WI 53202

12 T-5800-3/T-5800-4 Technical Bulletin

Позиції каталогу з цим документом

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.