System 350 Product Guide      930
                                                                                            Basic Controls Section
                                                                                         Product/Technical Bulletin   P352
                                                                                                       Issue Date     0714

                                    System 350
                          P352 Electronic Pressure Control

The P352 Series is an on/off electronic pressure
control with single-pole, double-throw relay output
and LED indication. The P352 Series is designed
with reverse or direct acting mode of operation,
adjustable differential, and an interchangeable
pressure transducer. The P352 will accept up to
five S352 Stage Modules to control a total of six
stages of HVAC and/or refrigeration equipment.

Like all System 350 products, the P352 is housed
in a NEMA 1 high-impact plastic enclosure. The
modular design provides easy, snap-together
connections for quick installation and future
expandability.
                                                                        Figure 1: P352 Electronic Pressure Control

                                              Features and Benefits
     Modular Design                         Provides the flexibility to add up to five S352 Stage Modules, a D352
                                             Display Module and a Y350R Power Module

     Plug-in Connectors and 35 mm           Eliminates wiring between modules and reduces installation costs
          DIN-rail Mountability

     Adjustable Setpoint Range of 90        Handles pressures required for most fan cycling and compressor unloading
          to 250 PSIG                        applications

     Differential Adjustable from 10 to     Enables user to match the equipment cycle rate and/or sequencing for a
          100 PSI                            given application

     Field-Selectable Reverse or Direct Energizes relay output on either an increase or decrease in pressures
          Acting Mode Jumpers

     Interchangeable Pressure               Increases versatility and serviceability
          Transducer

© 2014 Johnson Controls, Inc.                                                                                                1
  Part No. 24-7664-52, R e v . B
  Code No. LIT-930040
Application Overview                                Operation
The P352 Pressure Control can be used as a
standalone device or in conjunction with            IMPORTANT: Use the System 350 controls
System 350 plug-in accessory modules to             only as operating controls. Where failure or
control a variety of single- or multiple-stage      malfunction of the System 350 controls could
HVAC and refrigeration pressure control             lead to personal injury or property damage to
applications. The P352 setpoint range is from       the controlled equipment or other property,
90 to 250 PSIG. Typical applications include:       additional precautions must be designed into the
                                                    control system. Incorporate and maintain other
•   condenser fan cycling                           devices, such as supervisory or alarm systems
                                                    or safety or limit controls, intended to warn of or
•   compressor unloading
                                                    protect against failure or malfunction of the
•   high pressure alarm                             System 350 controls.

Typically, a System 350 pressure control            IMPORTANT: Utiliser ce System 350 controls
scheme would include the following:                 uniquement en tant que dispositif de contrôle de
•   P352 Pressure Control                           fonctionnement. Lorsqu'une défaillance ou un
                                                    dysfonctionnement du System 350 controls
•   S352 Stage Modules                              risque de provoquer des blessures ou
                                                    d'endommager l'équipement contrôlé ou un
•   D352 Digital Pressure Sensor/Setpoint           autre équipement, la conception du système de
    Display Module                                  contrôle doit intégrer des dispositifs de
                                                    protection supplémentaires. Veiller dans ce cas
•   Y350R Power Module (or 24 VAC
                                                    à intégrer de façon permanente d'autres
    transformer)
                                                    dispositifs, tels que des systèmes de
•   P99 Series Pressure Transducer                  supervision ou d'alarme, ou des dispositifs de
                                                    sécurité ou de limitation, ayant une fonction
                                                    d'avertissement ou de protection en cas de
                                                    défaillance ou de dysfonctionnement du System
                                                    350 controls.

                                                    The P352 Pressure Control operates on 24 VAC
                                                    and supplies a SPDT relay output. A front-panel
                                                    “ON” LED lights to indicate the relay is
                                                    energized. Adjustable features include:

                                                    •   setpoint
                                                    •   differential
                                                    •   reverse/direct acting mode

                                                    Setpoint Adjustment
                                                    Setpoint is defined as the pressure at which the
                                                    relay will de-energize. The setpoint can be
                                                    adjusted from 90 to 250 PSIG. Adjustment is
                                                    made using the concealed setpoint adjustment
                                                    dial located under the cover in the center of the
                                                    printed circuit board (see Figure 5).

