| Вид документа | Інструкція з монтажу |
|---|---|
| Виробник | JCI |
| Код документа | t-5800-1-and-t-5800-2-single-input-receiver-controllers-installation-and |
| Група обладнання | T-5800 Receiver-Controller |
| Сторінок | 8 |
| Мова документа | англійська |
| Розмір файлу | 0.3 МБ |
Текст документа
24- 7028- 6, Rev. A
Technical Bulletin T-5800-1/-2
Issue Date 0316
T-5800-1 and T-5800-2
Single Input Receiver-Controllers
Installation and Calibration
The T-5800 Series Receiver-
Controllers are designed for use
with remote temperature,
humidity, or pressure transmitters
(connected to the controlled
variable “CV” input) to provide
precise control of pneumatic
devices. The T-5800-1 is a single
input proportional-only receiver-
controller with field selectable
local or remote set point. The T-
5800-2 is also a single input
receiver-controller with field
selectable local or remote set
point; however, this model
provides proportional plus integral
(PI) control. In addition, an
automatic/manual integral control
Fig. 1: T-5800-1 Single Input Fig. 2: T-5800-2 Single Input
cutout feature is incorporated into
the T-5800-2 design. This Proportional Receiver-Controller PI Receiver-Controller
feature allows the system to start
up using proportional-only control
thus keeping the system from
going out of control on startup, as
is inherent to PI (automatic reset)
controllers, when the system has
been off for some time. Refer to
Product Data T-5800 for
instrument specifications and
additional details.
Installation
The T-5800 Series Receiver-
Controllers are designed for
surface mounting; refer to Fig. 3
for space requirements and
mounting details. All air line
connections are made to the units
through two snap-on input/output
connectors which have barbed
fittings for 1/4 in. O.D. polytubing.
Both single input models are
furnished with a clear cover,
snap-on air connectors, a .007 in.
orifice jumper, an additional set
point dial sticker marked with 50
graduations, and a yellow remote Fig. 3: T-5800 Series Dimensions in./mm and Mounting Details
indication set point dial sticker.
© 2016 Johnson Controls, Inc. 1
Part No. 24-7028-6, Rev. A
Code No. LIT-7171315X
Cover Removal
The cover can be removed by
applying an inward pressure to
one of the black tabs of the
receiver-controller main body to
unlatch it. The cover can also be
removed by simply taking hold of
the top and bottom sides of the
cover and pulling outward.
Oil Indicating Supply Air Filter
Check the oil indicating supply
air filter and replace as
necessary (A-4000-137 ordered
separately). When the filter is
dirty, a pressure drop will occur.
When filtering oil-contaminated
air, the filter will change from
white to red in color. If frequent
changes are necessary, check
the air supply system to
determine the cause of dirty or
oil-contaminated air.
Positioning the Action and
Orifice Jumpers
The T-5800 must be
programmed according to the
system requirements. Both
single input receiver-controllers jumper when the caps are Connect the tubing from the
are factory set in the direct installed on the controlled remote set point “SP” connection
acting mode and can be variable “CV” and supply “S” of the snap-on input/output
changed to reverse acting by spigots. connector. A low volume
interchanging the placement of restricted source of supply air is
the tube ends from one lower automatically furnished;
Set Point Selection - Local or
spigot to the other lower spigot therefore, use 75% of the overall
Remote
(see Figs. 9 and 12). line length that is recommended
Each single input T-5800 is Local: The arrow on the for a .005 in. orifice.
furnished with a .007 in. orifice set point dial represents
jumper and two yellow spigot approximately a 9 PSIG FC and PRV Test Points
caps (see Fig. 4). The orifice (63 kPa) set point pressure.
The dial sticker is designed The FC and PRV test points and
jumper provides a restricted
so that the actual set point their associated adjustments are
source of supply to low volume
non-relay type transmitters. For can be written directly on its for FACTORY USE ONLY.
best results, it is recommended surface using a common
that this jumper be used when pencil. Note: When local Supply Air Interruptions
the low volume transmitter is set point adjustment is
used, the set point “SP” Unlike the T-5800-1, the
located within 50 ft. (15m) of the T-5800-2 has within its circuitry
receiver-controller. For all other connection must be open
to atmosphere. an automatic/manual integral
applications, it is recommended control cutout feature which
that the spigots be capped and a Remote: Rotate the set point requires that the supply air
source of supply be furnished at dial fully counterclockwise until remain on at all times.
the transmitter. The non- it hits its mechanical stop. Affix
functional master “M” spigot the yellow dial sticker to
serves as a convenient storage indicate remote set point
location for the unused orifice adjustment mode (see Fig. 5).
