                                                                                    Product/Technical Bulletin
                                                                                                  Issue Date March 2016

                T-3100, T-3200, and T-3300 Series Controllers

The T-3100 and T-3300 Series proportional action                                                           W ARM

pneumatic thermostats are designed to maintain
temperature in accordance with the return air
temperature in terminal air conditioning units. The
T-3200 Series of pneumatic thermostats are designed
to control pneumatic actuators in single temperature,
dual pressure applications.

The T-3111 and T-3311 Series controllers are
combination pneumatic thermostats and valve
actuators. The T-3111 provides proportional control of
a steam or water valve on a single temperature
application, while the T-3311 provides control in              Figure 1: T-3100 Remote Mounted Thermostat and
dual temperature, dual pressure applications.                             T-3311 Valve Top Thermostat

                                              Features and Benefits
                   Models are Available in           Allows seasonal change over from cooling to
                       Direct-reverse Acting or       heating or heating to cooling automatically
                       Reverse-direct Acting

                   Direct or Reverse Acting          Suits heating or cooling applications
                       Models Available with Liquid
                       Filled Temperature
                       Measuring Elements

                   Models Available with an          Field adjustable or concealed to maintain system
                       External or Concealed          design as commissioned
                       Setpoint Adjusting Screw

                   Valve Top Models                  The T-3111 and T-3311 are direct replacements
                       Compatible with                for the T-3110 and T-3310 Series Valve Top
                       VG7000 Series Valves           Actuators

© 2016 Johnson Controls, Inc.                                                                                         1
  Part No. 14-1104-0, Rev. A
  Code No. LIT-7171156
O rdering Information
    Table 1: Ordering Information
             Code             Action                        Setpoint
                                               Element                  Mounting      Application
            Number        (Proportional)                   Adjustment
            T-3100-2   Direct Acting           Bulb        External     Remote      Single Temperature
            T-3100-3   Reverse Acting
            T-3111-1   Direct Acting
            T-3111-2   Reverse Acting          Bulb        External
            T-3111-3   Direct Acting           Averaging   External     Valve Top   Single Pressure
            T-3111-6   Direct Acting                       Concealed
                       DIR at 15 and 20 psig                                        Single Temperature
            T-3200-1                           Averaging   Concealed    Remote
                       (103/138 kPa)                                                Dual Pressure
                       DIR at 15 psig
            T-3300-1   (103 kPa)
                       REV at 20 psig
                       (138 kPa)               Bulb        External     Remote      Dual Temperature
                       DIR at 20 psig
            T-3300-2   (138 kPa)                                                    Dual Pressure
                       REV at 15 psig
                       (103 kPa)
                       DIR at 15 psig
            T-3311-1   (103 kPa)
                       REV at 20 psig
                       (138 kPa)               Bulb        External     Valve Top   Dual Temperature
                       DIR at 20 psig
            T-3311-2   (138 kPa)                                                    Dual Pressure
                       REV at 15 psig
                       (103 kPa)

2 T-3100, T-3200, and T-3300 Series Controllers Product/Technical Bulletin
D imensions
                                                                                      5-1/8
                                                              Extends to maximum                       Subordinate
                                                                                       130
                                                                                                    Connection 1/8 inch
                                     3-3/8                              4-3/4                       NPT, Internal Thread
                                      86                                 121
                         5/8
                         16                                                                      Supply Air to
                                                                                                  Restrictor
                                                                                                   Branch
          3/4     1/4
                   6                                                                                             Restrictor
          19
                                                                                                                  Branch
                                                    4-3/4
       3                                                                                                          Marked
                                                     121
       76 1-1/2
           38
                                                                                                                   Control Air
                  1/4
                   6                                                                                     3/4
                                                                                                         19

                                                                                       5-11/16
                                    42                                                   144
                  Capillary Length
                                   1067                                 Extends to maximum 8-11/16
                                                                                             220
                                                               6-9/16
                                                                167

                                                            5/16
                                                                 Diameter
                                                             8

                        Figure 2: Dimensions and Mounting Details for T-3100, in./mm

                                                 3-1/16
                                                   78         4-3/4                  Barbed
                                                               120                 Restrictor Tee

                                                                                    Subordinate
                                                                                    Connection
                                                                                   1/8 inch NPT,
                                                                                  Internal Thread
                                                 4-7/16
                                                  113                              Sealing Cap
                                                                                  (Open Branch)
                         Capillary Length 18
                                          457
                                                              2-1/4
                                                                                Supply Air Connection
                                                               57
                                                                                 (Restrictor Branch)

