                                                                    Product/Technical Bulletin   S350
                                                                                  Issue Date     April 8, 2014

                                           System 350™
                                S350A Temperature, S351A Humidity,
                                 and S352A Pressure Stage Modules

The S350A, S351A, and S352A Stage Modules are
intended to be used with System 350™ controls. Each
of these stage modules plugs into the respective
control module to add multiple-stage capability. These
stage modules have Single-Pole, Double-Throw
(SPDT) relay output with Light-Emitting Diode (LED)
indication.
As are all System 350 products, the stage modules are
housed in NEMA 1, high-impact thermoplastic
enclosures. The modular design provides easy,
plug-together connections for quick installation and
future expandability.

                                                                  Figure 1: System 350 Stage Module

                                            Features and Benefits
                   Modular Design                 Permits system to be configured to
                                                   equipment, with convenient, future expansion
                                                   made easy

                   Plug-together Connectors       Eliminates wiring between modules and
                       and 35 mm DIN Rail          reduces installation costs
                       Mounting

                   Selectable Mode of             Provides independent relay energization,
                       Operation                   either above or below setpoint, for
                                                   cooling/heating (S350A),
                                                   dehumidification/humidification (S351A), or
                                                   direct acting/reverse acting (S352A)

                   Adjustable Differential        Enables user to match the range of
                                                   temperature, humidity, or pressure stage
                                                   modules to specific application requirements

                   Adjustable Offset              Allows multiple stage sequencing of 1-30F°
                                                   (0.5-17C°) (S350A), 2-30% RH (S351A), or
                                                   2-50 psi (S352AA-2)

© 2014 Johnson Controls, Inc.                                                                                     1
  Part No. 24-7664-1, Rev. E                                                                 www.johnsoncontrols.com
  Code No. LIT-930080
A pplication
The S350A, S351A, and S352A Stage Modules                Table 2: Maximum Number of Add-on
receive power, setpoint, and sensor input from the       Modules when Powered by an External
respective System 350 control modules. When
connected, the individual modules act as a multistage    Transformer
control system.                                           Control             Stage                  Display
                                                          Module              Module                 Module
The maximum number of stages that can be used in a
system varies with the control module type                            No.        Model          No.     Model
(temperature, humidity, or pressure) and stage module                           Numbers                Number
design.                                                   A350A        9    S350As or S350Cs     1     D350
Refer to Table 1 or Table 2 to determine the maximum      A350B        8    S350As or S350Cs
number of stages that may be used with each control       A350E
                                                                            with 1 S350P
module. When mixing stage module designs, always                       7    S350As or S350Cs
use the lower number.                                                       with 2 S350Ps
Note:       When using an external transformer, the       A350P        9    S350As or S350Cs     1     D350
            Y65 Series or other 40 VA Class 2                          8    S350As or S350Cs
            transformers are recommended.                                   with 1 S350P
                                                                       7    S350As or S350Cs
Table 1: Maximum Number of Add-on                                           with 2 S350Ps
Modules when Powered by a Y350R
                                                          A350R        9    S350As or S350Cs     2     D350s
Power Module                                              A350S        8    S350As or S350Cs
    Control            Stage                  Display                       with 1 S350P
    Module             Module                 Module                   7    S350As or S350Cs
                No.       Model          No.     Model                      with 2 S350Ps
                         Numbers                Number    W351A        9    S351As               1     D351
    A350A        9    S350As or S350Cs    1     D350      W351P        9    S351As               1     D351
    A350B        6    S350As or S350Cs                    P352AB       9    S352As               1     D352A
    A350E
                      with 1 S350P
                                                          P352PN       9    S352As               1     D352A
                 4    S350As or S350Cs
                      with 2 S350Ps
    A350P        4    S350As or S350Cs    1     D350     Notes: This bulletin only refers to the S350A, S351A,
                 2    S350As or S350Cs                          and S352A Stage Modules.
                      with 1 S350P                                For information on the S350C refer to the
    A350R        9    S350As or S350Cs    2     D350s             System 350TM S350C Temperature Slave
    A350S        6    S350As or S350Cs                            Stage Module Product/Technical Bulletin
                      with 1 S350P                                (LIT-930084).
                 4    S350As or S350Cs                            For information on the S350P refer to the
                      with 2 S350Ps                               System 350TM S350P Proportional Plus
    W351A        5    S351As              1     D351              Integral Temperature Stage Module
    W351P                                                         Product/Technical Bulletin (LIT-930086).
                 4    S351As              1     D351
    P352AB       5    S352As              1     D352A             For information on the D350, D351 and D352
                                                                  refer to the System 350TM D350 Display
    P352PN       4    S352As              1     D352A             Modules Product/Technical Bulletin
                                                                  (LIT-930070).

