Product Bulletin
                                                                               Issue Date      March 27, 2009

     Single Duct Variable Air Volume Terminal (Model TSS)

Model TSS Terminals provide Variable Air Volume
(VAV) control beyond the typical single duct box. They
are specifically designed for precise air delivery
throughout the entire operating range, regardless of
the installed inlet conditions. These units can be
ordered with or without a Direct Digital Controller
(DDC), which can operate as a stand-alone unit, on a
Johnson Controls® N2 trunk, or on a LON trunk.
TSS Terminals take advantage of typical benefits
provided by single duct units while performing at
extremely low sound levels. This is critical in today’s
buildings where occupants are placing more emphasis
on indoor acoustics.
                                                           Figure 1: Single Duct Variable Air Volume Terminal
The ability to provide comfort to the occupant is the                         (Model TSS)
measurement of quality for any VAV terminal. Comfort
is achieved through quiet and precise control of airflow
to the occupied space.
The TSS Terminal is manufactured and assembled
with a multi-point, center-averaging airflow sensor.
This sensor provides a signal to the controller enabling
it to quietly and precisely measure airflow. Accurate
measurement is the basis for airflow control.
Bundled with the TSS Terminal is a digital controller
from the VAV Modular Assembly (VMA) Series or the
LN Series. Each model in the VMA1400 Series and
the LN Series combines a controller, pressure sensor,
and actuator housed in one preassembled unit.
Unique features that reduce installation and
commissioning time while enhancing VAV system
operation make the VMA the product of choice for VAV
systems.                                                           Figure 2: VMA1410 and VMA1420

The VMA and LN Series controls can be used in these
types of applications:
•   Cooling only
•   Cooling with Reheat and/or Exhaust
Note: For more information on the VMA1400 Series,
refer to the Variable Air Volume Modular Assembly
(VMA) 1400 Series Product Bulletin (LIT-635058).
Note: For more information on the LN Series, refer
to the Metasys® System LN Series VAV and VVT                         Figure 3: LN Series Controller
Profile Application Controllers Product Bulletin
(LIT-1201910).

© 2009 Johnson Controls, Inc.                                                                                      1
  Code No. LIT-1201825                                                                        www.johnsoncontrols.com
                                            Features and Benefits
                   Factory-Provided DDC           An integrated VAV box with controls
                                                  eliminates the coordination and difficulties
                                                  associated with factory mounting

                   Factory-Commissioned           Reduces startup time and lowers risk through
                   DDC                            downloading of software, setting of
                                                  parameters, addressing, and testing at the
                                                  factory

                   Flexible Design                Provides application flexibility, while providing
                                                  options that can meet even the most stringent
                                                  job requirements

                   Superior Flow Measuring        Provides for lower minimum Cubic Feet per
                                                  Minute (cfm) values, which reduces energy
                                                  costs and noise while maintaining comfort in
                                                  the zone

                   Integrated Module              Includes controller, pressure sensor, and/or
                                                  actuator, preassembled to reduce installation
                                                  time

                   Enhanced Actuator              Provides a fast response stepper motor that
                                                  drives the damper from full open to close in
                                                  30 seconds (VMA Series)

                   Automated Commissioning        Uses Proportional Adaptive (P-Adaptive) and
                                                  Pattern Recognition Adaptive Control (PRAC)
                                                  for continuous loop tuning (VMA Series)

                   Advanced Diagnostics           Offers damper stall detection, starved box
                                                  detection, actuator motor duty cycle, VAV box
                                                  flow test, and other diagnostics on most
                                                  models (VMA Series)

                   Multiple Network               Enables integration into a Building Automation
                   Communications                 System (BAS)

                   Standard Applications          Provides proven designs and quick selection
                                                  of proper variables to ensure proper operation

                   Quick Installation             Reduces installation time with the low profile
                                                  compact design and standard metal hanging
                                                  straps

                   Agency Certified               Wired in compliance with all applicable
                                                  National Electrical Code (NEC) requirements
                                                  and tested in accordance with Air
                                                  Conditioning and Refrigeration Institute (ARI)
                                                  Standard 880