                                                                         96
                                             Averaging Element Length
                                                                        2438

                               Figure 3: Concealed Adjustment for T-3111, in./mm

                                          T-3100, T-3200, and T-3300 Series Controllers Product/Technical Bulletin               3
                                                  3-3/16
                                                    80                4-3/4                    Barbed
                                                                       121                   Restrictor Tee

                                                                                                Subordinate
                                                                                                Connection
                                                                                               1/8 inch NPT,
                                                                                              Internal Thread
                                                  4-9/16
                                                   116                                        Sealing Cap
                                                                                             (Open Branch)

                                           42                         2-1/4
                          Capillary Length 1067                                           Supply Air Connection
                                                                       57
                                                                                           (Restrictor Branch)
                                                                           6-9/16
                                                                            167

                                                                    5/16
                                                                         Diameter
                                                                     8

                                Figure 4: Exposed Adjustment for T-3111, in./mm

                                                  COOL

                                                           WAR
                                                              M

                                                                                             Supply
                                                                                             Air
                                                                                    3/4
                                                                                    19

                                                                  5-3/16
                                                                   132

                                  Figure 5: Mounting Details for T-3111, in./mm

4 T-3100, T-3200, and T-3300 Series Controllers Product/Technical Bulletin
                                                                4-3/4            5-1/8
                                                                      to maximum
                                                                 121              130

                                                                                                 Barbed Restrictor
                                                                                                   Tee Supply
                                                                                                (Restrictor Branch)
                                                                                                     Marked
                            3-1/8
                             79
                                                                                                   Output
                   5/8                                                                          (Open Branch)
                   16

     3/4     1/4                                                                                     Switching Air
     19       6                                                                                      Connection
                                                   5-1/2
3                                                   140
76
     1-1/2
      38

             1/4
              6                                                                                         13/16
                                                                                                         21

                                                                       5-13/16            8-13/16
                                                                               to maximum
                                                                         148                224
             Capillary Length 18
                             457

                                                                        96
                                         Averaging Element Length
                                                                       2438

              Figure 6: Dimensions and Mounting Details for T-3200, in./mm

                                          3-1/16                                 Supply Air
                                            78                              Straight Connector
                                                             4-3/4           for 1/4 inch O.D.
                                                              121          Polyethylene Tubing

                                                                                Subordinate
                                                                                Connection
                                                                               1/8 inch NPT,
                                                                              Internal Thread
                                          4-9/16
                                           116

                                   42
               Capillary Length                             2-1/4
                                  1067
                                                             57
                                                              6-9/16
                                                               167

                                                           5/16
                                                                Diameter
                                                            8

                     Figure 7: Exposed Dimensions for T-3311, in./mm

                                  T-3100, T-3200, and T-3300 Series Controllers Product/Technical Bulletin            5
                                                                           4-3/4 to maximum 5-1/8
                                                                            121              130

                                          3-3/8
                                           86

                                                                                                           Output
                                 5/8                                                                   Air Connection
                                 16

                   3/4     1/4                                                                                  Supply Air
                   19       6                                                                                   Connection
                                                       5-9/16
               3                                        141
              76
                   1-1/2
                    38

                           1/4
                            6                                                                                    13/16
                                                                                                                  21

                                               42                                  5-13/16 to maximum 8-13/16
                           Capillary Length                                          148                224
                                              1067

                                                                          6-9/16
                                                                           167

                                                                       5/16
                                                                            Diameter Bulb
                                                                         8

                            Figure 8: Dimensions and Mounting Details for T-3300, in./mm

                                                     COOL

                                                               HEA T

                                                                                       3/16
                                                                                        21

