Security Control Panel Assembly
Mounted in a 20 in. x 42 in. Enclosure Part No. 24-10638-12, Rev. A
Issued March, 2012
Installation Instructions
SPA1D20012F10, SPA0D20012F10, SPA1D200-2F10, SPA0D200-2F10
Refer to the QuickLIT Web site for the most up-to-date version of this document.
Applications Mounting and Connecting the Panels
The 20 in. x 42 in. Security Control Panel is a pre-wired, • Mount the panel on a wall or other mounting surface located in a
preassembled standard control panel and enclosure that contains two restricted-access area.
S300-DIN-RDR8S (also called RDR8S) modules, and , optionally, a • Use the mounting template supplied with the panel.
CK721-A network controller. The control panel is shipped complete, • The horizontal distance between the mounting holes is 17 in.
(43.2 cm); the vertical distance is 40.4 in. (102.7 cm). Mounting
mounted in a steel enclosure. The panel is equipped with the required
hole diameter is 0.436 in. (1.1 cm).
number of 120 VAC/24 VDC power supplies, mounted on the panel • Ensure the door can swing fully open.
door. The power supply has Uninterruptible Power Supply (UPS) • Mount the panel in a location where airflow is uninhibited over the
capability. Using the factory cables, the UPS function is activated by exposed surfaces.
connecting batteries (S300-BAT). These enclosures are designed • Remove the back plate before securing the panel to the mounting
specifically for door access control for up to 16 doors, with battery surface and reinstall it when mounting is complete.
brackets, a wiring trough for excess cables, a lift-off door, 5 A circuit • Leave the 2 black plastic button caps in place until all pipe or
breaker for controllers, channels for wiring routing, quick disconnects conduit connections are completed. The button caps prevent dust
and metal chips from accidently getting into the cabinet
for power, a pre-wired door tamper switch, and a lockable door with electronics.
key.
Repair Information
If the Security Control Panel Assembly fails to operate within its
specifications, replace the failed component. For a replacement,
contact the nearest Johnson Controls® representative.
Refer to the Security Enclosure Components Catalog Page
(LIT-1900572) to order components separately.
Parts Included
• 20 in. x 42 in. (50.8 cm x 106.7 cm) enclosure, Type 1 with keyed
lock, 120 VAC outlet (optional), 5 A circuit breaker, door tamper
switch, and battery support brackets
• CK721-A network controller (optional) and two RDR8S eight-door
interface modules
• Two S300-DIN-L-PS 24 VDC, 5 A power supplies
Figure 1: Security Control Panel Mounted in a
20 in. x 42 in. Enclosure
Cable Requirements
Description Recommended Cable Recommended Composite Maximum Segment Length
Type1, 2 Cable Type1
CK721-A: RS485A, RS485B Listed, 18 AWG, 3-conductor, Listed, 18 AWG, 3-conductor, 4,000 ft (1,219 m) maximum
RDR8S: RS485+/- stranded, shielded, copper stranded, shielded, copper
CK721-A: ICOM1, ICOM2 Belden® 8761, 22 AWG, 1 twisted 500 ft (152 m)
RDR8S: Door Contact pair, stranded, unshielded, copper
CK721-A: OUT1 Belden 8760, 18 AWG, 1 twisted Depends on power requirements of the device. Voltage
RDR8S: Door Strike, Shunt pair, stranded, unshielded, copper to the device must not be reduced more than 10% over
the 18 AWG wire, measured when energized.
Request to Exit Belden 8761, 22 AWG, 1 twisted Belden B558AFS Shielded Riser 500 ft (152 m)
(RDR8S only) pair, stranded, unshielded, copper Rated or Belden B658AFS
Shielded Plenum Rated
Reader Power Belden 8760, 18 AWG, 1 twisted Refer to reader manufacturer’s specification for power
(RDR8S only) pair, stranded, unshielded, copper requirements.
Reader Data0/Data1 Belden 8723, 22 AWG, 2 twisted 500 ft (152 m). Refer to reader manufacturer’s
(RDR8S only) pairs, stranded, shielded, copper specification for data requirements.
RS232 A, RS232 B Listed DB9 F/F AT Null Modem Listed DB9 F/F AT Null Modem 25 ft (7 m). Cable must remain in the same room as the
cable cable CK721-A.
Ethernet Listed, Category 5, 24 AWG, solid, Listed, Category 5, 24 AWG, solid, 354 ft (100 m). Cable, RJ45 connector, and RJ45 crimp
2 pair or 4 pair type 2 pair or 4 pair type tool to be supplied by customer.
1. All data cables should be physically separated from power lines. If conduit is used, do not run data cables in the same conduit as power cables or certain door
strike cables, such as strike voltage greater than 30 V or magnetic door locks without Electromagnetic Interference (EMI) suppression. All cables must conform
with National Electrical Code, NFPA 70; or for Canadian installations, refer to the Canadian Electric Code C22.1.
