SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

T-5800-1 and T-5800-2 Single Input Receiver-Controllers Installation and Calibration Technical Bulletin

Вид документаІнструкція з монтажу
ВиробникJCI
Код документаt-5800-1-and-t-5800-2-single-input-receiver-controllers-installation-and
Група обладнанняT-5800 Receiver-Controller
Сторінок8
Мова документаанглійська
Розмір файлу0.3 МБ

Текст документа

24- 7028- 6, Rev. A
                                                                             Technical Bulletin T-5800-1/-2
                                                                                         Issue Date 0316

                                        T-5800-1 and T-5800-2
                                  Single Input Receiver-Controllers
                                     Installation and Calibration

The T-5800 Series Receiver-
Controllers are designed for use
with remote temperature,
humidity, or pressure transmitters
(connected to the controlled
variable “CV” input) to provide
precise control of pneumatic
devices. The T-5800-1 is a single
input proportional-only receiver-
controller with field selectable
local or remote set point. The T-
5800-2 is also a single input
receiver-controller with field
selectable local or remote set
point; however, this model
provides proportional plus integral
(PI) control. In addition, an
automatic/manual integral control
                                        Fig. 1: T-5800-1 Single Input            Fig. 2: T-5800-2 Single Input
cutout feature is incorporated into
the T-5800-2 design. This               Proportional Receiver-Controller         PI Receiver-Controller
feature allows the system to start
up using proportional-only control
thus keeping the system from
going out of control on startup, as
is inherent to PI (automatic reset)
controllers, when the system has
been off for some time. Refer to
Product Data T-5800 for
instrument specifications and
additional details.

Installation
The T-5800 Series Receiver-
Controllers are designed for
surface mounting; refer to Fig. 3
for space requirements and
mounting details. All air line
connections are made to the units
through two snap-on input/output
connectors which have barbed
fittings for 1/4 in. O.D. polytubing.
Both single input models are
furnished with a clear cover,
snap-on air connectors, a .007 in.
orifice jumper, an additional set
point dial sticker marked with 50
graduations, and a yellow remote             Fig. 3: T-5800 Series Dimensions in./mm and Mounting Details
indication set point dial sticker.

© 2016 Johnson Controls, Inc.                                                                                 1
  Part No. 24-7028-6, Rev. A
  Code No. LIT-7171315X
Cover Removal
The cover can be removed by
applying an inward pressure to
one of the black tabs of the
receiver-controller main body to
unlatch it. The cover can also be
removed by simply taking hold of
the top and bottom sides of the
cover and pulling outward.

Oil Indicating Supply Air Filter
Check the oil indicating supply
air filter and replace as
necessary (A-4000-137 ordered
separately). When the filter is
dirty, a pressure drop will occur.
When filtering oil-contaminated
air, the filter will change from
white to red in color. If frequent
changes are necessary, check
the air supply system to
determine the cause of dirty or
oil-contaminated air.

Positioning the Action and
Orifice Jumpers
The T-5800 must be
programmed according to the
system requirements. Both
single input receiver-controllers        jumper when the caps are             Connect the tubing from the
are factory set in the direct            installed on the controlled          remote set point “SP” connection
acting mode and can be                   variable “CV” and supply “S”         of the snap-on input/output
changed to reverse acting by             spigots.                             connector. A low volume
interchanging the placement of                                                restricted source of supply air is
the tube ends from one lower                                                  automatically furnished;
                                         Set Point Selection - Local or
spigot to the other lower spigot                                              therefore, use 75% of the overall
                                         Remote
(see Figs. 9 and 12).                                                         line length that is recommended
Each single input T-5800 is              Local: The arrow on the              for a .005 in. orifice.
furnished with a .007 in. orifice        set point dial represents
jumper and two yellow spigot             approximately a 9 PSIG               FC and PRV Test Points
caps (see Fig. 4). The orifice           (63 kPa) set point pressure.
                                         The dial sticker is designed         The FC and PRV test points and
jumper provides a restricted
                                         so that the actual set point         their associated adjustments are
source of supply to low volume
non-relay type transmitters. For         can be written directly on its       for FACTORY USE ONLY.
best results, it is recommended          surface using a common
that this jumper be used when            pencil. Note: When local             Supply Air Interruptions
the low volume transmitter is            set point adjustment is
                                         used, the set point “SP”             Unlike the T-5800-1, the
located within 50 ft. (15m) of the                                            T-5800-2 has within its circuitry
receiver-controller. For all other       connection must be open
                                         to atmosphere.                       an automatic/manual integral
applications, it is recommended                                               control cutout feature which
that the spigots be capped and a         Remote: Rotate the set point         requires that the supply air
source of supply be furnished at         dial fully counterclockwise until    remain on at all times.
the transmitter. The non-                it hits its mechanical stop. Affix
functional master “M” spigot             the yellow dial sticker to
serves as a convenient storage           indicate remote set point
location for the unused orifice          adjustment mode (see Fig. 5).