                                                            5-5/16
                                                             135

                                       Figure 9: Mounting Details for T-3311, in./mm

6 T-3100, T-3200, and T-3300 Series Controllers Product/Technical Bulletin
I nstallation Procedures
Tubing Installation
The T-3100, T-3200, and T-3300 Series Thermostats                  Route the capillary so it is not in contact with
are supplied with barbed fittings for the supply and the           extremely high or low temperature sources such as
output air connections. It is recommended that Type                steam lines, water pipes, or coils. Be sure to route the
“FR” polyethylene tubing be used on the barbed                     element and capillary so that routine maintenance can
fittings.                                                          be performed on the terminal unit without disturbing
                                                                   the element.
Note:    Cut tubing off square for a good fit on the
         barbed fitting.
If “HP” or copper tubing is used, the barbed fitting               Bulb Element
must be removed and replaced with a compression                    In most cases, a bulb element will be installed in the
fitting and an in-line restrictor when necessary.                  return air chamber of the terminal air unit in the
Note:    Figure 10 illustrates a copper tubing                     following manner:
         installation; “HP” tubing installation is the             1. Install the element behind the protective screen or
         same except the brass ferrule is replaced with               grille and in a location where normal maintenance
         a thermoplastic ferrule, which is supplied with              may be performed on the unit without interference.
         the R-3710-1007 restrictor.
                                                                   2. Be sure the bulb will sense only the return air and
                                                                      will not be influenced by other temperatures.
                         .007 inch In-Line
                       Restrictor with O-Ring                      3. Secure the bulb using holder, T-275-100 (ordered
                                   1/8 inch NPT, Internal Thread      separately) which can be hung or fastened in
              Brass Ferrule            Supply Air Connection          place and bent to the desired position.
            (Field Furnished)

 Air
 Flow
                  Compression
   1/4 inch O.D.     Nut                                                                                  Holder
                              Standard Compression
Soft Copper Tubing           Fitting (Field Furnished)

                                                                                     Bulb
         Figure 10: Copper Tubing Installation
          (Use R-3710-1007 In-Line Restrictor)
                                                                                                         5/16
                                                                                                              Diameter Hole
                                                                                                          8

Sensing Elements                                                                             8
                                                                                            203
Both the bulb and the averaging sensing element must
be carefully located so the elements measure only the                   Figure 11: Bulb Element Holder Dimensions,
intended air temperature. The majority of terminal air                     in./mm (T-275-100, ordered separately)
condition units are very compact and little clearance
exists between coils. Also, the air flows are of widely
varying temperature. Before selecting an element
location, study the unit interior and make certain that
the sensing element will not be affected by
undesirable temperatures or mechanical damage.
Avoid extremely sharp bends in the capillary which
could obstruct the liquid flow.

                                                T-3100, T-3200, and T-3300 Series Controllers Product/Technical Bulletin      7
Averaging Element                                            C alibration Procedures
In most cases, an averaging element will be installed        All Johnson Controls instruments are carefully tested
in the air chamber of the terminal air unit in the           and calibrated at the factory before shipment. If field
following manner:                                            calibration is required, it should not be started until all
                                                             installation procedures are complete. If, during
1. Install the element in a serpentine fashion across        calibration, the temperature at the measuring element
   the top of the unit coil.                                 fluctuates, place the element in a stable, well-
2. Secure the element along the entire length by             controlled temperature area such as a bucket of water,
   using holders, T-275-101 (ordered separately), so         preferably 75F (24C) for controllers and
   that no part of the element touches the coil. The         56F (13C) for low limit controllers.
   holder is very flexible and can be bent to any
                                                             Be sure the supply air to the instrument is clean and
   desired position.
                                                             free of moisture. The adjusting dial is graduated in
3. On face and bypass units, the element must be             1F increments and can be removed with a flexible
   placed in the space where a mixing of coil                hex head screwdriver (JC 5309, ordered separately).
   discharge air (face) and coil bypass air takes            It is recommended that the middle graduation be used
   place. Install the element as close as possible to        to represent the desired temperature setpoint.
   the bottom side of the discharge air grille. The
                                                             The adjusting screw for externally adjusted,
   element should be secured by using holders
                                                             Direct Acting (DIR) models is located inside the dial
   (T-275-101, ordered separately) fastened to the
                                                             post and is accessible by removing the dial (refer to
   unit casing.
                                                             Figure 13, Detail A). For DIR models with concealed
    For ASHRAE Cycle III applications, the element           adjustment, it is necessary to remove the small metal
    must be installed in the mixed air (outside and          button in the cover (refer to Figure 13, Detail B). A
    return) rather than in the discharge air. Install the    calibration tool (T-4002-5009, ordered separately)
    element so it will receive the best possible             should be used to adjust the setpoint on these models.
    sampling of the mixture temperature using holders
                                                             It is necessary to remove the dial and cover for models
    (T-275-101, ordered separately) fastened to the
                                                             with either Reverse Acting (REV) or low limit
    unit casing.
                                                             adjustments. Use a calibration tool (T-4002-5009,
                                                             ordered separately) for Reverse Acting adjustment of
            Bend prongs around                               the T-3100 and T-3300 Series Thermostats (refer to
             bulb or capillary.
                                                             Figure 13, Detail C).
                                                             Be sure each T-3100 and T-3111 Thermostat has a
                                                             0.007 inch in-line restrictor installed in the supply air
                  2-1/4            Twist here
                                                             connection. The T-3200 instruments should have a
                   57              if required.
     3/16                                                    0.007 inch in-line restrictor in the air line between the
       5                                   Slip prongs       instrument and the room thermostat.
                                           over coil fin.
             1
             25
                                                  Coil Fin