                   Easy Maintenance and           Requires no periodic maintenance and
                   Service                        provides trouble-free operation

2   Single Duct Variable Air Volume Terminal (Model TSS) Product Bulletin
                                                             Energy Efficiency
Model TSS Terminals
                                                             In addition to quiet and accurate temperature control,
Flexibility                                                  the building owner benefits from lower operating costs.
                                                             The highly amplified velocity pressure signal from the
Selection and Layout                                         inlet sensor allows precise airflow control at low air
The TSS provides flexibility in system design. The           velocities.
compact cabinet design and quiet operation give the          The sensor’s airfoil shape provides minimal pressure
system designer the versatility to place units directly      drop across the terminal. This allows the central fan to
above occupied spaces. It is not necessary to locate         run at a lower pressure and with less brake
the unit in the crowded space above a hall or corridor,      horsepower.
which reduces lengthy and expensive discharge duct
runs. The sensor ensures accurate control, even when         Agency Certification
space constraints do not permit long straight inlet duct
                                                             Model TSS Terminals with electronic controls and/or
runs to the terminal.
                                                             electric heat are listed with ETL as an assembly and
                                                             bear the ETL label.
Sizes
Model TSS Terminals are available in 10 unit sizes to        Note: ETL is a mark issued by Intertek Testing
handle airflow capacities between 45 and 8,000 Cubic         Services (ITS) ETL SEMKO Division.
Feet per Minute (cfm).                                       TSS Terminals and accessories are wired in
                                                             compliance with all applicable NEC requirements and
Convenience                                                  tested in accordance with ARI Standard 880.
Quality
                                                             Maintenance and Service
All TSS Terminals are thoroughly inspected during
                                                             TSS Terminals require no periodic maintenance and
each step of the manufacturing process, including a
                                                             provide trouble-free operation. Controls are located on
comprehensive pre-ship inspection, to ensure the
                                                             the outside of the unit casing for easy access by
highest quality product available. All TSS Terminals
                                                             maintenance personnel.
are packaged to minimize damage during shipment.

Quick Installation
A standard single point electrical main power
connection is provided with all electronic controls and
electrical components located on the same side of the
casing for quick access, adjustment, and
troubleshooting. Installation time is further minimized
due to the availability of factory-calibrated controls and
a low profile, compact design.
The sensor ensures accurate airflow measurement,
regardless of the field installation conditions. A
calibration label and wiring diagram is located on the
terminal for quick reference during startup.
The terminal is constructed to allow installation with
standard metal hanging straps. Optional hanger
brackets for use with all-thread support rods or wire
hangers are also available.

Value and Security

Quality
All metal components are fabricated from G90
galvanized steel. Unlike most manufacturers’
terminals, the TSS is capable of withstanding a
125-hour salt spray test without showing any evidence
of red rust.

                                         Single Duct Variable Air Volume Terminal (Model TSS) Product Bulletin      3
                                                             Optional Features
Standard Features
                                                             Construction
Construction
                                                             Optional construction features include:
Standard construction features include:
                                                             •   20-gauge G90 galvanized steel construction
•   ARI 880 certified and labeled
                                                             •   3/4” and 1” insulation
•   22-gauge, G90 galvanized steel casing and valve
                                                             •   scrim-reinforced, foil-faced insulation meeting
•   1/2" 4 lb.ft3 skin, dual density fiberglass insulation
                                                                 American Society for Testing and Materials
    (mechanically fastened for added security)
                                                                 (ASTM) C1136 for mold, mildew, and humidity
                                                                 resistance
Primary Air Valve
Standard primary air valve features include:                 •   1/2” closed cell insulation

•   embossed rigidity rings                                  •   double wall construction

•   low thermal conductance damper shaft                     •   mounting brackets to accept all thread hanging
                                                                 rods or wire hangers
•   position indicator on external end of damper shaft
                                                             •   low temperature construction for use in thermal
•   mechanical stops for open and closed position                storage applications (includes a thermally isolated
•   center-averaging airflow sensor                              primary air inlet and a composite damper shaft)

