FANs 930, 125
Product/Technical Bulletin S350
Issue Date April 8, 2014
System 350™
S350A Temperature, S351A Humidity,
and S352A Pressure Stage Modules
The S350A, S351A, and S352A Stage Modules are
intended to be used with System 350™ controls. Each
of these stage modules plugs into the respective
control module to add multiple-stage capability. These
stage modules have Single-Pole, Double-Throw
(SPDT) relay output with Light-Emitting Diode (LED)
indication.
As are all System 350 products, the stage modules are
housed in NEMA 1, high-impact thermoplastic
enclosures. The modular design provides easy,
plug-together connections for quick installation and
future expandability.
Figure 1: System 350 Stage Module
Features and Benefits
Modular Design Permits system to be configured to
equipment, with convenient, future expansion
made easy
Plug-together Connectors Eliminates wiring between modules and
and 35 mm DIN Rail reduces installation costs
Mounting
Selectable Mode of Provides independent relay energization,
Operation either above or below setpoint, for
cooling/heating (S350A),
dehumidification/humidification (S351A), or
direct acting/reverse acting (S352A)
Adjustable Differential Enables user to match the range of
temperature, humidity, or pressure stage
modules to specific application requirements
Adjustable Offset Allows multiple stage sequencing of 1-30F°
(0.5-17C°) (S350A), 2-30% RH (S351A), or
2-50 psi (S352AA-2)
© 2014 Johnson Controls, Inc. 1
Part No. 24-7664-1, Rev. E www.johnsoncontrols.com
Code No. LIT-930080
A pplication
The S350A, S351A, and S352A Stage Modules Table 2: Maximum Number of Add-on
receive power, setpoint, and sensor input from the Modules when Powered by an External
respective System 350 control modules. When
connected, the individual modules act as a multistage Transformer
control system. Control Stage Display
Module Module Module
The maximum number of stages that can be used in a
system varies with the control module type No. Model No. Model
(temperature, humidity, or pressure) and stage module Numbers Number
design. A350A 9 S350As or S350Cs 1 D350
Refer to Table 1 or Table 2 to determine the maximum A350B 8 S350As or S350Cs
number of stages that may be used with each control A350E
with 1 S350P
module. When mixing stage module designs, always 7 S350As or S350Cs
use the lower number. with 2 S350Ps
Note: When using an external transformer, the A350P 9 S350As or S350Cs 1 D350
Y65 Series or other 40 VA Class 2 8 S350As or S350Cs
transformers are recommended. with 1 S350P
7 S350As or S350Cs
Table 1: Maximum Number of Add-on with 2 S350Ps
Modules when Powered by a Y350R
A350R 9 S350As or S350Cs 2 D350s
Power Module A350S 8 S350As or S350Cs
Control Stage Display with 1 S350P
Module Module Module 7 S350As or S350Cs
No. Model No. Model with 2 S350Ps
Numbers Number W351A 9 S351As 1 D351
A350A 9 S350As or S350Cs 1 D350 W351P 9 S351As 1 D351
A350B 6 S350As or S350Cs P352AB 9 S352As 1 D352A
A350E
with 1 S350P
P352PN 9 S352As 1 D352A
4 S350As or S350Cs
with 2 S350Ps
A350P 4 S350As or S350Cs 1 D350 Notes: This bulletin only refers to the S350A, S351A,
2 S350As or S350Cs and S352A Stage Modules.
with 1 S350P For information on the S350C refer to the
A350R 9 S350As or S350Cs 2 D350s System 350TM S350C Temperature Slave
A350S 6 S350As or S350Cs Stage Module Product/Technical Bulletin
with 1 S350P (LIT-930084).
4 S350As or S350Cs For information on the S350P refer to the
with 2 S350Ps System 350TM S350P Proportional Plus
W351A 5 S351As 1 D351 Integral Temperature Stage Module
W351P Product/Technical Bulletin (LIT-930086).
4 S351As 1 D351
P352AB 5 S352As 1 D352A For information on the D350, D351 and D352
refer to the System 350TM D350 Display
P352PN 4 S352As 1 D352A Modules Product/Technical Bulletin
(LIT-930070).
2 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin
O peration
The S350A, S351A, and S352A Stage Modules
provide SPDT relay output. A front panel LED lights to Operation Mode Selection
indicate when the relay is energized. The S350A, S351A, and S352A utilize jumpers (at
jumper terminal J2) to select the operation mode. (See
IMPORTANT: Use the S350A, S351A, and S352A Adjustments section and Figures 3, 4, and 5.)