 Figure 12: Averaging Element Holder Dimensions,
       in./mm (T-275-101, ordered separately)

8 T-3100, T-3200, and T-3300 Series Controllers Product/Technical Bulletin
                                        Temperature Set Point
                                           Adjusting Dial
                                                                                         Flexible Driver
                                                                                  JC 5309 (Ordered Separately)

                                                                                Low Limit Setpoint
                                                                                Adjustment on Two
                                                                                Element Controllers

                   Switch Stack
                 Not Furnished on
                  T-3100 Series

                                                                                            Recalibration Tool
                                                                                       JC 5360 (ordered separately)

                                                         (Output Test Port)
                                                          Test Connection

                                                              For Concealed
                                                                or Remote
                                                            Adjustment Models

                                                   For External
                                                Adjustment Models

                                                                                             Direct Acting
    Direct Acting                                                 Reverse Acting         Set Point Adjustment
Set Point Adjustment                                            Set Point Adjustment          (Detail B)
     (Detail A)                                                      (Detail C)

                                    Figure 13: Setpoint Adjusting Features

                                      T-3100, T-3200, and T-3300 Series Controllers Product/Technical Bulletin        9
Temperature Setpoint Adjustment
For T-3100 and T-3200 Series follow                        For T-3300 Series proceed as follows:
Steps 1 through 7.
                                                           1. Supply the instrument with the appropriate air
1. Supply the instrument with the proper supply air           pressure for the Direct Acting (DIR) operation.
   pressure.
                                                           2. Insert the test gauge (JC 5310, ordered
2. Insert the test gauge (JC 5310, ordered                    separately) and the probe assembly (JC 5361,
   separately) and the probe assembly (JC 5361,               ordered separately) into the test port
   ordered separately) into the output test port.             (as illustrated in Figure 14).
Note:   For Reverse Acting thermostats it will be          3. Remove the knob and cover.
        necessary to remove the cover in order to turn
                                                           4. Turn the DIR screw until the output pressure is in
        the setpoint adjustment screw.
                                                              the middle of the actuator operating range.
3. Turn the setpoint adjustment screw until the
                                                           5. Change the supply air pressure to that required for
   pressure reading is approximately in the middle of
                                                              the Reverse Acting (REV) operation.
   the operating range of the actuator. For example,
   a 5 to 10 psig operating range would require an         6. Turn the REV adjusting screw until the output
   output pressure reading of 7.5 psig.                       pressure is in the middle of the actuator operating
                                                              range.
4. Remove the test gauge and probe assembly.
                                                           7. Remove the test gauge and probe assembly.
5. Determine the temperature at the measuring
   element.                                                8. Determine the temperature at the element.
6. Place the dial on the dial post (do not tighten) and    9. Attach the cover.
   position it to the temperature at the element.
                                                           10. Place the dial on the dial post (do not tighten) and
   Remember that each dial increment represents
                                                               position it to the temperature at the element.
   one Fahrenheit degree. For models with
   concealed adjustment, use recalibration tool            11. Tighten the dial and turn to the desired setpoint.
   JC 5360 (ordered separately).
                                                           Note:   If the setpoints of several instruments are to
7. Tighten the dial and turn it to the desired setpoint.           be adjusted before switching the supply
                                                                   pressure, be sure that the temperature at the
    Example:    If the desired temperature setpoint is
                                                                   element will not change during both stages of
                75F and the temperature at the
                                                                   adjustment.
                element is 71F, then place the dial on
                the dial post (do not tighten) and
                position it to 71F or four graduations
                (75F-71F = 4F) clockwise from the
                middle graduation (75F), the desired
                setpoint.
Note:   For T-3200 Series the low limit setpoint is
        56F. Use calibration tool T-4002-5009
        (ordered separately). Each graduation is
        9F (5C).