2 Basic Controls—P352 Electronic Pressure Control
Differential Adjustment
Differential is defined as the change in                   I nstallation and Wiring
transducer pressure between energization and               The P352 Electronic Pressure Control is housed
denergization of the relay. The differential can           in a compact NEMA 1 plastic enclosure
be adjusted from 10 to 100 PSI. Adjustment is              designed for standard 35 mm DIN-rail mounting.
made using the potentiometer marked “DIFF                  Four key-slot mounting holes on the back of the
ADJUST” located on the printed circuit board               control case are provided should surface
below and to the right of the setpoint dial (see           mounting be required.
Figure 5).
                                                           Note:       When mounting the P352 (or any
                                                                       System 350 Module) to rigid conduit,
Reverse/Direct Action Mode                                             attach the hub to the conduit before
                                                                       securing the hub to the control
With the reverse action (RA) mode selected,
                                                                       enclosure.
the differential is below the setpoint. The relay
will de-energize as the pressure rises to the
setpoint. As the pressure drops to the setpoint
minus the differential, the relay will energize and            !       WARNING: Risk of Electric Shock.
the LED will illuminate.                                               Disconnect the power supply before
                                                                       making electrical connections. Contact
With the direct action (DA) mode selected, the                         with components carrying hazardous
differential is above the setpoint. The relay will                     voltage can cause electric shock and
de-energize as the pressure drops to the                               may result in severe personal injury or
setpoint. As the pressure rises to the setpoint                        death.
plus the differential, the relay will energize and
the LED will illuminate.                                               AVERTISSEMENT : Risque de
                                                                       décharge électrique.
The direct/reverse action mode is selected via                         Débrancher l'alimentation avant de
jumper blocks marked “RA/DA” located on the                            réaliser tout branchement électrique.
right side of the circuit board above the relay                        Tout contact avec des composants
(see Figure 5). As shipped from the factory, the                       conducteurs de tensions dangereuses
RA/DA jumper blocks are installed in the                               risque d'entraîner une décharge
horizontal (direct action) position.                                   électrique et de provoquer des

D imensions
          0.145 Mounting Slot
                                                                       blessures graves, voire mortelles.

           3.68 For #6 Screws                              •       All wiring must be installed to conform to the
                                                                   National Electrical Code and local
                                                                   regulations. For maximum electrical rating of
           2.94                 5.00                               control see label inside control cover. Use
                                              P352
            75                  127          ON                    copper conductors only.

                                                           •       Consult the typical wiring diagrams
                                                                   (Figures 3 and 4) for proper wiring and
                                                                   terminal designations.
   1.56    0.42   DIN Rail                   2.40
    40      11    Mount             1.20      61
                                     31
                                                  P352     Transducer Wiring
                                                           The P352 Pressure Control is used with the
                             2.40
                              61                           P99 Series Active Pressure Transducer, which
                                                           is powered by the 14 VDC power supply of the
                                    0.85                   P352. The transducer is connected at the four-
                                           0.875 Conduit
                                     22      22 Hole
                                                           conductor screw terminal block located at the
                                                           upper left of the circuit board. (See Figure 5 and
          Figure 2: P352 Dimensions in./mm                 Table 1.)
                                                                   Basic Controls—P352 Electronic Pressure Control   3
Shielded cable is not generally required for                      Table 1: Pressure Transducer
transducer wiring on runs of less than 50 feet.                   Connections
When using shielded cable, isolate and tape the
shield at the transducer. Connect the shield to                              P352                    P99
the COM terminal on the P352.                                              Terminal                 Wire
                                                                         Designations               Color
A maximum shielded cable length of 1000 feet is
recommended using 14 to 22 AWG wire.                                         COM                   (A) Green
                                                                             SEN                   (B) White
                                                                             VDC                   (C) Brown

                                                                                      Transducer
                                      White-SEN
                                                  Brown-VDC
                                                              Green-COM

                                           P352                S352            D352

                           24
                          VAC

                           L
                            1
                           L
                            2
                                             Load                     Load

                 Figure 3: System 350 Powered by an External Transformer With the P99 Transmitter
                                     Located Less Than 50 Feet From the P352

4 Basic Controls—P352 Electronic Pressure Control
                                                                                  Transducer
            White-SEN
                         Brown-VDC
                                     Green-COM
                                                                    Isolate and
              Shield (Connect                                          Tape
             to COM at P352)

