24- 9954- 7, Rev . B

SEN-600-1 and SEN-600-4 Remote Indoor Temperature
Sensors
                                                                                           Part No. 24-9954-7, Rev. B
Installation Instructions                                                                            Issued March 2016

Application                                                   Installation
The SEN-600-1 and SEN-600-4 remote sensors are
designed to allow remote indoor temperature sensing in
applications with the T600 Series programmable and
non-programmable thermostats and the
                                                                                                     4.94
TEC2000 Series Network Thermostats. The                                                              125
SEN-600-1 and SEN-600-4 contain an integral sensor
and circuitry to interface with the T600 and
TEC2000 Series Thermostats. Additionally, the
SEN-600-4 has an override button and Light-Emitting
Diode (LED) indicator to enable and indicate                                            3.38
occupancy override from the remote sensor. Up to                                         86
three remote sensors can be wired together for                                                          1.13
averaging.                                                                                               29

Note: The SEN-600-4 remote indoor sensor is only                      Figure 1: Sensor Dimensions, in./mm
intended for use with programmable T600 Series
thermostats. Additionally, if the SEN-600-4 is used with      To install the sensor:
a T600 non-programmable thermostat, the LED does
                                                              1. Remove the security screw on the bottom of the
not light up to indicate occupancy status.
                                                                 sensor cover using a Phillips-head screwdriver.
Mounting                                                          Open the thermostat by pulling on the bottom side
Prior to installing the sensor, install the T600 or               of the sensor cover (see Figure 2).
TEC2000 Series Thermostat following the installation          2. Unlock the Printed Circuit Board (PCB) by carefully
instructions provided with the thermostat.                        pressing the locking tabs to the right. Open the
Location Considerations                                           sensor’s PCB to the left (see Figure 3).

Locate the sensors as follows:                                3. Pull out approximately 6 in. (152 mm) of wires from
                                                                  the wall and insert the cable through the hole in the
•   on a partitioning interior wall, and approximately 5 ft
    (1.5 m) above the floor in a location of average              base.
    temperature                                               4. Align the base on the wall, and using the base as a
•   away from direct sunlight, radiant heat, outside              template, mark the location of the two mounting
    walls, behind doors, air discharge grills, stairwells,        holes on the wall. Confirm the sensor base is
    or outside doors                                              installed with the proper side up.
•   away from steam or water pipes, warm air stacks,          5. Use the supplied anchors and screws for mounting
    unheated/uncooled areas, or sources of electrical            on drywall or plaster. Drill two 3/16 in. (4.7 mm)
    interference                                                 holes at the marked locations and tap nylon
                                                                 anchors flush to wall surface (see Figure 4).
                                                              6. Position base on the wall, insert screws through
                                                                  mounting base, and fasten into wall anchors. Do
                                                                  not overtighten screws.
                                                              7. Swing the sensor’s PCB back to the right to close.
                                                                  Gently press on the PCB to secure the locking tab.

                                 SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation              1
                                                                                          Instructions
                                                     Wiring
                                                                  CAUTION: Risk of Electric Shock.
                                                                  Disconnect the power supply before
                                                          !       making electrical connections to avoid
                                                                  electric shock.

                                                     Note: Keep sensor conductors as short as possible to
                                                     minimize temperature error. If necessary, the indoor
                                                     temperature displayed at the thermostat can be
                                                     adjusted (refer to the appropriate T600 or
                                                     TEC2000 Series Installation Instructions).

                                                     To wire the sensor:
                                                     1. Connect wires between the T600 or
    Figure 2: Removing the Sensor Cover                  TEC2000 Series thermostat and the SEN-600-1 or
                                                         SEN-600-4 sensors according to the appropriate
                                                         wiring diagram (see Figure 5).
                                                     2. Set the switch on the PCB in the remote indoor
                                                         sensor to the correct positions (see Table 1 for
                                                         switch positions).
                                                     3. Reattach the sensor cover to the installed base
                                                         (top side first) and install the security screw on the
                                                         bottom.
                                                     4. Verify that the sensor is functioning by checking the
                                                         temperature display on the T600 or
                                                         TEC2000 Series thermostat. If using the
                                        PCB              SEN-600-4 remote sensor, verify the functionality
                                     Locking Tab
                                                         of the override button and occupancy status LED.
                                                     Note: If using the SEN-600-4, the digital input on the
      Figure 3: Opening the Sensor PCB               thermostat to which the D1 terminal on the sensor is
                                                     connected must be configured for remote override
                                                     (RemOVR). Refer to the appropriate T600 Installation
                                                     Instructions for details on configuring the digital input.