2     S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin
O peration
The S350A, S351A, and S352A Stage Modules
provide SPDT relay output. A front panel LED lights to   Operation Mode Selection
indicate when the relay is energized.                    The S350A, S351A, and S352A utilize jumpers (at
                                                         jumper terminal J2) to select the operation mode. (See
 IMPORTANT: Use the S350A, S351A, and S352A              Adjustments section and Figures 3, 4, and 5.)
           Stage Modules only as an operating
           control. Where failure or malfunction         With the jumpers positioned horizontally, the stage
           of the modules could lead to personal         module is set for Cooling (S350A), Dehumidification
           injury or property damage to the              (S351A), or Direct Acting (DA) (S352A) operation. In
           controlled equipment or other                 this mode the relay and LED indicator de-energize
           property, additional precautions must         when the sensed temperature, humidity, or pressure
           be designed into the control system.          drops to the setpoint plus offset value.
           Incorporate and maintain other                Note:   The S350A, S351A, and S352A Stage
           devices, such as supervisory or alarm                 Modules are configured with the jumpers in
           systems or safety or limit controls,                  the horizontal position at the factory.
           intended to warn of or protect against
           failure or malfunction of the modules.        Refer to Figures 6, 7, and 8 for examples of S350A,
                                                         S351A, and S352A applications.
 IMPORTANT: Utiliser ce S350A, S351A, and S352A
           Stage Modules uniquement en tant
           que dispositif de contrôle de
           fonctionnement. Lorsqu'une
           défaillance ou un dysfonctionnement
                                                         D imensions
           du modules risque de provoquer des             Mounting Slots
                                                          For No. 6 Screws      1/8 (4)
           blessures ou d'endommager
           l'équipement contrôlé ou un autre
           équipement, la conception du système
           de contrôle doit intégrer des dispositifs                          2-15/16                                     S350

           de protection supplémentaires. Veiller                               (75)                   5 (127)       ON

           dans ce cas à intégrer de façon                                                                           JOHNSON
                                                                                                                      O
                                                                                                                 CONTROLS

           permanente d'autres dispositifs, tels
           que des systèmes de supervision ou
           d'alarme, ou des dispositifs de                            1-1/2     7/16
                                                                                          DIN Rail                2-3/8
           sécurité ou de limitation, ayant une                       (40)      (11)      Mount                    (61)
                                                                                                       1-3/16
           fonction d'avertissement ou de                                                               (31)
           protection en cas de défaillance ou de
           dysfonctionnement du modules.                                                             2-3/8
                                                                                                      (61)

Offset Adjustment                                                                                     7/8 (22)   Conduit
                                                                                                                   Hole
The offset adjustment determines the amount of offset                                                             7/8 (22)
from the control module setpoint at which the stage
module relay de-energizes.                                        Figure 2: System 350 Stage Module
                                                                         Dimensions, in. (mm)

Differential Adjustment
Differential is defined as the difference in degrees,
% RH, or psi between energization and
de-energization of the stage module’s relay.

