System 350 Product Guide 930
Add-On Modules Section
Product/Technical Bulletin D350
Issue Date 0414
System 350 Display Modules
The D350, D351, and D352 Display Modules are
TM
designed for use with System 350 temperature,
humidity, and pressure controls to provide a digital
readout of sensor or setpoint values—at the push of a
button.
As are all System 350 products, the display modules
are housed in a NEMA 1 high-impact thermoplastic
enclosure. The modular design provides easy,
plug-together connections for quick installation and
future expandability.
Figure 1: System 350 Display Module
Features and Benefits
Modular Design Enables control, stage, and display modules
to be purchased and installed as necessary
Plug-together Connectors Eliminates wiring between modules and
and 35 mm DIN Rail reduces installation costs
Mounting
Various Models Display Provides visual sensor and setpoint indication
Temperatures (°F and °C), for System 350 controls
Humidity Levels
(0 to 100%), or
Pressures (in psi or in. W.C.)
Continuous Readout of Permits use as a monitoring device and/or a
Sensor Value; Front Access setup tool
Button Can Be Pushed to
Display Setpoint
Can be Remote Mounted Extends monitoring capabilities up to 50 ft
Using WHA29A Cable (15.2 m)
Assemblies
© 2014 Johnson Controls, Inc. 1
Part No. 24-7664-206, Rev. J www.johnsoncontrols.com
Code No. LIT-930070
A pplication Overview I nstallation
System 350 Display Modules can be permanently
installed in a System 350 control system or used for ! WARNING: Risk of Electric Shock.
remote setup or troubleshooting.
Disconnect the power supply
All adjustments to the system can be made accurately before making electrical
by using the display modules during setup. For connections. Contact with
applications where a display module will not be components carrying hazardous
permanently mounted, the service technician can use voltage can cause electric shock
an optional extension cable (WHA29A-600R) to and may result in severe personal
temporarily connect a display module to the system to injury or death.
verify the sensor reading and setpoint.
AVERTISSEMENT : Risque de
décharge électrique.
Débrancher l'alimentation avant de
Module 3-Digit Module réaliser tout branchement
Connector LCD Display
Connector
électrique. Tout contact avec des
composants conducteurs de
D350
tensions dangereuses risque
PRESS FOR SETPOINT
d'entraîner une décharge électrique
Setpoint
Button et de provoquer des blessures
graves, voire mortelles.
The display modules are housed in a compact NEMA 1
plastic enclosure designed for standard 35 mm DIN rail
mounting. The modules are not position sensitive, but
they should be mounted for convenient wiring and
adjustment. Four key-slot mounting holes on the back
of the control case are provided for surface mounting
Figure 2: Display Module Features when required.
The display modules plug into the control and other
System 350 add-on modules via 5-pin connectors
located on either side of each module.
O peration System 350 modules can be arranged in any order;
The display modules receive their power, sensor, and external wiring is not required to interconnect
setpoint information from a System 350 control components. (For optimal system accuracy, mount the
module. A 3-digit LCD (Liquid Crystal Display) provides D350 series modules at the far right end of the
continuous readout of the sensor value. system.) The system becomes operational as soon as
power is applied.
To view the setpoint reading, press the PRESS FOR
SETPOINT button located on the face of the module. Five wire cable assemblies in various lengths are
The button must be pressed and held for available for remote mount applications. See Table 3.
approximately three seconds.
IMPORTANT: The D350, D351, and D352 Display
Modules are matched to the A350,
W351, and P352 controls,
respectively. If an incorrect display
module is used on a system, the
display provides inaccurate readings.
See Table 2 for more information on
choosing the correct D350 display
module.
2 Add-On Modules—System 350 Display Modules Product/Technical Bulletin
D imensions C heckout Procedure
Mounting Slots 3/16 (4) Before applying power, make certain that the
for No. 6 Screws
installation and wiring connections are according to job
1/2 (13)
specifications. After necessary adjustments and
electrical connections have been made, put the system
2-15/16 D350
into operation and observe at least three complete
5 PRESS FOR SETPOINT
operating cycles before leaving the installation.
(75)
(127)
1-9/16
R epairs and Replacement
DIN Rail 2-3/8 (61)
(40) 7/16 (11) Mounts
Field repairs or calibration must not be made.
1-3/16 For replacement modules, contact the nearest
(31) Johnson Controls representative.