2 T-5800-1/T-5800-2 Technical Bulletin
Calibration
General Instructions
Calibration and readjustment of
the T-5800 Receiver-Controller
should only be done by a
qualified Johnson Controls
representative, equipped with the
proper tools. An X-200-173
Calibration Kit (see Fig. 6,
ordered separately) is available
for making adjustments and
pressure checks on the
T-5800. This kit provides all of
the necessary gages, regulators,
and connectors for a more                     Fig. 6: X-200-173 Calibration Kit
convenient and quicker                   .
calibration procedure.
An X-200-140 Hypodermic
Needle Test Probe and
appropriate gage (see Fig. 7,
ordered separately) is also
available for troubleshooting, for
test point readings, or for final set
point adjustments under actual
job conditions. Note: Figure 8
illustrates an alternative
method of checking pressure
readings on the
T-5800 where use of a
hypodermic needle test probe
is prohibited.                               Fig. 7: X-200-140 Test Probe with Gage

Calibrating the T-5800-1
(See Fig. 9)
Set Point Adjustment
To make adjustments to the set
point, proceed as follows:
1.   Consult the system drawing to
     determine the required set
     point value. Convert this
     value to the pressure
     equivalent; see example
     highlighted in Fig. 10 (75°F on
     a 50 to 150°F range would be
     a set point of 6 PSIG).
2.   Take a set point pressure
     reading using the appropriate
     method and gage, as
     illustrated in Fig. 8. Adjust the
     local set point dial or the
     remote adjuster (manual or
     automatic) until the pressure
     matches the value noted in
     Step 1. Remove the pressure
     reading device and reconnect
     the jumper (if applicable).

                                                               T-5800-1/T-5800-2 Technical Bulletin 3
4 T-5800-1/T-5800-2 Technical Bulletin
3.   Start up the system to be      by small increments until the            function signal (minimum of
     controlled. After a            system becomes unstable and              12 PSIG) attached (example:
     reasonable period of time,     begins to cycle. Decrease the            fan on-off or water circulation
     the receiver-controller        gain setting slightly to remove          pump on-off), or the connection
     should be in control within    the cycling effect. Doing so will        must be capped.
     the throttling range of the    provide maximum controllability
                                                                             Putting the P/PI jumper (see
     controlled device.             with a minimum of offset.
                                                                             Fig. 13) off of its spigot causes
4.   Proceed to the Gain                                                     the receiver-controller to operate
     Adjustment section.                                                     as a proportional-only controller
                                                                             (no integral function). The
                                                                             jumper must be connected in
Gain Adjustment                                                              order for the system to have
(See Fig. 11)                                                                normal proportional plus integral
Adjusting the gain dial will not                                             control.
affect the controller set point;                                             The T-5800-2 has an
however, the output pressure                                                 automatic/manual integral
may change when the gain dial                                                control cutout feature when the
is adjusted. Increasing the gain                                             fan “F” connection is used. This
will narrow the throttling range                                             feature keeps the system from
(decrease offset), allowing the                                              going out of control on startup
control point to be closer to the                                            (after it’s been off for some time)
set point. Decreasing the gain      Calibrating the T-5800-2                 by allowing the system to start
will widen the throttling range,    (See Fig. 12)                            up using proportional-only
forcing the control point away                                               control. If it is determined that
from the set point.                 When connecting the T-5800-2
                                                                             there is not a need for the cutout
                                    Receiver-Controller to an
Normally, having the gain arrow                                              feature, cap the unused fan “F”
                                    operating system, the fan “F”
set at the pointer represents a                                              connection. Doing so will allow
                                    connection should either have
reasonable gain adjustment          the “system in operation”
which would provide stability.
Increase the gain setting

                                                                        T-5800-1/T-5800-2 Technical Bulletin 5
normal proportional plus integral
control of the system at all times,
provided that the P/PI jumper is
connected.