Stage Modules only as an operating
control. Where failure or malfunction With the jumpers positioned horizontally, the stage
of the modules could lead to personal module is set for Cooling (S350A), Dehumidification
injury or property damage to the (S351A), or Direct Acting (DA) (S352A) operation. In
controlled equipment or other this mode the relay and LED indicator de-energize
property, additional precautions must when the sensed temperature, humidity, or pressure
be designed into the control system. drops to the setpoint plus offset value.
Incorporate and maintain other Note: The S350A, S351A, and S352A Stage
devices, such as supervisory or alarm Modules are configured with the jumpers in
systems or safety or limit controls, the horizontal position at the factory.
intended to warn of or protect against
failure or malfunction of the modules. Refer to Figures 6, 7, and 8 for examples of S350A,
S351A, and S352A applications.
IMPORTANT: Utiliser ce S350A, S351A, and S352A
Stage Modules uniquement en tant
que dispositif de contrôle de
fonctionnement. Lorsqu'une
défaillance ou un dysfonctionnement
D imensions
du modules risque de provoquer des Mounting Slots
For No. 6 Screws 1/8 (4)
blessures ou d'endommager
l'équipement contrôlé ou un autre
équipement, la conception du système
de contrôle doit intégrer des dispositifs 2-15/16 S350
de protection supplémentaires. Veiller (75) 5 (127) ON
dans ce cas à intégrer de façon JOHNSON
O
CONTROLS
permanente d'autres dispositifs, tels
que des systèmes de supervision ou
d'alarme, ou des dispositifs de 1-1/2 7/16
DIN Rail 2-3/8
sécurité ou de limitation, ayant une (40) (11) Mount (61)
1-3/16
fonction d'avertissement ou de (31)
protection en cas de défaillance ou de
dysfonctionnement du modules. 2-3/8
(61)
Offset Adjustment 7/8 (22) Conduit
Hole
The offset adjustment determines the amount of offset 7/8 (22)
from the control module setpoint at which the stage
module relay de-energizes. Figure 2: System 350 Stage Module
Dimensions, in. (mm)
Differential Adjustment
Differential is defined as the difference in degrees,
% RH, or psi between energization and
de-energization of the stage module’s relay.
S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin 3
3. Set the mode of operation by positioning the
Mounting jumpers (at jumper terminal J2) for Cooling,
Dehumidification, or Direct Acting mode. Position
Each System 350 Stage Module is housed in a the jumpers vertically for Heating, Humidification,
compact NEMA 1 plastic enclosure designed for or Reverse Acting mode.
standard 35 mm DIN rail mounting. Four key-slot Note: The S350A, S351A, and S352A Stage
mounting holes on the back of the control case are Modules are configured with the jumpers in
provided for surface mounting. (See Figure 2.) The the horizontal position at the factory.
modules are not position sensitive, but should be
mounted for convenient access to wiring and 4. Adjust the differential using the potentiometer
adjustments. marked DIFF to the desired setting (the difference
in degrees, % RH, or psi between energization
Note: When mounting any System 350 module to and de-energization of the stage module’s relay).
rigid conduit, attach the hub to the conduit before
securing the hub to the control enclosure. 5. Adjust the offset using the potentiometer marked
OFFSET to the number of degrees, % RH, or psi
from the System 350 control’s setpoint at which
Adjustments the stage relay de-energizes (above setpoint with
Cooling, Dehumidification, or Direct Acting mode
Refer to the following steps for adjusting stage module selected, or below setpoint with Heating,
settings. (See Figures 3, 4, and 5.) Humidification, or Reverse Acting mode selected).
6. Replace the cover on the stage module and fasten
!
in place with screws.
WARNING: Risk of Electrical Shock. 7. Restore power to system.
Disconnect or isolate all power supplies before
making electrical connections. More than one Offset Differential
Potentiometer Potentiometer
disconnection or isolation may be required to
completely de-energize equipment. Contact with Module
components carrying hazardous voltage can cause Connector
Module
electric shock and may result in severe personal Connector
Jumper
injury or death. Position at J2
Relay Energized
LED Indicator Heating
AVERTISSEMENT: Risque de décharge Relay
électrique. Cooling
Débrancher ou isoler toute alimentation avant de Cover Screw
1 of 4
réaliser un branchement électrique. Plusieurs
isolations et débranchements sont peut-être
nécessaires pour -couper entièrement l'alimentation N.C. COM N.O.
Relay Output Terminals
de l'équipement. Tout contact avec des composants
conducteurs de tensions dangereuses risque
d'entraîner une décharge électrique et de provoquer Figure 3: Interior View of S350A Stage Module
des blessures graves, voire mortelles.
1. Ensure all power to system is off.
Each stage module may be receiving separate
power sources. Make sure all power sources to
each stage module are off.
2. Remove the stage module cover by loosening the
four captive cover screws.
