Series P28 Oil Pressure Cutout Differential Pressure Control With Built-In Time Delay Relay Product Bulletin

Вид документаБюлетень виробу
ВиробникJCI
Код документаseries-p28-oil-pressure-cutout-differential-pressure-control-with-built-in-time
Група обладнанняP28 and P128 Lube Oil Pressure Control
Сторінок5
Мова документаанглійська
Розмір файлу0.3 МБ

Текст документа

FAN 216
                                                                                           Section A
                                                                                   Product Bulletin
                                                                                       Issue Date 0622

                     P28 and P128 Series Oil Pressure Cutout
                     Differential Pressure Control with Built-in
                                  Time Delay Relay
Application                         Use the P28 control at normal             Timing is affected by voltage
                                    room temperatures of 32ºF to              variations.
                                    104ºF (0ºC to 40ºC) and in areas
                                    protected from the weather.               Installation
                                    Use P28 and P128 controls only            Mounting
                                    as an operating control. Where            1.   Position the control so that the
                                    failure or malfunction of the                  pressure connections on the
                                    controls could lead to personal                bellows are above the
                                    injury or property damage to the               crankcase liquid level of the
                                    controlled equipment or other                  equipment on which you use
                                    property, additional precautions               the control.
                                    must be designed into the control
                                    system. Incorporate and maintain          2.   Use the two mounting screw
                                    other devices, such as                         holes located on the back of
                                    supervisory or alarm systems or                the control case to mount the
                                    safety or limit controls, intended             control in any position, directly
                                    to warn of or protect against                  to a wall or panel board.
                                    failure or malfunction of the
                                                                              If required, universal mounting
                                    control.
                                                                              bracket Part No. 271-51 is available.
                                    Operation
                                    When the compressor starts, the
The P28 and P128 Series             time delay heater energizes. If
controls provide dependable         the net oil pressure does not
and economical oil pressure         build up to the heater off value in
cutout for pressure lubricated      the required time limit, the time
refrigeration compressors. The      delay trips to stops the
factory set pressure adjustment     compressor.
provides operation to the
compressor manufacturer’s           If the net oil pressure rises to the
specifications.                     heater off value in the required time
                                    after the compressor starts, the time
The P28 and P128 measure the        delay heater automatically de-
net oil pressure available to       energizes and the compressor
circulate oil through the           continues to operate normally.            Note: Use only mounting screws
lubrication system. Net oil                                                   supplied with control to avoid
pressure is the difference          If the net oil pressure drops below
                                                                              damage to internal components.
between the oil gage pressure       the heater on value, also known as
and the refrigerant pressure in     the scale setting, during the running     CAUTION: If you apply the P28
the crankcase.                      cycle, the time delay relay energizes.    control for ammonia service, you
                                    If the net oil pressure does not return   must mount the control separately
A built-in time delay relay,        to the heater off value in the time       from the electrical cabinet.
accurately compensated for          delay period, the compressor shuts
ambient temperature, provides       down.                                     Pressure connections
time for pressure to rise on                                                  •    Avoid sharp bends or kinks in
startup and avoids nuisance         Time delay relay                               the capillary tubing.
shutdowns on short duration
                                    The time delay relay is a trip-free,
pressure losses during the                                                    •    Purge all tubing and lines
                                    thermal expansion device. Manual
running cycle. When supplied                                                       before you connect the
                                    reset models are available with
with Terminal 3, you can wire the                                                  pressure controls. Connect the
                                    factory set and sealed time delays of
control to operate a runlight to                                                   oil pressure line to the
                                    30, 45, 60, 90, or 120 seconds.
indicate when sufficient net oil                                                   pressure connector labeled
pressure is present. Purchase a     The time delay relay is                        OIL and the crankcase line to
model with Terminal A if you        compensated to minimize the effect             the pressure connector labeled
need a shutdown alarm or signal.    of ambient temperature variations.             LOW.