•   brass balancing tees                                     Hot Water Coil
•   plenum-rated sensor tubing                               Optional hot water coil features include:
                                                             •   coil access plate for cleaning coil
Hot Water Coils
Standard hot water coil features include:                    Electrical Components
•   ARI 410 certified and labeled                            Optional electrical components include:

•   1-, 2-, 3-, 4-row coils                                  •   toggle disconnect switch

•   left- or right-hand connections                          •   primary and secondary transformer fusing

•   tested at a minimum of 450 psig under water and          Electric Heat
    rated at 300 psig working pressure at 200°F
                                                             Optional electric heat features include:
Electrical Components                                        •   proportional Solid State Relay (SSR) heater
Standard electrical components include:                          control

•   cETL listed for safety compliance with                   •   mercury contactors
    Underwriters Laboratories Inc.® (UL) 1995                •   door interlocking disconnect switches
•   National Electrical Manufacturers Association
    (NEMA) Type 1 wiring enclosure                           Controls
                                                             Optional controls include:
Electric Heat
                                                             •   Direct Digital Controls (DDC)
Standard electric heat features include:
                                                             •   pneumatic controls
•   cETL listed as an assembly for safety compliance
•   automatic reset primary and back-up secondary
    thermal limits
•   airflow switch
•   single-point power connection
•   hinged electrical enclosure door
•   fusing per NEC
4   Single Duct Variable Air Volume Terminal (Model TSS) Product Bulletin
                                                           Factory Commissioning
VMA1400 Series Controllers
                                                           Whenever the VMA Series controls are ordered on the
Actuator Enhancements                                      TSS Series, the factory downloads the correct
                                                           application into the controller. In addition, the factory
The VMA1410 and 1420 use an actuator with a fast
                                                           also sets the Area and K Factor for the size of the box
response stepper motor, which is quiet (<35 dBA) and
                                                           on which it is installed. If provided, the factory also
precise (23 K resolution). The stepper motor drives the
                                                           sets the minimum/maximum Cubic Feet per Minute
damper from full open to full close in 30 seconds. This
                                                           (cfm) and address. Each box is thoroughly tested at
significantly reduces the time to commission and
                                                           end-of-line prior to packaging.
balance a VAV terminal box. The stepper motor
quickly and accurately adjusts the damper position in
                                                           Automated Commissioning
response to new conditions, minimizing position
hunting and motor runtime.                                 Because the VMA1410 and 1420 perform loop tuning
                                                           automatically, there is no need to set proportional
Applications                                               bands and integration terms. There is no need to set
                                                           any jumpers or switches. Even network addressing
The VMA1400 Series controllers can be configured for
                                                           can be done via software, if desired.
most single duct VAV applications. The VMA1420
requires an additional damper actuator with Differential   The VMA1410 and 1420 are configured to detect the
Pressure Transducer (DPT) sensor for supply/exhaust        damper end-stops automatically. On power up, the
applications and dual duct applications.                   actuator drives to both hard stops on the VAV box and
                                                           remembers these positions. These automated features
Standard applications for the VMA1410 and 1420
                                                           get the system operating quickly.
reside in the Heating, Ventilating, and Air Conditioning
(HVAC) PRO library, which is a section of the Global
Operations Support library. See Table 1 for more           LN Series Controllers
detailed application and control options. Also refer to
                                                           LN-VAVL-0 and LN-VAVC-0 Controllers
the Variable Air Volume Modular Assembly (VMA)
1400 Series Application Note (LIT-6375125).                LN-VAVL-0 and LN-VAVC-0 controllers include an
                                                           enclosure with actuator, pressure sensor, eight
Advanced Diagnostics                                       Input/Outputs (I/Os), and LONWORKS® Network
                                                           Services (LNS®) plug-in.
The VMA1400 Series has several unique diagnostic
features. Diagnostics include damper stall detection,
                                                           Applications
starved box detection, actuator motor duty cycle,
VAV box flow test, and others.                             The LN-VAVL-0 Series controllers can be configured
                                                           for most single duct VAV applications. The LN-VAVC-0
The VMA constantly monitors the space temperature          requires an additional damper actuator with Differential
and airflow and generates alarms to alert the operator     Pressure Transducer (DPT) sensor for supply/exhaust
of setpoint deviations. The operator can react quickly,    applications and dual duct applications.
taking corrective action to get the system back into
desired operation. This ensures occupants better           Standard applications for the LN-VAVL-0 and the
comfort control.                                           LN-VAVC-0 reside in the Global Operations Support
                                                           library.