4 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin
Offset Differential Offset Differential
Potentiometer Potentiometer Potentiometer Potentiometer
Module Module
Connector Connector
Module Module
Connector Jumper Connector Jumper
Position at J2 Position at J2
Relay Energized Reverse
Relay Energized Humidification
LED Indicator Relay Acting
LED Indicator
Relay Direct
Dehumidification
Acting
Cover Screw
Cover Screw 1 of 4
1 of 4
N.C. COM N.O.
N.C. COM N.O. Relay Output Terminals
Relay Output Terminals
Figure 5: Interior View of S352A Stage Module
Figure 4: Interior View of S351A Stage Module
S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin 5
Higher ON Higher
Temperature Pressure
Differential
ON
Differential
ON
Differential
ON
Differential
OFF
OFFSET OFF
Setpoint OFFSET
Temperature OFF
OFFSET Setpoint
OFFSET Pressure OFF
OFF
OFFSET
Differential
OFF OFFSET OFFSET
ON = Energized OFF
Differential
OFF = De-energized
Differential
OFF
Differential
OFF ON = Energized
OFF = De-energized
Differential
Lower ON
Temperature ON
ON
Lower ON
Pressure
ON
A350 S350A S350A S350A S350A P352AB S352A S352A S352A
Stage 1 Stage 2 Stage 3 Stage 4 Stage 5 Stage 1 Stage 2 Stage 3 Stage 4
Cooling Heating Direct Reverse
Figure 6: Example of a Heating/Cooling Figure 8: Example of a Reverse Acting/Direct
Application Using One A350 and Four S350As Acting Application Using One P352AB
and Three S352As
Higher ON
Humidity
W iring
Differential
ON
Refer to the following guidelines and wiring diagrams
Differential
for proper wiring and terminal designations (See
OFF Figures 9, 10, and 11.)
OFFSET
Setpoint
Relative Note: For information on connecting to an external
OFF
Humidity transformer refer to the applicable control
OFFSET
OFFSET bulletin.
OFF
Differential
ON = Energized OFF
OFF = De-energized
!
Differential
WARNING: Risk of Electrical Shock.
Lower Disconnect or isolate all power supplies before
Humidity ON making electrical connections. More than one
ON disconnection or isolation may be required to
completely de-energize equipment. Contact with
components carrying hazardous voltage can cause
W351 S351 S351 S351 electric shock and may result in severe personal
Stage 1 Stage 2 Stage 3 Stage 4
Humidify
injury or death.
Dehumidify
Figure 7: Example of a AVERTISSEMENT: Risque de décharge
Humidification/Dehumidification Application électrique.
Using One W351 and Three S351As Débrancher ou isoler toute alimentation avant de
réaliser un branchement électrique. Plusieurs
isolations et débranchements sont peut-être
nécessaires pour -couper entièrement l'alimentation
de l'équipement. Tout contact avec des composants
conducteurs de tensions dangereuses risque
d'entraîner une décharge électrique et de provoquer
des blessures graves, voire mortelles.
6 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin
IMPORTANT: Make all wiring connections in The stage modules plug into the control and other
accordance with the National add-on modules via 5-pin connectors located on either
Electrical Code and all local side of each module. Wiring is made at the Normally
regulations. Use copper Open (N.O.)/Normally Closed (N.C.) relay terminal
conductors only. Do not exceed strip. (See Figures 3, 4, and 5.)
the control’s electrical ratings.
SEN
COM Sensor
Shield (Connect Isolate and tape. (Do not ground
only to COM on A350) this end of cable shield.)
A350 Y350R S350A S350A S350A D350
Wire
Terminal
Block
24V
COM
VDC
SEN
120 VAC
Load Load Load Load
Figure 9: Typical Multistage Temperature Control System Using 120 VAC Power Supply
Transmitter
SEN
VDC
COM
Shield (Connect Isolate and tape. (Do not ground
only to COM on W351) this end of cable shield.)
W351 Y350R S351A S351A S351A D351
Wire
Terminal
Block
24V
COM
VDC
SEN
120 VAC
Load Load Load Load
Figure 10: Typical Multistage Humidity Control System Using 120 VAC Power Supply
S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin 7
Wiring Harness P399 Transducer
SEN
VDC
COM
Shield (Connect Isolate and tape. (Do not ground
only to COM on P352AB) this end of cable shield.)
P352AB Y350R S352A S352A S352A D352A
Wire
Terminal
Block
24V
COM
VDC
SEN
120 VAC
Load Load Load Load
Figure 11: Typical Multistage Pressure Control System Using 120 VAC Power Supply
8 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin
C heckout Procedure
Before applying power, make sure installation and Table 4: S351A Relay Troubleshooting
wiring connections are according to job specifications.
