Security Control Panel Assembly
Mounted in a 20 in. x 42 in. Enclosure                                                                              Part No. 24-10638-12, Rev. A
                                                                                                                                      Issued March, 2012
Installation Instructions
SPA1D20012F10, SPA0D20012F10, SPA1D200-2F10, SPA0D200-2F10

                                                                    Refer to the QuickLIT Web site for the most up-to-date version of this document.

Applications                                                                         Mounting and Connecting the Panels
The 20 in. x 42 in. Security Control Panel is a pre-wired,                           •   Mount the panel on a wall or other mounting surface located in a
preassembled standard control panel and enclosure that contains two                      restricted-access area.
S300-DIN-RDR8S (also called RDR8S) modules, and , optionally, a                      •   Use the mounting template supplied with the panel.
CK721-A network controller. The control panel is shipped complete,                   •   The horizontal distance between the mounting holes is 17 in.
                                                                                         (43.2 cm); the vertical distance is 40.4 in. (102.7 cm). Mounting
mounted in a steel enclosure. The panel is equipped with the required
                                                                                         hole diameter is 0.436 in. (1.1 cm).
number of 120 VAC/24 VDC power supplies, mounted on the panel                        •   Ensure the door can swing fully open.
door. The power supply has Uninterruptible Power Supply (UPS)                        •   Mount the panel in a location where airflow is uninhibited over the
capability. Using the factory cables, the UPS function is activated by                   exposed surfaces.
connecting batteries (S300-BAT). These enclosures are designed                       •   Remove the back plate before securing the panel to the mounting
specifically for door access control for up to 16 doors, with battery                    surface and reinstall it when mounting is complete.
brackets, a wiring trough for excess cables, a lift-off door, 5 A circuit            •   Leave the 2 black plastic button caps in place until all pipe or
breaker for controllers, channels for wiring routing, quick disconnects                  conduit connections are completed. The button caps prevent dust
                                                                                         and metal chips from accidently getting into the cabinet
for power, a pre-wired door tamper switch, and a lockable door with                      electronics.
key.

Repair Information
If the Security Control Panel Assembly fails to operate within its
specifications, replace the failed component. For a replacement,
contact the nearest Johnson Controls® representative.
Refer to the Security Enclosure Components Catalog Page
(LIT-1900572) to order components separately.

Parts Included
•    20 in. x 42 in. (50.8 cm x 106.7 cm) enclosure, Type 1 with keyed
     lock, 120 VAC outlet (optional), 5 A circuit breaker, door tamper
     switch, and battery support brackets
•    CK721-A network controller (optional) and two RDR8S eight-door
     interface modules
•    Two S300-DIN-L-PS 24 VDC, 5 A power supplies
                                                                                                 Figure 1: Security Control Panel Mounted in a
                                                                                                            20 in. x 42 in. Enclosure
Cable Requirements
    Description                 Recommended Cable                      Recommended Composite                Maximum Segment Length
                                Type1, 2                               Cable Type1
    CK721-A: RS485A, RS485B     Listed, 18 AWG, 3-conductor,           Listed, 18 AWG, 3-conductor,         4,000 ft (1,219 m) maximum
    RDR8S: RS485+/-             stranded, shielded, copper             stranded, shielded, copper
    CK721-A: ICOM1, ICOM2       Belden® 8761, 22 AWG, 1 twisted                                             500 ft (152 m)
    RDR8S: Door Contact         pair, stranded, unshielded, copper
    CK721-A: OUT1               Belden 8760, 18 AWG, 1 twisted                                              Depends on power requirements of the device. Voltage
    RDR8S: Door Strike, Shunt   pair, stranded, unshielded, copper                                          to the device must not be reduced more than 10% over
                                                                                                            the 18 AWG wire, measured when energized.
    Request to Exit             Belden 8761, 22 AWG, 1 twisted         Belden B558AFS Shielded Riser        500 ft (152 m)
    (RDR8S only)                pair, stranded, unshielded, copper     Rated or Belden B658AFS
                                                                       Shielded Plenum Rated
    Reader Power                Belden 8760, 18 AWG, 1 twisted                                              Refer to reader manufacturer’s specification for power
    (RDR8S only)                pair, stranded, unshielded, copper                                          requirements.
    Reader Data0/Data1          Belden 8723, 22 AWG, 2 twisted                                              500 ft (152 m). Refer to reader manufacturer’s
    (RDR8S only)                pairs, stranded, shielded, copper                                           specification for data requirements.
    RS232 A, RS232 B            Listed DB9 F/F AT Null Modem           Listed DB9 F/F AT Null Modem         25 ft (7 m). Cable must remain in the same room as the
                                cable                                  cable                                CK721-A.
    Ethernet                    Listed, Category 5, 24 AWG, solid,     Listed, Category 5, 24 AWG, solid,   354 ft (100 m). Cable, RJ45 connector, and RJ45 crimp
                                2 pair or 4 pair type                  2 pair or 4 pair type                tool to be supplied by customer.