        S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin                           3
                                                          3. Set the mode of operation by positioning the
Mounting                                                     jumpers (at jumper terminal J2) for Cooling,
                                                             Dehumidification, or Direct Acting mode. Position
Each System 350 Stage Module is housed in a                  the jumpers vertically for Heating, Humidification,
compact NEMA 1 plastic enclosure designed for                or Reverse Acting mode.
standard 35 mm DIN rail mounting. Four key-slot               Note: The S350A, S351A, and S352A Stage
mounting holes on the back of the control case are                  Modules are configured with the jumpers in
provided for surface mounting. (See Figure 2.) The                  the horizontal position at the factory.
modules are not position sensitive, but should be
mounted for convenient access to wiring and               4. Adjust the differential using the potentiometer
adjustments.                                                 marked DIFF to the desired setting (the difference
                                                             in degrees, % RH, or psi between energization
Note: When mounting any System 350 module to                 and de-energization of the stage module’s relay).
rigid conduit, attach the hub to the conduit before
securing the hub to the control enclosure.                5. Adjust the offset using the potentiometer marked
                                                             OFFSET to the number of degrees, % RH, or psi
                                                             from the System 350 control’s setpoint at which
Adjustments                                                  the stage relay de-energizes (above setpoint with
                                                             Cooling, Dehumidification, or Direct Acting mode
Refer to the following steps for adjusting stage module      selected, or below setpoint with Heating,
settings. (See Figures 3, 4, and 5.)                         Humidification, or Reverse Acting mode selected).
                                                          6. Replace the cover on the stage module and fasten

    !
                                                             in place with screws.
        WARNING: Risk of Electrical Shock.                7. Restore power to system.
Disconnect or isolate all power supplies before
making electrical connections. More than one                                Offset               Differential
                                                                         Potentiometer          Potentiometer
disconnection or isolation may be required to
completely de-energize equipment. Contact with                                                      Module
components carrying hazardous voltage can cause                                                    Connector
                                                                   Module
electric shock and may result in severe personal                  Connector
                                                                                                         Jumper
injury or death.                                                                                       Position at J2
                                                             Relay Energized
                                                              LED Indicator                                  Heating
AVERTISSEMENT: Risque de décharge                                                       Relay
électrique.                                                                                                  Cooling
Débrancher ou isoler toute alimentation avant de                    Cover Screw
                                                                       1 of 4
réaliser un branchement électrique. Plusieurs
isolations et débranchements sont peut-être
nécessaires pour -couper entièrement l'alimentation                            N.C.    COM         N.O.
                                                                               Relay   Output    Terminals
de l'équipement. Tout contact avec des composants
conducteurs de tensions dangereuses risque
d'entraîner une décharge électrique et de provoquer         Figure 3: Interior View of S350A Stage Module
des blessures graves, voire mortelles.

1. Ensure all power to system is off.
        Each stage module may be receiving separate
        power sources. Make sure all power sources to
        each stage module are off.
2. Remove the stage module cover by loosening the
   four captive cover screws.

4   S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin
           Offset               Differential                             Offset              Differential
       Potentiometer           Potentiometer                          Potentiometer         Potentiometer

                                   Module                                                       Module
                                  Connector                                                    Connector
   Module                                                       Module
  Connector                              Jumper                Connector                            Jumper
                                       Position at J2                                             Position at J2
                                                              Relay Energized                         Reverse
Relay Energized                          Humidification
                                                               LED Indicator       Relay               Acting
 LED Indicator
                       Relay                                                                           Direct
                                         Dehumidification
                                                                                                       Acting
                                                                 Cover Screw
    Cover Screw                                                     1 of 4
       1 of 4

                                                                           N.C.    COM          N.O.
              N.C. COM       N.O.                                          Relay   Output     Terminals
              Relay Output Terminals

                                                            Figure 5: Interior View of S352A Stage Module
Figure 4: Interior View of S351A Stage Module

     S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin                5
  Higher                                       ON                                                                                                              Higher
Temperature                                                                                                                                                   Pressure