Operation LED N.O. Setpoint Dial
After necessary adjustments and electrical
Mode Relay Setting
connections have been made, put the system in
Status
operation and observe at least three complete
operating cycles before leaving the installation. Dehumidify On Closed (RHT)* -offset
- differential
Dehumidify Off Open (RHT) - offset
Humidify On Closed (RHT) + offset
T roubleshooting + differential
Humidify Off Open (RHT) + offset
If the control system does not function properly, first
verify that the control, power, and display modules are *(RHT) = actual relative humidity at transducer
all operating correctly (refer to the respective
literature). Then inspect the stage modules for proper Table 5: S352A Relay Troubleshooting
operation.
Operation LED N.O. Setpoint Dial
Check that the proper operating mode Mode Relay Setting
(Cooling/Heating, Dehumidification/Humidification, or Status
Direct Acting/Reverse Acting) has been selected on
each stage module. (See Adjustments section and Direct On Closed (psiT)*- offset -
Figures 3, 4, and 5.) Then perform the following differential
procedures to determine the problem. Direct Off Open (psiT) - offset
1. Verify the system has power. Reverse On Closed (psiT) + offset +
differential
2. Note the offset and differential settings on the
Reverse Off Open (psiT) + offset
stage module.
*(psiT) = actual pressure at transducer
3. Turn the setpoint dial on the control module to
minimum. 5. If the relays do not perform as indicated in
Tables 3, 4, or 5, adjust the stage module’s
4. Increase the setpoint by slowly adjusting the differential and offset potentiometers to minimum
setpoint dial until the stage relay LEDs turn On and repeat Steps 1 through 3.
and Off as shown in Tables 3, 4, or 5.
6. If the relays still do not turn on and off, replace the
Table 3: S350A Relay Troubleshooting defective stage modules.
Operation LED N.O. Setpoint Dial Note: There is the unlikely possibility that a defect in
Mode Relay Setting one stage module could cause defective
Status symptoms in all modules. Plug each stage into
Cooling On Closed (Ts)* - offset the control individually and check the
- differential performance of each as explained above.
Cooling Off Open (Ts) – offset
Heating On Closed (Ts) + offset
+ differential
R epairs and Replacement
Do not make field repairs or perform calibration.
Heating Off Open (Ts) + offset
Sensors and replacement controls are available
*(Ts) = sensed temperature through your local Johnson Controls representative.
S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical Bulletin 9
O rdering Information
Table 6: Ordering Information
Item Product Code Description
Number
S350A Temperature Stage S350AA-1C Temperature Stage Module with Fahrenheit Scale
Module
S350AB-1C Temperature Stage Module with Celsius Scale
S351A Humidity Stage Module S351AA-1C Humidity Stage Module with percent RH Scale
S352A Pressure Stage Module S352AA-2C Pressure Stage Module with psi Scale
S pecifications
Product S350AA: Temperature Stage Module with Fahrenheit Scale
S350AB: Temperature Stage Module with Celsius Scale
S351AA: Humidity Stage Module with Percent RH Scale
S352AA-2: Pressure Stage Module with psi Scale
Input Voltage S350AA: Provided by the A350
S351AB: Provided by the W351
S352AA-2: Provided by the P352AB
Power Consumption 1.0 VA maximum
Output Relay Electrical SPDT Enclosed Relays
Ratings 10 Ampere Non-inductive, 125 VA Pilot Duty, 24/240 VAC
1/2 hp 120/240 VAC
Differential Adjustment S350AA: 1 to 30F°
Range S350AB: 0.5 to 17C°
S351AA: 2 to 10% RH
S352AA-2: 2 to 50 psi
Offset Range S350AA: 1 to 30F°
S350AB: 0.6 to 16.7C°
S351AA: 2 to 30% RH
S352AA-2: 2 to 50 psi
Ambient Temperature Operating: -30 to 150°F (-34 to 66°C)
Shipping: -40 to 185°F (-40 to 85°C)
Ambient Humidity 0 to 95% RH (Non-condensing)
Material Case, Cover: NEMA 1 High Impact Thermoplastic
Mounting Wall or DIN Rail
Agency Listing UL Listed, CCN XAPX, File E27734
UL Listed for Canada, CCN XAPX7, File E27734
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls/Penn Application Engineering at (414) 524-5535. Johnson Controls, Inc. shall not be liable for
damages resulting from misapplication or misuse of its products.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
® Johnson Controls and PENN are registered trademarks of Johnson Controls, Inc. in the
United States of America and/or other countries. All other trademarks used herein are the property
of their respective owners. © Copyright 2014 by Johnson Controls, Inc. All rights reserved.
10 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules Product/Technical BulletinПозиції каталогу з цим документом
Документ виробника, опублікований як довідковий матеріал на обладнання, яке ми постачаємо. Правовласник може попросити прибрати його — приберемо.