1. All data cables should be physically separated from power lines. If conduit is used, do not run data cables in the same conduit as power cables or certain door
   strike cables, such as strike voltage greater than 30 V or magnetic door locks without Electromagnetic Interference (EMI) suppression. All cables must conform
   with National Electrical Code, NFPA 70; or for Canadian installations, refer to the Canadian Electric Code C22.1.
2. Shielded cable is not required but is strongly recommended to minimize the effects of electromagnetic interference or radio frequency noise.

                            Security Control Panel Assembly Mounted in a 20 in. x 42 in. Enclosure Installation Instructions                                         1
Door Termination                                                                              Selection Chart
•     Terminate door 1 to 4 first, since the connectors are located at the back
      rows.                                                                                       Product Code        Description
•     Single Door Connector Termination (typical of 8):                                           Number
                                                                                                  SPA1D20012F10       20 in. x 42 in. (50.8 cm x 106.7 cm) security control
                               Output side       Input side
                                                                                                                      panel with a CK721-A controller, two RDR8S
    Door Strike NO Contact                                    Door Strike                                             modules, a 5 A circuit breaker, a 120 VAC outlet, and
      Door Strike Common                                      Door Strike Common                                      two power supplies
    Door Strike NC Contact                                    Request to Exit                     SPA0D20012F10       20 in. x 42 in. (50.8 cm x 106.7 cm) security control
         Shunt NO Contact                                     Red LED                                                 panel with two RDR8S modules, a 5 A circuit breaker, a
           Shunt Common                                       LED Common                                              120 VAC outlet, and two power supplies
         Shunt NC Contact                                     Green LED                           SPA1D200-2F10       20 in. x 42 in. (50.8 cm x 106.7 cm) security control
               Input Tamper                                   Reader Power (+12 VDC)                                  panel with a CK721-A controller, two RDR8S
             Input Common                                     Power Common                                            modules, a 5 A circuit breaker, and two power supplies
                 Input Spare                                  Data 0/RS-485
                                                              Data 1/RS-485                       SPA0D200-2F10       20 in. x 42 in. (50.8 cm x 106.7 cm) security control
                                                                                                                      panel with two RDR8S modules, a 5 A circuit breaker,
                                                                                                                      and two power supplies
AC Power Connection
•    Put the AC
     power wiring                To AC            G
                                                            GREEN
                                                                           Wired at           Technical Specification
     through a                   power            N
                                                            BLUE           the factory
     knockout.                   source                     BROWN                                 Security Control Panel Assembly Mounted in a 20 in. x 42 in.
                                                  L
•    Connect the AC                                                                               Enclosure
     power wiring to                             TB-1                      L = Line
                                                                                                  Electrical Rating      SPA1D20012F10: 120 VAC, 3.6 A, 50/60 Hz
     terminal block                                                        N = Neutral
                                                                                                                         SPA0D20012F10: 120 VAC, 3.6 A, 50/60 Hz
     TB-1.                                                                 G = Ground
                                                                                                                         SPA1D200-2F10: 120 VAC, 3.6 A, 50/60 Hz
                                                                                                                         SPA0D200-2F10: 120 VAC, 3.6 A, 50/60 Hz
                   WARNING: Risk of Electric Shock.                                               Enclosure Rating       NEMA Type 1