                P352                 Y350R           S352          S352             S352            D352

      L
        1
      L
       2

                       Load                          Load          Load              Load

                    Figure 4: System 350 Powered by Y350R Power Module With P99 Transmitter
                                     Between 50 and 1000 Feet From the P352

                                                            Y350R Power Module
A   dd-On Modules                                           The Y350R Power Module provides a
The S352 Stage, D352 Digital Pressure Display,              convenient method of powering System 350
and Y350R Power Modules snap together and                   modules from a 120 or 240 VAC power source.
plug into the P352 Electronic Pressure Control              The Y350R supplies a rectified 24 VAC to the
via connectors on the both sides of each add-on             modules.
module.                                                     The Y350R can be plugged into the right side of
                                                            the P352 Control or any of the add-on modules.
S352 Pressure Stage Modules                                 The Y350R is capable of providing power to a
The S352 Stage Modules receive their power,                 P352, a D352 Display Module, and up to five
setpoint, and sensor input from the P352                    S352 Stage Modules.
Control. As many as five S352 Stage Modules
can plug into the P352 Control.                             IMPORTANT: Verify that the jumpers are in
                                                            the proper position before powering the System
D352 Digital Pressure Display Module                        350 components. If the jumpers on the System
The D352 Display Module receives its power,                 350 components are in the wrong position, the
sensor, and setpoint information from the P352.             device will activate the relay in response to the
A three-digit liquid crystal display (LCD) gives a          opposite signal. The relay may remain
continuous readout of the sensed pressure.                  energized until the jumper position is corrected.
When the "PRESS FOR SETPOINT" button is
depressed the setpoint of the adjoining P352 is
displayed.

                                                                Basic Controls—P352 Electronic Pressure Control   5
                                                                     S352
A   djustments
                                                                     1. Remove the S352 cover by loosening the
P352                                                                    four captive cover screws.
1. Remove the P352 cover by loosening the                            2. Set the reverse/direct action (RA/DA)
   four captive cover screws.                                           jumper blocks to the desired mode of
2. Set the reverse/direct action (RA/DA)                                operation. (See Figure 6.)
   jumper blocks to the desired mode of                              3. Adjust the differential potentiometer to the
   operation. Position the jumper blocks                                desired setting. (Refer to the typical
   vertically for reverse action or horizontally                        multistage application in Figure 7.)
   for direct action. (See Figure 5.)
                                                                     4. Adjust the offset potentiometer to the
3. Adjust the differential potentiometer to the                         desired pressure from the P352 setpoint
   desired setting. Clockwise rotation                                  (above setpoint with direct action mode
   increases the differential.                                          selected or below setpoint with reverse
4. Turn the setpoint adjustment dial to the                             action mode selected) at which the stage
   desired setpoint.                                                    relay will
                                                                        de-energize.
5. Replace the cover and tighten the captive
   cover screws.                                                     5. Replace the cover on the S352.

Note:     Use the D352 Pressure Display Module
          for the most accurate setpoint selection.                                    S352 Stage Module
                                                                              Offset                  Differential
                                                                          Potentiometer              Potentiometer
                                                                                                        Module
                                                                                                       Connector
                    P352 Pressure                                      Module
                                                                      Connector                                Jumper Block
                    Control Module
                                                                                                                 Position
  24V
  COM              Concealed Setpoint                                Relay Energized                                 Reverse Action
  VDC
                    Adjustment Dial                                   LED Indicator          Relay                   Direct Action
  SEN                                    Module
                                        Connector
                                               Jumper Block
 Differential                                    Position
Potentiometer                                                                     N.C.     COM       N.O.
                                                    Reverse Action
Relay Energized                                                                   Relay Output Terminals
 LED Indicator             Relay                    Direct Action

                                                                             Figure 6: S352 Stage Module Adjustment
                                                                            Potentiometer Locations and Board Layout
                   N.C.    COM      N.O.
                  Relay Output Terminals

Figure 5: P352 Electronic Pressure Control Adjustment
      Potentiometer Locations and Board Layout

6 Basic Controls—P352 Electronic Pressure Control
                           Figure 7: Typical Reverse Action/Direct Action Application
                                       Using One P352 and Three S352s