                                                                  CAUTION: Risk of Property Damage.
                                                                  Do not apply power to the system before
                                                          !       checking all wiring connections. Short
                                                                  circuited or improperly connected wires
                                                                  may result in permanent damage to the
                                                                  equipment.

                                                     Table 1: Switch Positions for Single or Multiple
                                                              Sensor Installations
                                                      Number of              Switch 1          Switch 2
                                                      Sensors
                                                      1 Sensor               On                On
     Figure 4: Mounting the Sensor Base
                                                      2 Sensors              Off               On
                                                      3 Sensors              Off               Off

2   SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions
                                 RS                      RS                               RS                 RS
                                 Scom                   Scom                              Scom
                                                                                                             Scom
                                 AU                   SEN-600-1                           AU                 AUX
                                    C                                                     C                   C
                            D2 D1                                                  D2 D1                      D1
                      T600 or TEC2000 Series                                        T600                   SEN-600-4

                        This is a wiring example of a single remote room sensor (S1=On, S2=On).

                                                        RS               RS                      RS
                                                        Scom            Scom                     Scom
                                                        AU            SEN-600-1           SEN-600-1
                                                         C
                                               D2 D1
                                         T600 or TEC2000 Series

            RS                RS                   RS                                      RS                 RS             RS
            Scom             Scom               Scom                                       Scom
                                                                                                              Scom          Scom
            AU               AUX             SEN-600-1                                     AU                 AUX           AUX
                C               C                                                           C                  C              C
        D2 D1                   D1                                                   D2 D1                     D1            D1
         T600               SEN-600-4                                                 T600                 SEN-600-4      SEN-600-4

        This is a wiring example of two remote room sensors for averaging applications (S1=Off, S2=On).

                                               RS              RS         RS                     RS
                                               Scom            Scom      Scom                 Scom
                                               AU        SEN-600-1     SEN-600-1 SEN-600-1
                                               C
                                      D2 D1
                                T600 or TEC2000 Series

         RS           RS                RS               RS                        RS              RS              RS             RS
         Scom         Scom              Scom            Scom                       Scom           Scom             Scom       Scom
         AU           AUX        SEN-600-1 SEN-600-1                               AU             AUX              AUX      SEN-600-1
        C              C                                                      C                       C             C
     D2 D1             D1                                                  D2 D1                      D1            D1
     T600           SEN-600-4                                               T600                 SEN-600-4    SEN-600-4

     This is a wiring example of three remote room sensors for averaging applications (S1=Off, S2=Off).

                                                               RS           RS
                                                               Scom        Scom
                                                               AU          AUX
                                                           C                   C
                                                        D2 D1               D1
                                                       TEC2x45-4         SEN-600-4

      This is a wiring example of a single remote room sensor for TEC2x45-4 applications (S1=On, S2=On).

                                        IMPORTANT: The SEN-600-1 is not compatible
                                        with TEC2x45-4 thermostat models. On
                                        SEN-600-4 sensors, only the remote override
                                        function is compatible with TEC2x45-4 thermostat
                                        models.

Note: When wiring the SEN-600-4 remote indoor sensor to
a non-programmable model of the T600, the AUX terminal
on the SEN-600-4 is not used. Additionally, when using the
SEN-600-4 remote indoor sensor with a non-programmable
model of the T600, the LED does not light to indicate
occupancy status.