                                            Differential
                                                                                                                                                                                                       ON

                                                                                                                                                                                                Differential
                          ON

                       Differential
                                                                                                                                                                                      ON

                                                                                                                                                                                Differential
                                            OFF
                                            OFFSET                                                                                                                                             OFF
  Setpoint                                                                                                                                                                                     OFFSET
Temperature           OFF
                                                                          OFFSET                                                                              Setpoint
                                                                                                         OFFSET                                               Pressure         OFF
                                                           OFF
                                                                                                                                                                                                                  OFFSET

                                                                          Differential
                                                                                                         OFF                                 OFFSET                                                                      OFFSET
                   ON = Energized                                                                                                                                                                                 OFF

                                                                                                          Differential
                  OFF = De-energized

                                                                                                                                                                                                                    Differential
                                                                                                                                                                                                                         OFF

                                                                                                                                                                                                                                         Differential
                                                                                                                                             OFF                           ON = Energized
                                                                                                                                                                          OFF = De-energized

                                                                                                                                             Differential
      Lower                                                                              ON
    Temperature                                                                                                          ON
                                                                                                                                                                                                                                   ON
                                                                                                                                                               Lower                                                                                    ON
                                                                                                                                                              Pressure
                                                                                    ON
                   A350 S350A                                S350A S350A S350A                                                                                             P352AB S352A                        S352A                S352A
                  Stage 1 Stage 2                            Stage 3 Stage 4 Stage 5                                                                                       Stage 1 Stage 2                     Stage 3              Stage 4
                      Cooling                                         Heating                                                                                                    Direct                            Reverse

       Figure 6: Example of a Heating/Cooling                                                                                                                  Figure 8: Example of a Reverse Acting/Direct
     Application Using One A350 and Four S350As                                                                                                                   Acting Application Using One P352AB
                                                                                                                                                                            and Three S352As
      Higher                                                   ON
     Humidity
                                                                                                                                                            W iring
                                                           Differential
                                 ON
                                                                                                                                                            Refer to the following guidelines and wiring diagrams

                             Differential
                                                                                                                                                            for proper wiring and terminal designations (See
                                                           OFF                                                                                              Figures 9, 10, and 11.)
                                                           OFFSET
    Setpoint
    Relative                                                                                                                                                Note:   For information on connecting to an external
                       OFF
    Humidity                                                                                                                                                        transformer refer to the applicable control
                                                                                          OFFSET
                                                                                                                          OFFSET                                    bulletin.
                                                                                         OFF

                                                                                          Differential
                   ON = Energized                                                                                         OFF
                  OFF = De-energized
                                                                                                                                                              !
                                                                                                                              Differential
                                                                                                                                                                    WARNING: Risk of Electrical Shock.
      Lower                                                                                                                                                 Disconnect or isolate all power supplies before
     Humidity                                                                                            ON                                                 making electrical connections. More than one
                                                                                                                                             ON             disconnection or isolation may be required to
                                                                                                                                                            completely de-energize equipment. Contact with
                                                                                                                                                            components carrying hazardous voltage can cause
                     W351                    S351                          S351     S351                                                                    electric shock and may result in severe personal
                    Stage 1                 Stage 2                       Stage 3 Stage 4
                                                                              Humidify
                                                                                                                                                            injury or death.
                       Dehumidify

                Figure 7: Example of a                                                                                                                      AVERTISSEMENT: Risque de décharge
      Humidification/Dehumidification Application                                                                                                           électrique.
         Using One W351 and Three S351As                                                                                                                    Débrancher ou isoler toute alimentation avant de
                                                                                                                                                            réaliser un branchement électrique. Plusieurs
                                                                                                                                                            isolations et débranchements sont peut-être
                                                                                                                                                            nécessaires pour -couper entièrement l'alimentation
                                                                                                                                                            de l'équipement. Tout contact avec des composants
                                                                                                                                                            conducteurs de tensions dangereuses risque
                                                                                                                                                            d'entraîner une décharge électrique et de provoquer
                                                                                                                                                            des blessures graves, voire mortelles.