C
                                                                        - If an external transformer is used,
    heckout Procedure                                                     select AC volts on the DVM and verify
                                                                          that the voltage is between 20 and
Before applying power, make sure installation                             30 VAC.
and wiring connections are according to job
specifications. After necessary adjustments and                         - If a Y350R Power Module is used,
electrical connections have been made, put the                            select DC volts on the DVM and verify
system in operation and observe at least three                            that the voltage is between 16 and
complete operating cycles before leaving the                              38 VDC.
installation.                                                    b) If the DVM reading is within the
                                                                    indicated voltage range, proceed to Step
                                                                    2.
T roubleshooting                                                 c) If the DVM reading is NOT within the
                                                                    indicated voltage range, check wiring
If the control system does not function properly,                   then replace the Y350R or the external
verify that the proper mode is selected on each                     transformer.
module (e.g. reverse action/direct action) and
then use the following procedures to determine              Table 2: P352 Control Relay Troubleshooting
the cause of the problem:
                                                              Action        LED    N.O. Relay    Setpoint Dial
1. Check for proper voltage applied to the                                         Status        Setting
   control module.
                                                              Reverse       ON     Closed        (PSIGT) + differential
    a) Connect a digital voltmeter (DVM)                      Reverse       OFF    Open          (PSIGT)
       between the “24V” (+) and “COM” (-)
                                                              Direct        ON     Closed        (PSIGT) - differential
       terminals located on the control's left-
       side terminal block (Figure 2).                        Direct        OFF    Open          (PSIGT)

                                                                 Basic Controls—P352 Electronic Pressure Control          7
2. Check pressure transducer for proper                 d) If the relays still do NOT turn on and off,
   output voltage.                                         replace the defective stage module(s).
    a) Disconnect the transducer “OUT” wire             Note:    There is the unlikely possibility that
       from the P352 “SEN” terminal.                             a defect in one stage module could
                                                                 cause defective symptoms in all
    b) Connect a DC voltmeter between the
                                                                 modules. Plug each stage into the
       transducer “OUT” wire and the control
                                                                 control individually and check its
       “COM” terminal. Measure voltage.
                                                                 performance as outlined in Steps 3a
Note:    A transducer output of 0 to 10 VDC                      and 3b.
         should correspond to a pressure of 0 to
                                                     5. Check the display module for proper
         435 PSIG.
                                                        operation.
         -   If the voltage conversion to pressure
                                                        If there is no display module in the system,
             is close to the expected PSIG at the
                                                        skip this step.
             transducer (PSIGT), proceed to
             Step 3.                                    Note: Steps 1 through 4 must be performed
                                                              first.
         -   If the voltage conversion to pressure
             is not what was expected, replace          a) Check pressure at the transducer
             the transducer.                               (PSIGT) as determined in Step 2a. The
                                                           display should read the same value.
3. Check the control for proper operation.
                                                        b) If the display module does NOT read the
Note:    Steps 1 and 2 must be performed first.
                                                           correct transmitter pressure (PSIGT),
    a) Adjust the setpoint dial to at least                replace the display module.
       100 PSIG below the pressure expected
                                                        c) Pressing the button on the display
       at the transducer (PSIGT) as determined
                                                           module should cause the display to read
       in Step 2.
                                                           the selected setpoint.
    b) Increase the setpoint by slowly adjusting
                                                        d) If pressing the SETPOINT button results
       the dial until the control relay and LED
                                                           in an out-of-range reading (greater than
       turn ON and OFF as shown in Table 2.
                                                           435 PSIG) replace the display module.
    c) If the relay performs as expected,
                                                        e) If pressing the SETPOINT button results
       continue to Step 4.
                                                           in a reading other than the expected
    d) If the relay does NOT perform as                    setpoint value, check the setpoint
       indicated in Table 2, replace the control.          potentiometer setting and correct if
4. Check the stage modules for proper                      necessary. If the display continues to
operation.                                                 read an incorrect value, replace the
                                                           display module.
    If this is a single-stage system, skip to
    Step 5.                                          Note:   If the control and add-on modules all
                                                             appear to be operating properly, but the
    Note:    Steps 1, 2 and 3 must be performed              field device still does not turn on and off
             first.                                          as expected, check the wiring from the
    a) Turn the setpoint dial on the control to              control or stage module to the field
       the 90 PSIG setting.                                  device.

    b) Increase the setpoint by slowly adjusting
       the dial until the stage relays and LEDs
       turn ON and OFF as shown in Table 3.
    c) If the relays do NOT perform as
       indicated in Table 4, adjust the
       differential and offset potentiometers to
       their minimum values and try again.