                                        Single Duct Variable Air Volume Terminal (Model TSS) Product Bulletin      5
Table 1: Applications
 Applications              Control Options                        VMA1400               LON
                                                                1410    1420    LN-VAVL-0   LN-VAVC-0
 System Types              Single Duct                            X         X      X           X
                           Pressure Independent                   X         X      X           X
                           Supply/Exhaust                                   X                  X
 Heating (Terminal Box)    Floating 3-Wire Valve Actuator                   X      X           X
                           Proportional Valve Actuator                      X      X           X
                           Normally Open or Normally Closed                 X      X           X
                           Valve
                           1- to 3-Stage Electric                           X
                           Electric Coil SSR Control                        X      X           X
 Heating (Supplemental)    Floating 3-Wire Valve Actuator                   X      X           X
                           Proportional Valve Actuator                      X      X           X
                           Normally Open or Normally Closed                 X      X           X
                           Valve
                           Single Stage Electric                            X      X           X
 Cooling (Terminal Box)    Stepper Motor Damper Actuator          X         X
 Floating/3-Wire           External Damper and Valve                        X                  X
 (Incremental) Actuator    Valve Only                                       X      X           X
 Proportional Actuator     External Damper and Valve                        X                  X
 Lighting                  On/Off (In Relation to Occupancy                 X                  X
                           Mode)
 Modes                     Occ/Temp                               X         X      X           X
                           Occ/Unocc                              X         X      X           X

6   Single Duct Variable Air Volume Terminal (Model TSS) Product Bulletin
Standard Terminal Construction
Accurate Airflow Control Sensor
The air valve features an airflow sensor that has
brought new meaning to airflow control accuracy. The
multi-axis design uses between 12 and 20 sensing
points that sample total pressure at center points
within equal concentric cross-sectional areas,
effectively traversing the air stream in two planes.
Each distinct pressure reading is averaged within the
center chamber before exiting the sensor to the
controlling device.
This sensor adds a new dimension to signal
amplification. Most differential pressure sensors
provide a signal equal to 1.5 times the equivalent
velocity pressure signal. This sensor provides a
                                                                           Figure 4: Airflow Sensor
differential pressure signal that is 2.5 to 3 times the
equivalent velocity pressure signal. This amplified
signal allows more accurate and stable airflow control
at low airflow capacities. Low airflow control is critical
for indoor air quality, reheat minimization, and the
prevention of overcooling during light loads.
Unlike other sensors, which use a large probe surface
area to achieve signal amplification, this sensor uses
an unprecedented, streamlined design that generates
amplified signals. This streamlined design also
generates less pressure drop and noise.
The VAV schedule should specify the minimum and
maximum airflow setpoints, maximum sound power
levels, and maximum air pressure loss for each
terminal. The specification for the VAV terminal must
detail the required performance of the airflow sensor.