© 2022 Johnson Controls                                                                                        1
  LIT-121400, Rev. C
•   Coil and secure the excess              Table 1: Electrical power                   setting to 9 psi (62 kPa). Upon an
    capillary to avoid vibration.           required for time delay relay               initial start of the compressor, or if
    Allow some slack in capillary to                                                    the oil pressure drops during the
    avoid violin string vibration            Timing (s)                Voltage          running cycle, the time delay
    which can cause the tubing to                            24 V or       240 V        heater energizes. If during the time
    break. Do not allow the tubing                           120 V                      period the lube oil pressure does
    to rub against metal surfaces                                                       not build up to the scale setting
    where friction can damage the            30, 45, 60,     15 VA         30 VA        plus 5 psi (34 kPa) for the switch
    capillary.                               90, or 120                                 differential, which is a total of 14
                                                                                        psi (97 kPa), the control breaks the
CAUTION: With a 1/4 in. male SAE            Note: 240 V includes dropping
                                                                                        circuit to the compressor. If it
flare fitting and 1/4 in. tubing, a         resistor wattage.
                                                                                        reaches the pressure of 14 psi (97
pulsation dampener must be used                                                         kPa) during the timing period, the
where there is a possibility of                                                         time delay heater de-energizes and
pulsation.                                  Adjustment                                  the compressor can continue
Wiring                                      You can change the factory setting in       normal operation.
                                            the field. The standard stock setting       Pressure specifications
WARNING: Disconnect the power               is:
supply before the wiring connections
                                                                                        •    The time delay shutdown
are made to avoid possible electrical           Cutout 9 psi (62 kPa) pressure
                                                                                             range, in pressure difference,
shock or damage to the equipment.               difference.
                                                                                             is 8 psi to 70 psi (55 kPa to
On multiple circuit units, more than            Heater off pressure is
                                                                                             480 kPa)
one circuit may have to be                      approximately 5 psi (34 kPa)
disconnected.                                   higher than the cutout.                 •    The maximum allowable
                                                                                             overrun pressure is 325 psig
Make all wiring connections with            Note: When the controls are shipped
                                                                                             (2,240 kPa)
copper conductors only, and in              as an accessory to the compressor
accordance with the National                unit, time delay and pressure are set       Note: The time delay heater de-
Electrical Code and local regulations.      to manufacturer’s specifications.           energizes at 5 psi (34 kPa) pressure
For the maximum electrical rating of        Ensure that replacement controls            difference above the scale setting.
the control, see the label inside the       duplicate the manufacture’s
control cover.                              specifications for time delay and           Test for shutdown
                                            pressure settings.                          Immediately after you install the
Note: Use the terminal screws
supplied in the Pennswitch (8-32 x          When manufacturer’s settings are            control, and at regular intervals
1/4 in. binder head). Substitution of       not known, call the nearest                 thereafter, test the time delay relay to
other screws may cause problems             distributor or proceed as follows:          be sure that all circuits operate
in making correct connections.                                                          correctly. Proceed as follows:
                                            1. With the compressor running, read
See the label inside the control               the oil pressure and crankcase           1.   Pull the disconnect switch and
cover or in the manufacturer’s                 pressure.                                     remove the cover from the P28
specifications for a typical wiring                                                          control.
                                            2. Subtract the crankcase pressure
diagram.                                                                                2.   Connect a jumper between
                                               from the oil pressure gage
For external wiring diagrams, see              reading. This is the net oil                  terminals 1 and 2.
Fig. 4 to Fig. 11.                             pressure to the bearings.                3.   Close the line switch to start the
For standard applications that use          3. Set the cutout pointer 6 psi to 8             compressor.
a 208 V control circuit, use one leg           psi (41 kPa to 55 kPa) below the         The time delay relay stops the
of the 208 V circuit and a neutral or          established running net oil              compressor after the time delay
ground wire as a 120 V source to               pressure.                                interval.
power the time delay heater.
                                            CAUTION: Obtain the compressor              Note: If the control is mounted on
When you install a P28 control on a         manufacturer’s net oil pressure             a condensing unit where air from
440 VAC or 550 VAC system, use an           specifications as soon as possible,         auxiliary equipment, such as
external step-down transformer to           and reset the cutout pointer if it is not   blowers or fans, can strike the
provide either 120 V or 240 V to the        in accordance with the                      control, replace the cover before
pilot and time delay relay circuits.        manufacturer’s specifications.              the test. After testing the time
The transformer must be of sufficient                                                   delay relay, again pull the
                                            To raise the cutout setting, turn
volt-ampere capacity to operate the                                                     disconnect switch and remove
                                            adjusting disk C to the left as
motor starter and the P28’s time                                                        the jumper between terminals 1
                                            viewed from the front of the control.
delay relay.                                                                            and 2. Place the cover on the
                                            Turn the disk to the right to lower
                                            the cutout setting.                         control and close the disconnect
                                                                                        switch. Manually reset the time
                                            Example: Suppose the minimum                delay relay.
                                            lube oil pressure required to the
                                            bearings is 9 psi (62 kPa) (oil pump
                                            pressure minus crankcase
                                            pressure). You set the control scale
2 P28 and P128 Series Oil Pressure Cutout Differential Pressure Control With Built-In Time Delay Relay Product Bulletin
Checkout procedure
Before you leave the installation, observe at least three complete operating cycles to be sure that all components
function correctly.