Set Point Adjustment
To make adjustments to the set
point, proceed a follows:
1.   Pull the P/PI jumper off of its
     spigot so that the receiver-
     controller will operate as a
     proportional-only controller
     (no integral function).
2.   Consult the system drawing
     to determine the required
     set point value. Convert this
     value to the pressure
     equivalent; see example
     highlighted in Fig. 10 (75°F
     on a 50 to 150°F range
     would be a set point of             control point to be closer to the        After the system stabilizes again,
     6 PSIG).                            set point. Decreasing the gain           reconnect the P/PI jumper to
                                         will widen the throttling range,         return the integral function to the
3.   Take a set point pressure           forcing the control point away           receiver-controller. After a
     reading using the appropriate       from the set point.                      reasonable period of time, the
     method and gage, as                                                          control point should stabilize at
     illustrated in Fig. 8. Adjust the   Normally, having the gain arrow
                                                                                  the set point value and no further
     local set point dial or the         set at the pointer represents a
                                                                                  adjustments will be required. If
     remote adjuster (manual or          reasonable gain adjustment
                                                                                  the control point does not
     automatic) until the pressure       which would provide stability.
                                                                                  stabilize at the set point value or
     matches the value noted in          Increase the gain setting by
                                                                                  if excessive cycling occurs,
     Step 2. Remove the pressure         small increments until the
                                                                                  proceed to the Integral Time
     reading device and reconnect        system becomes unstable and
                                                                                  Adjustment section.
     the jumper (if applicable).         begins to cycle. Decrease the
                                         gain setting slightly to remove
4.   Start up the system to be           the cycling effect and mark this         Integral Time Adjustment
     controlled. After a                 position on the dial. Rotate the         (See Figs. 14 & 15)
     reasonable period of time,          dial fully clockwise until it hits its   Adjusting the integral time dial
     the receiver-controller should      mechanical stop, then                    will not affect the controller set
     be in control (as a                 counterclockwise to the midpoint         point. If the system response
     proportional-only controller)       between the stop and the                 toward the set point is too slow,
     within the throttling range of      marked position. Doing so will           decrease the integral time
     the controlled device.              provide a suitable gain to allow         and/or increase the gain dial
5.   Proceed to the Gain                 the introduction of the integral         settings by small increments
     Adjustment section.                 function.                                each. If cycling occurs,
                                                                                  increase the integral time and/or
Gain Adjustment (See Fig. 14)                                                     decrease the gain dial settings
                                                                                  by small increments each.
Note: All gain adjustments
must be made with the P/PI                                                        Mark the set point dial position.
jumper still removed from the                                                     Upset the system by rotating the
spigot.                                                                           set point dial to force the controlled
                                                                                  device to an open position. Wait a
Adjusting the gain dial will not                                                  sufficient period of time to cause
affect the controller set point;                                                  controlled variable deviation, then
however, the output pressure                                                      return the set point dial to its
may change when the gain dial                                                     original position. If the system
is adjusted. Increasing the gain                                                  response is not as desired, adjust
will narrow the throttling range                                                  the
(decrease offset), allowing the

6 T-5800-1/T-5800-2 Technical Bulletin
integral time and gain dials as           deviates from the set point.                reconnect the P/PI jumper,
prescribed above to obtain the            (Remember when the system                   and observe to see how well
desired system response.                  is off, the receiver-controller             the system comes into
                                          returns to proportional-only                control. If the system
                                          control. This feature                       response is not as desired,
                                          eliminates integral windup                  repeat the Integral Time
                                          during off periods.) Restart                Adjustment procedure
                                          the system and observe to                   above.
                                          see how well it comes into
                                          control. When the system is
                                          started and the fan signal is           T-5800-100 Time Delay
                                          increased to maximum                    After system startup, if the
                                          (20 PSIG), the proportional-            system response is too slow, the
                                          only controller returns to              integral control function will act
                                          proportional plus integral              on the signal before the
                                          control to cause the control            proportional control function
                                          point to equal the set point. If        settles out. To eliminate this
System Startup Response
                                          the system response is not as           problem a T-5800-100 Time
The following procedure is for            desired, determine whether              Delay (ordered separately) must
determining whether an                    the cause is an incorrect time          be added to the fan “F”
additional time delay is required         delay setting (see T-5800-100           connection (see Fig. 16). This
for proper system startup.                Time Delay section) or an               device will delay the pressure
                                          incorrect integral time setting         increase to the fan “F”
                                          (repeat Integral Time                   connection of the receiver-
 !   WARNING: Before                      Adjustment procedure above).            controller, allowing more time for
     stopping a system, be sure
     that a change in output                                                      the system to achieve
                                     B.   Receiver-Controllers                    proportional control (in control)
     pressure will not upset the
                                          Having Fan “F”                          before the integral control
     system and cause
                                          Connection Capped                       function is initiated.
     damage.
                                          When the system becomes
                                          stable, stop the system and
A.   Receiver-Controllers
                                          disconnect the P/PI jumper.
     Using Fan “F” Connection
                                          Allow enough time to pass
     When the system becomes              until the controlled variable
     stable, stop the system and          deviates from the set point.
     allow enough time to pass            Restart the system,
     until the controlled variable

                                                                             T-5800-1/T-5800-2 Technical Bulletin 7
European Single Point of Contact:        NA/SA Single Point of Contact:   APAC Single Point of Contact:
JOHNSON CONTROLS                         JOHNSON CONTROLS                 JOHNSON CONTROLS
WESTENDHOF 3                             507 E MICHIGAN ST                C/O CONTROLS PRODUCT MANAGEMENT
45143 ESSEN                              MILWAUKEE WI 53202               NO. 22 BLOCK D NEW DISTRICT
GERMANY                                  USA                              WUXI JIANGSU PROVINCE 214142
                                                                          CHINA

Controls Group
507 E. Michigan Street
P.O. Box 423                                                                               Printed in U.S.A.
Milwaukee, WI 53202

8 T-5800-1/T-5800-2 Technical Bulletin

Позиції каталогу з цим документом

Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.