8 Basic Controls—P352 Electronic Pressure Control
Table 3: S352 Stage Relay Troubleshooting
 Action                     LED                N.O. Relay Status         Setpoint Dial Setting
 Reverse (RA)               ON                 Closed                    (PSIGT) + offset + differential
 Reverse (RA)               OFF                Open                      (PSIGT) + offset
 Direct (DA)                ON                 Closed                    (PSIGT) - offset - differential
 Direct (DA)                OFF                Open                      (PSIGT) - offset

R epairs and Replacement
Field repairs or calibration must not be made.                     and wholesale distributors.
Transmitters and replacement controls are
available through local Johnson Controls branch

O rdering Information
Table 4: Ordering Information
  Item                                  Product Code Number                    Description
  Electronic Pressure Control           P352AA-1C                              With SPDT Relay and 90 to 250 PSIG Range
  Pressure Transducer                   P99V-2C                                0 to 435 PSIG; 1/4 in. SAE Flare Connector
  Display Module                        D352AA-1C                              Digital Pressure Display Module
  Stage Module                          S352AA-1C                              Pressure Stage Module with PSIG Scale
  Power Module                          Y350R-1C                               Rectified 24 VAC from 120/240 VAC Source
  DIN Rail Sections                     BKT287-1R                              35 x 7.5 mm, 0.305 m (12 in.) long
                                        BKT287-2R                              35 x 7.5 mm, 0.914 m (36 in.) long
  DIN Rail End Clamps                   PLT344-1R                              Consists of Two End Clamps
  Cable for Remote Mounting             WHA29A-600R                            3 ft (0.9 m)*
  of D352 Display Module                WHA29A-603R                            25 ft (7.6 m)
                                        WHA29A-604R                            50 ft (15.2 m)
* WHA29A-600R can also be used to daisy chain S352 Stage Modules together.

                                                                       Basic Controls—P352 Electronic Pressure Control      9
                                                     Notes

10 Basic Controls—P352 Electronic Pressure Control
Notes

        Basic Controls—P352 Electronic Pressure Control   11
S pecifications
                                 Product      P352 Electronic Pressure Control
                    Differential Range        10 to 100 PSI
            Pressure Setpoint Range           90 to 250 PSIG
                     DC Power Supply          14 VDC Provided to Power the Pressure Transmitter
                         Input Voltage*       24 VAC Class 2; 50/60 Hz +15%, -10%
                                    Relay     SPDT Enclosed Relay; Contacts Rated at 10 Amp Non-inductive, 1/2 hp 120/240 VAC
                          Current Draw        1.8 VA
                            Input Signal      0 to 10 VDC Corresponding to 0 to 435 PSIG
                     Electrical Ratings       Full Load Amps:                 9.8 (120 VAC)                      4.9 (208/240 VAC)
                                              Locked Rotor Amps:              58.8 (120 VAC)                     29.4 (208/240 VAC)
                                              Non-Inductive Amps:             10 at 24/240 VAC
                                              Pilot Duty:                     125 VA at 24/240 VAC
                Ambient Temperature           Operating : -30 to 150°F (-34 to 66°C)
                                              Shipping: 40 to 185°F (-40 to 85°C)
                    Ambient Humidity          0 to 95% RH Non-Condensing
                                 Material     Case, Cover: NEMA 1 High Impact Noryl Plastic
                         Agency Listing       UL Guide No. XAPX, File E27734
                                              CSA Class No. 4813 02, File LR948
   *Only one input voltage source may be used.
   Noryl is a registered trademark of the General Electric Company.

                     Add-on Modules:
                               S352           Input Voltage:            14 VDC Reference Provided by the P352; 24 VAC Power Supply
                                              Relay Contacts:           SPDT, 10 amps Non-inductive, 1/2 hp 120/240 VAC
                                              DIFF & OFFSET:            10 to 100 PSI Differential; 10 to 60 PSIG Offset
                                   Y350R      Input Voltage:            120/240 VAC, 50/60 Hz
                                              Output Power:             24 VAC Rectified, 10 VA Maximum
                                    D350      Display Range:            90 to 250 PSIG
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications,
consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

Controls Group                                                                                                                                           FAN 930
507 E. Michigan Street                                                                                                                  System 350 Product Guide
P.O. Box 423                                                                                                                                     Printed in U.S.A.
Milwaukee, WI 53201

12 Basic Controls—P352 Electronic Pressure Control