                                          Figure 5: Wiring Diagrams

  SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions                                                   3
Troubleshooting
Table 2: Troubleshooting
    Symptom                                Possible Cause                           Corrective Action
    Temperature displayed at the T600 or   Remote sensor is not correctly           Check wiring connections at the
    TEC2000 Series does not correlate      connected.                               thermostat terminal blocks and
    with the temperature at the remote                                              between the thermostat and the remote
    sensor.                                                                         sensor.
                                           T600, TEC2000 Series, or remote          Short the appropriate sensor terminals
                                           sensor has failed.                       at the thermostat. The display should
                                                                                    indicate 122ºF (50ºC). If the reading is
                                                                                    not 122ºF (50ºC), replace the
                                                                                    thermostat. If the reading is 122ºF
                                                                                    (50ºC), check the resistance across the
                                                                                    sensor with the wires removed from the
                                                                                    thermostat. The resistance should be
                                                                                    10,000 ohms at 77ºF (25ºC). If the
                                                                                    resistance is not correct, replace the
                                                                                    sensor.
    Override button on SEN-600-4           SEN-600-4 is incorrectly wired to the    Check wiring connections with the
    remote sensor is not functional.       thermostat.                              corresponding digital input at the
                                                                                    thermostat, at the D1 terminal on the
                                                                                    remote sensor, and between the
                                                                                    thermostat and remote sensor.
                                           The appropriate digital input on the     Configure the appropriate digital input
                                           thermostat is not configured to remote   at the thermostat for remote override
                                           override (RemOVR).                       (RemOVR). Refer to the appropriate
                                                                                    T600 Installation Instructions for
                                                                                    details.
    Remote LED is not functional on the    SEN-600-4 is incorrectly wired to the    Check wiring connections at the
    SEN-600-4 remote sensor.               thermostat.                              auxiliary output at the programmable
                                                                                    T600 thermostat, at the AUX terminal
                                                                                    on the remote sensor, and between the
                                                                                    thermostat and remote sensor.
                                           The auxiliary output is not properly     Configure the auxiliary output at the
                                           configured at the T600 programmable      T600 programmable thermostat for
                                           thermostat.                              Normally Open (N.O.). Refer to the
                                                                                    appropriate T600 Installation
                                                                                    Instructions for details.
                                           The T600 Series thermostat to which      The LED does not indicate occupancy
                                           the SEN-600-4 is connected is not a      status on non-programmable T600
                                           programmable model.                      models (there is no auxiliary contact at
                                                                                    the thermostat). Replace the T600 with
                                                                                    a programmable model.

4        SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions
Technical Specifications
SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors
 Power Requirements                        Supplied by the T600 or TEC2000 Series Thermostat
 Sensor Accuracy                           ±0.9 Fº from 32 to 158ºF; ±0.5 Cº from 0 to 70ºC
 Sensor Ambient Operating                  32 to 122ºF (0 to 50ºC); 0 to 95% RH noncondensing
 Conditions
 Sensor Ambient Storage                    -22 to 122ºF (-30 to 50ºC); 0 to 95% RH noncondensing
 Conditions
 Dimensions (H x W x D)                    4.94 x 3.38 x 1.13 in. (125 x 86 x 29 mm)
 Shipping Weight                           0.75 lb (0.34 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liable for damage resulting from misapplication or
misuse of its products.

European Single Point of Contact:               NA/SA Single Point of Contact:                   APAC Single Point of Contact:
JOHNSON CONTROLS                                JOHNSON CONTROLS                                 JOHNSON CONTROLS
WESTENDHOF 3                                    507 E MICHIGAN ST                                C/O CONTROLS PRODUCT
45143 ESSEN                                     MILWAUKEE WI 53202                               MANAGEMENT
GERMANY                                         USA                                              NO. 22 BLOCK D NEW DISTRICT
                                                                                                 WUXI JIANGSU PROVINCE 214142
                                                                                                 CHINA

                                                                                                                      Building Efficiency
                                                                                             507 E. Michigan Street, Milwaukee, WI 53202
                                              Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                     All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.

                        SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions                                      5

Published in U.S.A.                                                                                            www.johnsoncontrols.com