         !
                   Disconnect the power supply before making
                                                                                                  Ambient Operating      32 to 122°F (0 to 50°C), 10 to 85% RH,
                   electrical connections. Contact with components                                Condition              noncondensing
                   carrying hazardous voltage can cause electric shock
                   and may result in severe personal injury or death.                             Dimensions (Width      20 in. x 42 in. x 7.5 in.
                                                                                                  x Height x Depth)      (50.8 cm x 107 cm x 19.1 cm)

S300-BAT Battery Connection                                                                       Ambient Storage        -4 to 158°F (-20 to 70°C), 5 to 95% RH,
                                                                                                  Condition              noncondensing
The optional S300-BAT feature
                                          RED
                                                      WHT          BLK                            Compliance             United States:
uses two PowerSonic, Model
PS-1270, 12 VDC, 7 Ah,                                                                                                   UL Listed under UL 1076 for Proprietary Burglar
                                             +        -   +    -         + - + -      G N L
                                                                                                                         Alarm Units and Systems, and under UL 294 for
sealed lead acid batteries per                                                 DC
                                                                         BAT
                                                                                     HIGH
power supply. To ensure                      B-1A         B-1B                 OUT   VOLT                                Access Control Systems Units;
                                                                                     AGE
proper operation, the batteries                                                                                          FCC compliant to the limits for a Class B digital
should be replaced every three                                                 PS-1                                      device, pursuant to Part 15 of the FCC rules
years whether or not they have                                                                                           Canada:
been placed into use by an AC             RED
                                                      WHT          BLK
                                                                                                                         Class B digital apparatus, complies with Canadian
power failure.                                                                                                           ICES-003;
                                             +        -   +    -         + - + -      G N L
The RED (+), BLK (-), and                                                      DC                                        cUL Listed for Signaling Appliance
                                                                         BAT
                                                                                     HIGH
WHT cables are provided with                 B-2A         B-2B                 OUT   VOLT
                                                                                     AGE
the enclosure. Observe the                                                                                               Europe:
polarity when connecting the                                                   PS-2                                      CE Mark – Johnson Controls, Inc., declares that this
batteries.                                                                                                               product is in compliance with the essential
                                                                                                                         requirements and other relevant provisions of the
Field Devices                                                                                                            EMC Directive 2004/108/EC and LVD 2006/95/EC.
For information on wiring the CK721-A controller or the RDR8S                                                            Australia and New Zealand:
module, refer to the documentation provided with these devices.                                                          C-Tick Mark, Australia/NZ Emissions Compliant
Use a separate Class 2 transformer or power supply for door strike
power. Under no circumstances connect a door strike to the
enclosure power supply.                                                                       Installation of Ferrite Clamps for CE Compliance
                                                                                              •     Clamp the ferrite clamp
                                                                                                    provided with the panel
                                                                                                    to the panel input power
                                                                                                    at the circuit breaker
                                                                                                    (see the left picture).
                                                                                              •     Wrap the Ethernet cable
                                                                                                    once around the clamp,
                                                                                                    and clamp it to the cable
                                                                                                    (see the right picture).

                                                                                                                                           Building Efficiency
                                                                                                                  507 E. Michigan Street, Milwaukee, WI 53202
                                                          Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc.
                                                 All other marks herein are the marks of their respective owners. © 2012 Johnson Controls, Inc.

2          Security Control Panel Assembly Mounted in a 20 in. x 42 in. Enclosure Installation Instructions

Published in U.S.A.                                                                                                                         www.johnsoncontrols.com