Repairs and replacement
In the field, you can replace or interchange the time delay relay assembly, which consists of the timer and terminal board.
Do not make field repairs except for replacement of the time delay relay assembly. For a replacement control or time delay
relay assembly, contact the nearest Johnson Controls® wholesaler.
Table 2: Replacement time delay relay assemblies
 Part number               Voltage                 Reset type               Timing in seconds           Alarm circuit

 RLY13A-600R               120/240 VAC             Manual                   60                          No
 RLY13A-609R               24 VAC/VDC              Manual                   120                         No
 RLY13A-610R               120/240 VAC             Manual                   30                          No
 RLY13A-616R               120/240 VAC             Manual                   120                         No
 RLY13A-617R               120/240 VAC             Manual                   45                          No

Wiring diagram definitions
PC1: Pressure actuated contacts. The contacts open on
an increase in pressure difference between oil and low
pressure connectors. The contacts make and break the
time delay heater circuit.
PC2: The contacts close simultaneously when PC1
contacts open. Use PC2 for the runlight circuit.
TD1: Time delay relay. The contacts open after the factory-
set time delay interval if the pressure difference between
oil and low pressure connectors is not established or
maintained.
TD2: The contacts close simultaneously when TD1
contacts open. Use TD2 for the alarm circuit.
DR: Voltage dropping resistor used in dual voltage
models.                                                             Connect Terminals L and M as a single-pole switch. Connect
                                                                   Terminals 2 to the 240 V or 120 V terminal to energize the circuit
H: Heater for time delay relay.                                       only when the motor starter is closed. See standard wiring
                                                                                         diagrams for details.
A, 3: In Figure 4, Figure 6 to Figure 9, and Figure 11, the
shutdown alarm circuit is A and the runlight is Terminal 3.         Fig 4 — Internal circuit for a 120 VAC/240 VAC P28 control

Wiring diagrams
Note: Observe the instructions for the jumper for each
diagram.

                                                                    You cannot cycle a crankcase heater with this configuration. For
                                                                                       an alternative, see Fig 6.
                                                                   Fig 5 — Standard wiring for a P28 on a 240 V system with 240
                                                                                       V magnetic coil starter

      P28 and P128 Series Oil Pressure Cutout Differential Pressure Control With Built-In Time Delay Relay Product Bulletin       3
 In the field, you must install a jumper between 2 and either M or
                                   L.
            Fig 6 —P28 with 3-wire control, not 4-wire
                                                                        In the field, you must install a jumper between 2 and either M or
                                                                       L. Additional controls could be high pressure cutout, low pressure,
                                                                                             or temperature controls.
                                                                        Fig 9 —Standard wiring for P28 with manual start-stop push
                                                                                                       button

 In the field, you must install a jumper between 2 and either M or
 L. The magnetic coil in the starter must be the same voltage as
  the control circuit supply. Only install the operating control and
                 addition controls between M and C4.
     Fig 7 —P28 with separate supply to the control circuit

                                                                             Connect Terminal L so that the circuit only energizes when
                                                                              the operating control and overload terminals are closed.
                                                                                  Fig 10 —Low voltage P28 internal wiring

 In the field, you must install a jumper between 2 and either M or
L. Use the correct transformer if you use a 550 V supply. Only use
a crankcase heater if the control transformer has sufficient output
    for the additional load. Only install the operating control and
                 addition controls between M and C4.
   Fig 8 —P28 for 440 V or 550 V supply and 240 V magnetic
                              starter coil
                                                                         Fig 11 —P28 with 24 V control circuit power from a step-
                                                                                           down transformer

4 P28 and P128 Series Oil Pressure Cutout Differential Pressure Control With Built-In Time Delay Relay Product Bulletin
                                                                                                                    FAN 216
                                                                                                                  Section A
                                                                                                          Product Bulletin
                                                                                                              Issue Date 0622

Conformity declaration information
 Specification                      Description
 Purpose of control                 Pressure operating controls
 Method of mounting control         Flat surface or with a universal mounting bracket (Part No. 271-51)
 Method of earthing of control      Wiring binding screw terminal
 Type 1 or Type 2 action            Type 1.C (micro-interruption)
 External pollution situation       Pollution degree 3
 Rated impulse voltage              4,000 VAC

                                                                                                          www.penncontrols.com

                                            ® Johnson Controls and Penn are registered trademarks of Johnson Controls in the
                             United States of America and/or other countries. All other trademarks used herein are the property
                                         of their respective owners. © Copyright 2022 by Johnson Controls. All rights reserved.

© 2022 Johnson Controls                                                                                                           5
  LIT-121400, Rev. C