24- 9954- 7, Rev . B
SEN-600-1 and SEN-600-4 Remote Indoor Temperature
Sensors
Part No. 24-9954-7, Rev. B
Installation Instructions Issued March 2016
Application Installation
The SEN-600-1 and SEN-600-4 remote sensors are
designed to allow remote indoor temperature sensing in
applications with the T600 Series programmable and
non-programmable thermostats and the
4.94
TEC2000 Series Network Thermostats. The 125
SEN-600-1 and SEN-600-4 contain an integral sensor
and circuitry to interface with the T600 and
TEC2000 Series Thermostats. Additionally, the
SEN-600-4 has an override button and Light-Emitting
Diode (LED) indicator to enable and indicate 3.38
occupancy override from the remote sensor. Up to 86
three remote sensors can be wired together for 1.13
averaging. 29
Note: The SEN-600-4 remote indoor sensor is only Figure 1: Sensor Dimensions, in./mm
intended for use with programmable T600 Series
thermostats. Additionally, if the SEN-600-4 is used with To install the sensor:
a T600 non-programmable thermostat, the LED does
1. Remove the security screw on the bottom of the
not light up to indicate occupancy status.
sensor cover using a Phillips-head screwdriver.
Mounting Open the thermostat by pulling on the bottom side
Prior to installing the sensor, install the T600 or of the sensor cover (see Figure 2).
TEC2000 Series Thermostat following the installation 2. Unlock the Printed Circuit Board (PCB) by carefully
instructions provided with the thermostat. pressing the locking tabs to the right. Open the
Location Considerations sensor’s PCB to the left (see Figure 3).
Locate the sensors as follows: 3. Pull out approximately 6 in. (152 mm) of wires from
the wall and insert the cable through the hole in the
• on a partitioning interior wall, and approximately 5 ft
(1.5 m) above the floor in a location of average base.
temperature 4. Align the base on the wall, and using the base as a
• away from direct sunlight, radiant heat, outside template, mark the location of the two mounting
walls, behind doors, air discharge grills, stairwells, holes on the wall. Confirm the sensor base is
or outside doors installed with the proper side up.
• away from steam or water pipes, warm air stacks, 5. Use the supplied anchors and screws for mounting
unheated/uncooled areas, or sources of electrical on drywall or plaster. Drill two 3/16 in. (4.7 mm)
interference holes at the marked locations and tap nylon
anchors flush to wall surface (see Figure 4).
6. Position base on the wall, insert screws through
mounting base, and fasten into wall anchors. Do
not overtighten screws.
7. Swing the sensor’s PCB back to the right to close.
Gently press on the PCB to secure the locking tab.
SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation 1
Instructions
Wiring
CAUTION: Risk of Electric Shock.
Disconnect the power supply before
! making electrical connections to avoid
electric shock.
Note: Keep sensor conductors as short as possible to
minimize temperature error. If necessary, the indoor
temperature displayed at the thermostat can be
adjusted (refer to the appropriate T600 or
TEC2000 Series Installation Instructions).
To wire the sensor:
1. Connect wires between the T600 or
Figure 2: Removing the Sensor Cover TEC2000 Series thermostat and the SEN-600-1 or
SEN-600-4 sensors according to the appropriate
wiring diagram (see Figure 5).
2. Set the switch on the PCB in the remote indoor
sensor to the correct positions (see Table 1 for
switch positions).
3. Reattach the sensor cover to the installed base
(top side first) and install the security screw on the
bottom.
4. Verify that the sensor is functioning by checking the
temperature display on the T600 or
TEC2000 Series thermostat. If using the
PCB SEN-600-4 remote sensor, verify the functionality
Locking Tab
of the override button and occupancy status LED.
Note: If using the SEN-600-4, the digital input on the
Figure 3: Opening the Sensor PCB thermostat to which the D1 terminal on the sensor is
connected must be configured for remote override
(RemOVR). Refer to the appropriate T600 Installation
Instructions for details on configuring the digital input.
CAUTION: Risk of Property Damage.
Do not apply power to the system before
! checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
Table 1: Switch Positions for Single or Multiple
Sensor Installations
Number of Switch 1 Switch 2
Sensors
1 Sensor On On
Figure 4: Mounting the Sensor Base
2 Sensors Off On
3 Sensors Off Off
2 SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions
RS RS RS RS
Scom Scom Scom
Scom
AU SEN-600-1 AU AUX
C C C
D2 D1 D2 D1 D1
T600 or TEC2000 Series T600 SEN-600-4
This is a wiring example of a single remote room sensor (S1=On, S2=On).