Amplifying the Airflow Sensor Signal Provides for                      Figure 5: Airflow Sensor in Collar
Lower Minimum Airflow Setpoints
Many VAV controllers require a minimum differential          Table 2: Airflow Sensor Features
pressure signal of 0.03 inches wg. The airflow sensor           Feature     Description
should be able to generate this signal with only 400 to
450 FPM air velocity through the inlet collar.                     1        Each pressure input signal is routed to the
                                                                            center averaging chamber
Conventional airflow sensors without amplification
                                                                   2        Equal, concentric circular areas (three to
capabilities require approximately 700 FPM to                               five circles based on size)
generate a 0.03 inches wg signal. If 700 FPM
                                                                   3        Total pressure measured at the center of
represents a 20% minimum condition, the inlet velocity
                                                                            each concentric circle (12 to 20 sensing
would be 3500 FPM at the maximum airflow setpoint,                          points based on size)
resulting in extremely noisy conditions. In addition, the
                                                                   4        Airfoil-shaped averaging chamber for low-
airflow sensor should generate a differential pressure
                                                                            pressure loss and noise
range of at least 1-inch wg over the operating range of
the terminal unit.                                                 5        Two-axis low profile design
                                                                   6        Averaged and amplified differential
                                                                            pressure output to controlling device
                                                                   7        Pressure output is routed behind probe to
                                                                            minimize pressure loss and noise
                                                                   8        Brass field-pressure measuring tap

                                          Single Duct Variable Air Volume Terminal (Model TSS) Product Bulletin           7
Model TSS
The TSS Terminal incorporates many unique features.
Most of these standard features are expensive options
for other manufacturers.

       Figure 6: Model TSS – Standard Features                              Figure 7: Model TSS – Standard Features
                     (Front View)                                                         (Rear View)

Table 3: Model TSS – Standard Features
     Feature      Description
        1         Product label includes tagging, airflow, and electrical information
        2         Mechanical lock construction ensures lowest possible casing leakage
        3         G90 galvanized steel casing withstands 125-hour salt spray test per ASTM B-117
        4         Roll-formed inlet collar with integral stiffening ribs adds strength and rigidity
        5         Patented airflow sensor
        6         Electrical devices installed within a NEMA Type 1 Enclosure, with single point power connection
        7         Units with electronic controls listed with ETL for safety compliance
        8         Slip and drive discharge collar for quick field installation
        9         Self-lubricating bearing to reduce friction and air leakage
        10        Insulation edge covered by metal — no raw edges of insulation exposed to airstream
        11        Solid composite damper shaft prevents condensation and breakage
        12        Low leakage damper incorporates closed cell foam gasket
        13        Mechanically fastened insulation for added security
                  1/2" thick, 4 lb.ft skin, dual density insulation complying with UL 181 and National Fire Protection
                                     3
        14
                  Association (NFPA) 90A, and ASTM C1071
    (not shown)   Factory-supplied and installed controls

8    Single Duct Variable Air Volume Terminal (Model TSS) Product Bulletin
                                                            Model TSS-E Standard Features
Electric Heater Selection
                                                            Model TSS-E standard features include:
Model TSS-E                                                 •   cETL listed as an assembly
                                                            •   single-point power connection
                                                            •   primary auto-reset high limit
                                                            •   secondary high limit
                                                            •   airflow switch
                                                            •   hinged control panel
                                                            •   ni-chrome elements
                                                            •   primary/secondary power terminations

         Figure 8: Model TSS-E – Inlet View                 •   fusing per NEC
                                                            •   wiring diagram and ETL label
                                                            •   Available kW increments are as follows:
                                                                0.5 to 5.0 kW - .25 kW; 5.0 to 10.0 kW - .50 kW;
                                                                Above 10 kW - 1.0 kW

                                                            Model TSS-E Optional Features
                                                            Model TSS-E optional features include:
                                                            •   disconnect (toggle or door interlocking)
                                                            •   Pneumatic Electric (PE) switches
      Figure 9: Model TSS-E – Rear Inlet View               •   mercury and magnetic contactors
Historically, heater elements placed downstream of a        •   manual reset secondary limit
VAV damper have experienced two major problems:
                                                            •   proportional control (SSR)
•   elements fail prematurely due to hot spots
    resulting from an uneven air velocity profile over      •   24 volt control transformer
    the heater face
•   heaters suffer rapid nuisance cycling of the
    contactors and elements because the airflow
    switch probe is located on the low-pressure
    (downstream side) of the VAV damper
Our unique electric heat VAV terminal, the TSS-E,
solves these problems. The heater elements are
located midway between the air inlet and the damper.
This design provides uniform airflow over the face of
the electric heater at all damper positions. Element life
is extended, reducing repair cost and inconvenience.
With the heater elements located on the high-pressure
side of the VAV damper, the airflow pressure switch
receives a reliable pressure signal even at minimum
damper positions. This arrangement provides greater
safety, as well as enhanced reliability.
The TSS-E design permits tremendous flexibility when
selecting kW, voltage, phase, balanced or unbalanced
circuiting and method of control.