2-3/8
(61)
7/8 (22)
7/8 (22)
Conduit
Hole
Figure 3: Module Dimensions, in. (mm)
Add-On Modules—System 350 Display Modules Product/Technical Bulletin 3
T roubleshooting
Before troubleshooting the display module, verify that Table 1: Out-of-Range Values
the system control is functioning properly. Consult the
appropriate System 350 bulletin for operating Display Out-of-Range Out-of-Range
specifications and troubleshooting instructions. Module Setpoint Value Sensor Value
Model
If the control is functioning properly, use the following
procedure to troubleshoot the display module. D350AA-1 Greater than Greater than 300°F or
260°F or 130°C 150°C
1. Measure the temperature, pressure, or humidity
with an instrument that is at least as accurate as D351AA-1 Greater than Greater than
the sensor in the system, and compare this with 95% RH 100% RH
the readout on the display module. D352AA-2 Greater than Greater than 750 psi
a. If these values do not match within a 700 psi
reasonable range (for example, 0.5F°), check D352CA-1 Greater than none
the sensor for proper wiring and performance. 5.20 in. W.C.
Refer to the appropriate sensor bulletin for
D352CA-2 Greater than Greater than
information on sensor troubleshooting.
0.260 in. W.C. 0.520 in. W.C.
b. If the sensor is wired and operating correctly
and the display reading is incorrect, the display
module must be replaced. Table 2: Controls and Related Display
2. Press the PRESS FOR SETPOINT button on the Modules
front of the display module. If the value displayed Control Module Display Module
on the LCD is out of range, replace the display Models Models
module. Refer to Table 1 for out-of-range values
for the various display modules. A350A/B, A350E, A350P, D350
A350R, A350S
3. If pressing the PRESS FOR SETPOINT button W351, W351P D351
results in a reading other than the expected
setpoint value, check the setpoint dial setting and P352AB-2, P352AB-3, D352AA-2
P352AB-4, P352PN-2,
correct if necessary. If the display continues to
P352PN-3, P352PN-4
read an incorrect value, replace the display
module. P352PQ-1 D352CA-1
P352PQ-2 D352CA-2
4 Add-On Modules—System 350 Display Modules Product/Technical Bulletin
O rdering Information
Table 3: Ordering Information
Product Code Number Description
D350AA-1C Temperature Display Module with Fahrenheit Scale
D350BA-1C Temperature Display Module with Celsius Scale
D351AA-1C Humidity Display Module with Percent RH Scale
D352AA-2C Pressure Display Module with 0 to 750 psi Scale
(Not interchangeable with D352AA-1C)
D352CA-1C Pressure Display Module with 0 to 9.99 in. W.C. Scale
D352CA-2C Pressure Display Module with 0 to 0.999 in. W.C. Scale
WHA29A-600R 3 ft (0.9 m) Cable, 5-wire
WHA29A-603R 25 ft (7.6 m) Cable, 3-wire; Requires Y350R at D350 Location
WHA29A-604R 50 ft (15.2 m) Cable, 3-wire; Requires Y350R at D350 Location
S pecifications
Product System 350 Display Modules
Readout 3-digit LCD Continuous Display
Supply Voltage D350 Provided by the A350 Temperature Control Module
D351 Provided by the W351 Humidity Control Module
D352AA-1;
D352AA-2;
D352CA-1;
D352CA-2: Provided by the P352 Pressure Control Module
Current Draw 4 mA (typical)
Mounting Surface or DIN Rail
Ambient Temperature Operating: -30 to 150°F (-34 to 66°C)
Shipping: -40 to 167°F (-40 to 75°C)
Ambient Humidity 0 to 95% RH non-condensing
Material Case, Cover: NEMA 1 High-impact Thermoplastic
Agency Listings UL CNN XAPX
UL Listed for Canada, CNN XAPX7, File E27734 (all models)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls/PENN Application Engineering at (414) 524-5535. Johnson Controls, Inc. shall not be liable for
damages resulting from misapplication or misuse of its products or misuse of its products.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
® Johnson Controls and PENN are registered trademarks of Johnson Controls, Inc. in the
United States of America and/or other countries. All other trademarks used herein are the property
of their respective owners. © Copyright 2014 by Johnson Controls, Inc. All rights reserved.
Add-On Modules—System 350 Display Modules Product/Technical Bulletin 5Позиції каталогу з цим документом