RS RS RS
Scom Scom Scom
AU SEN-600-1 SEN-600-1
C
D2 D1
T600 or TEC2000 Series
RS RS RS RS RS RS
Scom Scom Scom Scom
Scom Scom
AU AUX SEN-600-1 AU AUX AUX
C C C C C
D2 D1 D1 D2 D1 D1 D1
T600 SEN-600-4 T600 SEN-600-4 SEN-600-4
This is a wiring example of two remote room sensors for averaging applications (S1=Off, S2=On).
RS RS RS RS
Scom Scom Scom Scom
AU SEN-600-1 SEN-600-1 SEN-600-1
C
D2 D1
T600 or TEC2000 Series
RS RS RS RS RS RS RS RS
Scom Scom Scom Scom Scom Scom Scom Scom
AU AUX SEN-600-1 SEN-600-1 AU AUX AUX SEN-600-1
C C C C C
D2 D1 D1 D2 D1 D1 D1
T600 SEN-600-4 T600 SEN-600-4 SEN-600-4
This is a wiring example of three remote room sensors for averaging applications (S1=Off, S2=Off).
RS RS
Scom Scom
AU AUX
C C
D2 D1 D1
TEC2x45-4 SEN-600-4
This is a wiring example of a single remote room sensor for TEC2x45-4 applications (S1=On, S2=On).
IMPORTANT: The SEN-600-1 is not compatible
with TEC2x45-4 thermostat models. On
SEN-600-4 sensors, only the remote override
function is compatible with TEC2x45-4 thermostat
models.
Note: When wiring the SEN-600-4 remote indoor sensor to
a non-programmable model of the T600, the AUX terminal
on the SEN-600-4 is not used. Additionally, when using the
SEN-600-4 remote indoor sensor with a non-programmable
model of the T600, the LED does not light to indicate
occupancy status.
Figure 5: Wiring Diagrams
SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions 3
Troubleshooting
Table 2: Troubleshooting
Symptom Possible Cause Corrective Action
Temperature displayed at the T600 or Remote sensor is not correctly Check wiring connections at the
TEC2000 Series does not correlate connected. thermostat terminal blocks and
with the temperature at the remote between the thermostat and the remote
sensor. sensor.
T600, TEC2000 Series, or remote Short the appropriate sensor terminals
sensor has failed. at the thermostat. The display should
indicate 122ºF (50ºC). If the reading is
not 122ºF (50ºC), replace the
thermostat. If the reading is 122ºF
(50ºC), check the resistance across the
sensor with the wires removed from the
thermostat. The resistance should be
10,000 ohms at 77ºF (25ºC). If the
resistance is not correct, replace the
sensor.
Override button on SEN-600-4 SEN-600-4 is incorrectly wired to the Check wiring connections with the
remote sensor is not functional. thermostat. corresponding digital input at the
thermostat, at the D1 terminal on the
remote sensor, and between the
thermostat and remote sensor.
The appropriate digital input on the Configure the appropriate digital input
thermostat is not configured to remote at the thermostat for remote override
override (RemOVR). (RemOVR). Refer to the appropriate
T600 Installation Instructions for
details.
Remote LED is not functional on the SEN-600-4 is incorrectly wired to the Check wiring connections at the
SEN-600-4 remote sensor. thermostat. auxiliary output at the programmable
T600 thermostat, at the AUX terminal
on the remote sensor, and between the
thermostat and remote sensor.
The auxiliary output is not properly Configure the auxiliary output at the
configured at the T600 programmable T600 programmable thermostat for
thermostat. Normally Open (N.O.). Refer to the
appropriate T600 Installation
Instructions for details.
The T600 Series thermostat to which The LED does not indicate occupancy
the SEN-600-4 is connected is not a status on non-programmable T600
programmable model. models (there is no auxiliary contact at
the thermostat). Replace the T600 with
a programmable model.
4 SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions
Technical Specifications
SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors
Power Requirements Supplied by the T600 or TEC2000 Series Thermostat
Sensor Accuracy ±0.9 Fº from 32 to 158ºF; ±0.5 Cº from 0 to 70ºC
Sensor Ambient Operating 32 to 122ºF (0 to 50ºC); 0 to 95% RH noncondensing
Conditions
Sensor Ambient Storage -22 to 122ºF (-30 to 50ºC); 0 to 95% RH noncondensing
Conditions
Dimensions (H x W x D) 4.94 x 3.38 x 1.13 in. (125 x 86 x 29 mm)
Shipping Weight 0.75 lb (0.34 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liable for damage resulting from misapplication or
misuse of its products.
European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact:
JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS
WESTENDHOF 3 507 E MICHIGAN ST C/O CONTROLS PRODUCT
45143 ESSEN MILWAUKEE WI 53202 MANAGEMENT
GERMANY USA NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc.
SEN-600-1 and SEN-600-4 Remote Indoor Temperature Sensors Installation Instructions 5