                                        Single Duct Variable Air Volume Terminal (Model TSS) Product Bulletin      9
Model TSS-E Selection Procedure
With standard heater elements, the maximum capacity
(kW) is obtained by dividing the heating (minimum)
Standard Cubic Feet per Minute (scfm) by 70. In other
words, the terminal must have at least 70 scfm per
kW. In addition, each size terminal has a maximum
allowable kW based upon the specific heater element
configuration (for example, voltage, phase, and
number of steps).
Heaters require a minimum of 0.07" wg downstream
static pressure to ensure proper operation.

Table 4: Selection Equations
 Equations
 kW       = scfm x ΔT x 1.085*      *Air density at sea
            3413                    level - reduce by
                                    0.036 for each 1,000
 scfm     = kW x 3413               feet of altitude above
            ΔT x 1.085 *            sea level.
 ΔT       = kW x 3413
            scfm x 1.085*

                                                               Figure 11: Electric Heater Pressure Drop
Table 5: Calculating Line Amperage
 Equations
 Single Phase Amperes       =    kW x 1,000
                                 Volts
 Three Phase Amperes        =    kW x 1,000
                                 Volts x 1.73

          Figure 10: Electric Heat Diagram
The TSS-E uses a unique design that has the electric
heater elements upstream of the air valve, enabling
lower scfm to be used due to an even flow across the
coils. By controlling the air after the coils, the TSS-E
provides more reliable sensing of static pressure in the
duct and longer life of the heating coils.

10    Single Duct Variable Air Volume Terminal (Model TSS) Product Bulletin
                                                                    Model TSS-W Optional Features
Hot Water Coil Selection
                                                                    Model TSS-W optional features include:
Model TSS-W                                                         •     low-pressure steam coils
                                                                    •     multi-circuit coils for reduced water pressure drop
                                                                    •     opposite hand water connections
                                                                    •     bottom and top access plates for cleaning

                                                                    Model TSS-W Selection Procedure
                                                                    Performance is based on a temperature difference of
                                                                    125°F between the entering water and the entering air.
                                                                    For Variable Air Volume Applications, the static
                                                                    pressure drop must be based on the maximum air
                                                                    volume.
                                                                    Table 8 gives correction factors for various entering
               Figure 12: Model TSS-W                               ΔTs (difference between EWT and EAT). Multiply MBH
                                                                    values obtained from selection tables by the
Table 6: Model TSS-W – Definition of Terms                          appropriate correction factor to obtain the actual MBH
                                                                    value. Air and water pressure drop can be read directly
    Term     Definition
                                                                    from the selection tables. The LAT and LWT can be
    EAT      Entering Air Temperature (°F)                          calculated from the following fundamental formulas:
    EWT      Entering Water Temperature (°F)
    LWT      Leaving Water Temperature (°F)                         Table 7: LAT/LWT Fundamental Formulas
    LAT      Leaving Air Temperature                                    Formulas
    CFM      Air Volume (cubic feet per minute)                         LAT    =      EAT      +     BTUH
    GPM      Water Capacity (Gallons per Minute)                                                     1.085 x cfm
    MBH      1,000 BTUH                                                 LWT    =      EWT      -     BTUH
    BTUH     Coil Heating Capacity (British Thermal Units                                            500 x GPM
             per Hour)