2 T-5800-1/T-5800-2 Technical Bulletin
Calibration
General Instructions
Calibration and readjustment of
the T-5800 Receiver-Controller
should only be done by a
qualified Johnson Controls
representative, equipped with the
proper tools. An X-200-173
Calibration Kit (see Fig. 6,
ordered separately) is available
for making adjustments and
pressure checks on the
T-5800. This kit provides all of
the necessary gages, regulators,
and connectors for a more Fig. 6: X-200-173 Calibration Kit
convenient and quicker .
calibration procedure.
An X-200-140 Hypodermic
Needle Test Probe and
appropriate gage (see Fig. 7,
ordered separately) is also
available for troubleshooting, for
test point readings, or for final set
point adjustments under actual
job conditions. Note: Figure 8
illustrates an alternative
method of checking pressure
readings on the
T-5800 where use of a
hypodermic needle test probe
is prohibited. Fig. 7: X-200-140 Test Probe with Gage
Calibrating the T-5800-1
(See Fig. 9)
Set Point Adjustment
To make adjustments to the set
point, proceed as follows:
1. Consult the system drawing to
determine the required set
point value. Convert this
value to the pressure
equivalent; see example
highlighted in Fig. 10 (75°F on
a 50 to 150°F range would be
a set point of 6 PSIG).
2. Take a set point pressure
reading using the appropriate
method and gage, as
illustrated in Fig. 8. Adjust the
local set point dial or the
remote adjuster (manual or
automatic) until the pressure
matches the value noted in
Step 1. Remove the pressure
reading device and reconnect
the jumper (if applicable).
T-5800-1/T-5800-2 Technical Bulletin 3
4 T-5800-1/T-5800-2 Technical Bulletin
3. Start up the system to be by small increments until the function signal (minimum of
controlled. After a system becomes unstable and 12 PSIG) attached (example:
reasonable period of time, begins to cycle. Decrease the fan on-off or water circulation
the receiver-controller gain setting slightly to remove pump on-off), or the connection
should be in control within the cycling effect. Doing so will must be capped.
the throttling range of the provide maximum controllability
Putting the P/PI jumper (see
controlled device. with a minimum of offset.
Fig. 13) off of its spigot causes
4. Proceed to the Gain the receiver-controller to operate
Adjustment section. as a proportional-only controller
(no integral function). The
jumper must be connected in
Gain Adjustment order for the system to have
(See Fig. 11) normal proportional plus integral
Adjusting the gain dial will not control.
affect the controller set point; The T-5800-2 has an
however, the output pressure automatic/manual integral
may change when the gain dial control cutout feature when the
is adjusted. Increasing the gain fan “F” connection is used. This
will narrow the throttling range feature keeps the system from
(decrease offset), allowing the going out of control on startup
control point to be closer to the (after it’s been off for some time)
set point. Decreasing the gain Calibrating the T-5800-2 by allowing the system to start
will widen the throttling range, (See Fig. 12) up using proportional-only
forcing the control point away control. If it is determined that
from the set point. When connecting the T-5800-2
there is not a need for the cutout
Receiver-Controller to an
Normally, having the gain arrow feature, cap the unused fan “F”
operating system, the fan “F”
set at the pointer represents a connection. Doing so will allow
connection should either have
reasonable gain adjustment the “system in operation”
which would provide stability.
Increase the gain setting
T-5800-1/T-5800-2 Technical Bulletin 5
normal proportional plus integral
control of the system at all times,
provided that the P/PI jumper is
connected.
Set Point Adjustment
To make adjustments to the set
point, proceed a follows:
1. Pull the P/PI jumper off of its
spigot so that the receiver-
controller will operate as a
proportional-only controller
(no integral function).