10 T-3100, T-3200, and T-3300 Series Controllers Product/Technical Bulletin
                                                   Test Probe Assembly
                                               (JC 5361, ordered separately)

                                                       Test Gauge
                                               (JC 5310, ordered separately)

Output Pressure
                                                                           15
   Test Port                                      1/8 inch          10           20
                                                 NPT, Internal
                                                   Thread          5             25

                                                                       0        30

                                     Figure 14: Test Gauge

                                      Temperature at Element
                                          71°F (22°C)

                        se
               k    w
                    i
             Clo                         H
                c        CO                T
                            OL           EA

                                                75°F (24°C) Desired
                                                Temperature Setting

               Mid-point of Dial
                 75°F (24°C)
                              Pointer
                                         H
                             CO            T
                                OL       EA

          Figure 15: Temperature Setpoint Dial

           T-3100, T-3200, and T-3300 Series Controllers Product/Technical Bulletin   11
                                                           M aintenance and
Restricted Adjustment                                      Troubleshooting Procedures
The dial pointer on externally adjusted models has         These instruments are designed so that a minimum of
tabs which are factory set to restrict the dial            routine maintenance is required. The following
adjustment to a span of 15F (7.5F on either side of      procedures should be used to ensure proper operation
the pointer). The restriction can be changed to the        and to locate malfunctioning components:
spans indicated in Table 2 by bending up the               1. Check all air lines, connections, and diaphragms
appropriate tabs and flattening the factory set tabs.         for air leaks. Make sure that the in-line restrictors
Table 2: Span Adjustment                                      are not defective.

            Span                       Tab                 2. Check the operation of the thermostat to be sure it
                                                              is passing the correct control signal and that it is
     F            C         F              C              functioning properly. Make sure it has the proper
     20            11.1        + 10           + 5.6           supply air pressure and that air is exhausting from
     15            8.3         + 7.5          + 4.2
                                                              the control port. The port must exhaust
                                                              continuously to ensure proper operation of the
     10            5.6         +5             + 2.8           thermostat.
                                                           3. Check that the temperature measuring element
     5             2.8         + 2.5          + 10
                                                              has not been damaged or moved from its intended
                                             10°F             sensing position.
                                             7.5°F         4. Check that the valve packing nut is tight enough to
                                             5°F              prevent leaks, but not so tight that the packing
                                             2.5°F            becomes distorted and binds the stem; usually
                                                              finger tight is sufficient. If the valve is leaking
          10°F                                                around the centerpiece, tighten it with the
                                                              appropriate wrench.
         7.5°F
                                                           5. Verify that the valve seats completely when the
           5°F
                                                              actuator is fully stroked. If there is fluid flow after
         2.5°F                                                the plug is seated, the seat, plug, or disc may be
                                                              worn or scored and should be repaired or
            Figure 16: Restricted Adjustment                  replaced.
                                                           6. If there are subordinate actuators, make sure the
                                                              actuators are operating in the proper sequence
                                                              and adjusted correctly.

12 T-3100, T-3200, and T-3300 Series Controllers Product/Technical Bulletin
A ccessories
Table 3: Accessories (Order Separately)
          Description               Code Number
Hex Head Flexible Screwdriver     JC 5309
Control Line Test Gauge and
                                  JC 5310
Adaptor
Recalibration Tool                JC 5360                               Figure 17: QEO-1, Averaging
Test Probe Assembly               JC 5361                                      Element Holder
                                  Order QEO-1 from
                                  Temperature Control
Averaging Element Holder for      Specialties
3 inch (76 mm) Coil               2800 Laura Lane
(See Figure 17.)                  Middleton, WI 53562
                                  (608) 836-9034
Restrictor Tee (.007 inch)        R-3710-1007
“B” Bulb Holder                   T-275-100
Averaging Element Holding Clip    T-275-101
Supply Inlet Filter
                                  T-3100-605
(Order in multiples of 100.)
Calibration Tool                  T-4002-5009
Averaging Element Holder for
                                  TE-6001-8
Radius Bends (minimum 3-1/2 in.
(See Figure 18.)                                                            Figure 18: TE-6001-8,
Diaphragm for Exposed Actuator                                            Averaging Element Holder
                                  V-3000-600
V-3000-1 only