Model TSS-W Standard Features
Model TSS-W standard features include:
•   aluminum fin construction with die-formed spacer
    collars for uniform spacing
•   mechanically expanded copper tubes leak tested
    to 450 psig air pressure and rated at 300 psig
    working pressure at 200°F
•   male sweat type water connections
•   1-, 2-, 3-, and 4-row configurations

Table 8: Model TSS-W Correction Factors
                             Entering Water - Air Temperature Differential (ΔT) Correction Factors
     ΔT         20     25      30      35       40    45     50          55    60       65         70     75       80     85     90
    Factor     0.15   0.19    0.23   0.27      0.31   0.35   0.39       0.43   0.47     0.51       0.55   0.59     0.63   0.67   0.71
     ΔT         95     100    105    110       115    120    125        130    135      140        145    150      155    160    165
    Factor     0.75   0.79    0.83   0.88      0.92   0.96   1.00       1.04   1.08     1.13       1.17   1.21     1.25   1.29   1.33

                                            Single Duct Variable Air Volume Terminal (Model TSS) Product Bulletin                      11
Technical Specifications
VAV Modular Assembly (VMA) 1400 Series
Product Code Number          Cooling Only:         Cooling w/Reheat
                                                   and/or Fan:
          Single Unit:       AP-VMA1410-0          AP-VMA1420-0
          Bulk Pack:         AP-VMA1410-0D         AP-VMA1420-0D
          Buy American:      AP-VMA1410-0G         AP-VMA1420-0G
Supply Voltage               20-30 VAC at 50 or 60 Hz
Optional Fuse Current        0.6 ampere for VMA1410; 2.0 amperes for a VMA1420
Power Consumption            VMA1410/1420:                10 VA maximum (Relay and valve requirements not included.)
Ambient Operating            0 to 50°C (32 to 122°F)
Conditions
Ambient Storage              -40 to 70°C (-40 to 158°F)
Conditions
Terminations                 6.3 mm (1/4 in.) spade lugs (Communication has screw terminals.)
Serial Interfaces            N2 Bus and Zone Bus
N2 Controller Addressing     DIP switch set (1-253) Addresses 254 and 255 are reserved. Software addressable with
                             HVAC PRO software, Release 7.02 or later.
Communications Bus           N2 between VMA and the Network Control Module (NCM) or N30.
                             Zone Bus between VMA and room sensor (8-pin phone jack or wire to spade lugs or
                             optional plug-on terminals) (Not available when the TE-7720 RF Receiver is applied.)
Mounting                     One screw (included) mounts the VMA1410/1420 to the VAV box. One screw attaches the
                             damper shaft to the actuator, 8 mm (5/16 in.) square head set screw with 44 N⋅m
                             (389.4 lb⋅in.) of axial holding power for up to 13 mm (1/2 in.) round damper shafts. Minimum
                             damper shaft length is 44.5 mm (1 3/4 in.).
Housing                      Plastic housing for controller/actuator with UL94-5VB Plenum Flammability Rating
Dimensions (L x W x H)       VMA1410/1420:                153 x 102 x 102 mm (6 x 4 x 4 in.)
Actuator Torque              4 N⋅m (35 lb⋅in) minimum (VMA1410/1420 only)
Shipping Weight              VMA1410/1420:                13.1 kg (29 lb) for a box of ten, 1.3 kg (2.8 lb) each
Electrical Inputs            Analog Inputs:
                             Nickel, silicon, platinum (1 K ohm), or NTC (2.25 K) RTD room sensors,
                             1.6 K setpoint potentiometer (2-wire)
                             Voltage input for 0-10 VDC (humidity or pressure sensor)
                             Binary Inputs: Dry contacts
                             Input configurations vary based on model type.
Velocity Pressure            Velocity Pressure for 374 Pa (0-1.5 inches wc)
Outputs                      No outputs on VMA1410 (internal stepper motor)
                             Binary outputs, 24 VAC triac switched, 25-500 mA loads
                             Stepper drive, 2 to 767 steps per second (23,000 step resolution) (VMA1410/1420 only)
                             Analog output, 0-10 VDC @ 10 mA maximum
Standards Compliance         CSA 22.2 No. 205, UL 916, UL 94-5VB, FCC Part 15, Subpart B, Class A and B, C-tick
                             Australia/NZ, AS/NZS 4251.1, CISPR 22, Class B, CE Directive (89/336/EEC, EN50081-1,
                             EN50082-2) Industrial, IEEE 472, IEEE518, IEEE587 Category A/B, IEC-950, IEC 801-2, -
                             3, -4, -6, -7, -8, ANSI C62.41 A/B