2. Consult the system drawing
to determine the required
set point value. Convert this
value to the pressure
equivalent; see example
highlighted in Fig. 10 (75°F
on a 50 to 150°F range
would be a set point of control point to be closer to the After the system stabilizes again,
6 PSIG). set point. Decreasing the gain reconnect the P/PI jumper to
will widen the throttling range, return the integral function to the
3. Take a set point pressure forcing the control point away receiver-controller. After a
reading using the appropriate from the set point. reasonable period of time, the
method and gage, as control point should stabilize at
illustrated in Fig. 8. Adjust the Normally, having the gain arrow
the set point value and no further
local set point dial or the set at the pointer represents a
adjustments will be required. If
remote adjuster (manual or reasonable gain adjustment
the control point does not
automatic) until the pressure which would provide stability.
stabilize at the set point value or
matches the value noted in Increase the gain setting by
if excessive cycling occurs,
Step 2. Remove the pressure small increments until the
proceed to the Integral Time
reading device and reconnect system becomes unstable and
Adjustment section.
the jumper (if applicable). begins to cycle. Decrease the
gain setting slightly to remove
4. Start up the system to be the cycling effect and mark this Integral Time Adjustment
controlled. After a position on the dial. Rotate the (See Figs. 14 & 15)
reasonable period of time, dial fully clockwise until it hits its Adjusting the integral time dial
the receiver-controller should mechanical stop, then will not affect the controller set
be in control (as a counterclockwise to the midpoint point. If the system response
proportional-only controller) between the stop and the toward the set point is too slow,
within the throttling range of marked position. Doing so will decrease the integral time
the controlled device. provide a suitable gain to allow and/or increase the gain dial
5. Proceed to the Gain the introduction of the integral settings by small increments
Adjustment section. function. each. If cycling occurs,
increase the integral time and/or
Gain Adjustment (See Fig. 14) decrease the gain dial settings
by small increments each.
Note: All gain adjustments
must be made with the P/PI Mark the set point dial position.
jumper still removed from the Upset the system by rotating the
spigot. set point dial to force the controlled
device to an open position. Wait a
Adjusting the gain dial will not sufficient period of time to cause
affect the controller set point; controlled variable deviation, then
however, the output pressure return the set point dial to its
may change when the gain dial original position. If the system
is adjusted. Increasing the gain response is not as desired, adjust
will narrow the throttling range the
(decrease offset), allowing the
6 T-5800-1/T-5800-2 Technical Bulletin
integral time and gain dials as deviates from the set point. reconnect the P/PI jumper,
prescribed above to obtain the (Remember when the system and observe to see how well
desired system response. is off, the receiver-controller the system comes into
returns to proportional-only control. If the system
control. This feature response is not as desired,
eliminates integral windup repeat the Integral Time
during off periods.) Restart Adjustment procedure
the system and observe to above.
see how well it comes into
control. When the system is
started and the fan signal is T-5800-100 Time Delay
increased to maximum After system startup, if the
(20 PSIG), the proportional- system response is too slow, the
only controller returns to integral control function will act
proportional plus integral on the signal before the
control to cause the control proportional control function
point to equal the set point. If settles out. To eliminate this
System Startup Response
the system response is not as problem a T-5800-100 Time
The following procedure is for desired, determine whether Delay (ordered separately) must
determining whether an the cause is an incorrect time be added to the fan “F”
additional time delay is required delay setting (see T-5800-100 connection (see Fig. 16). This
for proper system startup. Time Delay section) or an device will delay the pressure
incorrect integral time setting increase to the fan “F”
(repeat Integral Time connection of the receiver-
! WARNING: Before Adjustment procedure above). controller, allowing more time for
stopping a system, be sure
that a change in output the system to achieve
B. Receiver-Controllers proportional control (in control)
pressure will not upset the
Having Fan “F” before the integral control
system and cause
Connection Capped function is initiated.
damage.
When the system becomes
stable, stop the system and
A. Receiver-Controllers
disconnect the P/PI jumper.
Using Fan “F” Connection
Allow enough time to pass
When the system becomes until the controlled variable
stable, stop the system and deviates from the set point.
allow enough time to pass Restart the system,
until the controlled variable
T-5800-1/T-5800-2 Technical Bulletin 7
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS
WESTENDHOF 3 507 E MICHIGAN ST C/O CONTROLS PRODUCT MANAGEMENT
45143 ESSEN MILWAUKEE WI 53202 NO. 22 BLOCK D NEW DISTRICT
GERMANY USA WUXI JIANGSU PROVINCE 214142
CHINA
Controls Group
507 E. Michigan Street
P.O. Box 423 Printed in U.S.A.
Milwaukee, WI 53202
8 T-5800-1/T-5800-2 Technical BulletinПозиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.