                                       T-3100, T-3200, and T-3300 Series Controllers Product/Technical Bulletin   13
R epair Procedures
                                                                                               Thermostat
Actuators
To replace the diaphragm, follow Steps 1 through 7
below.                                                                                         Diaphragm
                                                                                               V-3000-600
1. Remove the eight screws holding the thermostat
   to the integral actuator.
2. Lift the thermostat exposing the diaphragm and
   remove the piston.
                                                                                              Piston
3. Turn the new diaphragm inside out and place it
   over the piston. Smooth out all of the wrinkles and
   release any air trapped between the head of the                                            Spider
   piston and the diaphragm, then pull the flange up.
   The diaphragm will assume its shape, as
   illustrated in Figure 19.
4. On piston top valve actuators, place the piston
   straight within the new diaphragm and insert into               Figure 19: Diaphragm Installation for
   the bell housing.                                                     T-3111 and T-3311 Series
5. Replace the thermostat.
6. Replace all the screws and tighten equally.
7. Place the instrument in operation and check its
   action.

14 T-3100, T-3200, and T-3300 Series Controllers Product/Technical Bulletin
S pecifications
                                        Product     T-3100, T-3200, and T-3300 Series Controllers
                                         Models     See Table 1.
                           Proportional Action      See Table 1.
                   Maximum Supply Pressure          25 psig (172 kPa)
                  Ambient Temperature Limits        -20 to +150F (-29 to 66C)
                                                      T-3100       Barbed Restrictor Tee for 1/4 inch O.D. Polyethylene Tubing
                                                      T-3111
                                         Supply       T-3200
      Air Connections                                 T-3311
                                                      T-3300       Straight Connector for 1/4 inch O.D. Polyethylene Tubing;
                                                                   1/8 inch NPT Barbed Fitting for 5/32 or 1/4 inch O.D.
                                                                   Polytubing*
                                     Subordinate All Models        1/8 inch NPT, Internal Thread

                                                      T-3111       Bulb with 42 inch (1067 mm) Capillary

                                           Type     T-3111 and     8 ft (2438 mm) Averaging with 18 inch (457 mm) Capillary
                                                    T-3200
                                                      T-3100       Bulb with 42 inch (1067 mm) Capillary
               Element                                T-3300
                                                      T-3311
                                          Range       T-3100       60 to 150F (16 to 66C)
                                                      T-3200
                                                      T-3300
                                                      T-3311
                                                      T-3111       Bulb, 60 to 150F (16 to 66C)
                                                                   Averaging, 30 to 175F (-1 to 80C)
                                           Span                    20F (11C) Maximum
                                                    All Models     Factory Set at + 7.5F (+ 4C)
                   Dial                   Range       Except
                                                      T-3200
                                        Marking                    “Cool-Warm,” Graduated in one degree “F” Increments
                                                      T-3100       2.5 psi/F (31 kPa/C)
                                                      T-3111
            Sensitivity                               T-3300
                                  Remote Bulb         T-3311
                                Averaging Bulb        T-3111       0.5 psi/F (31 kPa/C)
                                                      T-3200
                                                      T-3100       75F (24C)
                               Factory Setpoint       T-3200       56F (13C)
                                                      T-3300       75F (24C)
 Continued on next page. . .
* The maximum length of 5/32 inch tubing is 15 feet. It is recommended that 1/4 inch tubing is used at all times to ensure
  proper switchover.

                                             T-3100, T-3200, and T-3300 Series Controllers Product/Technical Bulletin            15
S pecifications (Cont.)
                                                  Body      All Models       Die Cast Aluminum
                                                 Cover      All Models       Die Cast Zinc
                 Material                                   T-3111 and       Die Cast Aluminum
                                                  Yoke      T-3311
                                                            T-3111 and       Molded Synthetic Rubber
                                          Diaphragm         T-3311
                                                Finish      Green Lacquer
                 Accessories (Order Separately)             See Table 3.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications,
consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

 European Single Point of Contact:                   NA/SA Single Point of Contact:                       APAC Single Point of Contact:
 JOHNSON CONTROLS                                    JOHNSON CONTROLS                                     JOHNSON CONTROLS
 WESTENDHOF 3                                        507 E MICHIGAN ST                                    C/O CONTROLS PRODUCT
 45143 ESSEN                                         MILWAUKEE WI 53202                                   MANAGEMENT
 GERMANY                                             USA
                                                                                                          NO. 22 BLOCK D NEW DISTRICT
                                                                                                          WUXI JIANGSU PROVINCE 214142
                                                                                                          CHINA

Controls Group
507 E. Michigan Street
P.O. Box 423
Milwaukee, WI 53201                                                                                                                       Printed in U.S.A.