12   Single Duct Variable Air Volume Terminal (Model TSS) Product Bulletin
Metasys System LN Series Variable Air Volume Profile Application Controller
Product Code Number           LN-VAVLx-0
Power Requirements            Voltage: 24 VAC, ±15%, 50/60 Hz
                              Typical Consumption: 5 VA
                              Maximum Consumption: 10 VA
                              Protection: 5 Ampere removable fuse
Environmental                 Operating Temperature: 0 to 70°C (32 to 158°F)
                              Storage Temperature: -20 to 70°C (-4 to 158°F)
                              Relative Humidity: 0 to 90% Noncondensing
General                       Standard: LONMARK® Functional Profile VAV #8010
                              Processor: Neuron® 3150; 8 bits, 10 MHz
                              Memory: Nonvolatile Flash 64 K (APB application and configuration properties)
                              Communication: LonTalk® Protocol
                              Transceiver: TP/FT-10; 78 kbps
                              Battery (for clock only): Real-time Clock Chip
                              Enclosure:
                                 Material: PVC, flammable class VO
                                 Dimension: 124 x 226 x 63 mm (4.88 x 8.9 x 2.48 in.)
                                 Weight: 0.835 kg (1.84 lbs)
                              Safety: CSA and UL Listed
Damper Motor                  Motor: LM24-Mus
                              Torque: 4 N⋅m (35 lb⋅in.)
                              Angle of Rotation: 95° adjustable
                              Fits shaft diameter: 8.5 to 18.2 mm (5/16 to 3/4 in.)
                              Power Supply from Controller
Inputs                        Number: 4 Universal
                              Digital: Dry Contact
                              Voltage: 0-10 VC, Accuracy ±0.5%
                              Current: 4-20 mA with 500 K ohms external resistor, Accuracy: ±0.5%
                              Resistor:
                                 Thermistor Type 2 10 K ohms
                                 Accuracy: ±0.5°C (±0.9°F)
                                 Resolution: 0.1°C (0.18°F)
                                 Range: -40 to 55°C (-40 to 131°F)
                                 Potentiometer 10 K ohms
                                 Linear 2-point setpoint adjustment
                                 Min/Max linear configuration
                                 Configurable on several points
                              Input Resolution: 12 bits analog/digital converter
                              One Differential pressure: Range 125-250-500 Pa (0.5-1-2 inches wc), Accuracy ±3% full
                              scale
Continued on next page. . .

                                      Single Duct Variable Air Volume Terminal (Model TSS) Product Bulletin            13
Metasys System LN Series Variable Air Volume Profile Application Controller (Cont.)
 Outputs                              Number: 4
                                      3 Digital: Triac 24 VAC ±15%, 50/60 Hz, maximum charge 1.0 Ampere, internal or external
                                      supply
                                      1 Tri-mode Analog:
                                      0-10 VDC (linear), PWM or digital 0-12 VDC
                                      60 mA maximum @ 12 VDC (60°C [140°F])
                                      Maximum load: 200 ohms
                                      Auto reset fuse: 60 mA @ 60°C (140°F), 100 mA @ 20°C (68°F)
                                      Analog Output Resolution: 8 bits digital/analog converter
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.

Controls Group
507 E. Michigan Street
P.O. Box 423                                                                                                                 Published in U.S.A.
Milwaukee, WI 53201                                                                                                    www.johnsoncontrols.com

14    Single Duct Variable Air Volume Terminal (Model TSS) Product Bulletin