6     S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin
IMPORTANT:     Make all wiring connections in             The stage modules plug into the control and other
               accordance with the National               add-on modules via 5-pin connectors located on either
               Electrical Code and all local              side of each module. Wiring is made at the Normally
               regulations. Use copper                    Open (N.O.)/Normally Closed (N.C.) relay terminal
               conductors only. Do not exceed             strip. (See Figures 3, 4, and 5.)
               the control’s electrical ratings.

                                          SEN
                                                   COM                              Sensor
                                   Shield (Connect               Isolate and tape. (Do not ground
                                only to COM on A350)                  this end of cable shield.)
                                   A350     Y350R        S350A     S350A      S350A      D350

                       Wire
                     Terminal
                      Block
                     24V
                    COM
                    VDC
                    SEN

                     120 VAC

                                   Load                   Load      Load       Load

      Figure 9: Typical Multistage Temperature Control System Using 120 VAC Power Supply

                                                                                 Transmitter

                                 SEN
                                            VDC
                                                    COM
                                    Shield (Connect               Isolate and tape. (Do not ground
                                 only to COM on W351)                  this end of cable shield.)
                                   W351     Y350R        S351A     S351A      S351A      D351

                      Wire
                    Terminal
                     Block
                    24V
                   COM
                   VDC
                   SEN

                      120 VAC

                                    Load                  Load      Load        Load

       Figure 10: Typical Multistage Humidity Control System Using 120 VAC Power Supply

    S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin            7
                                                                     Wiring Harness    P399 Transducer
                                      SEN
                                                VDC
                                                        COM
                                        Shield (Connect              Isolate and tape. (Do not ground
                                   only to COM on P352AB)                 this end of cable shield.)
                                    P352AB     Y350R     S352A         S352A        S352A D352A

                          Wire
                        Terminal
                         Block
                        24V
                       COM
                       VDC
                       SEN

                         120 VAC

                                      Load                    Load       Load         Load

           Figure 11: Typical Multistage Pressure Control System Using 120 VAC Power Supply

8   S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin
C heckout Procedure
Before applying power, make sure installation and         Table 4: S351A Relay Troubleshooting
wiring connections are according to job specifications.
                                                           Operation          LED     N.O.          Setpoint Dial
After necessary adjustments and electrical
                                                           Mode                       Relay         Setting
connections have been made, put the system in
                                                                                      Status
operation and observe at least three complete
operating cycles before leaving the installation.          Dehumidify         On      Closed        (RHT)* -offset
                                                                                                    - differential
                                                           Dehumidify         Off     Open          (RHT) - offset
                                                           Humidify           On      Closed        (RHT) + offset
T roubleshooting                                                                                    + differential
                                                           Humidify           Off     Open          (RHT) + offset
If the control system does not function properly, first
verify that the control, power, and display modules are   *(RHT) = actual relative humidity at transducer
all operating correctly (refer to the respective
literature). Then inspect the stage modules for proper    Table 5: S352A Relay Troubleshooting
operation.
                                                           Operation          LED     N.O.          Setpoint Dial
Check that the proper operating mode                       Mode                       Relay         Setting
(Cooling/Heating, Dehumidification/Humidification, or                                 Status
Direct Acting/Reverse Acting) has been selected on
each stage module. (See Adjustments section and            Direct             On      Closed        (psiT)*- offset -
Figures 3, 4, and 5.) Then perform the following                                                    differential
procedures to determine the problem.                       Direct             Off     Open          (psiT) - offset
1. Verify the system has power.                            Reverse            On      Closed        (psiT) + offset +
                                                                                                    differential
2. Note the offset and differential settings on the
                                                           Reverse            Off     Open          (psiT) + offset
   stage module.
                                                          *(psiT) = actual pressure at transducer
3. Turn the setpoint dial on the control module to
   minimum.                                               5. If the relays do not perform as indicated in
                                                             Tables 3, 4, or 5, adjust the stage module’s
4. Increase the setpoint by slowly adjusting the             differential and offset potentiometers to minimum
   setpoint dial until the stage relay LEDs turn On          and repeat Steps 1 through 3.
   and Off as shown in Tables 3, 4, or 5.
                                                          6. If the relays still do not turn on and off, replace the
Table 3: S350A Relay Troubleshooting                         defective stage modules.
 Operation        LED        N.O.     Setpoint Dial       Note:     There is the unlikely possibility that a defect in
 Mode                        Relay    Setting                       one stage module could cause defective
                             Status                                 symptoms in all modules. Plug each stage into
 Cooling          On         Closed   (Ts)* - offset                the control individually and check the
                                      - differential                performance of each as explained above.
 Cooling          Off        Open     (Ts) – offset
 Heating          On         Closed   (Ts) + offset
                                      + differential
                                                          R epairs and Replacement
                                                          Do not make field repairs or perform calibration.
 Heating          Off        Open     (Ts) + offset
                                                          Sensors and replacement controls are available
*(Ts) = sensed temperature                                through your local Johnson Controls representative.