2. Shielded cable is not required but is strongly recommended to minimize the effects of electromagnetic interference or radio frequency noise.
Security Control Panel Assembly Mounted in a 20 in. x 42 in. Enclosure Installation Instructions 1
Door Termination Selection Chart
• Terminate door 1 to 4 first, since the connectors are located at the back
rows. Product Code Description
• Single Door Connector Termination (typical of 8): Number
SPA1D20012F10 20 in. x 42 in. (50.8 cm x 106.7 cm) security control
Output side Input side
panel with a CK721-A controller, two RDR8S
Door Strike NO Contact Door Strike modules, a 5 A circuit breaker, a 120 VAC outlet, and
Door Strike Common Door Strike Common two power supplies
Door Strike NC Contact Request to Exit SPA0D20012F10 20 in. x 42 in. (50.8 cm x 106.7 cm) security control
Shunt NO Contact Red LED panel with two RDR8S modules, a 5 A circuit breaker, a
Shunt Common LED Common 120 VAC outlet, and two power supplies
Shunt NC Contact Green LED SPA1D200-2F10 20 in. x 42 in. (50.8 cm x 106.7 cm) security control
Input Tamper Reader Power (+12 VDC) panel with a CK721-A controller, two RDR8S
Input Common Power Common modules, a 5 A circuit breaker, and two power supplies
Input Spare Data 0/RS-485
Data 1/RS-485 SPA0D200-2F10 20 in. x 42 in. (50.8 cm x 106.7 cm) security control
panel with two RDR8S modules, a 5 A circuit breaker,
and two power supplies
AC Power Connection
• Put the AC
power wiring To AC G
GREEN
Wired at Technical Specification
through a power N
BLUE the factory
knockout. source BROWN Security Control Panel Assembly Mounted in a 20 in. x 42 in.
L
• Connect the AC Enclosure
power wiring to TB-1 L = Line
Electrical Rating SPA1D20012F10: 120 VAC, 3.6 A, 50/60 Hz
terminal block N = Neutral
SPA0D20012F10: 120 VAC, 3.6 A, 50/60 Hz
TB-1. G = Ground
SPA1D200-2F10: 120 VAC, 3.6 A, 50/60 Hz
SPA0D200-2F10: 120 VAC, 3.6 A, 50/60 Hz
WARNING: Risk of Electric Shock. Enclosure Rating NEMA Type 1
!
Disconnect the power supply before making
Ambient Operating 32 to 122°F (0 to 50°C), 10 to 85% RH,
electrical connections. Contact with components Condition noncondensing
carrying hazardous voltage can cause electric shock
and may result in severe personal injury or death. Dimensions (Width 20 in. x 42 in. x 7.5 in.
x Height x Depth) (50.8 cm x 107 cm x 19.1 cm)
S300-BAT Battery Connection Ambient Storage -4 to 158°F (-20 to 70°C), 5 to 95% RH,
Condition noncondensing
The optional S300-BAT feature
RED
WHT BLK Compliance United States:
uses two PowerSonic, Model
PS-1270, 12 VDC, 7 Ah, UL Listed under UL 1076 for Proprietary Burglar
+ - + - + - + - G N L
Alarm Units and Systems, and under UL 294 for
sealed lead acid batteries per DC
BAT
HIGH
power supply. To ensure B-1A B-1B OUT VOLT Access Control Systems Units;
AGE
proper operation, the batteries FCC compliant to the limits for a Class B digital
should be replaced every three PS-1 device, pursuant to Part 15 of the FCC rules
years whether or not they have Canada:
been placed into use by an AC RED
WHT BLK
Class B digital apparatus, complies with Canadian
power failure. ICES-003;
+ - + - + - + - G N L
The RED (+), BLK (-), and DC cUL Listed for Signaling Appliance
BAT
HIGH
WHT cables are provided with B-2A B-2B OUT VOLT
AGE
the enclosure. Observe the Europe:
polarity when connecting the PS-2 CE Mark – Johnson Controls, Inc., declares that this
batteries. product is in compliance with the essential
requirements and other relevant provisions of the
Field Devices EMC Directive 2004/108/EC and LVD 2006/95/EC.
For information on wiring the CK721-A controller or the RDR8S Australia and New Zealand:
module, refer to the documentation provided with these devices. C-Tick Mark, Australia/NZ Emissions Compliant
Use a separate Class 2 transformer or power supply for door strike
power. Under no circumstances connect a door strike to the
enclosure power supply. Installation of Ferrite Clamps for CE Compliance
• Clamp the ferrite clamp
provided with the panel
to the panel input power
at the circuit breaker
(see the left picture).
• Wrap the Ethernet cable
once around the clamp,
and clamp it to the cable
(see the right picture).
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. © 2012 Johnson Controls, Inc.
2 Security Control Panel Assembly Mounted in a 20 in. x 42 in. Enclosure Installation Instructions