        S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin                  9
O rdering Information
Table 6: Ordering Information
 Item                                     Product Code            Description
                                          Number
 S350A Temperature Stage                  S350AA-1C               Temperature Stage Module with Fahrenheit Scale
 Module
                                          S350AB-1C               Temperature Stage Module with Celsius Scale
 S351A Humidity Stage Module              S351AA-1C               Humidity Stage Module with percent RH Scale
 S352A Pressure Stage Module              S352AA-2C               Pressure Stage Module with psi Scale

S pecifications
                         Product     S350AA:          Temperature Stage Module with Fahrenheit Scale
                                     S350AB:          Temperature Stage Module with Celsius Scale
                                     S351AA:          Humidity Stage Module with Percent RH Scale
                                     S352AA-2:        Pressure Stage Module with psi Scale
                  Input Voltage      S350AA:          Provided by the A350
                                     S351AB:          Provided by the W351
                                     S352AA-2:        Provided by the P352AB
         Power Consumption           1.0 VA maximum
      Output Relay Electrical        SPDT Enclosed Relays
                    Ratings          10 Ampere Non-inductive, 125 VA Pilot Duty, 24/240 VAC
                                     1/2 hp 120/240 VAC
      Differential Adjustment        S350AA:          1 to 30F°
                       Range         S350AB:          0.5 to 17C°
                                     S351AA:          2 to 10% RH
                                     S352AA-2:        2 to 50 psi
                  Offset Range       S350AA:          1 to 30F°
                                     S350AB:          0.6 to 16.7C°
                                     S351AA:          2 to 30% RH
                                     S352AA-2:        2 to 50 psi
        Ambient Temperature          Operating:       -30 to 150°F (-34 to 66°C)
                                     Shipping:        -40 to 185°F (-40 to 85°C)
            Ambient Humidity         0 to 95% RH (Non-condensing)
                         Material    Case, Cover: NEMA 1 High Impact Thermoplastic
                       Mounting      Wall or DIN Rail
                Agency Listing       UL Listed, CCN XAPX, File E27734
                                     UL Listed for Canada, CCN XAPX7, File E27734
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls/Penn Application Engineering at (414) 524-5535. Johnson Controls, Inc. shall not be liable for
damages resulting from misapplication or misuse of its products.

                                                                                                                   Building Efficiency
                                                                                          507 E. Michigan Street, Milwaukee, WI 53202

                                        ® Johnson Controls and PENN are registered trademarks of Johnson Controls, Inc. in the
                                United States of America and/or other countries. All other trademarks used herein are the property
                                        of their respective owners. © Copyright 2014 by Johnson Controls, Inc. All rights reserved.